Product Guide
VITM4-2CH-2S
Vitesse Modular 4 - 2 Ch / 2 supply Switching Modules
Overview
The Vitesse modular system is a cost effective method of providing power and control for lighting installations in in-
dustrial, commercial and retail buildings. The system is designed for ease of installation: mains input is connected
using the spacious wiring compartment; control inputs and outputs are pluggable using industry standard connectors.
The modular approach allows for between 4 and 16 luminaires to be connected.
The VITM4-2CH-2S is a two channel, non-dimming distribution box for use in applications that require two independ-
ent supplies for switching lighting or lighting and ventilation circuits. For example this product is ideal for installations
that have essential and non-essential supplies for lighting circuits and require common switching using presence detectors. This product provides connections for separate Live, Neutral and Permanent Live inputs.
System Components
202mm
150mm
146mm
127mm
Channel 1 Channel 2 Channel 1
VITM4-S-2CH-2S
Vitesse modular starter for non-dimming systems
Height - allow 150mm for total height of unit (including connectors and cable)
Fixing points
VITM4-E-2CH-2S
Vitesse modular extender f or non-dimming systems
122mm
75mm
Channel 2
9 pole interface
connector and lead
supplied with
detectors
Installation
BESA box fixings
Channel for channel nuts (zebs)
3 x Ø20mm knockouts for rear
cable entry
4 x key slots to accept M6 (1/4”)
fixings
Removable gland plate with
3 x Ø20mm knockouts
Warning. This device works at mains voltage. Be sure to take care when working with electricity.
The box should be fixed on a smooth, flat surface or using drop rod fixings attached to channel nuts.
Ensure that there is easy access to the wiring compartment and all connectors once the box is in-situ.

Wiring
Permanent Live 1
Neutral 1-Supply in
Earth
Live 1-Switched
Live 2-Switched
Neutral 2-Supply in
Permanent Live 2
Live 1-Supply in
Large
cables
Small
cables
Channel 1
Channel 2
Live 2-Supply in
Cable clamps
All wiring should be mains rated.
Remove wiring compartment cover.
Wire the box using the diagrams below
Switched live turns the lights on and off
Use the cable clamps to secure the wiring or use cable glands
(not supplied). The clamps can be split, and flipped over to
clamp different cable diameters.
Replace wiring compartment cover.
Plug in the luminaires ensuring that the connector latches to
the box.
Connecting a detector
Luminaire connections / Lead colours
Permanent Live Black (4 core only)
Neutral Blue
Earth Green / Yellow
Switched Live Brown
Detector lead needs to be ordered separately from the
detector. Order code VITM4-L3-2CH-2S.
Where two detectors connect to a single box a dual
lead is available VITM4-LD3-2CH-2S.
CH1 and CH2 plugs are coded.
Ensure that the plugs are
inserted correctly and do not
apply excessive force
Sensor
2

Local emergency test switch
Wiring
N1
N2
E L1
L2
Local emergency test switch supply 1
Local emergency test switch supply 2
Emergency test using central switch
N1 E
N2
L2 L1
Local emergency
test switch supply 1
Multiple boxes
Local emergency
test switch supply 2
Emergency test using power interruption
N2
N1 E
L1 L2
Wire link 1
Wire link 2
A local lighting switch may still be used when there
is a central emergency test switch or when a circuit
breaker is used to interrupt the power.
3
DO NOT WIRE ACROSS
PHASES