COX SO-225, SO-300, SO-400, HO-225, HO-300 Installation And Operator's Manual

...
Page 1
Heating
Products
Commercial
Furnace
Installation
And
Manual
Nov-99
Page 2
Cox systems are shipped “ready to use”. All Employ qualified, experienced installers, to necessary standard equipment, controls, and wiring insure the safe and efficient operation of your are packaged with the heating systems. heating system. Use the supplied furnace and burner manual, together, to install the system.
TABLE OF CONTENTS
PACKING PROCEDURE…………2 SEQUENCE OF OPERATION…….. 8
FURNACE ASSEMBLY MAINTENANCE………………….. 9 DRAWINGS ….………………….. 3 WIRING DIAGRAM……………….10 FURNACE SPECIFICATIONS..…4 MISCELLANEOUS……………….. 11 CLEARANCES……………………5 A. FILTER RACK ……………….. 11
B. DRAFT HOOD ……………….. 11 INSTALLATION INSTRUCTIONS C. OIL BURNER BLAST TUBE A. GENERAL ...………………….. 5 LOCATION ………………….11 B. FLUE………...…………………5 D. BLEEDER TUBE …………….. 12 C. COMBUSTION AIR SUPPLY ……………………… 6 D. BLOWER ADJUSTMENT…… 6 E. BURNER INSTALLATION…. 7
PACKING
1 – Package - 1 – Package-
Prewired and tested furnace assembly: Gas or oil burner: 1- Heat exchanger/combustion chamber and 1- Oil or gas burner and controls casing 1- Oil nozzle 1- Blower and pulley 1- Instruction manual and literature 1- Motor and pulley 1- Gas burner mounting flange 1- Belt (2 on dual drives)
1- Instruction envelope and (2) wiring diagrams 1- Fan limit installed 1 – Package- 1- Oil burner mounting flange Draft control or draft hood
NOTE: Actual packing may vary according to sizes, weights, models, custom jobs, etc. Optional equipment may or may not be packed separately.
FOR YOUR SAFETY FOR YOUR SAFETY
If you smell gas: Do not store or use gasoline
1. Open windows or other flammable vapors
2. Don’t touch electrical switches and liquids in the vicinity of
3. Extinguish any open flame this or any other appliance.
4. Immediately call your gas supplier.
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference.
2
Page 3
ASSEMBLIES
A. Casing Jacket F. Stack B. Fan and Motor C. Felt Pad Exc D. Radiator I. Heat Exchanger Baffle N. Refractory Lining E. Radiator Baffle O. Burner Port
G. C H. Heat hanger M. Combustion Chamber
onnector L. Fiberglass Rope Seal
J. Air Tubes
K. Inspection Port
3
Page 4
SPECIFICATIONS
SO Series (Hor
izontal Units)
Model SO-300 400
utput BTU/HR 2 300,000 ,000 O
put-Gas BTU/HR 281,250 375,000 500,000
In
Input-Oil GPH 2.00 2.50 3.50
CFM @ .33WC ESP 2400 3000 4400 Blower Motor HP 3/4 1 1-1/2
Stack Diameter (in.) 9 10 12
SO-225 SO-
25,000 400
HO Series (High-Boy Units)
Model Output BTU/HR 225,000 300,000 400,000
Input –Gas BTU/HR 281,250 375,000 500,000
Input-Oil GPH 2.00 2.50 3.50
CFM @ .33 WC ESP 2400 3400 4400 Blower Motor HP 3/4 1 1-1/2
Stack Diameter (in.) 9 10 12
HO-225 HO-300 HO-400
LO-Series (Low-Boy Units)
Model LO-225 LO-300 LO-400 Output BTU/HR 225,000 300,000 400,000
Input-Gas BTU/HR 245,000 375,000 500,000
Input-Oil GPH 2.00 2.50 3.50
CFM @ .33 WC ESP 2400 3400 4800 Blower Motor HP 3/4 1 1-1/2
Stack Diameter (in.) 9 10 12
NOTES: 1. Gas burner through 40 ,000 BTU are AGA listed.
2. Oil Burner is UL listed
0
.
