Microwave Presence Detector with Pre-wired 3 Metre Lead
Contents
Section Contents Page
1 Dimensional information 1
2 Description and operation 2
3 Wiring & Installation 3
4 Fixing - Flush 4
5 Fixing - Surface 4
6 Head locking 5
7 Time, Lux & Sensitivity adjusters 5
8 Programming 6
9
Detection pattern diagrams
10
Fault finding
11
Specification
12
Part numbers
1. Dimensions
7
8
8
8
page
2. Description and Operation
The MWS3A-PRM-L3 (microwave) detector provides automatic control of lighting loads with optional
manual control. It can be used on incandescent, fluorescent and compact fluorescent lighting, and has the
added benefit of being able to connect an external switch. The MWS3A-PRM-L3 detects movement using
a highly sensitive microwave detector. This works by emitting low power microwave signals and measuring
the reflections as the signals bounce off moving objects. The MWS3A-PRM-L3 has a unique adjustable
sensor head that allows the area of detection to be optimised for the application.
When movement is detected the load will automatically turn on. When the area is no longer occupied the
load will automatically switch off after an adjustable time period. An integral adjustable photocell allows the
lights to be kept off if there is sufficient ambient light.
An integral infra-red sensor in the unit allows the unit to be programmed using the optional DD-LCDHS
programming handset. This gives complete flexibility over many of the operating parameters. Without the
handset, manual adjustments can be made to the sensitivity, lux and time settings using controls
accessible behind the lens.
The UHS user handset can be used to change output lux levels and override the lights on or off.
This product is supplied complete with a 3m lead.
page 2
3. Wiring & Installation
1. Wire the products using the diagram opposite.
2. To switch from more than one position simply wire two or more units in parallel using the Live,
Neutral and Switched Live wires only.
3. The detector should be sited so that the occupants of the room fall inside the detection pattern
shown in section 9.
4. Corridors or aisles: the unit should be placed at the end of the corridor or aisle and the sensor
head should be angled to look down the corridor or aisle.
5. Open plan areas and offices: the unit can be mounted in a corner looking outwards in which
case the sensor head should be angled . Or the unit can be mounted in the centre of the area
with the sensor head flat.
Note that the higher the sensor is installed the shorter the detection range will be.
Sites as far away as possible from any lighting or ventilation equipment.
Do not fix to a vibrating surface.
Do not fix to a suspended luminaire.
Site as far away as possible from the surface of metal objects.
7. Mount using one of the two options overleaf.
8. Connect the sensor via the prewired lead. Live supply to the Brown core; Load to the Black core;
Neutral to the Blue core.
9. Use a small screwdriver to set the LUX level adjuster fully clockwise, the time to minimum (fully
anticlockwise) and the sensitivity to maximum (fully clockwise) using the diagram in section 7.
10. Power the unit up—the load should come on immediately.
11. Vacate the room or remain very still and wait for the load to switch off (should take no more than 2
minutes).
12. Check that the load switches on when movement is detected.
13. The LUX thumbwheel determines the ambient light level at which the lights turn on.
14. Select the time using the adjuster, fully clockwise is the maximum.
15. The area of detection can be varied by altering the angle of the sensor head and the sensitivity
adjuster. Note: on maximum sensitivity this unit is extremely sensitive to movement and may
detect through glass, thin walls or partitions. If this causes a problem reduce the sensitivity by
turning the adjuster anticlockwise.
16. Using the UHS or UHS3 infra-red handset: the override on button turns the unit on permanently;
the override off button turns the unit off permanently; the cancel button cancels the overrides.
When an override is selected an LED will flash inside the unit. The UHS handset can also be used
to set the lux levels—see Section 8.3
Note: the above adjustments can also be made using the DD-LCDHS handset instead of the manual
adjusters or external switches. See section 8.
page 3
4. Fixing - Flush
Warning - be careful bending springs when mounting unit.
1 3 2
Hole Ø74mm
5. Fixing - Surface
Warning - be careful bending springs when mounting unit.
1
Hole Ø30mm MAX
50mm or 60mm
fixing centres
page 4
2
Remove wiring
compartment cover
3
6. Head Locking
1
Remove metal locking clip from
rear of unit.
2
Adjust head to required position.
Push clip into position shown below to lock head.
