CP Electronics VITM6-EBDSPIR-AD User Manual

Product Guide
EBDSPIR-AD, EBDSPIR-AD-IP
Ceiling PIR presence detector – 1-10V dimming
The EBDSPIR-AD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional manual control.
Output Channel 1 comprises a mains voltage relay capable of simple on/off switching, while Output Channel 2 provides dimmable control of 1-10V ballasts.
Functioning as a presence detector, the unit can turn lights on when a room is occupied and off when the room is empty. Optional settings allow lights to be turned off in response to ambient daylight, or to implement a maintained illuminance (daylight harvesting) system.
Overview
Front features
Mounting Bezel
Sensor Lens
which covers...
PIR Sensor
IR Receiver
Light Level Sensor
Status LEDs
All functionality is fully programmable using an IR handset.
Features
PIR Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs The LED flashes Red to indicate the following:
Walk Test LED active
Valid setting received
when movement is detected
Back features
Retaining Spring
Power Input & Switched Output Connector
(Channel 1)
Retaining Spring
Dimmable
Control Output
Connector
(Channel 2)
Switch Input
Connector
Power Input & Switched Output Connector (Channel 1)
Used to connect mains power to the unit and to connect a switched load.
Dimmable Control Output Connector (Channel 2) Used to connect 1-10V controllable ballasts and transformers for dimmable loads.
Switch Input Connector
Two input terminals can be used to manually override the dimming levels and override the lights on or off.
EBDSPIR-AD-IP-LT30
A special order version that can be used down to -30ºC
Detection diagram
Area of lower sensitivity Area of high sensitivity
2
Installation
Choosing a Suitable Location
The EBDSPIR-AD is designed to be ceiling mounted and must satisfy the following criteria:
Avoid positioning the unit where direct sunlight may enter the sensor element. Do not site the sensor within 1m of any lighting, forced air heating or ventilation. Do not fix the sensor to an unstable or vibrating surface.
Sensor functionality
Detection Mode
The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode: Presence When movement is detected the load will automatically turn on. When the area is no longer occupied the
load will automatically switch off after an adjustable time period.
Absence The load is manually switched on. When the area is no longer occupied the load will automatically switch
off after the adjustable time period has elapsed.
In either case, sensitivity to movement of the PIR sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected.
Switch Level On/Off
Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters.
Maintained Illuminance (daylight harvesting)
The detector measures the overall light level in the detection area and calculates the correct output for the luminaires, to achieve a preset lux level (maintained illuminance or daylight harvesting).
Burn-in
Overview
It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life (refer to the manufacturer’s datasheet for details) As this EBDSPIR-AD is able to dim the lamps using 1-10V, the product provides a facility to disable this for a given period of time.
Operation
By setting the “Burn in” parameter, you can select a time during which the lamps are not allowed to deviate from
maximum output. The unit counts the time, and even remembers how long has elapsed in the event of a power failure. To cancel the burn in function, simply select a time of 0. Note that when the lamps are changed, the burn in time should be set again.
3
Installation
The EBDSPIR-AD is designed to be mounted using either:
Flush fixing, or
Surface fixing, using the optional Surface Mounting Box (part no. DBB).
Both methods are illustrated below.
Note: EBDSPIR-AD-IP & LT30 - use the supplied gasket to ensure IP rating (not compatible with Surface Mounting Box part no.
Flush Fixing
Warning - be careful bending springs when mounting unit.
1 2 3
Hole Ø64mm
4
Surface Fixing
1
50mm or 60mm fixing centres
2 3
Pull out spring tab and rotate spring arm as shown
Wire stripping details
Readback function (UNLCDHS handset only)
4
Important
Ensure that the cables are formed as shown before affixing the cable clamp. The clamp MUST clamp the outer sheath(s) only.
Bend cores as shown.
The UNLCDHS has the ability to read back the settings stored in a device.
To read back individual parameters
Navigate to the parameter and press the ‘R’ (Read) button whilst pointing at the device. The handset will click
when the parameter has been read back, the device will flash its LED, and the value will be shown against the parameter in the menu.
To read back all of the parameters in a menu
Press and hold the ‘R’ (Read) button for more than 1 second.
The handset will click every time a parameter is received
