CP Electronics MWS6-PRM-2CH User Manual

Product Guide
MWS6-PRM-2CH, MWS6-PRM-2CH-NC
Ceiling Microwave presence/absence detector 2 channel
Overview
The MWS6-PRM-2CH Microwave presence detector provides automatic control of lighting loads with optional manual control. It detects movement using a highly sensitive microwave detector. This works by emitting low power microwave signals and measuring the reflections as the signals bounce off moving objects. The detector provides two independently controlled output channels that can be used for a variety of applications. Occupancy of two independent lighting circuits using
a single detector, e.g. for essential and non-essential supplies.
Occupancy and lux control of one lighting circuit and
just occupancy control of a second circuit, e.g. where a row of luminaries by a window is lux controlled whilst inner rows are switched on occupancy only .
Occupancy and lux control of a lighting circuit and
just occupancy control of a ventilation circuit .
Occupancy on both lighting circuits, with separate lux
control on each circuit. All functionality is fully programmable using an IR handset. MWS6-PRM-2CH Ceiling Microwave presence/
absence detector 2 channel
MWS6-PRM-2CH-NC Ceiling Microwave presence/
absence detector 2 channel normally closed
Front features
Mounting Bezel
Back features
Retaining Spring
Sensor Lens
which covers...
Microwave Sensor
IR Receiver
Light Level Sensor
Status LEDs
Channel 2
Connector
Features
Microwave Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs The LED flashes Red to indicate the following:
Walk Test LED active
Valid setting received
Channel 1 Connector
Live input and output for Channel 1. Switch input connection that can be used to manually override the lights on or off.
Channel 2 Connector
Live input and output for Channel 2. Common Neutral connection.
when movement is detected
Channel 1 Connector
Retaining Spring
Detection diagram
Area of lower sensitivity Area of high sensitivity
Note. If the range is compromised by the ceiling construction / material. Add the supplied 20mm spacer ring. See page 4 for fitting details.
Sensor functionality
Detection Mode
The Detection Mode can be set to behave in Presence or Absence mode:
Presence When movement is detected the load will automatically turn on. When the area is no longer occupied the
load will automatically switch off after an adjustable time period.
Absence The load is manually switched on. When the area is no longer occupied the load will automatically switch
off after the adjustable time period has elapsed.
In either case, sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected.
Switch Level On/Off
Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level
parameters.
The level can be set independently for each channel (UNLCDHS only). For example Channel 1 turns on with
occupancy whereas Channel 2 is held off by Lux.
Normally closed option
The MWS6-PRM-2CH-NC provides a normally closed contact for fail safe operation. If the unit fails, the outputs will default to on.
2
Installation
Choosing a Suitable Location
The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite).
Avoid positioning the unit where direct sunlight may enter the sensor element.
Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
Do not fix the sensor to an unstable or vibrating surface.
Avoid metallic objects directly in front of the sensor head.
Note 1. When controlling two circuits, the circuits must be on the same phase.
2. L/In Ch1 is used to supply the detector with power.
Wiring Diagram
CH1 and CH2 plugs are coded. Ensure that the plugs are inserted correctly and do not apply excessive force
Absence detection
To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the
diagrams. Note that this will be switching mains voltage.
The unit ships with presence detection as default. To change to absence detection, press and release the
external switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate absence mode has been selected.
To change back to presence detection, repeat the above procedurethe LED will flash for 30 seconds to indicate
presence mode has been selected.
Note: the above adjustments can also be made using the UHS5 or UNLCDHS handsets. See Programming sections.
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
3