Cortex CT1001, CT1002 User Manual

Page 1
CT1001/CT1002 Touchscreen
Programmable Thermostat
Room
Running As SCHED
SYSTEM
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
WED
PM
AUTO
HEAT
Page 2
CT1001/CT1002 Touchscreen Programmable Thermostat
Contents
Application/Features................................................................................................................2
Specifications/Ordering Information........................................................................................ 4
Installation..............................................................................................................................14
Wiring.....................................................................................................................................18
Power the Thermostat............................................................................................................35
Installer Setup.........................................................................................................................48
Installer System Test...............................................................................................................59
Operation................................................................................................................................62
Programming ..........................................................................................................................68
Troubleshooting .…..................................................................................................................98
1t
Page 3
CT1001/CT1002 Touchscreen Programmable Thermostat
PRODUCT DATA
APPLICATION
The CT1001/CT1002 Touchscreen Programmable Thermostat is an effortless, 7-Day programmable thermostat that provides universal system compatibility, precise comfort control and is easy-to-program. The CT1001/CT1002 Thermostats provide temperature control for gas, oil, electric and heat pumps for up to 3 heats, 2 cool systems including dual fuel operation plus dehumidification control.
2t
Page 4
CT1001/CT1002 Touchscreen Programmable Thermostat
FEATURES
·Large, clear display with backlight shows the current and set temperature and thermostat in the dark.
·Menu-driven programming make setup effortless.
·Beautiful ergonomic design is smart and sophisticated to match your customer
lifestyle.
·Touchscreen interaction
·Real-time clock keeps time during power failures and automatically updates to
daylight savings.
·"Saving Changes" notification lets you know when the schedule changes have been saved.
·Change/check reminders let you know when to service or replace filters or batteries
·Various Hold options allow you to override the program schedule, as desired.
·Armchair programming allows you to remove the thermostat from the wall for
programming.
3
Page 5
CT1001/CT1002 Touchscreen Programmable Thermostat
SPECIFICATIONS
Thermostat Description:
Feature
Description
Powering methods
Common wire with battery backup
System types (up to3 heat/2 cool)
·Gas, oil or electric heat with air conditioning
·Warm air, hot water, high-efficiency furnaces, heat
pumps, steam and gravity
·Heat on
ly inclu
des power to open and power to close zone valves and normally-open zone valves
·Heat only with fan
·Cool only
·750 mV heating systems
Changeover
Manual or Auto changeover selectable
System setting
HEAT-OFF-COOL-AUTO (EMER for heat pumps)
Fan setting
AUTO-ON-CIRC
4
Page 6
CT1001/CT1002 Touchscreen Programmable Thermostat
Electrical Ratings:
Temperature Setting Range:
Heating: 40°F to 90°F (4°C to 32°C). Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature: 32°F to 120°F (0°C to 49°C).
Shipping Temperature: CT1001/CT1002 Thermostats: -30 °F to 150 °F
(-34.4°C to 65.6°C).
5
Terminal
Voltage (50/60 Hz)
Running Current
W Heating
20 - 30 VAC
1 AMP max.
W Heating (Power pile)
750 mVDC
100 mAMP
Y Cooling
20 - 30 VAC
1 AMP max.
G Fan
20 - 30 VAC
1 AMP max.
Page 7
CT1001/CT1002 Touchscreen Programmable Thermostat
Operating Relative Humidity (Non-condensing):
CT1002 Thermostats: 5% to 90%. IAS-1: 5% to 95%. OAS-1: 5% to 95%.
Humidity Setting Range (CT1002 models only): Cooling: 40% to 80% RH.
Humidity Display Range (CT1002 models only): 0% to 99%.
Cycle Rates (at 50% Load): Heating: Selectable 1 - 12 cycles per hour. Cooling: Selectable 1 - 6 cycles per hour.
Clock Accuracy: +/- 1 minute per month.
6
Batteries: Two replaceable AA alkaline batteries will power the thermostat when 24VAC common is not used. A non-replaceable lithium battery with ten-year life is inside the thermostat. Under normal use the lithium battery will maintain the calendar and time settings. The Alkaline batteries maintain the calendar and time after lithium battery is no longer functional.
Page 8
CT1001/CT1002 Touchscreen Programmable Thermostat
Cool Indication: CT1001/CT1002 Touchscreen Thermostats show "Cool On" on the screen when Cool is activated.
Heat Indication: CT1001/CT1002 Touchscreen Thermostats show "Heat On" on the screen when Heat is activated.
7
Auxiliary Heat Indication: CT1001/CT1002 Touchscreen Thermostats show "Aux Heat On" on the screen when Auxiliary Heat is activated.
Emergency Heat Indication: CT1001/CT1002 Touchscreen Thermostats show "Heat On" on the screen when Emergency Heat is activated and the System mode is in the EMER position.
Calibration: CT1001/CT1002 Touchscreen Thermostats are factory-calibrated and require no field calibration.
Page 9
CT1001/CT1002 Touchscreen Programmable Thermostat
ORDERING INFORMATION
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
8
Page 10
CT1001/CT1002 Touchscreen Programmable Thermostat
Nomenclature:
Series
System Stages
Application
CT1001 CT1002
3H/2C
CT1001 - Standard CT1002 - Humidity Sensor
Mounting Means: CT1001/CT1002 Touchscreen Thermostat: Mounts directly on the wall in the living space using mounting screws and anchors provided. Outdoor Sensor: Mounts outside of living space with mounting clip and screws provided. Remote Indoor Sensor: Mounts directly on the wall using mounting screws and anchors provided.
9
Dimensions:
1. CT1001/CT1002 Touchscreen Thermostat: see Fig 1.
2. CT1001/CT1002 Touchscreen Thermostat Back Case: see Fig. 2
3. CT1001/CT1002 Outdoor Sensor Mounting Clip: see Fig 3.
4. CT1001/CT1002 Cover Plate: see Fig 4.
Page 11
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 1. Touchscreen Thermostat dimensions in inches. (mm).
5.98 in.(152mm)
4.48in. (114mm)
1.235 in.(30.60mm)
Page 12
CT1001/CT1002 Touchscreen Programmable Thermostat
11
Fig. 2. Touchscreen Thermostat Back Case dimensions in inches. (mm).
1.51 in.(38.5mm) 0.84 in .(21.5mm)
1.77 in.(45mm)
1.67 in.(42.5mm)
Page 13
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 3. Outdoor Sensor Mounting Clip dimensions in inches. (mm).
12
R1.6 in.(4mm)
1.82 in.(46.3mm)
R0.04 in.(1mm)
R0.098 in.(2.5mm)
1.10 in.(28.1mm)
0.62 in.(16mm)
1.56 in .(39.7mm)
0.24 in.(6.2mm)
0.44 in .(11.2mm)
R0.098 in.(2.5mm)
0.08 in.(2mm)
1.49 in.(38mm)
0.17in .(4.2mm)
Page 14
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 4. Cover Plate dimensions in inches. (mm).
13
3.29 in.(83.5mm)
0.85 in .(21.5mm)
3.29 in.(83.5mm)
5.35 in.(136mm)
4.13 in.(105mm)
Page 15
CT1001/CT1002 Touchscreen Programmable Thermostat
INSTALLATION
When Installing this
Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Selecting
Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 5.
Do not install the thermostat where it can be affected by:
----Drafts or dead spots behind doors and in corners.
----Hot or cold air from ducts.
----Radiant heat from sun or appliances. Concealed pipes and chimneys.
----Unheated (uncooled) areas such as an outside wall behind the thermostat. 14
Page 16
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 5. Selecting thermostat location.
15
5FEET
1.5METERS
Page 17
CT1001/CT1002 Touchscreen Programmable Thermostat
Installing Wallplate
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage. Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall
1. Position and level the wallplate (for location only).
2. Use a pencil to mark the mounting holes.
3. Remove the wallplate from the wall and, if drywall, drill two holes in the wall, as marked.
For firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 6
5. Insert the mounting screws into the holes and tighten.
16
Page 18
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 6. Mounting wallplate.
17
WALL
WIRES THROUGH WALL AND WIRE SLOT
WALL ANCHORS
M0UNTING HOLES(2)
M0UNTING
SCREWS(2)
Page 19
CT1001/CT1002 Touchscreen Programmable Thermostat
WIRING (FIG. 9
-
21)
All wiring must comply with local electrical codes and ordinances.
