Cornelius R-134A User Manual

IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (612) 422-3246
Installation/Service
Manual
VENTURE POST--MIX DISPENSER W/BUILT--IN COLD CARBONATOR (R--134A REFRIGERANT)
IMPORTANT:
TO THE INSTALLER. It is the responsibility of the Installer
to ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112. 1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local laws.
Part No. 312027000 July 18, 1995 Revised: April 1, 1999 Control Code D
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 1995--99Ó
PRINTED IN U.S.A
TABLE OF CONTENTS
SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RECOGNIZE SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNDERSTAND SIGNAL WORDS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOLLOW SAFETY INSTRUCTIONS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 (CARBON DIOXIDE) WARNING 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHIPPING, STORING, OR RELOCATING UNIT 1. . . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL DESCRIPTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT DESCRIPTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY REFERENCE INFORMATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THEORY OF OPERATION 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNPACKING AND INSPECTION 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IDENTIFICATION OF LOOSE-SHIPPED PARTS 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
SELECTING LOCATION 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLING WATER ONLY LEVER KIT (P/N 3297) ON UF-1 DISPENSING
VALVE 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLING UNIT 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUTTING HOLE IN COUNTERTOP 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING PLAIN WATER SOURCE LINE(S) TO UNIT 10. . . . . . . . . . . . .
CONNECTING SYRUP SOURCE LINES TO UNIT 12. . . . . . . . . . . . . . . . . . . . .
CONNECTING CO2 SOURCE LINE TO UNIT 13. . . . . . . . . . . . . . . . . . . . . . . . .
SEALING UNIT BASE TO COUNTERTOP 13. . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREPARING UNIT FOR OPERATION 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FILL WATER TANK AND STAR T REFRIGERATION SYSTEM 13. . . . . . . . . . .
UNIT OPERATION 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUST WATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED PRODUCT 15
OPERA TOR’S INSTRUCTIONS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
OPERATING CONTROLS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVE LEVER 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVE WITH WATER LEVER 17. . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVES KEYED LOCK-OUT SWITCH 17. . . . . . . . . . . . . . . . . .
UNIT POWER SWITCH (115 VAC, 60 HZ UNITS ONLY) 17. . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP MOTOR POWER SWITCH 17. . . . . . . . . . . . .
DAILY PRE-OPERATION CHECK 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT OPERATION 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENTS 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING CO2 REGULATORS 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING DISPENSING VALVE WATER FLOW RATE 18. . . . . . . . . . . . . .
ADJUSTING WATER-TO-SYRUP “RATIO” OF DISPENSED PRODUCT 18. .
REPLENISHING CO2 SUPPLY 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING SYRUP SUPPLY 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND SANITIZING 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY CLEANING OF UNIT 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i 312027000
TABLE OF CONTENTS (cont’d)
SANITIZING SYRUP SYSTEMS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHECKING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL
FOR RESTRICTIONS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHECKING ICE WATER BATH 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER
SYSTEM DISRUPTIONS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING CO2 GAS CHECK VALVES 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE AND MAINTENANCE 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREPARING UNIT FOR SHIPPING, STORING, OR RELOCATING 21. . . . . . . . . .
HOOD AND FRONT PANEL REMOVAL 21.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
HOOD REMOVAL 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FRONT ACCESS PANEL REMOVAL 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC INSPECTION 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENTS 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING CO2 REGULATORS 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING DISPENSING VALVES WATER FLOW RATE 23. . . . . . . . . . . . .
ADJUSTING WATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED
PRODUCT 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL 26. . . .
CHECKING ICE WATER BATH 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING WATER TANK 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND SANITIZING 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY CLEANING OF UNIT 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SANITIZING POST-MIX SYRUP SYSTEMS 29. . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER
SYSTEM DISRUPTIONS 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING CO2 SUPPLY 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING SYRUP SUPPLY 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYRUP TANK SYSTEM 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BAG-IN-BOX SYRUP SYSTEM 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYRUP FLAVOR CHANGE 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING CO2 SYSTEM CO2 GAS CHECK VALVES 35. . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
TROUBLESHOOTING POST-MIX SYSTEM SYSTEM 42. . . . . . . . . . . . . . . . . . . . . .