To remove clip, lever out with a small screwdriver.
1 2
Slide open window.
7. Time, Lux & Sensitivity Adjusters
Sensitivity
Lux
Time
page 5
8. Programming
All the following functions can be programmed using the remote control DD-LCDHS handset:
1. Detector Parameters (factory default in brackets):
1.1 Time adjustment 10 seconds to 99 minutes time delay (select 0 for 10 second delay –
1.2 Sensitivity On (9) Sensitivity level when the detector is already operational adjustable
1.3 Sensitivity Off (9)Sensitivity level for switching the detector on – adjustable between 1
1.4 Power Up On (Y) Select No for a 30 second delay on start up. If Yes is selected, there
1.5 Walk Test (N) An LED behind the detector lens will flash to show movement has
1.6 Disable Detector (N) Disables detection. In this mode the detector acts as a photocell only.
2. Switching functions (factory default in brackets):
2.1 Switch level on (9)Lux level setting to prevent the luminaires being switched on if the
2.2 Switch level off (9)Lux level setting to switch the luminaires off during occupancy if
3 User Menu
DD-LCDHS user menu or UHS handset functions:
3.1 Lux up Can only be used with the set button—see 3.6.
3.2 Lux down Can only be used with the set button—see 3.6.
3.3 Override on Permanently overrides the luminaire output on.
3.4 Override off Permanently overrides the luminaire output off.
3.5 Cancel Cancels the on or off override, returning the detector to normal
3.6 Set Send before using lux up or lux down. The switch level on (see 2.1)
use for commissioning only).
between 1 (min.) and 9 (max.)
(min.) and 9 (max.).
will be no delay on start up and the detector will always power up
detecting.
been detected (use for commissioning).
The lux preset determines the light level at which the output is turned
on. The sensitivity preset determines the light level at which the output
turns off. The time preset prevents nuisance tripping and in this mode
is adjustable between 0-13 minutes.
ambient light level is sufficient (adjustable between 1 and 9). The
luminaires will always be switched on at level 9.For a higher resolution
of ‗switch level on‘ a scale of 101-199 is available in the ‗Special
menu‘.
between 1 and 9). Level 9 will always keep the lights on. This setting
can be used for ―window row switching‖. For a higher resolution of
‗switch level off‘ a scale of 101-199 is available in the ‗Special menu‘.
operation.
can then be adjusted using the lux up or lux down buttons.
page 6
Ideal for large office or classroom
Ideal for corridor or aisle applications
9. Detection Patterns
Ideal for open plan areas and offices
LOAD DOES NOT COME ON
Check to see if the live supply to the circuit is
good. Strap across the L and LIVE OUT terminal
to turn the load on.
If the supply and wiring are good, check the LUX
level setting. Increase the LUX level setting to
allow the controller to turn on at higher ambient
natural light level.
10. Fault Finding
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccupied for a
greater time period than the time out period set
using the switch.
Make sure that the sensor is not adjacent to
vibrating surfaces or objects (e.g. ventilation
equipment).
The unit may pick up movement through thin
partitions or walls. Reduce the sensitivity by
turning the adjuster anticlockwise.
page 7
11. Specification
LOAD
10A of lighting and or ventilation including incandescent, fluorescent, compact fluorescent, low voltage
(switch primary of transformer).
SUPPLY VOLTAGE 220-240 Volts AC 50 Hz
TIME OUT PERIOD Adjustable 10 seconds to 99 minutes
LIGHT LEVEL Light to dark
TERMINAL CAPACITY 2.5mm2
MATERIAL Flame retardant ABS
TYPE Class 2
TEMPERATURE -10°C to 35°C
SAFETY The microwave radiation emitted by these units is exteremely low power.
At a distance of > 50mm the power density is <6% of the ANSI IEEE C95.1 –1991
recommended microwave power density.
At a distance of 5mm from the unit it is <84% of recommended power density.
CONFORMITY EMC-89/336/EEC
LVD-73/23/EEC
12. Part Numbers
MWS3A-PRM-L3 Microwave presence detector with 3m pre-wired lead
MWS3A-DBB Surface mounting box
DD-LCDHS IR remote control programming handset with LCD screen
UHS IR remote control user handset with lux setting functionality
UHS3 IR remote control user handset with on/off override only
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.
FM 45789 EMS 534520