CP Electronics KH3N, KH3 User Manual

KH3 Product Guide
Weatherproof Electronic Time Lag Switch
The KH3 time lag switch is a quick and effective way to reduce energy consumption for lighting applications. Pressing the touch pad brings the lights on; the lights will then switch off automatically after a preset time period has elapsed.
These units do not require a neutral connection, therefore they can be used to replace an existing light switch. The duration of the time delay is set by a thumbwheel on the reverse of the unit.
Time lag switches can be used in two way and intermediate switch­ing arrangements without any extra wiring.
Overview
Wiring
Conventional Wiring
Wire the units as in diagram 1. When using multiple switch posi­tions see diagram 2.
For two way and intermediate switching follow the diagrams over­leaf. Note that as long as each switch position has a Live feed and a Live Out connection to the load then the switch will be properly wired.
Ensure that all cable entry to the enclosure is via suitable
cable glands and seal with silicone sealant where appropri­ate.
If it is necessary to screw through the rear of the enclosure
ensure that any holes are covered with the caps provided and sealed with silicone sealant where appropriate.
Diagram 1 Conventional wiring
Installation
Warning. This device works at mains potential. Be sure to take care when working with electricity.
1. Make sure the load is connected and in working order.
2. Isolate the mains supply to the circuit at the main consumer unit.
3. Connect the controller via the terminal block. Live supply to the L terminal and the load to the LIVE OUT terminal.
4. Push the override switch to the off position (see diagram).
5. Set the timing range using the thumbwheel. Turn clockwise to increase timing.
6. Screw the unit to the wall and switch the mains supply back on at the distribution board.
7. Wait 20 seconds before pushing the touch pad
8. Push the touch pad and the lights will come on
9. Wait for the time period and the lights will turn off again.
Diagram 2 Multiple switch locations
Fault Finding Specification
LIGHTS DO NOT COME ON
Check to see if the live supply to the circuit is good. Strap across the L and LIVE OUT termi­nal to turn the load on.
LIGHTS DO NOT GO OFF
Ensure that you have waited for the time out period.
If the lights still do not go off then it is likely the unit was not given the 20 seconds start up pe­riod on installation. Follow this procedure:
1. Isolate the mains supply to the circuit at the main consumer unit and unscrew the unit from the wall.
2. Push the override switch to the off posi­tion.
3. Reapply the mains and wait for 20 sec­onds.
4. Activate timer as normal.
LIGHTS FLICKER
Ensure that there are sufficient power factor correction capacitors fitted.
LOAD
10A of lighting including incandescent, fluorescent, compact fluorescent, low voltage (switch primary of transformer).
Fluorescent and compact fluorescent fittings with “switch start” ballasts - 10 ballasts maximum. Power factor correction capacitors must be fitted.
Most fluorescent fittings have power factor correction capacitors fitted. If they are not present the unit may fail to turn off properly or flicker. In this case fit one capacitor per circuit with a minimum value of 1μF for every unit installed. The capacitor should be fitted across switched live and neutral. Note that it is not necessary to fit a capacitor on every fitting. This also applies to fittings controlled with high frequency ballasts and maintained emergency fittings.
Not suitable for switching contactors Not suitable for SON lighting Not suitable for heating or ventilation loads.
Please contact our sales department for a suitable alternative product.
SUPPLY VOLTAGE 220-240 Volts AC 50 Hz TIME OUT PERIOD 20 seconds to 20 minutes (approximate) FIXING METHOD Surface fixing 25mm deep plastic surface mount moulded box.
Flush fixing 25mm steel wall box or 32mm deep cavity wall box.
TERMINAL CAPACITY 1.5mm2 IP RATING IP 66 MATERIAL Flame retardant ABS TYPE Class 2 TEMPERATURE -10°C to 35°C CONFORMITY EMC-2004/108/EC
LVD-2006/95/EC
Part Numbers
KH3 Weatherproof electronic time lag switch touch activated KH3N Weatherproof electronic time lag switch touch activated with neon
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE W iring Regulations and any applicable Building Regulations.