1. Select set of terminal identifications (Table 1) that corresponds with system type (conventional or heat pump in Fig. 7).
2. Loosen the screws for the appropriate system type selected; see Table 1. See Table 2 for terminal designation descriptions. Insert wires in the terminal block under the loosened screw. See Fig. 8.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
6. See Fig. 9 through 21 for typical wiring hookups.
Fig. 7. Selecting terminal identifications for system type.
18
CONVENTIONAL
HEAT PUMP
SCREW TERMINALS
S1 S2 C R RC E L Y2 Y G
S1 S2 C R RC W W2 Y2 Y G
O/B AUX
Page 20
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 1. Selecting Terminal Identifications for System Type.
System Type
Wallplate Terminal
Identifications
Wiring Diagram
Reference
Standard Heat/Cool
Conventional
9, 10
Heat Only
Conventional
11
Heat Only with Fan
Conventional
12
Heat Only Power to open and power to
close zone valves
Conventional
13
Normally Open Zone Valves Heat Only
Conventional
14
Cool Only
Conventional
15
Standard Multistage up to 2 Heat/2 Cool
Conventional
16, 17
Heat Pump with No Auxiliary Heat
Heat Pump
18, 19
Heat Pump with Auxiliary Heat
Heat Pump
20, 21
19
Page 21
CT1001/CT1002 Touchscreen Programmable Thermostat
IMPORTANT: Use 18 gauge thermostat wires.
Fig. 8. Inserting wires in terminal block.
20
Page 22
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 2. Terminal Designation Descriptions.
Terminal Designation
Description
RC (see Note 1)
Power for cooling--connect to secondary side of cooling system transformer
R (see Note 1)
Power for heating--connect to secondary side of heating system transformer
C (see Note 2)
Common wire from secondary side of cooling system transformer
W
Heat relay
Y
Compressor contactor
G
Fan relay
Y2
Second stage cooling
W2
Second stage heat relay
O/B (see Note 3)
Changeover valve for heat pump systems
AUX
Auxiliary heat relay for heat pump systems
E
Emergency heat relay for heat pump systems
L (see note 4)
Equipment monitor for heat pump systems
S1, S2
Optional outdoor or indoor remote sensor
21
NOTES:
1. When used in a single-transformer system, leave metal jumper wire in place between RC and R. If used on a two-transformer system, remove metal jumper wire between RC and R.
2. Common wire is optional when thermostat is used with batteries.
3. If thermostat is configured for a heat pump system in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
4. L terminal is an input (system monitor) when the System mode is in the HEAT, OFF, COOL or AUTO position. L terminal is a 24VAC output when System mode is Emergency Heat. When using the L terminal connect the 24VAC Common. See LCD indications on page 90.
.
Page 23
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 9. Typical hookup of conventional single-stage heat and cool system with single
transformer (1H/1C conventional).
22
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
COMPRESSOR CONTACTOR
OPTIONAL 24VAC COMMON CONNECTION
R C
1
2
FAN RELAY
HEAT RELAY
Page 24
CT1001/CT1002 Touchscreen Programmable Thermostat
1.POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2.OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 10. Typical hookup of conventional single-stage heat and cool system with two
transformers (1H/1C conventional).
23
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE SENSOR
2
R
C
1
FAN RELAY
HEAT RELAY
R
C
1
COMPRESSOR CONTACTOR
OPTIONAL 24VAC COMMON CONNECTION
Page 25
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 11. Typical hookup of heat-only system (1H conventional).
24
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
HEAT RELAY
OPTIONAL 24VAC COMMON
CONNECTION
C
R
1
2
Page 26
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 12. Typical hookup of heat only system with fan (1H conventional).
25
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
HEAT RELAY
OPTIONAL 24VAC COMMON CONNECTION
R
C
1
2
FAN RELAY
Page 27
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 13. Typical hookup of heat only power to open and power to close zone valve
system.
26
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
R
C
1
2
W
B
R
TR
TR
MOTOR OR VALVE
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
Page 28
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 14. Typical hookup of heat only system with normally open zone valves.
27
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
NORMALLY OPEN
ZONE VALVE
OPTIONAL 24VAC COMMON CONNECTION
R
C
1
2
Page 29
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 15. Typical hookup of cool only system (1C conventional).
28
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
3
COMPRESSOR CONTACTOR
OPTIONAL 24VAC COMMON CONNECTION
R
C
1
2
FAN RELAY
Page 30
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 16. Typical hookup of conventional multistage two-stage heating and two-stage
cooling in a single-transformer system (2H/2C, 2H/1C or 1H/2C conventional).
29
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE SENSOR
3
OPTIONAL 24VAC COMMON CONNECTION MUST COME FROM THE COOLING TRANSFORMER
FAN RELAY
HEAT RELAY 1
HEAT RELAY 2
COOL RELAY 2
COOL RELAY 1
R
C
1
2
Page 31
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 17. Typical hookup of conventional multistage two-stage heating and two-stage
cooling in a two-transformer system (2H/2C, 2H/1C or1H/2C conventional).
30
CONVENTIONAL
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR TEMPERATURE SENSOR
2
OPTIONAL 24VAC COMMON CONNECTION MUST COME FROM THE COOLING TRANSFORMER
R
C
1
FAN RELAY
HEAT RELAY 1
HEAT RELAY 2
COOL RELAY 2
COOL RELAY 1
R
C
1
Page 32
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
4. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 18. Typical hookup of single-stage heat pump with no auxiliary/backup heat
(1H/1C heat pump).
31
HEAT PUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y G
O/B AUX
OUTDOOR/INDOOR TEMPERATURE SENSOR
4
2
R
C
1
CHANGEOVER VALVE
COMPRESSOR RELAY
FAN RELAY
OPTIONAL 24VAC COMMON
CONNECTION
3
Page 33
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE
USED AS A 24VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
4. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
5. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
Fig. 19. Typical hookup of multistage heat pump with no auxiliary/backup heat
(2H/2C heat pump).
32
HEAT PUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y G
O/B AUX
OUTDOOR/INDOOR TEMPERATURE SENSOR
2
R
C
1
CHANGEOVER VALVE
FAN RELAY
OPTIONAL 24VAC COMMON
CONNECTION
5
COMPRESSOR 2
COMPRESSOR 1
4
3
Page 34
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL
KIT.
4. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
5. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24VAC OUTPUT. SEE HEAT PUMP SECTION ON PAGE 90.
6. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 20. Typical hookup of single-stage heat pump with auxiliary/backup heat
(2H/1C heat pump).
33
3
4
HEAT PUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y G
O/B AUX
OUTDOOR/INDOOR TEMPERATURE SENSOR
2
R
C
1
CHANGEOVER VALVE
FAN RELAY
OPTIONAL 24VAC COMMON
CONNECTION
6
5
COMPRESSOR RELAY
EMERGENCY HEAT RELAY
HEAT 2 RELAY
(AUXILIARY HEAT)
EQUIPMENT
MONITOR
Page 35
CT1001/CT1002 Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL
KIT.
4. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
5. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24VAC OUTPUT. SEE HEAT PUMP SECTION ON PAGE 90.
6. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 21. Typical hookup of multistage heat pump with auxiliary/backup heat
(3H/2C heat pump).
34
3
4
HEAT PUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y G
O/B AUX
OUTDOOR/INDOOR TEMPERATURE SENSOR
2
R
C
1
CHANGEOVER VALVE
FAN RELAY
OPTIONAL 24VAC COMMON CONNECTION
6
5
COMPRESSOR 2
EMERGENCY HEAT RELAY
HEAT 2 RELAY
(AUXILIARY HEAT)
EQUIPMENT
MONITOR
COMPRESSOR 1
Page 36
CT1001/CT1002 Touchscreen Programmable Thermostat
POWER THE THERMOSTAT
Wiring
24VAC Common
· Single-Transformer
System:
Conn
ect the common side of the transformer to the C screw terminal of the thermostat
wallplate. Leave the metal jumper wire in place between RC and R.
·
Two Transformer System:
Connect power side of "Cooling" transformer to RC terminal. Remove factory installed
jumper. Connect common side of "COOLING" transformer to the compressor contactor, relay, etc. Connect power side of "HEATING" transformer to the R terminal. Connect the common side of the Heat relay to the C terminal.
35
You can choose from three methods to power the thermostat.
· Batteries only (AA alkaline).
· 24VAC common wire only.
· 24VAC common wire with battery backup (AA alkaline).