The device will show multiple flashes of its LED
All of the values will be shown against the parameters in the menu.
The individual parameters may be edited and then saved as a ‘Macro’.
Notes
If a parameter(s) has been missed because of a communication error, the missing value(s) is replaced by dashes.
When reading back, the Channel 1 relay (where fitted) will temporarily be switched off, and will return to it’s normal
state 2 seconds after the read back has been completed.
4
L/OUT
L
N
SW1/UP
+
-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(1-10V)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
Wiring diagrams
Multiple luminaires may be connected in parallel to Channel 1 (via the N and L/Out terminals) as long as the maximum total load is not exceeded.
Channel 2 (dimmable output) of the EBDSPIR-AD can be used to control the light output of luminaires that are fitted with dimming ballasts/transformers.
The ballasts/transformers can be connected in parallel to Channel 2 (via the DIM– and DIM+ terminals). Refer to the specification on page 12 for ballast quantities.
The wiring examples below show common methods of connecting the output channels for a single detector unit.
Single channel dimming
Functions: Switches the luminaire with occupancy and maintains illuminance. Dims and switches using optional centre biased retractive switch (MK K4900 or similar).
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance. Press and release down switch to turn off. Press and release up switch to turn back on. Press and hold up switch to dim up, press and hold down switch to dim down. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Maintains illuminance. Press and release down switch to turn off. Press and hold up switch to dim up, press and hold down switch to dim down. Turns off after occupancy.
Channel mode: Set to “Switch and dim together”.
5
L/OUT
L
N
SW1/UP
+
-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(1-10V)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
L/OUT
L
N
SW1/UP
SW2
DOWN
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
LUMINAIRE
(NON-DIMMING)
+
-
Single channel switching
Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.
Configured to presence detection: Turns on automatically with occupancy. Press and release down switch to turn off.
Press and release up switch to turn back on. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Press and release down switch to turn off. Turns off after occupancy.
Channel mode: Set to “Switch only”
Switch mode: Set to “2 position switch together”. Note: a single position switch can be used instead to toggle the
output, set to “1 position switch separate”.
6
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
Fault finding
What if the load does not turn ON?
Check that the live supply to the circuit is good.
Check that the load is functioning by bypassing the sensor (e.g. link terminals L and L/ Out on Channel1).
If the detection range is smaller than expected, check the diagram on page 2. Rotating the sensor slightly may
improve the detection range.
HINT: The Walk Test LED function can be used to check that the unit is detecting movement in the required area.
What if the load does not turn OFF?
Ensure that the area is left unoccupied for longer than the Time Out Period.
Ensure that the sensor is not adjacent to circulating air, heaters or lamps.
7
Basic programming
The functionality of the EBDSPIR-AD is controlled by a number of parameters which can be changed or programmed by any of the following devices:
UHS5 Infrared Handset. See below for programmable functions. UNLCDHS Infrared Handset (with LCD). See user guide for full programming details.
For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device. Point the handset at the Sensor and send the required programming commands to the unit as shown below. Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. Note: other functions on the UHS5 which are not shown below are not applicable to this product.
Number of Shift key presses
Parameter Name
Default Value
0 1 2 3 UHS5 Handset Graphics Description
SHIFT 1 SHIFT 2 SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
Button Activation
On / Raise
Off / Lower
Walk test
Time Out
(Time adjustment)
Lux on level
(Switch level on)
Light Level
Lux off level
(Switch level off)
Sensitivity
Defaults
On Raise
Off Lower
Off On Off
20 mins 1, 10 &
20 minutes
5, 15 & 30 minutes
10 seconds
9 2, 5 & 7 4, 6 & 9
6 (600) 2 (200)
5 (500) 7 (700)
4 (400) 6 (600) 9 (999)
9 2, 5 & 7 4, 6 & 9
9 1, 5 & 9 3, 6 & 8
D
Turn lights on or to raise lights.
Turn lights off or to lower lights.
When set to On this causes a red LED to flash on the sensor when it detects movement. Use this feature to check for adequate sensitivity levels.