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH 42. . . . . . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 42. .. .. .. .. ..
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 43. . . . . . . . . .
DISPENSED PRODUCT CARBONATION TOO LOW. 43. . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR
BUT FOAMS IN CUP OR GLASS. 43.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING
VALVE. 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES. 44. . . . . . . .
ONLY CARBONATED WATER DISPENSED. 44. . . . . . . . . . . . . . . . . . . . . . . . . .
312027000
ii
TABLE OF CONTENTS (cont’d)
ONLY SYRUP DISPENSED. 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING REFRIGERATION SYSTEM 45. . . . . . . . . . . . . . . . . . . .
COMPRESSOR DOES NOT OPERATE. 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS PRODUCED. (NOTE: ICE BANK SHOULD JUST COVER CONTROL
BULB). 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM
SUFFICIENT ICE BANK. 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AGITATOR MOTOR NOT OPERATING. 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
FIGURE 1. VENTURE SIX-FLAVOR POST-MIX DISPENSER 3. . . . . . . . . . . . . . .
FIGURE 2. FLOW DIAGRAM (FIVE-FLAVOR UNIT WITH BUILT-IN COLD
CARBONATOR) 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. FLOW DIAGRAM (SIX-FLAVOR UNIT WITH BUILT-IN COLD
CARBONATOR) 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 4. SYRUP INLET SUPPLY LINE CONNECTIONS (SIX-FLAVOR
UNIT SHOWN) 11.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 5. DISPENSER COMPONENTS 22.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 6. SF-1 DISPENSING VALVE 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 7. UF-1 DISPENSING VALVE 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 8. WATER TANK 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 9. WATER STRAINER SCREEN AND DOUBLE-LIQUID CHECK
VALVE 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 10. LIQUID CHECK VALVE ASSEMBLY 34. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 11. CO2 GAS CHECK VALVE ASSEMBLY 35. . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 12. WIRING SCHEMATIC FOR ELECTRONIC ICE BANK CONTROL
(OPTIONAL) 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 13. WIRING DIAGRAM (50 AND 60 HZ UNIT WITH 1/3 H.P.
REFRIGERATION ASSEMBLY) 37. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 14. WIRING DIAGRAM (60 HZ UNIT WITH 1/4 H.P. REFRIGERATION
ASSEMBLY AND BUILT-IN COLD CARBONATOR) 38.. . . . . . . . . . . . . . . . . . . . . . .
FIGURE 15. WIRING DIAGRAM (50 HZ UNIT WITH 1/4 H.P. REFRIGERATION
ASSEMBLY AND BUILT-IN COLD CARBONATOR) 39.. . . . . . . . . . . . . . . . . . . . . . .
FIGURE 16. WIRING DIAGRAM (SF-1 DISPENSING VALVE) 40. . . . . . . . . . . . . . .
FIGURE 17. WIRING DIAGRAM (UF-1 DISPENSING VALVE) 40. . . . . . . . . . . . . . .
Page
LIST OF TABLES
TABLE 1. DESIGN DATA 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE 2. LOOSE-SHIPPED PARTS 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii 312027000
SAFETY INFORMATION
Recognize Safety Information
This is the safety-alert symbol. When you see this symbol on our machine or in this manual, be alert to the potentially of personal injury.
Follow recommended precautions and safe operating practices.
Understand Signal Words
A signal word - DANGER, WARNING, OR CAUTION is used with the safety-alert symbol. DANGER identi­fies the most serious hazards.
DANGER
Safety signs with signal word DANGER or WARNING are typically near specific hazards.
General precautions are listed on CAUTION safety signs. CAUTION also calls attention to safety mes­sages in this manual.
WARNING
CAUTION
Follow Safety Instructions
Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to use the controls properly . Do not let anyone operate the machine without instructions. Keep your machine in proper working condition. Unauthorized modifications to the machine may impair function and/or safety and affect the machine life.
CO2(Carbon Dioxide) Warning
CO2Displaces Oxygen. Strict Attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Person­nel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
Shipping, Storing, Or Relocating Unit
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient temperature will cause residual water remaining inside the Unit to freeze resulting in damage to internal components of the Unit.