Page 37
CT1001/CT1002 Touchscreen Programmable Thermostat
Installing Batteries
1. Install Two AA alkaline batteries on the back of the thermostat as marked on the thermostat. See Fig. 22.
Fig. 22. Installing batteries.
2. Locate and remove the tab. See Fig. 23.
Fig. 23. Remove tab
on thermostat back.
36
BATTERIES(2)
- + - +
REMOVE
TAB
Page 38
CT1001/CT1002 Touchscreen Programmable Thermostat
Mount
Thermostat
to
Wallplate
1. Align the terminal screw blocks with the pins on the back of the thermostat. Push the
thermostat straight onto the wallplate until it snaps into place. See Fig 24.
Fig. 24. Mount thermostat to wallplate.
37
WALLPLATE
TERMINAL SCREW BLOCK
PINS ON BACK OF THERMOSTAT
Page 39
CT1001/CT1002 Touchscreen Programmable Thermostat
Locate and
Mount Outdoor
Temperature
Sensor (Optional)
Mount the sensor where (see Fig. 25):
·the settings cannot be tampered with.
·there is good air circulation.
·it can measure true outdoor ambient temperature.
·there is a flat surface.
·wire distance between sensor and thermostat should be 65.61 ft (20m).
Do not mount the sensor:
·in direct sunlight.
·where hot or cold air blows on the sensor. Discharge line from an outdoor compressor
unit, vent or fan causes inaccurate temperature readings.
·where snow, ice or debris can cover it. Use the following steps to mount the sensor:
1. Remove the sensor from the mounting clip.
2. Mark the area on the location selected for mounting the sensor mounting clip.
3. Mount the clip.
38
Page 40
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 25. Typical locations for ORS-1 Outdoor Sensor.
39
Page 41
CT1001/CT1002 Touchscreen Programmable Thermostat
CAUTION
Electrical Interference (Noise) Hazard. Can cause erratic system operation.
Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. Use shielded cable to reduce interference when rerouting is not possible.
IMPORTANT
Erratic temperature readings from a sensor can occur as a result of any of the wiring practices that are not to local and national electrical standards. Avoid these practices to assure correct operation. Use shielded cable to reduce interference if rerouting sensor wiring is not possible.
40
Page 42
CT1001/CT1002 Touchscreen Programmable Thermostat
CAUTION
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable code s, ordinances and regulations:
1. Wire Outdoor Sensor to S1and S2 terminals on the thermostat. If leadwire provided is not
long enough, you need an extra cable to reach the hole at location. a. Using color-coded, 18-gauge thermostat wire is recommended. For example of general wiring of sensor, see Fig. 26. b. Pigtail wiring can be used.
2. Mount Sensor in its mounting clip.
3. Plug wiring holes using non-hardening caulk or putty.
41
Be sure wires have a cable separate from the thermostat cable. Do not route temperature sensor wiring with building power wiring, next to control contactors or near light dimming circuits, electric motors or welding equipment. Avoid poor wiring connections. Avoid intermittent or missing building earth ground.
Page 43
CT1001/CT1002 Touchscreen Programmable Thermostat
1. USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.
2. PLUG WIRING HOLE WITH NON-HARDENING CAULK OR PUTTY.
Fig. 26. Wire Outdoor Sensor to the thermostat.
42
1 2 WIRING HOLE
THROUGH
STRUCTURE
ORS-01
Page 44
CT1001/CT1002 Touchscreen Programmable Thermostat
Locate and
Mount
Remote
Indoor
Temperature
Sensor (Optional)
1. Choose a location (see Fig. 27) for mounting the sensor on an inside wall about 5 ft (1.5m) above the floor.
2. Be sure wire distance between sensor and thermostat is less than 19.6 ft6m.
3. Make sure there is good air circulation at average temperature at the chosen location.
Avoid the following locations because they can introduce errors in sensor measurements. See Fig. 27. Hot areas caused by: (a) Concealed pipes or ducts. (b) Drafts from fireplaces or other heat sources. (c) Convection or radiant heat from the sun or electrical equipment. Cold areas caused by: (a) Concealed pipes or ducts. (b) Drafts from windows and doors.
Dead air areas: (a) Behind doors, furniture and curtains. (b) In corners and alcoves.
4. Mark the area on the wall selected for mounting the Sensor or junction box.
5. Run wire cable to a hole at the selected wall location. Pull approximately three inches of
wire through the opening. Color-coded, 18-gauge thermostat wire is recommended.
43
Page 45
CT1001/CT1002 Touchscreen Programmable Thermostat
44
Fig. 27. Typical location for Indoor Sensor.
5FEET
1.5METERS
Page 46
CT1001/CT1002 Touchscreen Programmable Thermostat
Wire
Indoor Sensor
CAUTION
Electrical Interference (Noise) Hazard. Can cause erratic system operation.
Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels.
Be sure wires have a separate cable from the thermostat cable. Do not route temperature sensor wiring with building power wiring, next to
control contactors or near light dimming circuits, electric motors or welding equipment. Avoid poor wiring connections. Avoid intermittent or missing building earth ground.
45
IMPORTANT
Erratic temperature readings from a sensor can occur as a result of any of the wiring practices described below. Avoid these practices to assure correct operation.
Page 47
CT1001/CT1002 Touchscreen Programmable Thermostat
CAUTION
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and regulations.
1. Wire Indoor Sensor to S1 and S2 terminals on the thermostat. For an example of general wiring of IRS-1, see Fig. 28 to wire one sensor and 29 to wire multiple sensors.
2. Push excess wire back into the hole. Plug the hole using non-hardening caulk, putty or insulation to prevent drafts from affecting performance.
3. Remove IRS-1 sensor cover.
4. Mount IRS-1 to the wall or junction box using the screws and anchors provided.
5. Level the IRS-1 for appearance only. Device functions correctly even when not level.
6. Install IRS-1 cover. 46
Page 48
CT1001/CT1002 Touchscreen Programmable Thermostat
Fig. 28. Wiring a single Indoor Sensor.
47
Fig. 29. Wiring Multiple Sensors.
1SENSORS MUST BE ARRANGED IN THIS CONFIGURATION TO OPERATE CORRECTLY.
2WIRES MUST HAVE A CABLE SEPARATE FROM THERMOSTAT CABLE.
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. IF MORE THAN ONE REMOTE SENSOR IS REQUIRED, REFER TO FIGURE 29.
3. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
R
C
1
2
IRS-01
3
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC
IRS-01
1
2
S1 S2 C R RC
1
2
IRS-01
IRS-01IRS-01
IRS-01 IRS-01 IRS-01
IRS-01 IRS-01 IRS-01
IRS-01 IRS-01IRS-01
Page 49
CT1001/CT1002 Touchscreen Programmable Thermostat
INSTALLER SETUP
Installer setup instructions intentionally
removed from online manual
48
Page 50
CT1001/CT1002 Touchscreen Programmable Thermostat
49
Installer setup instructions intentionally
removed from online manual
Page 51
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Date
(Year Upper)
Select first two digits of current calendar year
(20 for year 2001-2099).
It cannot be changed.
Date
(Year Lower)
Select last two digits of current calendar year (08 for year 2008, etc).
2001 - 2099 available.
Date (Month)
Select number that represents current calendar month.
Date (Day)
Select number that represents current calendar date.
Schedule Options
0-nonprogrammable. 4-7-day programmable.
When it is changed, the Schedule must be reprogrammed.
System Type
Selection
1-1 heat/1 cool conventional (factory setting). 2-single-stage heat pump (no auxiliary heat). 3-heat only conventional (no fan) Also for 750mV. 4-heat only conventional (with fan). 5-heat only (power to open and power to close zone valves or normally-open zone valves). 6-cool only conventional. 7-2 heat/1 cool heat pump (with auxiliary heat). 8-2 heat/2 cool multistage conventional. 9-2 heat/1 cool multistage conventional. 10-1 heat/2 cool multistage conventional. 11-2 heat/2cool heat pump (no auxiliary heat). 12-3 heat/2cool heat pump (with auxiliary heat).
Available options and defaults vary by thermostat. System selection automatically modifies some default settings and/or hides other Installer Setup options.
50
Table 3. Installer Setup Menu.
NOTE: For easier installer setup, write the selected options in the "INITIAL SETTING RECORD" column.
Page 52
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Fan Control in
Heating
0-gas or oil furnace equipment controls fan in heating (factory setting). 1-electric furnace thermostat controls fan in heating.