Once the detector is turned on, this value sets how long the lights will stay on once movement has ceased.
Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient (adjustable between 1 and 9). The luminaires will always be switched on at level 9.
Sets a target light level to be maintained by the lighting system. 9 (999) = disabled.
Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the setting (adjustable between 1 and 9). Level 9 will always keep the lights on. This setting can be used for “window row switching”.
Note: the Lux Off Level value must always be greater than the Lux On Level value.
Sensitivity level for detecting movement. 1 = low sensitivity 9 = high sensitivity
Returns the unit to the default settings.
Burn-in
Presence / Absence
Shift
8
0 0 50 100
Presence Presence Absence
Determines how long the output will be at 100% so that lamps ‘burn-in’. The ’burn-in’ time is not affected by power supply interruptions.
Presence mode allows the output to turn on when movement is detected and off when movement ceases. Absence mode allows the output to turn off when movement ceases, but must be manually turned on first.
Use this button to select the settings in red and blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs
Advanced programming
Parameter Name Default Value Range / Options Description
Detector Parameters
Walk Test LED Off On or Off
Time Out
(Time adjustment)
Manual Time Out 10 minutes 0-99 minutes
Sensitivity On 9 1 (min) to 9 (max)
Sensitivity Off 9 1 (min) to 9 (max)
Lux time 0 0 (disabled)
Power Up State On On or Off
Disable Detector N Y or N
On Delay 0 minutes 0-99 minutes
Inhibit 4 seconds 1 to 999 seconds
Factory default
20 minutes 0-99 minutes
1-99 minutes
-
-
When set to On this causes a red LED to flash on the sensor when it detects movement. Use this feature to check for adequate sensitivity levels.
Once the detector is turned on, this value sets how long the lights will stay on once movement has ceased. Select 0 for 10 second delay – use for commissioning only.
When a manual operation occurs, either via the switch input or the infrared, it invokes the timeout period. Example 1: a detector in presence mode has a detector timeout of 15 minutes and a manual timeout of 3 minutes. When the user leaves the room they press the off button. The sensor will revert to automatic after 3 minutes, and then walking back in the room will turn the lights on. Example 2: using the settings above, the user turns the lights off (say for a presentation) but stays in the room. Every time a movement is detected, the manual timeout period is re-triggered, but when it doesn’t pick up for the short timeout period, the sensor will timeout and revert to automatic. This means the lights may turn on inadvertently during the presentation, if the occupants are still for the manual timeout period, so adjust the timing carefully. Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
Sensitivity level for detecting movement when the detector is off. *UHS5 sets Sensitivity On and Off to the same value.
If the detector measures the lux level and decides that the output needs switching on or off as a consequence, the lux time must elapse first. If at any time during the timed delay the lux change reverses then the process is cancelled. Lux Time enables absence detection to be implemented with a lux off level set. When the button is pressed, the lights will go on, regardless of ambient light level. However, if there is sufficient ambient light, they will turn off again after the Lux Time. Note
that whenever the an external switch is pressed, whether in absence or presence mode, if the lights were out because of the lux level, they will be immediately turned on again for at least the Lux Time.
Select No for a 30 second delay on start up. If Yes is selected, there will be no delay on start up and the detector will always power up detecting.
Disables detection, leaving the relay output permanently off with the dimming output operational. This mode is used when the unit is for maintained illuminance only.
The On Delay to allows the first channel to switch on after the second channel. A typical application for this would be where a detector is controlling lighting and air conditioning in an area. When the occupant is detected, the lighting will be turned on immediately, whereas the air conditioning may be turned on after 15 minutes. If the area is vacated and the detector times out before the delay, then the air conditioning would never go on. The delay can be set only for channel 1 using the on delay parameter. When the detector turns off, a delay is instigated to prevent retriggering. In certain circumstances this delay may not be enough. This parameter allows the delay to be changed.
Restores factory default settings
UHS5 UNLCDHS
 