1 312027000
THIS PAGE LEFT BLANK INTENTIONALLY
312027000
2
GENERAL INFORMATION
IMPORTANT: To the user of this manual - This manual is a guide for installing, operating, and main­taining this equipment. Refer to the Table of Contents for page location for detailed information per­taining to questions that arise during installation, operation, service, or maintenance of this equipment.
GENERAL DESCRIPTION
This section gives the Unit description, theory of operation, and design data for the five and six-flavor Ventures Post-Mix Dispensers with Built-In Cold Carbonators (hereafter referred to as Units).
This Unit must be installed and serviced by a qualified Service Person. This Unit contains no User serviceable parts.
UNIT DESCRIPTION
The Units are compact with high-impact and corrosion-resistant moulded lower housings and may be island­mounted or installed on a front or rear counter. Their refrigeration assemblies are the 1/3 H.P. drop-in type that can be easily removed for service and maintenance. The Units are equipped with built-in cold carbonators with their carbonated water tanks located inside the Units lower housings water tanks. Adjustable syrup flow regulators, located on the electrically operated dispensing valves, are easily accessible to control water-to-syrup “Ratio” of the dispensed product.
Installation of the Unit on a countertop, installation of LOOSE-SHIPPED PAR TS, connection of plain water and syrup supplies, adjustment of CO2regulators, filling water tank with water, and plugging the Unit power cord into an electrical outlet is all that is required for operation.
NOTE: Optional 4-inch Legs (P/N 314744000) that will elevate the Unit 4-inches above the countertop are available. When ordering legs, order a quantity of four.
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must
also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
FIGURE 1. VENTURE SIX-FLA VOR POST-MIX DISPENSER
3
312027000
WARRANTY REFERENCE INFORMATION
Warranty Registration Date
(to be filled out by customer) Unit Part Number: Serial Number: Install Date: Local Authorized
Service Center:
Table 1. Design Data
Unit Part Numbers see Unit Nameplate
Overall Dimensions:
Width 16-1/4 inches Height 27 5/8 inches Depth 24 1/2 inches
Weights:
Shipping (one carton) 127 Pounds Dry Weight (Approximate) 115 Pounds Ice Bank Weight (approximate) 30 Pounds Drop-In Refrigeration Assembly 66 Pounds
Water Tank Capacity (no ice bank) approximate 8-3/4 Gallons
Dispensing Rate:
12-0z Drinks 2/min. or below *70 (see NOTE)
NOTE: Number of drinks dispensed 40° F or below with 75° F syrup and water inlet temperature and 75° F ambient.
Refrigeration System:
Compressor Horsepower 1/3 H.P. Refrigerant Type and Amount See Unit Nameplate
Ambient Operating Temperature 40° F to 100° F
Electrical Requirements: See Unit Nameplate
312027000
4
THEORY OF OPERATION
(see applicable Figure 2 or 3)
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
NOTE: The six-flavor (see Figure 3) Unit was set up at the factory to dispense a still (noncarbonated) drink from No. 3 dispensing valve and carbonated drinks from the remaining dispensing valves.
A CO2cylinder delivers carbon dioxide (CO2) gas through adjustable CO2regulators to applicable syrup tanks or bag-in-box syrup system syrup pumps and to a built-in carbonator located inside the Unit. Plain water is pumped into the carbonator carbonated water tank by a water pump and is carbonated by regulated CO2gas pressure also entering the tank. When a dispensing valve is opened, CO2gas pressure exerted upon the syrup tank or on the bag-in-box system syrup pump, pushes syrup through the Unit syrup cooling coils, and on to the dispensing valve. Carbonated water is pushed by CO passes through the Unit carbonated water cooling coils, and on to the dispensing valve.
Syrup and carbonated water meet simultaneously at the dispensing valve resulting in a carbonated drink being dispensed. On the six-flavor Unit, a still (noncarbonated) drink is dispensed from the No. 3 dispensing valve in the same manner as the carbonated drink except plain water is substituted for carbonated water.
gas pressure from the carbonated water tank and
2
The carbonated water tank is replenished when the carbonated water level inside the tank drops, which in turn automatically starts the carbonator water pump. When the carbonated water level inside the tank has been re­plenished, the carbonated water pump will stop.