Only shown if conventional system is selected. If heat pump is chosen, fan defaults to electric.
Changeover Valve
O/B Terminal
Energized in Heating
or Cooling (Heat
Pumps Only)
0-changeover valve O/B terminal setting. 1-changeover valve O/B terminal is energized in heating.
Only shown if heat pump system is chosen.
Backup Heat Source
(Auxiliary Heat)
0-heat pump backup heat source is electric (factory setting). 1-heat pump backup heat source is fossil fuel.
Only shown if 2 heat/1 cool or 3 heat/2 cool heat pump is chosen.
External Fuel Fossil
Fuel Kit
0-no external fossil fuel kit is controlling heat pump backup heat. This thermostat controls the dual fuel. Must install outdoor sensor and set Installer Setup Number 0340 to number 2. 1-external fossil fuel kit is controlling heat pump backup heat.
Only shown if fossil fuel is chosen as backup heat source.
Cycles per hour (cph)
for 1st Stage
Compressor
3-cph recommended for compressors (factory setting).
1, 2, 4, 5, 6-other cycle rate settings.
Cycles per hour (cph)
for 2nd Stage
Compressor
3-cph recommended for compressors (factory setting).
1, 2, 4, 5, 6other cycle rate settings.
Only shown if two stages of cool are selected.
Table 3. Installer Setup Menu. (CONTINUED)
51
Page 53
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Cycles per hour (cph)
for 1st Stage
Conventional Heat
1- 1 cph used for steam and gravity. 3-3 cph used for hot water system and high
efficiency (90% or better) furnaces. 5-5 cph used for standard fossil fuel forced air (less
than 80% efficient) systems (factory setting) 9-9 cph used for electric furnaces. 2, 4, 6, 7, 8, 10, 11, 12other cycle rate settings.
Not shown if system selection is heat pump. Selection in this stage changes default cph for 2nd stage heat.
Cycles per hour (cph)
for 2nd Stage Heat
(Aux Heat for 2H/1C
Heat Pumps)
1-1 cph used for steam and gravity. 3-3 cph for hot water systems and high efficiency
(90% or better) furnaces. 5-5 cph for standard fossil fuel forced air (less than
90% efficient) systems (factory setting). 9-9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems. 2, 4, 6, 7, 8, 10, 11, 12other cycle rate settings.
Only shown if two stages of heat are selected.
Cycles per hour (cph) for 3rd Stage Heat Aux Heat for 3H/2C
(Heat Pumps)
1-1 cph used for steam and gravity. 3-3 cph for hot water systems and high efficiency
(90% or better) furnaces. 5-5 cph for standard fossil fuel forced air (less than
90% efficient) systems (factory setting). 9-9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems. 2, 4, 6, 7, 8, 10, 11, 12-other cycle rate settings.
Only shown if 3H/2C heat pump is selected.
52
Page 54
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Cycles per hour
(cph) for Emer
3-3 cph for hot water systems and high efficiency (90% or better) furnaces.
5-5 cph for standard fossil fuel forced air (less than 90% efficient or better) systems.
9-9 cph for electric strip heat for heat pumps.
Only shown if 2H/1C or 3H/2C heat pump is selected.
Continuous
Backlight
0-Backlight function disable. 1-Backlight function enable.
If set to 1 , the backlight will illuminate for 10 seconds after any touchscreen press.
Changeover
0-manual changeover (factory setting). 1-auto changeover.
Dead band
Heating and cooling set-points can be set no closer than chosen value:
2-2°F (1.5°C) 3-3°F (2°C) 4-4°F (2.5°C) 5-5°F (3°C) 6-6°F (3.5°C) 7-7°F (4°C) 8-8°F (4.5°C) 9-9°F (5°C)
Shown only if automatic changeover is selected.
Temperature
Indication
Scale
0-fahrenheit temperature display (factory setting).
1-celsius temperature display.
When it is changed, the schedule must be reprogrammed.
53
Page 55
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Daylight Savings
1-daylight savings is on (factory setting). 0-daylight savings is off.
Set to 0 in areas that do not follow daylight savings.
Remote
Temperature
Sensor (Outdoor or
Indoor)
0-no remote temperature sensor. 1-outdoor temperature sensor for display only. 2-outdoor temperature sensor for control.
Outdoor sensor used for Heat Pump Lockout settings. (See Heat Pump Temperature Lockout section for more details.).
3-indoor temperature sensor.
Defaults and Options depend on System Type selection.
Indoor Temperature Sensor uses an averaging network and does not include on-board sensor.
Heat Pump
Compressor
Lockout or (Balance
Point)
0-no compressor lockout. 15°F (-9.5°C) 20°F (-6.5°C) 25°F (-4°C) 30°F (-1°C) 35°F (1.5°C) 40°F (4.5°C) 45°F (7°C)
Default depends on other selections. Shown if control is selected. (See section for more information.)
54
Page 56
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Heat Pump
Auxiliary Lockout
0-no auxiliary heat lockout. 40°F (4.5°C) 45°F (7°C) 50°F (10°C) 55°F (13°C) 60°F (15.5°C)
Shown if electric is chosen for backup heat source and outdoor temperature sensor for control is selected. (See Advanced Features section for more information.)
Indoor
Dehumidification
Control
0-No indoor dehumidification control. 1-Dehumidification control activated.
Available on select models. If dehumidification control is activated and auto- changeover is selected in Installer Setup Number 0300, the dead band minimum is defaulted to 5°F (3°C) in Number 0310.
Filter Change
Reminder
0-furnace filter reminder off. 1-10 run time days. 2-30 run time days. 3-60 run time days. 4-90 run time days. 5-120 run time days. 6-365 run time days.
Run time based on call for fan.
55
Page 57
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Humidifier Pad
Replacement
Reminder
0-humidifier pad replacement reminder off. 1-90 calendar days. 2-180 calendar days. 3-365 calendar days.
UV Lamp
Replacement
Reminder
0-UV lamp replacement reminder off. 1-365 calendar days.
Adaptive Intelligent
Recovery
1-Adaptive Intelligent Recovery control is activated (system starts early so set-point is reached by start of program period).
0-Conventional Recovery (system starts recovery at programmed time).
Number of Periods
2-two periods available (Wake and Sleep) 4-four periods available (Wake, Day, Evening and Sleep).
Not shown if non- programmable is selected. 2 or 4 applies to all days of the week. When it is changed the schedule must be reprogrammed.
Minimum
Compressor
Off Time
5-five-minute compressor off-time setting (factory setting).
0, 2, 3, 4-other compressor off-time settings.
Heat Temperature
Range Stop
40-90-temperature range (1°F increments) of heating set-point.
Shown in 1/2 °C.
Cool Temperature
Range Stop
50-99-temperature range (1°F increments) of cooling set-point.
Shown in 1/2 °C.
Table 3. Installer Setup Menu. (CONTINUED)
56
Page 58
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting Record
Clock Format
12-12 hour clock (factory setting). 24-24 hour clock.
Extended Fan On
Time
Heat
0-no extended fan operation after call for heat ends.
90- fan operation is extended 90 seconds after call for heat ends.
Not shown if fan operation is set to fossil fuel or in Cool Only Systems.
Extended Fan On
Time
Cool
0-no extended fan operation after call for cool ends.
90-fan operation is extended 90 seconds after call for cool ends.
Not shown in Heat Only Systems.
Keypad Lockout
0-unlocked keypad. 1-partially locked keypad. 2-fully locked keypad.
Unlocked all functions are available. Partially locked only.
Temperature up and down keys and ability to enter and modify Installer Setup mode are available.
Fully locked only ability to enter and modify-Installer Setup mode are available.
Temperature Control
in Heat
1-less aggressive temperature control (could cause temperature undershoot).
2-Standard temperature control in heating (factory setting).
3-more aggressive temperature control (could cause temperature overshoot).
Applies to recovery ramp and use of auxiliary heat during recovery.
Choose 1 if getting temperature overshoot.
Choose 3 if getting temperature undershoot.
57
Page 59
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Notes
Initial Setting Record
Temperature
Control in
Cool
1-less aggressive temperature control (could cause temperature undershoot).
2-Standard temperature control in cooling (factory setting). 3-more aggressive temperature control (could cause temperature overshoot).
Applies to recovery ramp. Choose 1 if getting temperature overshoot. Choose 3 if getting temperature
undershoot.
