CP Electronics VITM4-E-2CH, VITM4-LD3-2CH Installation Instructions

Product Guide
VITM4-2CH
Vitesse Modular 4 - 2 Channel Switching Modules
Overview
The Vitesse modular system is a cost effective method of providing power and control for lighting installations in in-
dustrial, commercial and retail buildings. The system is designed for ease of installation: mains input is connected using the spacious wiring compartment; control inputs and outputs are pluggable using industry standard connectors. The modular approach allows for between 4 and 16 luminaires to be connected.
The VITM4-2CH is a two channel, non-dimming distribution box for use in applications that require two independently
switched lighting circuits, or lighting and ventilation circuits. For example this product is ideal for connection to a 2 channel presence detector for separate window row switching. It has two live inputs, a common neutral and two switch inputs.
System Components
Fixing points 202mm 150mm
M6 (1/4”)
122mm 75mm
9 pole interface connector and lead supplied with detectors
146mm
127mm
Channel 1
VITM4-S-2CH
Vitesse modular starter for non-dimming systems
Height - allow 150mm for total height of unit (including connectors and cable)
BESA box fixings
Channel for channel nuts (zebs)
Channel 2 Channel 1
VITM4-E-2CH
Vitesse modular extender f or non-dimming systems
Channel 2
Installation
Removable gland plate with
3 x Ø20mm knockouts
3 x Ø20mm knockouts for rear cable entry
4 x key slots to accept M6 (1/4”) fixings
Warning. This device works at mains voltage. Be sure to take care when working with electricity.
The box should be fixed on a smooth, flat surface or using drop rod fixings attached to channel nuts. Ensure that there is easy access to the wiring compartment and all connectors once the box is in-situ.
Wiring
Permanent Live
Neutral-Supply in
Earth
Live 1-Switched
Live 2-Switched
On / Off 1
On / Off 2
Live 1-Supply in
Live 2-Supply in
Large
cables
Cable clamps
Small
cables
All wiring should be mains rated. Remove wiring compartment cover. Wire the box using the diagrams below
On/off 1 and On/Off 2 connect switches through to detectors Switched live turns the lights on and off
Use the cable clamps to secure the wiring or use cable glands (not
supplied). The clamps can be split, and flipped over to clamp different cable diameters.
Replace wiring compartment cover. Plug in the luminaires ensuring that the connector latches to the box.
Wiring using single supply
Local lighting switch and local emergency test switch
N E L
Local lighting
switch 1
Local emergency
test switch
Emergency test using central switch
N E L
Channel 1
Luminaire connections / Lead colours
Permanent Live Black (4 core only)
Neutral Blue
Earth Green / Yellow
Switched Live Brown
Channel 2
Multiple boxes
Wire link
Local lighting
switch 2
Emergency test using power interruption
N E L
Wire link
Central
emergency test
switch
A local lighting switch may still be used when there is a central emergency test switch or when a circuit breaker is used to interrupt the power.
Wire link
DO NOT WIRE ACROSS
PHASES
2
Wiring using dual supply
Local lighting switch and local emergency test switch
N E L1
L2
Local lighting
switch 1
Local emergency
test switch
Local lighting
switch 2
Emergency test using power interruption
N E
L1
L2
Emergency test using central switch
N E
L2 L1
Central
emergency test
switch
Multiple boxes
Wire link
A local lighting switch may still be used when there is a central emergency test switch or when a circuit breaker is used to interrupt the power.
DO NOT WIRE ACROSS
PHASES
Connecting a detector
CH1 and CH2 plugs are coded.
Ensure that the plugs are
inserted correctly and do not
apply excessive force
Detector lead needs to be ordered separately from the detector. Order code VITM4-L3-2CH. Where two detectors connect to a single box a dual lead is available VITM4-LD3-2CH.
Sensor
3
Presence detector connections - Automatic on, automatic off
Single live supply Dual live supply
N E L
Wire link
N E L1 L2
Absence detector connections - Manual on, automatic off
Diagrams show separate switches for each channel. One switch can be used for both channels. For 2 switches set
switch mode on detector to 1 position switch separate, for 1 switch set to 1 position switch together. See detector installation instructions for further information.
This wiring may also be used for presence override switches.
Single live supply Dual live supply
N E L
Wire link
N E L1
L2
4
Applications
2 Channel detectors
The flexibility of using two channels detectors allows the following scenario: Channel 1 - occupancy and lux
Channel 1 of the detector can be used to switch the Channel 1 luminaires at a preset lux level. These luminaires are typically situated nearest the windows. The luminaires will also switch with occupancy.
Channel 2 - occupancy only
The inner luminaires, ie those furthest from the windows, are switched with occupancy only.
Switch inputs
One or two manual switches, ie for luminaires on channels 1 and 2, can be used to manually override the lights on
or off, or in the case of absence detection activate the luminaires on entry.
The diagrams below illustrate a typical application.
Window / room switching
Window / room switching + Extender
5
This page intentionally left blank
6
This page intentionally left blank
7
Part numbers
Presence / Absence Detectors
EBDSPIR-PRM-2CH PIR 2-Channel presence detector EBDSPIR-PRM-2CH-NC PIR 2-Channel presence detector, normally closed fail safe contacts MWS3A-PRM-2CH Microwave 2-Channel presence detector MWS3A-PRM-2CH-NC Microwave 2-Channel presence detector, normally closed fail safe contacts MWS6-PRM-2CH Microwave 2-Channel presence detector MWS6-PRM-2CH-NC Microwave 2-Channel presence detector, normally closed fail safe contacts
Modules
VITM4-S-2CH 4 pole starter box, 2 channel VITM4-E-2CH 4 pole extender box, 2 channel
Detector Leads (LSF)
VITM4-L3-2CH 3m 2 channel sensor lead VITM4-LD3-2CH 3m 2 channel dual detector sensor lead
Luminaire Leads (LSF)
VITM4L303100W 3 core 3m 1.0mm2 White plug VITM4L305100W 3 core 5m 1.0mm2 White plug VITM4L403100R 4 core 3m 1.0mm2 Red plug VITM4L405100R 4 core 5m 1.0mm2 Red plug Other leads available to order.
Connectors
VITM4-LPW 4 pole luminaire plug white
Ratings
Voltage 230VAC +/- 10% Frequency 50Hz Terminal capacity 4mm2 in wiring compartment Temperature 0ºC to 35ºC Power Rating of system 16A. Rating of each output 10A Note: detector may have different rating, check datasheet Compliance BS 5733:1995
For lighting purposes only with suitable circuit protection. For fixed wiring only
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
FM 45789 EMS 534520
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
8
UK Patent no. GB2463063
EU patent pending
EU registered design no.
001587544-0001, 001587544-0002
C.P. Electronics Ltd
Brent Crescent London NW10 7XR United Kingdom Tel: + 44 (0) 333 900 0671 Fax: + 44 (0) 333 900 0674 www.cpelectronics.co.uk enquiry@cpelectronics.co.uk
Ref: #WD325 Issue 3