CP Electronics Vitesse Plus Quick Start Manual

Vitesse Plus Quick Start
Connect alldetectors and switches to the LCM before following this procedure. Refer to the VITP7-MB installation guide for details on how to do this.
CH1
CH5
CH2
CH3
CH6
CH7
CH1 CH2 CH3 CH4 CH5
CH6
CH7
CH6
Master switch
Emergency
lighting
test
CH4
Use the following procedure with the UNLCDHS handset to get your Vitesse Plusinstallation up and running:
1
Connect the power to the LCM. It then goes through a power-up sequence of 8 seconds, after which all connected lightsswitch on.
2
Press
ON/OFF
to turn on the programming handset.
3
Select Vitesse Plusfrom the main PRODUCT FAMILY
menu and press .
PRODUCT FAMILY
Rapid >
à
Vitesse Plus
>
Handset Config >
4
Select LCM and press
or .
VITESSE PLUS
à
LCM
>
Detector >
Scene Panel >
5
Select Program and press
or .
LCM
à
Program
>
Lux Settings >
Device Info >
6
Select Presetand type in the number of the preset.
PROGRAM
à
Preset 7
Load Type DALI
Detection Mode
Pres
7
Point the handset directly at the device and press
. An LED flashes red/green to acknowledge the command, then green till the preset isprogrammed.
8
Press twice to return to the Vitesse Plus menu.
VITESSE PLUS
à
LCM
>
Detector >
Scene Panel >
9
Select Detector and press
or .
VITESSE PLUS
LCM >
à
Detector
>
Scene Panel >
10
Select Program and press
or .
DETECTOR
à
Program
>
User >
Device Info >
11
Select Time Out (mins) and enter the number of minutes to wait (0 - 99) before lights turn off when absence detected.
PROGRAM
à
Time Out (mins)
10
Light Level 600
Detection Mode
No
12
Select Light Level and enter the target lux value (0-
999) that daylight linking isto maintain.
PROGRAM
Time Out (mins)
10
à
Light Level 600
Detection Mode No
13
Point the handset directly at the device and press
.
14
Perform this sequence with the centre-biased retractive switch to activate daylight linking:
1. Dim allthe way down
2. Dim allthe way up
3. Switch off
4. Switch on