Temperature
Display
Offset
-3°F (-1.5°C)
-2°F (-1°C)
-1°F (-.5°C) 0°F (0. °C) (no difference in displayed
temperature and actual room temperature )
1°F (.5°C) 2°F (1°C 3°F (1.5°C)
Reset Thermostat
0-no thermostat reset. 1-resets all Installer Setup Options to
default values and resets schedule to default setting.
Only calendar settings and time are retained.
Table 3. Installer Setup Menu. (CONTINUED)
58
Page 60
CT1001/CT1002 Touchscreen Programmable Thermostat
INSTALLER SYSTEM TEST
Use the Installer System Test to test the W1 W2 E AUX Y1 Y2 and L terminals.
CAUTION
Equipment Damage Hazard. Minimum compressor off time is bypassed during Installer System Test. Avoid cycling compressor quickly.
59
How
to
Use
the
Installer System Test
The Installer Test is part of the Installer Setup Menu.
1. Enter the Installer System Test by entering the Installer Setup.
2. Note that the test appears at the end of the Installer Setup Numbers.
3. See Fig. 30 to review how the thermostat buttons are used during the Installer System
Test. See Table 4 for available Installer System Tests.
Page 61
CT1001/CT1002 Touchscreen Programmable Thermostat
60
Fig. 30. Review thermostat buttons used during Installer System Test.
DONE
DOWN ARROW
TURNS THE SYSTER OFF
DONE KEY
EXITS INSTALLER SYSTEM TEST
UP ARROW
TURNS THE SYSTER ON
SYSTEM STAUS NUMBER
SYSTEM TEST NUMBER
UP ARROW KEY
ADVANCES TO
NEXT SYSTEM
TEST NUMBER
Page 62
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer System Tests
Table 4. Installer System Test.
System Test Number
Test Type
System Status Number and
Description
Test 1
Cooling System Test
1-Cool stage 1 and stage 2 turn on.
0-Cool is off.
Test 2
Fan System Test
1-Fan turns on. 0-Fan turns off.
Test 3
Heating System Test
1-Heat stage 1 and stage 2 (aux
heat) turn on.
0-Heat is off.
Test 4
Emergency Heat Test
1-Emergency heat and L turn on. 0-Emergency heat and L turns off.
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer System Test.
61
Page 63
CT1001/CT1002 Touchscreen Programmable Thermostat
OPERATION
Thermostat Keys
Thermostat Display
62
AM
TUE
SHOWS CURRENT DAY OF THE WEEK
SYSTEM
SHOWS CURRENT SYSTEM POSITION
RUNNING AS SCHED
SHOWS THE THERMOSTAT IS FOLLOWING THE PROGRAMMED SCHEDULE
TIME
DISPLAY CURRENT TIME OF DAY. HOLD TIME REMAINING OR NUMBER OF VACATION DAYS REMAINING
INSIDE TEMPERATURE
SHOWS THE CURRENT INSIDE TEMPERATURE
SET TO TEMPERATURE
SHOWS THE CURRENT SET TEMPERATURE
FAN
SHOWS FAN SETTING
Room
Running As SCHED
Set To
SYSTEM
COOL
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
TUE
AM
FAN
SELECTS ON/AUTO/CIRC
UP ARROW
RAISES
TEMPERATURE SETTING
DOWN ARROW
LOWERS TEMPERATURE SETTING
MORE
SHOWS ADDITIONAL
ACCESSORY AND MAINTENANCE OPTIONS
HOLD
SETS A PERMANENT HOLD AND ACTIVITIES VACATION HOLD
SYSTEM
SELECTS EM. HEAT/OFF/COOL AUTO/EMER
SCREEN
LOCKS OUT THE SCREEN TO ALLOW FOR CLEANING
CLOCK
SETS THE TIME FORWARD OR BACK
SCHED
ENTERS SCHEDULING MODE
Room
Running As SCHED
Set To
SYSTEM
COOL
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
TUE
Page 64
CT1001/CT1002 Touchscreen Programmable Thermostat
63
System and Fan
Settings
System
The SYSTEM key selections vary based on your heating and/or cooling system type.
HEAT Thermostat controls the heating system. OFF Both heating and cooling systems are off. COOL Thermostat controls the cooling system. AUTO Thermostat automatically changes between heating and cooling operation,
depending on indoor temperature.
EMER Emergency heat cycles to maintain temperature. Compressor is locked out (used
only for 2H/1C or 3H/2C heat pump systems) and auxiliary heat turns on as second stage if needed.
FAN The Fan key selections vary based on the heating and/or cooling system type.
ON Fan runs continuously. Use this setting for improved air circulation or for more
efficient central air cleaning.
AUTO Fan follows the fan program schedule. CIRC Fan runs randomly approximately 35% of the time when there is no call for cooling
or heating. Use this setting for improved air circulation or for more efficient central air cleaning when you do not want the fan running continuously.
Page 65
CT1001/CT1002 Touchscreen Programmable Thermostat
User
Setup
64
User setup instructions intentionally
removed from online manual
Page 66
CT1001/CT1002 Touchscreen Programmable Thermostat
65
User setup instructions intentionally
removed from online manual
Page 67
CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Date (Year Upper)
It cannot be changed.
Date (Year Lower)
Select last two digits of current calendar year (08 for year 2008, etc). Date (Month)
Select number of current calendar month (1-12).
Date (Day)
Select number of current calendar date (1-31).
Schedule Options
0-Non-programmable. 4-7-day programmable (factory setting)(when it is changed, the schedule need to be reprogrammed).
Display temperature in °F or °C
0-°F setting (factory setting). 1-°C setting.
Daylight savings time
1-Daylight Savings function is enabled. 0-Daylight Savings is disabled.
Furnace air filter
0-off (factory setting). 1-10 fan run time days (about one month). 2-30 fan run time days (about three months). 3-60 fan run time days (about six months). 4-90 fan run time days (about nine months). 5-120 fan run time days (about one year). 6-365 fan run time days (about three years).
Humidifier pad reminder
0-off. 1-3 months. 2-6 months. 3-12 months.
Table 5. User Setup Settings.
66
Page 68
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 5. User Setup Settings. (CONTINUED)
Installer Setup
Name
Settings
UV lamp reminder
0-off (factory setting). 1-1 year.
Number of schedule periods available
2-two (WAKE and SLEEP). 4-four (WAKE, DAY, EVENING, SLEEP) factory setting.
Clock format
12-12-hour clock (factory setting).
24-24-hour clock.
Screen lockout
0-all keys available; screen is unlocked (factory setting). 1-screen is partially locked. All key functions locked except Temperature Up and Down keys and Cancel key. 2-screen is fully locked
66
Page 69
CT1001/CT1002 Touchscreen Programmable Thermostat
PROGRAMMING
Preprogrammed
Energy Star Settings
Table 6 shows default program settings. Visit the Energy Star web site at www.energystar.gov for additional education and resources on programmable thermostats.
Table 6. Energy Star Default Program Settings.
68
Schedule Period
Time
Set-points
Fan Setting
Heat
Cool
WAKE
6:00AM
68°F (20°C)
78°F (26°C)
AUTO
DAY
8:00AM
60°F (16°C)
85°F (29°C)
AUTO
EVENING
4:00PM
68°F (20°C)
78°F (26°C)
AUTO
SLEEP
10:00PM
60°F (16°C)
82°F (28°C)
AUTO
Program
Heating and
Cooling
Schedule
Your thermostat can control up to four different schedule periods per day:
WAKE-Period when you awaken and want your home at a comfortable temperature. DAY-Period when you are away from home and want an energy-saving temperature. EVENING-Period when you return home and want your home back to a comfortable
temperature.
SLEEP-Period when you are asleep and want an energy-saving temperature.
NOTE: Schedule times are in 15 minute intervals.
Page 70
CT1001/CT1002 Touchscreen Programmable Thermostat
Edit
Schedule
1. Press SCHED key.
2. Press PROG DAY key to review the programs to see that the settings are compatible with your lifestyle.
69
3. Press the EDIT then you press PROG DAY key to select the program days.
Room
Running As SCHED
Set To
SYSTEM
COOL
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
PM
WED
MON TUE WED THU FRI
AM
HEAT
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
AUTO
FAN
PROG
DAY
COOL
EDIT
AUTO
PROG
Page 71
CT1001/CT1002 Touchscreen Programmable Thermostat
70
4. Press WAKE key. Once pressed, Wake flashes to show it is selected. Same as the other schedule.
5. Press Up and Down keys to modify time and heat and cool temperatures from this screen.
6. The Fan setting can be programmed for ON, AUTO, or CIRC for each period. Please see Fan Schedule for more information about the Programmable FAN.