*
*
 
 
 
 
 
Channel Modes
Switch only - -
Switch and dim together
User Modes
Raise
Lower
Scene up
Scene down
Scene #
Override On
Override Off
Cancel
Default -
- -
- -
- -
- -
- -
- -
- -
- -
Usually used for absence detection - in this mode the dimming channel is not used.
The detector will switch and dim the lighting together.
Increase light level. Reverts when occupancy cycle complete.
Decrease light level. Reverts when occupancy cycle complete.
Steps up between 6 pre-defined scenes.
Steps down between 6 pre-defined scenes.
Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%; 3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)
If the lights are off, sending the IR command will turn them on immediately and revert to automatic operation using the manual timeout period .
If the lights are on, sending the IR command will turn them off immediately. After the manual timeout period (described above), the sensor will revert to automatic.
Cancels the on or off override, returning the detector to normal operation.
   
 
 
 
 
9
Advanced programming
Parameter Name Default Value Range / Options Description UHS5 UNLCDHS
Channel 1 –Switching Channel
Detection Mode Presence Presence or
Lux on level
(Switch level on)
Lux off level
(Switch level off)
Channel 2 -Dimming Channel
Detection Mode Presence Presence or
Lux on level
(Switch level on)
Lux off level
(Switch level off)
Light Level
(maintained illuminance)
Max Value 100% 0 to 100%
Min Value 0% 0 to 100%
Memorise N Yes or No
On value 99 0 to 99
Off value 0 0 to 99
Burn-in 0 0 (disabled) or
Fade value 10 0 to 99
Fade mins 0 0 to 99
Speed On 40 Measured in 0.1
Speed Set 5 Measured in 0.1
Set Seconds 120 1 to 999 seconds
9 1 to 9
9 1 to 9
9 1 to 9
9 1 to 9
600 1 to 998 (999
Absence
For a higher resolution a scale of 101-199 is available
For a higher resolution a scale of 101-199 is available
Absence
For a higher resolution a scale of 101-199 is available
For a higher resolution a scale of 101-199 is available
disabled)
1 to 999 hours
sec intervals.
sec intervals.
Presence mode allows the output to turn on when movement is detected and off when movement ceases. Absence mode allows the output to turn off when movement ceases, but must be manually turned on first.
Sets a minimum light level below which the PIR sensor is enabled, allowing lights to be turned on by movement.
Note: the Lux Level Off value must always be greater than the Lux Level On value.
Sets a maximum light level above which the PIR sensor is disabled, preventing lights from being turned on by movement.
Presence mode allows the output to turn on when movement is detected and off when movement ceases. Absence mode allows the output to turn off when movement ceases, but must be manually turned on first. Sets a minimum light level below which the PIR sensor is enabled, allowing lights to be turned on by movement.
Note: the Lux Level Off value must always be greater than the Lux Level On value.
Sets a maximum light level above which the PIR sensor is disabled, preventing lights from being turned on by movement.
Sets a target light level to be maintained by the lighting system.
Maximum dimming output level.
Minimum dimming output level.
If this is set to Yes, the last manual lux level set will be memorised and used as the new switch on level.
Dimming output level when switched on (0-99).
Dimming output level when switched off (0-99). If a non-zero off value is set, then the output will toggle between this value and completely off depending on the switch level on and off values. For example, if it is light outside, the fittings will be off if there is no occupancy. If it is dark outside, they will adopt the preset off value.
This feature is only enabled if ‘Min value’ is set to 99.
Determines how long the output will be at 100% so that lamps ‘burn-in’. The ’burn­in’ time is not affected by power supply interruptions.
After occupancy ceases, this dimming output level is loaded for the fade time (adjustable between 0 and 99).
This is the time period (adjustable between 0 and 99 minutes) that the luminaire will be held at the fade value before turning off. A value of 0 disables the fade function.
Determines the dimming response speed after the setup time has finished.
Determines the dimming response speed during the set up time. Measured in 0.1
sec intervals. If set to 0 will disable dimming for “Set seconds” below, used if
fittings are required to warm up before dimming.
Determines how long the dimming response set-up period lasts on power-up or on setting change. This enables the desired lux level to be achieved rapidly when the lights come on, or during setup.
 
 
 
 
 
 
 
 
 
 
Switch Modes
2 position switch together
1 position switch together
10
Default
- -
-
A single centre biased retractive switch will be used to control both channels together.
A single position retractive switch controls both channels together.
 
 
This page intentionally left blank
11
Technical data
Dimensions See diagrams opposite Weight 0.15kg Supply Voltage 230VAC +/- 10% Frequency 50Hz Maximum Load Channel 1 (switching):
10A of lighting and/or ventilation
including incandescent, fluorescent, compact fluorescent, low voltage (by switching the primary of transformer).
Channel 2 (dimming):
Maximum number of 1-10V ballasts is 10.
Power consumption On 724mW, Off 260mW
Dimming output Basic insulation only. Although low
voltage, this is not an SELV output and should be treated as if mains
potential. Use mains rated wiring. Terminal Capacity 2.5mm2 Temperature EBDSPIR-AD -10ºC to 35ºC EBDSPIR-AD-IP -10ºC to 35ºC EBDSPIR-AD-IP-LT30 -30ºC to 35ºC Humidity 5 to 95% non-condensing Material (casing) Flame retardant ABS and PC/ABS Type Class 2 IP rating EBDSPIR-AD IP40 EBDSPIR-AD-IP IP55 EBDSPIR-AD-IP-LT30 IP55
Compliance EMC-2004/108/EC
LVD-2006/95/EC
EBDSPIR-AD
DBB
Part numbers
Part number Description Detector EBDSPIR-AD Ceiling PIR presence detector – 1-10V dimming EBDSPIR-AD-IP Ceiling PIR presence detector – 1-10V dimming sealed to IP55 EBDSPIR-AD-IP-LT30 Ceiling PIR presence detector – 1-10V dimming sealed to IP55 -30ºC Accessories DBB Surface mounting box UHS5 Programming IR handset UNLCDHS Universal LCD IR handset
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations.
FM 45789 EMS 534520
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
12
C.P. Electronics Ltd
Brent Crescent London NW10 7XR United Kingdom Tel: + 44 (0) 333 900 0671 Fax: + 44 (0) 333 900 0674 www.cpelectronics.co.uk enquiry@cpelectronics.co.uk
Ref: #WD485 Issue 4