CP Electronics GITLC-B User Manual

GITLC User Guide
Single gang time lag switch
Replaces a standard light
switch or dimmer
Suitable for lighting, heating or
ventilation loads
Turns on for adjustable time period
Switches all lighting, heating and venti-
lation loads up to 10A
installation
This product should be installed in accordance with the current IEE wiring regulations. If in doubt consult a qualified electrician.
Compatible with all BS4662 dimen­sions back boxes.
Remove top and bottom lugs if fitted.
Do not overtighten
wiring1 way switching
1 way switching
If the lights are controlled from one location only, wire as in the diagram.
Use the extender if there is less than 25mm free space.
REMEMBERput the wires through the ex­tender before connecting
May have red or brown sleeve
LINK com L1
wiring2 way switching
2 way switching
If more than one time lag switch is required to switch the lighting (e.g. At the top and bot­tom of a staircase) they can be wired in parallel, as in the diagram.
LINK com L1 LINK com L1
Locating ring
The GITL comes with an LED locating ring which is used to locate the buttons at night. If the load does not turn off properly (e.g. lamp flickers, fan continues to run, contactor does not open) then the LED needs to be disabled. To achieve this, remove the link as shown below.
Remove link to disable LED locating ring
LINK com L1
operation
time setting
on
off
battery
green-i locator
setting
Short presslights on for time period
Press for more than 5 seconds to activate (see Activate section).
Short presslights off
Press for more than 5 seconds to de-activate (see Activate section).
setup
Remove front cover
Time setting (determined by switch, see below) 5 sec15min 15min2hour
The lights will turn off after the time setting has fin­ished. Clockwise = longer delay.
Standard operation
Bottom button de-activated. The lights will turn off automatically, but will not turn off manually.
15min-2hour time range
5sec-15min time range
activate
Before using, the unit needs to be activated.
Press and hold the top button for more than 5 seconds.
The red LED will flash to indicate that has activated and the unit will now operate.
If the unit is going to be out of use for prolonged peri-
ods (more than 6 months) it should be de-activated by repeating the procedure above with the bottom button. This will help to prolong battery life.
batteries
The internal battery should last more than 5 years
When it needs replacing, a red LED will flash on the front of the unit
Follow the steps opposite to replace the battery
Use only good quality, 9V alkaline batteries type PP3
2. Remove switch
3. Lever out battery
cover
1. Remove front cover
4. Replace battery 5. Push into holder
7. Replace front cover
8. Activate
6. Replace switch cover
troubleshooting
Lights flicker when off Fan does not stop completely when off Contactor does not open when off
Remove the link wire to disable the locating ring—see “wiring” section
ratings
Voltage 230VAC +/- 10% Frequency 50Hz Temperature 0ºC to 35ºC Power 10A Compliance BS EN60669-2-1 & BS EN55015
EU registered design no. 000638069-0003, 000638069-0004
Recycling Information According to the W EEE (2002/96) and Battery directive (2006/66), at end of the life of the product or battery, you must dispose them at an appropriate collection point.
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
FM 45789 EMS 534520
Due to our policy of continual product im provement CP Electronics reserves the right to alter the specification of this product without prior notice.
C.P. Electronics Ltd
Brent Crescent London NW10 7XR United Kingdom Tel: + 44 (0) 333 900 0671 Fax: + 44 (0) 333 900 0674 www.green-iswitches.co.uk enquiry@green-iswitches.co.uk
Ref #WD264 Issue 3