MON TUE WED THU FRI
AM
HEAT
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
AUTO
FAN
CANCEL PERIOD
COOL
PROG
DAY
MON TUE WED THU FRI
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
PROG
DAY
Page 72
CT1001/CT1002 Touchscreen Programmable Thermostat
7. To exit schedule without saving changes, press CANCEL key any time.
Cancel a Schedule
Period
1. Press SCHED key.
2. Press EDIT key.
3. Select the Day(s) of the week desired.
4. Press schedule period you want to cancel
(WAKE, DAY, EVENING or SLEEP). Once selected, the period flashes.
5. Press CANCEL PERIOD key.
NOTE: To set a Program Schedule for the
remaining days of the week, repeat steps 1-6. Example: If MON – FRI was selected first, go back and repeat steps 1-6 for SAT and SUN.
6. The time, temperature(s) and fan setting
disappear. The bar above the selected period is removed, indicating the scheduled period was cancelled. NOTE: To reinstate a schedule period, press
arrow keys to set desired time and temperatures.
71
MON TUE WED THU FRI
AM
HEAT
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
AUTO
FAN
CANCEL PERIOD
COOL
PROG
DAY
Page 73
CT1001/CT1002 Touchscreen Programmable Thermostat
7. Press DONE key.
ON Fan runs continuously (programmable for
all schedule periods).
CIRC Fan runs randomly for approximately
35% of schedule period when there is no call for cooling or heating (programmable for all schedule periods).
Fan Schedule
Press FAN key while in the Scheduling Screen to program the System Fan. Choices available from the Scheduling Screen:
AUTO (default position)Fan runs with equipment. Programmable for all schedule periods (WAKE, DAY, EVENING and SLEEP).
72
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
AUTO
FAN
CANCEL PERIOD
COOL
PROG
DAY
MON TUE WED THU FRI
HEAT
MON TUE WED THU FRI
AM
HEAT
CANCEL
SLEEP
WAKE DAY
EVENING
DONE
AUTO
FAN
CANCEL PERIOD
COOL
EDIT
PROG
DAY
Page 74
CT1001/CT1002 Touchscreen Programmable Thermostat
Manual Override of Fan Schedule
Use FAN key to change fan work states by manual.
AUTO-fan is automatically following the Fan
schedule(choices are Auto, On or Circulate).
ON-
Fan runs randomly for approximately 35% of schedule period when there is no call for cooling or heating. CIRC- Fan circulates randomly for approximately 35% of time. When the program reaches to next schedule, the fan will run as the setting in the period.
Operate CT1001/CT1002 Touchscreen
Set
Time
1. Press CLOCK.
2. Use arrows to set current
73
CANCEL
DONE
AM
Page 75
CT1001/CT1002 Touchscreen Programmable Thermostat
74
IMPORTANT
The current day of the week should already be set correctly. If not, see Installer Setup to set the day.
Set
Temperature Overrides
The thermostat has three temperature override options: Override Until,
Permanent Override and Vacation Hold.
Override Until (TEMPORARY Override)
Holds temperature temporarily until the next scheduled period time or until time is selected.
1. Press the Up or Down arrow below to the temperature you want to adjust. Override Until and set time appears on the screen.
2. Press Up or Down arrow next to the Time to change the time to hold the adjusted temperature setting.
3. If you want to exit Override Until, please press the CANCEL key. Override Until will be also exit until reach the set time.
Room
Set To
SYSTEM
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
TUE
HEAT
CANCEL
Override Until
PM
Page 76
CT1001/CT1002 Touchscreen Programmable Thermostat
75
Vacation Hold Change temperature setting for a designated number of days. 1Press HOLD key twice. Screen shows Override Until and 1 DAYS. 2Press the Up and Down arrow keys to set the desired temperature while away on vacation. Notice that Override Until days is shown on the screen. (This is the time the Vacation Hold override expires after the number of day’s ends.) 3Press Up and Down arrow keys to change the number of Days you desire thermostat to override the schedule.
Permanent Override
Keep user set-point permanently. 1Press HOLD key once. Screen shows Permanent Override.
2. Press Up or Down arrow you want to adjust.
3. If you want to exit Permanent Override, please press the CANCEL key, or press the HOLD key then press the CANCEL key.
Room
Set To
SYSTEM
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
TUE
HEAT
CANCEL
Permanent Override
PM
Page 77
CT1001/CT1002 Touchscreen Programmable Thermostat
Clean Thermostat Screen
The thermostat has a touch screen interaction. Follow these steps to clean the screen without making thermostat parameter changes:
1. Press the SCREEN key. Thermostat locks out all touch keys for 30 seconds to allow for cleaning.
76
4. To cancel the Vacation Hold override early, press the CANCEL key.
NOTE: When the number of days of
Vacation Hold expires, the screen shows Running As SCHED to indicate that Vacation Hold has ended.
Room
Set To
SYSTEM
SCHED
CLOCK
SCREEN
AUTO
FAN
TUE
HEAT
Override Until
DAYS
CANCEL
CLEAN SCREEN
Page 78
CT1001/CT1002 Touchscreen Programmable Thermostat
2. Use damp cloth slightly moistened with water or household glass cleaner to clean the screen.
3. Repeat the above steps, as necessary.
IMPORTANT
Do not spray any type of liquid directly on the thermostat itself. If using household glass cleaner, spray cleaner on cloth. Then use a cloth to clean the thermostat screen.
4. Press the DONE key to return to the Home Screen and normal operation.
Replace Batteries
1. When the Battery indicator is flashing, replace the batteries promptly with two fresh AA alkaline batteries.
2. Remove thermostat from the wallplate by pulling straight out.
3. Remove the old batteries and insert two fresh AA alkaline batteries, as marked on the thermostat.
77
WALL
Page 79
CT1001/CT1002 Touchscreen Programmable Thermostat
4. Align the screw blocks with the pins on the back of the thermostat.
5. Push the thermostat straight onto the wallplate until it snaps into place.
78
BATTERIES(2)
- + - +
PINS ON BACK OF THERMOSTAT
WALLPLATE
TERMINAL SCREW BLOCK
Page 80
CT1001/CT1002 Touchscreen Programmable Thermostat
Battery Tips
1. Replace the batteries as soon as ―Batt‖ flashes in the display. The Battery indicator flashes in the display one month before the batteries run down completely.
2. Always use fresh AA alkaline batteries. Non-alkaline batteries do not last as long and can leak, causing thermostat damage.
3. Although the thermostat has a Low Battery indicator, replace the batteries once a year to prevent the thermostat and heating/cooling system from shutting down due to lack of battery power.
Screen Locks
Partially Locked Screen
When partially locked, the screen indicates Screen Locked for 5 to 7 seconds whenever the user attempts to press a key that is locked. Pressing a locked key, while Screen Locked is shown, flashes Screen Locked on the screen. In this mode, all keys are locked except the
Temperature Up and Down arrow keys: User can change temperature up or down but cannot change schedule settings. Temporary temperature change lasts until next scheduled period and that time shows on screen. To cancel temperature override and begin following schedule, press CANCEL key. To unlock screen, see Installer Setup section.
Fully Locked Screen
In this mode, all keys are locked and not functional. To unlock screen, see Installer Setup section. The screen continuously displays Screen Locked.
79
SCREEN LOCKED
PM
TUE
Room
Running As SCHED
Set To
SYSTEM
HEAT
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
Page 81
CT1001/CT1002 Touchscreen Programmable Thermostat
80
Outdoor
Temperature
If an outdoor temperature sensor is installed, the thermostat displays the outside temperature in the lower right corner of the Home Screen.
If thermostat is set to Auto Changeover System mode, press the MORE key until the outside temperature is shown on the screen. You can also press MORE key again to check and edit Filter Reminder if the Filter Change Reminder function is chosen. (Press MORE key again to check the humidity for CT1002 only)
TUE
AM
Room
Running As SCHED
Set To
SYSTEM
HEAT
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
Outside
CANCEL
DONE
Outside
MORE
Page 82
CT1001/CT1002 Touchscreen Programmable Thermostat
81
Remote
Indoor
Temperature
If a remote indoor temperature sensor is installed, the thermostat displays the inside temperature on the screen from the remote sensor(s).The thermostat internal temperature sensor is not used.