3. Rights retained to cha e specifications and ratings without notice or liability.
ng
4
Page 5
CLEARANCES
Un nstruction,
less materials used in building co
and/
or application of the heating equipment are of
such
a nature that local authorities to require
othe
rwise, the clearance about the furnace should be:
ABO
VE-6”, SIDES AND REAR-6”, FRONT-48”,
FLU
E PIPE-18”.
W
RNING: LO Models must be placed on non-
A
com
bustible flooring only.
SO
(Horizontal) clearances
Ma
be installed in an alcove with the following
y
clea
rances to unprotected combustible material:
6” a
ove furnace casing, bonnet or plenum.
b 6” above horizontal warm air duct within 6” of furn
ace.
48”
from front of furnace. 18” om flue pipe in any direction.
fr 6” f
rom back of furnace.
6” f right side of furnace.
rom
6” f
rom any side of plenum.
6” f floor.
rom
INSTALLATION A.
General
1.
When burner is furnished with separate flange, caution should be used to insure the air tube penetrating the chamber to within ½” of the inside chamber surface. (Don’t push in too
).
far
2. agram. One
Wire burner as per wiring di diagram is fixed to the inside of the
opy is placed with this manual.
and a c
3.
See installation and operation instructions for
lower drive adjustment in D.5.
b
4.
OIL MOTOR according to instructions on
tor.
mo
5.
Suspend SO units by means of inserting hanging
ds through hanging lugs on furnace. Mount
ro LO models on non-combustible floor only.
6. ing to NFPA standards
Must be installed accord for installation of oil burning equipment.
phlet No.31 or NO. 54 for gas.
Pam
7.
Must be installed according to Building Code
andards for the installation of heat producing
St appliances: heating, ventilating, air-
nditioning, warm air heating and ventilating
co systems
.
blower door
Area of room shall be not less than twice the area of the flue outlet.
Ready access shall be provided for components in service.
Draft regulator shall bear the listed mark
The combination fan and limit control sh control listee’s name and listed marking.
The safety control shall bear the contro name, listed markings and group designat
SO-300 and SO-400 “Air filters shall mounted on the unit or in the air duct syst ONLY.
8. Must be installed according to NFPA sta
for the installation of air-conditioning, warm air heating and ventilating systems.
9. Air requirement into the furnace room for
satisfactory combustion is an area not smaller than twice the cross sectional area of the flue pipe. See burner manual.
B. Flue
The chimney must be in good condition
cracks or openings or obstructions in the f sufficient height to prevent a down dr installing an oil burner, the smoke pipe and should be thoroughly cleaned and re required.
Minimum recommended chimney sizes: Oil
Two gallons of oil per hour and under ….. Two to three gallons of oil per hour…8”x1 Over three gallons of oil per hour….12”x1
All manual dampers sho smoke pipe before an oil b
lts the draft should beresu
inches at the inspection door and from .05 to .06
the ventilating opening into the furnace
all electrical
ing.
all bear the
l listee’s
ion.
not be
em.” UL
ndards
without
lue and of
aft. Before
chimney
paired if
8”x8”
2”
2”
uld be removed from the
urner is installed. For best
preferably from .02 to .03
5
Page 6
inches at the stack. measu
red with any good draft gauge.
Excessive draft causes high stack temperatures and consequently a waste of fuel. Therefore, a reliable draft regulator is strongly recommended for p
ractically all installations. Proper, uniform draft insures efficient, economical operation of the burner. A good draft regul sh
ort time through a substantial savings in fuel costs.
Minimum recommended chim
Draft Hood &
Input/hour
Up to 120,000…………………………... 5” 120,001-180,000………………………….. 6 180,001-250,000………………………….. 7” 250,001­320,001-410,000………… 410,001-510,000…………………… 510,001-610,000………… 610,001-730,000……………………… 730,001-860,000…………… 860,001-1,000,0 1,
NOTE: contains more than pipe and
C.
OIL
D install in rooms with insufficient air to sup ly combustion. Occasionally, it is necessary to inst to ent less atmospheric air pressure in the room. If there is a lack flame will be yellow and formation of soot will occur in heating unit ldings of conventional frame, brick or stone construction without utility rooms, basement win adeq r operation of the barometric draft control. For inst outs he outside should be made with a free cross sectional area of twic each GPH the ng by at least four percent. The ro
xhaust fans. Do not install an exhaust fan in this
e ro
320,000………………………….. 8”
000,001-1,140,000……………………… 15”
If the flue pipe exceeds 10 ft. in length, or
draft hood
Combustion Air Supply
o not p all windows or louvers in a door to these rooms,
obtain sufficient air and to prev
of combustion air, the burner
. In bui
dows, or stair doors, infiltration is normally
uate to provide air for combustion and fo
allation in an enclosed utility room with an
ide wall, a fresh air opening to t
e the area of the flue outlet of 100 sq. inches for
gallon nozzle size (Example: 10x10 for 1.00
). For each 1,000 feet above sea level, increase
fresh air openi
om should be isolated from any area served by
om.
The draft may be accurately
ator will usually pay for itself in a
ney sizes: Gas
Flue Pipe Size
……………….. 9”
…….. 10”
……………….. 11”
….. 12”
…………….. 13”
00………………………... 14”
2 elbows use next size larger
.
GAS
Fresh air requirement into the furnace room for
atisfac
s for each 1,000 BTU input and a minimum of 100 sq. in.
tory combustion is 1 square inch of free area
D. Blower Adjustment
Because the Cox Heating unit is so versatile in its application, it is impossible to be specific in
commending blower speed. Obvi
re quantity and quality of the duct work and the manner in which it is applied affects the air delivery.
To adjust blower speed to the applied conditions, it is recommended that the thermostat be set at highest setting to gain prolonged burner operation. By
f thermometers, adjust the blower speed
eans o
m
ntil the temperature rise through the unit is equal to
u
5 degrees – 80 degrees (difference in temperature
7
etween air entering and leaving the unit).
b
Unless the temperature of the air entering the units
excessively high (75 degrees or more) such
is
djustment will result in continued burner operation
a
ith a high limit setting of 180 degrees to 200
w
egrees. Should it be impossible to gain an 85
d
egree temperature rise through the unit, the
d
dications are that the fan is running too fast for the
in
en
int ded application of the furnace. Should the air
n
bei g su pplied to the unit be at a temperature higher than
95 degrees, the indications are that the heated
ir rcuited back to
leaving the unit is being short cia
th
e unit. The remedy is revision of the supply
system, return system, or both.
In
many instances, it will be possible to adjust the
low thermostat to highest
er speed by setting the
b
ti purposes of continued burner operation
t ng (for
se during adju 200 degrees, increasing then, the blower speed until the burner no longer cuts out on high limit. Should the burner cycle on high limit setting, indications are that the duct static pressure is higher than intended by the manufacturer, or the temperature of the air being supplied the unit is excessive. This latter method is foregoing paragraph which will be applied better qualified installer. Should the blowe cut out, indications are: inadequate firing rate, fa off setting too high, overload of motor, too temperature air supplied to the unit or a combin of same. Duct heaters have a minimum air requirement as given in “Furnace Specification” Section Chart.
NOTE: Do not exceed motor rating.
6
stment) and limit control 180 degrees to
not as reliable as that described in the
ously, the
by the
r
r moto
n
high
ation
Page 7
E. Burner Installation
OIL
Equipment – The following equipment shall be available on each oil burner installation before the tests are started:
1) Where the oil rate is not indicated on the
nozzle tip, a suitable device for determining the rate in terms of gallons per hour fed to the burner shall be used. This may be in the form of a graduated glass vessel.
2) A suitable flue gas analyzer for determining
the percentage of CO2 in the flue gases.
3) A suitable draft gauge graduated in
hundredths of an inch of water.
4) A suitable thermometer to indicate the
gas temperatures.
5) Provision for inserting a thermometer in
pipe as follows: Not more than 12” from furnace outlet, measured on the center li the flue pipe, there shall be a hole not m than ½” diameter, located at the side of pipe on the center line so that thermometer may be inserted horizontally.
The thermometer is to be placed so that
the
ensitive element is one fourth of the pipe diameter
s
rom the far side of the flue pipe. The opening around
f
he thermometer shall be sealed to prevent air
t
eakage. This same
l opening may be used for checking draft and sampling flue gases.
ocedure – The test procedure is as follows:
Test Pr
1 e burner shall be operated and the fuel rate
) Th
adjusted to that required for the particular installation.