ONE REMOTE INDOOR SENSOR INSTALLED (OPTIONAL)
If one remote indoor temperature sensor is used, the screen showing the Inside temperature reading shows the temperature at the indoor remote sensor location. The thermostat internal temperature sensor is not used.
MULTIPLE REMOTE INDOOR SENSORS
INSTALLED (OPTIONAL)
If more than one remote indoor sensor is
used, the screen showing inside temperature
reading shows the average of all the remote
indoor sensors. The thermostat internal
temperature sensor is not used.
Room
Set To
SYSTEM
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
TUE
HEAT
Heat On
AM
Running As SCHED
Page 83
CT1001/CT1002 Touchscreen Programmable Thermostat
82
Indoor Air
Quality Reminders
Filter Change Reminder
The filter change reminder must be turned on from the Installer Setup. Once expired, the screen flashes RENEW FILTER. Press the RESET key to reset the change reminder.
NOTE: The days are counted as fan run time, so anytime the fan is running, the reminder is counting that time against the number of days selected.
The remaining run time days can be viewed by pressing the MORE key; the remaining days can be edited by using the MORE key or from the Installer Setup. To view or reset the reminder by following steps before it expires:
1. Press the MORE key until the filter reminder appears on the screen. This is the number of fan run-time days remaining on the filter reminder.
Room
Set To
SYSTEM
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
TUE
PM
HEAT
RESET
Override Until
RENEW FILTER
Room
Set To
SYSTEM
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
TUE
PM
HEAT
Page 84
CT1001/CT1002 Touchscreen Programmable Thermostat
83
2. Press the EDIT key.
4. Press the DONE key to go back to the viewing screen.
3. Use the Up and Down keys to change the number of run-time days.
CANCEL
DONE
DAYS
FILTER
RESET
MORE
EDIT
CANCEL
DONE
DAYS
FILTER
Page 85
CT1001/CT1002 Touchscreen Programmable Thermostat
84
5. Press the RESET key to activate the new number of days selected in the previous screen.
6. Press the DONE key to return to the Home Screen.
CANCEL
DONE
DAYS
FILTER
RESET
MORE
EDIT
Page 86
CT1001/CT1002 Touchscreen Programmable Thermostat
85
Humidifier Pad Reminder (CT1002 Only)
The Humidifier Pad change reminder must be
turned on from the Installer Setup. Once
expired, the screen flashes, Change
Humidifier Pad and a RESET key appear.
Press the RESET key to reset the change
reminder.
The remaining calendar days can be viewed
by pressing the MORE key. The remaining
days can be edited using the MORE key or
from the Installer Setup. To view or reset the
reminder before it expires; follow these steps
using the MORE key:
1. Press the MORE key until the Humidifier
Pad change reminder appears on the screen.
This is the number of calendar days remaining
on the Humidifier Pad reminder.
2. Press the EDIT key.
3. Use the Up and Down keys to change the
number of calendar days.
4. Press the DONE key to go back to the
viewing screen.
5. Press the RESET key to activate the new number of days selected in the previous screen.
6. Press the DONE key to return to the Home Screen.
UV Lamp Reminder
The UV Lamp change reminder must be turned on from the Installer Setup. Once expired, the screen flashes, Change UV Lamp and a RESET key appear. Press the RESET key to reset the change reminder.
1. Press the MORE key until the UV Lamp change reminder appears on the screen. This is the number of calendar days remaining on the UV Lamp reminder.
2. Press the EDIT key.
3. Use the Up and Down keys to change the number of calendar days.
4. Press the DONE key to go back to the viewing screen.
5. Press the RESET key to activate the new number of days selected in the previous screen.
6. Press the DONE key to return to the Home Screen.
Page 87
CT1001/CT1002 Touchscreen Programmable Thermostat
86
Temperature Recovery
The thermostat feature, Adaptive Intelligent Recovery,
eliminates all guesswork when setting the thermostat schedule. Simply set the program schedule to the time that the comfort temperature is desired. The thermostat then turns on the heating or cooling at just the right time to have the home reach the scheduled temperature at the scheduled time. For example get up at 6:00 AM and want the temperature to be 70°F. Set the Wake period for 6:00 AM and 70°F. The thermostat then turns on the heat before 6:00 AM to raise the temperature to 70°F by 6:00 AM. The thermostat alerts that the heating or cooling system to turn on before a scheduled time by showing Recovery on the screen.
Room
Set To
SYSTEM
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
TUE
Recovery
PM
HEAT
Page 88
CT1001/CT1002 Touchscreen Programmable Thermostat
When the minimum-off timer expires, Cool On or Heat Ona appears solidly in the display and the compressor and fan turn on.
a
Heat Pumps only
.
87
Minimum Off-Timer
The Thermostat has built-in compressor protection (minimum- off timer) that prevents the compressor from restarting too early after
a shutdown. The minimum-off timer is activated after the compressor turns off. If there is a call during the minimum-off timer, the thermostat shows Wait in the display.
Room
Running As SCHED
Set To
SYSTEM
COOL
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
PM
WED
Wait
Page 89
CT1001/CT1002 Touchscreen Programmable Thermostat
88
Inside Humidity Level (CT1002 Only)
Select models can sense the humidity level in the home. The humidity level in the home is shown in the lower right corner of the Home Screen.
If thermostat is set to Auto Changeover System mode, press the MORE key until the humidity level is shown on the screen.
.
THU
Room
Running As SCHED
Set To
SYSTEM
COOL
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
Humidity
PM
Humidity
CANCEL
DONE
Page 90
CT1001/CT1002 Touchscreen Programmable Thermostat
89
Control Dehumidification Setting (CT1002 Only)
Select models read the inside humidity level and allow for a dehumidification setting:
1. Press the MORE key until the inside humidity percent and dehumidification set-point are shown.
2. Use Up and Down arrow keys, located to the right of the dehumidifier set-point, to set desired humidity level dehumidification in the summer.
3. Press DONE key.
Dehumidification
Droop Control
(CT1002 Only)
The dehumidification control attempts to control to the user's humidity set-point by turning on the air conditioner. In extremely high humidity conditions, the thermostat keeps the air conditioner running (energizing Y and G) for up to 3°F below the temperature set-point. It does this while trying to achieve the desired humidity set-point and balancing that with the temperature set-point. The thermostat controls up to 3° F below the temperature setting until either the humidity is satisfied or conditions change.
Humidity
CANCEL
DONE
DEHUMIDIFICATION
Page 91
CT1001/CT1002 Touchscreen Programmable Thermostat
Special Heat Pump Operat
ion
Heat Pump Indication (Requires 24VAC Common
Connections)
E5 indication is located in the screen of the thermostat. It is only visible when lighted. When the L terminal is wired to an equipment monitor, this is operational in the HEAT, OFF, COOL or AUTO positions. When the ―E5‖ is illuminated call for service. See Fig. 31.
Fig. 31. L terminal switch to R (power)
side of system transformer.
Heat Pump Emergency Heat
LCD Indication (Requires 24VAC Common
Connection)
The thermostat indicates ―E5‖ indicator when the thermostat is in the Emergency Heat mode. The E5 is located in the LCD screen of the thermostat. It is visible only when on. When the thermostat is in the EMER system mode, the L terminal is continuously energized and the E5 is displayed.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Temperature Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) installed; the thermostat controls this function.
90
TUE
AM
Set To
SYSTEM
HEAT
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
Page 92
CT1001/CT1002 Touchscreen Programmable Thermostat
BALANCE POINT
OUTDOOR TEMPERATURE
COMPRESSOR ONLY
FOSSIL FUEL ONLY
Fig. 32. Dual Fuel Heat Pump Operation
in Heat mode with Balance Point Set.
91
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option to control the back up heat in Installer Setup Number 0210.
4. Choose Outdoor Temperature Sensor
for Heat Pump Temperature Lockouts Option in Installer Setup Number 0340.
5. Choose appropriate Balance Point Temperature in Installer Setup Number
0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected Balance Point Temperature (ISU 0350), only the compressor operates and the fan (G terminal) energizes when the thermostat calls for heat. See Fig. 32.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected Balance Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary heat) operates and the fan (G terminal) does not energize when the thermostat calls for heat.
Page 93
CT1001/CT1002 Touchscreen Programmable Thermostat
92
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the Emergency heat mode. When the thermostat is moved to the Emergency Heat position, the compressor is locked out. The first stage of heat is whatever is connected to the E terminal. The second stage of heat is what is connected to the Aux. terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Electric as Auxiliary (Backup) Heat Source in Installer Setup Number
0200.
3. Choose Outdoor Temperature Sensor for Control Option in Installer Setup Number 0340.
4. Choose Compressor Lockout Temperature in Installer Setup Number
0350.
5. Choose Auxiliary Lockout Temperature in Installer Setup Number
0360. NOTE: There is a 5°F dead band between the Compressor and Auxiliary Heat Lockout.
Page 94
CT1001/CT1002 Touchscreen Programmable Thermostat
Operation in Heat Mode
When the outdoor temperature is below the Compressor Lockout Temperature, only the
Auxiliary Heat operates. When the outdoor temperature is above the Auxiliary Lockout Temperature, only the Compressor operates. See Fig. 33.
AUXILIARY LOCKOUT
TEMPERATURE
COMPRESSOR
LOCKOUT
TEMPERATURE
OUTDOOR TEMPERATURE
BOTH
COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
COMPRESSOR
Fig. 33. Heat Pump Operation with Lockout
Temperatures Set.
When the outdoor temperature is between the
two temperatures, both the Compressor and
Auxiliary Heat operate.
Operation in Emergency Heat Mode
Once the thermostat is placed into the Emergency Heat mode, the compressor and auxiliary lockout features are turned off. In the Emergency heat mode, the compressor is locked out. The first stage of heat is whatever is connected to the E terminal. The second stage of heat is connected to the Aux. terminal. Usually the emergency and auxiliary heat sources are electric strip heat in these cases.
Operating Sequence
The thermostat energizes specific terminal(s), depending on the demand for heating, cooling or fan. The thermostat screen shows the time, inside temperature, system and fan selections. Additional indicators are shown when the heating, cooling or fan is energized. See Tables 7 - 9 for specification information.
93
Page 95
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 7. Sequence of Operation for Conventional Systems.
Table 8. Sequence of Operation for Power Open and Power Closed Valves or Normally
Open Valves.
94
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
OFF
AUTO
None
None
None
COOL
AUTO
None
None
None
COOL or AUTO
AUTO
Stage 1 Cooling
Y, G
Cool On
COOL or AUTO
AUTO
Stage 1 and Stage 2
Cooling
Y, Y2b, G
Cool On
HEAT
AUTO
None
None
None
HEAT or AUTO
AUTO
Stage 1 Heating
W, Ga
Heat On
HEAT or AUTO
AUTO
Stage 1 and Stage 2
Heating
W, W2c, Ga
Heat On
a
G energizes only if Installer Setup number 0180 is set to Electric.
b
If Installer Setup System type is set to two stages of cooling.
c
If Installer Setup System type is set to two stages of heating.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
OFF
AUTO
None
None
None
HEAT
N/A
None
Y
None
HEAT
N/A
Heat
W
Heat On
Page 96
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 9. Sequence of Operation for Heat Pump Systems.
95
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
OFF
AUTO
None
O/ Ba
None
COOL
AUTO
None
O/ Ba
None
COOL or AUTO
AUTO
Stage 1 Cooling
Y, G, O/Ba
Cool On
COOL or AUTO
AUTO
Stage 1 and Stage 2
Cooling
Y, Y2d, G, O/Ba
Cool On
HEAT
AUTO
None
O/Ba
None
HEAT or AUTO
AUTO
Stage 1 Heating
Y, G, O/Ba
Heat On
HEAT or AUTO
AUTO
Stage 1 and Stage 2
Heating
Y, AUXc, G, O/Ba
Aux Heat On
HEAT or AUTO
AUTO
Stage 1, 2 and 3
Heating
Y, Y2d, AUXe, G,
O/Ba
Aux Heat On
Em. HEAT
AUTO
None
L, O/Ba
None
Em. HEAT
AUTO
Stage 1 Heating
E, G, L, O/Ba
Heat On
Em. HEAT
AUTO
Stage 1 and Stage 2
Heating
E, AUX, G, L, O/Ba
Aux Heat On
a
Configure O/B in Installer Setup. Based on last piece of equipment called (cooling = O or
heating = B).
c
If Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.
d
If Installer Setup System Type is set to 3Heat/2Cool Heat Pump with Auxiliary Heat.
e
This terminal does not energize if Installer Setup System type is set to 2 Heat/2 Cool Heat
Pump with no Auxiliary Heat.
Page 97
CT1001/CT1002 Touchscreen Programmable Thermostat
Outdoor
Temperature
Sensor
Operation
When installed with Thermostat Installer Setup
Number 0340 set to 1 or 2, the outside
temperature can be displayed on the
thermostat. See Fig. 34.
Fig. 34. Outside temperature reading on
CT1001/CT1002 Thermostat.
The Outdoor Sensor converts outdoor
ambient temperature to a resistance that
the thermostat can interpret.
The sensor has a negative temperature
coefficient (NTC), which means that
resistance decreases as the temperature
increases.
Checkout
With an accurate thermometer (±1°F
[0.5°C]) measure the temperature at the
sensor location, allowing time for the
thermometer to stabilize before reading.
Calibration
The Outdoor Sensor is calibrated at the
factory and cannot be recalibrated in the
field.
96
TUE
AM
Room
Running As SCHED
Set To
SYSTEM
HEAT
MORE
SCHED
HOLD CLOCK
SCREEN
AUTO
FAN
Outside
Page 98
CT1001/CT1002 Touchscreen Programmable Thermostat
Remote
Indoor
Temperature
Sensor
Operation
When installed with Thermostat Installer
Setup Number 0340 set to 3, the remote
inside temperature is displayed on the
Thermostat Home Screen as Inside
Temperature. The thermostat internal
temperature sensor is not used. See Fig.
35.
Fig. 35. Inside temperature reading on
CT1001/CT1002 Thermostat.
The Wall Mount Temperature Sensor converts room temperature to a resistance that the thermostat can interpret.
The sensor has a negative temperature
coefficient (NTC), which means that resistance
decreases as the temperature increases.
The sensor can be used to provide one remote
sensor input (see Fig. 28) or as a temperature
averaging network with multiple Sensors
connected, as shown in Fig. 29.
Checkout
For best results, allow Wall Mount Temperature Sensor to absorb the air moving through the room for a minimum of twenty minutes before taking a resistance measurement.
With an accurate thermometer (±1°F [0.5°C])
measure the temperature at the sensor location,
allowing time for the thermometer to stabilize
before reading.
Calibration
The Wall Mount Temperature Sensor is calibrated at the factory and cannot be recalibrated in the field.
97
TUE
AM
Room
Running As SCHED
Set To
SYSTEM
HEAT
MORE
SCHED HOLD CLOCK
SCREEN
AUTO
FAN
Heat On
Page 99
CT1001/CT1002 Touchscreen Programmable Thermostat
TROUBLESHOOTING (TABLE 10)
Table 10. Troubleshooting.
Symptom
Possible Cause
Action
Display does not come on.
Thermostat is not being powered.
Check for 24VAC between C and RC. Check that AA batteries are installed correctly and are good.
Temperature settings do not change. The upper or lower temperature limits
were reached.
Check temperature set-points. Check Installer Setup Numbers 0600 and 0610; modify as needed.
The keypad is fully locked.
Check Installer Setup Number 0670 to change keypad locked options.
Heating or cooling does not come on.
Thermostat minimum off-time is activated.
Wait up to five minutes for the system to respond.
System selection is not set to Heat or Cool.
Set system Selection to correct position.
System type Selection is incorrect.
Check Installer Setup Number 0170 and make sure correct System type is chosen.
Thermostat is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running.
Heating or cooling equipment is not operating.
Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode.
98
Page 100
CT1001/CT1002 Touchscreen Programmable Thermostat
Table 10. Troubleshooting. (CONTINUED)
Symptom
Possible Cause
Action
Heat does not turn on (Heat On is solid in the display).
Heating equipment failure.
Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem. Check for 24VAC between the heat terminal (W) and transformer common. If 24VAC is present, the thermostat is functional. Check the heating equipment to find the cause of the problem.
Loose or broken wire connection between thermostat and heating equipment.
Check for 24VAC between the heat terminal (W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment.
Cooling does not turn on (Cool On is solid in the display)
Cooling equipment failure.
Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem. Check for 24VAC between the cool terminal (Y) and transformer common. If 24VAC is present, the thermostat is functional. Check the cooling equipment to find the cause of the problem.
99