2
) The draft then shall be adjusted to meet the
burner manufacturer’s specifications, both over the fire and at the breeching. Refer to “Installation Instructions” Section, B.
3
) Combustion air adjustments are to be made to
give the highest CO2 without visible smoke (unburned carbon) at the chimney. If the minimum required percentage of CO2 cannot be obtained in the breeching, it will be permissible to take CO2 over the fire, which will be acceptable. In this event, both CO2 readings shall be recorded after 10 minutes of operation.
Readings – During the period of operation to permit flue gas temperature to reach maximum, periodic readings of draft CO2 and oil rate shall be taken and the average recorded on the certificate.
All controls and limiting devices shall be checked for prop
er operation.
flue-
flue
the
n
e of
ore the the
Air for
Combustion – There must be openings into
the furnace room to admit free air to maintain combustion, minimum opening of not less than twice the area of flue outlet of furnace.
Size – The burner shall be of adequate size for the
furnace and the connected
mended on the oil bu
recom installer. Models and Firing Rate : See “Furnace Specification” Section.
heating load as
rner certificate by the
Certificate – Following installation of the burner, certain test data shall be obtained and recor
e installer on the oil burner certificate to be placed
th with each oil burner installation. The test shall cover the following points: CO2 in the flue gas by analysis, draft, stack temperature, firing rate, and smoke.
Requirements – The standard requirements as approved by the industry as follows:
1) CO2 – The CO2 in the flue gas by analysis
shall not be less than 8%.
2) Draft - The draft shall be in accordance with
specifications in the manufacturer’s installation manual. An automatic draft regulator or its equivalent is required.
3) Stack Temperature – The stack temperature
shall be measured on the furnace side of automatic draft regulator and not more than 12 inches from the smoke connection. The stack temperature shall be measured at the certified firing rate. If an automatic draft regulator is built into the furnace, such regulator shall be clos temperature is measured.
4) Firing rate – The firing rate shall be based on
the burner manufacturer’s recommendation for the existing total connected load. Burner shall be fired at that rate.
5) Smoke – During the above test, there shall be
no visible smoke at the chimney.
6) Installation Manual – The burner shall be
installed in accordance with manufacturer’s installation manual.
Fuel Tank Connections – Pipe connections between fuel tank and the oil burner should be made with 3/8” copper tubing and brass fittings, however, galvanized pipe is quite satisfactory. All joints should be sealed with key paste or other good oil resisting compound, and pulled up tight. Where fuel tank is installed in a basement, a one-pipe system to the burner will be found entirely satisfactory. When fuel ta
nnections should be arranged so they will not be
co
oken if the tank should settle. Always use a good
br leak-proof check valve in the suction lin
7
nk is buried underground, all pipe
ed when the stack
e.
ded by
Page 8
Adjusting the Burner – Afte
rn
b
u er, tank, and controls have been completed and
all wiring ca
1) Leave line switch open and set thermostat well
above room temperature.
2) Make sure that the resetting device on the control
panel is in operating position. Set can at gauge port or bleeder tube opening to
3)
ca pu res switch and replace plug or gauge.
Close line switch. The burner then should start.
4)
Check oil pressure and adjust, if necessary, to
5) 100 lbs.
Adjust air shutter on burner so that flame burns
6) clean with slightly smoky tips. Burner is shipped with air shutter closed.
Start and stop the burner several times by
7) op
8) Cl ad sh
AS
G
Size – The burner shall be adequate size for the furnace and the connected heating load as recommended on the gas burner certificate by the installer. Models and BTU input rating: See “Furnace Specification” Section.
refully checked.
tch oil. Close line switch and allow burner to
mp oil until flows clear. If control locks out,
et, and when oil comes out clear, open line
ening and closing main line switch. ose main line switch and change thermostat justment to below room temperature. Burner
ould stop.
r the installation of the
SEQUENCE OF OPERATION
OIL
Thermostat calls for heat. 1.
2. Protector relay energizes motor and ignition transformer. Pump supplies fuel to nozzle.
3. Burner ignites.
4. Furnace blower activates at blower “ON” setting.
5. Area is heated and thermostat is satisfied.
6. Protector relay de-energizes burner components.
7. Furnace blower continues to operate until fan
8. limit “OFF” setting.
9. End of cycle.
Certificate – Following the installation of the burner certain test data shall be obtained and recorded by the installer on the gas burner certificate to be placed wit each gas burner installation. The fo
llowing points: CO2 in the flue gas by analysis, draft,
stack temperature, firing rate.
test shall cover the
h
Requirements – The standard requirements as approved by the industry are as follows:
1) CO2 – The CO2 in
not be less than 8%.
2) Draft – The draft shall be in accordance with
specifications in the manufacturer’s installation manual. An automatic draft regulator or it’ equivalent is required.
3) Stack Temperature – The stack temperature shall
be measured on the furnace side of automatic draft regulato smoke connect measured at the certified firing rate. If an automatic draft regulator is built into the furnace, such regulator shall be closed when the stack te perature is measured.
4)
Firing Rate – The firing rate shall be based on the
burner manufacturer’s recommendation for the ex at
5)
Smoke – During the above test, there shall be no
vi ible smoke at the chimney.
6) In
in ma
r and not more than 12 inches from the
m
isting total connected load. Burner shall be fired that rate.
s
stallation Manual – The burner shall be in stalled
accordance with manufacturer’s installation
nual.
the flue gas by analysis shall
ion. The stack temperature shall be
GAS
1. h
T
ermostat calls for heat.
2.
Burner motor starts and spark ignition begins.
3. i
lot valve opens.
P
4.
Pilot ignites.
5. Fla
6. M .
7. Burner ignites.
8. Furnace blower activates at blower “ON” limit
9. Area is heated and the thermostat is satisfied.
10. Thermostat de-energizes burner components.
11. Furnace blower continues to operate until fan
12. End of cycle.
me sensor proves pilot.
ain gas valve is opened
setting.
limit “OFF” setting.
,
s
8
Page 9
MAINTENANCE
Servicing the Burner – After the burner installation
been put in service, it shou
has ld be rechecked during the first two weeks to make certain that it is
tioning properly. Note the com
func bustion is proper and there are no gas or oil leaks, also that the
rent controls perform correctly.
diffe
OIL
ery oil burner should be serviced a Ev t least once a year, preferably at the beginning of the heating season.
1) Remove electrode assembly and clean, replace
nozzle.
Oil motor.
2)
Check all oil lines con
3) nections and make sure that there are no leaks.
Clean strainers in fuel unit.
4)
5) Test starting and stopping of burner by moving thermostat.
Make certai
6) n that fire burns clean and that draft
gulator is in good working order and adjusted
re
r proper amount of draft.
fo
GAS
Every gas burner should be serviced at least once a year, preferably at the beginning of the heating season.
1) Check and adjust electrode assembly.
2) Oil motor.
3) Check all gas lines connections and make
sure that there are no leaks.
4) Test starting and stopping of burner by
moving thermostat.
5) Make certain that fire burns cle
draft regulator is in good working order and adjusted for proper amount of draft.
N
OTE: For complete burner operation
i nual.
nstructions see th e respective burner ma
an and that
Employ only qualified personnel to service heating
equipment. For safety, the main power switch must be in the “OFF” position.
1. Air filters – Inspect filters monthly and replace
or clean when necessary.
Oiling – Oil the burn2. er motor and blower motor according to the instructions on the motors. The blower bearing may be permanently lubricated and sealed and require no oil or grease.
3. Belts – Check belts for wear and proper tension.
Belts may stretch or wear and require replacement. Belt tension may be checked by, depressing the belt at a point halfway between the pulleys. The belt should travel one inch.
Burner – Refer to the manual that was supplied
4.
with the burner for speci nozzles should be replaced at least once in a season. Gas orifices should be cleaned yearly. Electrodes should be checked and set according to the burn housing should be cleaned if necessary.
er manual. The blower wheel and
fic information. Oil
5. Combustion – Using proper equipment, recheck
for proper and efficient combustion (No CO, or less than #
1 smoke, 8-9% CO2).
9
Page 10
10
Page 11
11
Page 12
12
Loading...