5
312027000
VALVE (5)
DISPENSING
1
CAP NUT
MANIFOLD
CARB WATER
2
3
4
5
DISPENSER
WATER TANK
CARBONATOR
LINE LEGEND
CO2PLAIN WATER
CARB WATER
SYRUP
CHECK
2
VALVE
CO
CHECK VALVE
DOUBLE LIQUID
WATER PUMP
FIGURE 2. FLOW DIAGRAM (FIVE-FLAVOR UNIT WITH BUILT-IN COLD CARBONATOR)
NOTE: SYRUP SOURCE MAY BE SYRUP
TANKS OR BAG-IN-BOX SYSTEM
SYRUP 1
SYRUP 2
SYRUP 3
SYRUP 4
SYRUP 5
INLET
2
CO
WATER TANK
CARBONATED
INLET
PLAIN WATER
CARBONATOR
312027000
6
VALVE (6)
DISPENSING
(NON-CARB)
STILL DRINK
1
2
CAP NUT
3
4
MANIFOLD
CARB WATER
CHECK
2
VALVE
CO
5
6
DISPENSER
WATER TANK
CARBONATOR
NOTE: SYRUP SOURCE MAY BE SYRUP
TANKS OR BAG-IN-BOX SYSTEM
CHECK VALVE
DOUBLE LIQUID
WATER PUMP
FIGURE 3. FLOW DIAGRAM (SIX-FLAVOR UNIT WITH BUILT-IN COLD CARBONATOR)
SYRUP 1
SYRUP 2
SYRUP 3
SYRUP 4
SYRUP 5
SYRUP 6
NO. 3 VALVE
PLAIN WATER
INLET
2
INLET
CO
PLAIN WATER
CARBONATOR
WATER TANK
CARBONATED
LINE LEGEND
CO2PLAIN WATER
CARB WATER
SYRUP
7
THIS PAGE LEFT BLANK INTENTIONALLY
312027000
8
INSTALLATION
This section covers unpacking and inspection, selecting location, installing the Unit, preparing the Unit for op­eration, and Unit operation.
UNPACKING AND INSPECTION
NOTE: The Unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any damage or irregularities should be noted at the time of delivery (or not later than 15 days from date of delivery) and immediately reported to the delivering carrier. Request a written inspec­tion report from Claims Inspector to substantiate any necessary claim. File claim with the delivering carrier, not with IMI Cornelius Inc.
1. After the Unit has been unpacked, remove shipping tape and other packing material.
2. Lift hood straight up and off the Unit.
3. Remove four shipping hex nuts that secure the drop-in refrigeration assembly in the Unit.
4. Unpack LOOSE-SHIPPED PARTS. Make sure all items are present and in good condition.
Table 2. Loose-Shipped Parts
Item
No. Part No. Name 5-FL 6-FL
1 317659039 Drip Tray 1 1 2 317660000 Cup Rest 1 1 3 3573 Rear access Panel 1 1 4 17619300 Adaptor Fitting, 7/16-20 (2) -- 1 5 187254000 Sheet Metal Screw, Phil Truss Hd; Type A, No. 6 by 3/8-in. Long 2 2 6 318516000 Drain Hose Clamp 1 1 7 311304000 Tapered Gasket, Black 2 2 8 309852000 Tubing Clamp, .669 I.D. Open .571 I.D. Closed 2 2 9 77040900 Fitting, 90° Swivel Elbow 1 1
10 3297 Water Only Lever Kit, UF-1 Dispensing Valve (see Note) -- 1
NOTE: Loose-shipped with Six-Flavor Dispensers equipped UF-1 dispensing valves.
IDENTIFICATION OF LOOSE-SHIPPED PARTS
1. DRIP TRAY (item 1) to be installed on the Unit, then CUP REST (item 2) to be installed in the drip tray .
2. REAR ACCESS PANEL (item 3) to be installed over Unit base back access hole if power cord, drain hoses, and inlet supply lines will not be routed out back of the Unit. Rear access panel to be secured to the Unit with SHEET METAL SCREWS (item 5).
3. FITTING (item 4) is used to connect plain water inlet source line to the six-flavor Dispenser plain water inlet line that provides plain water to the No. 3 dispensing valve.
4. DRAIN HOSE CLAMP (item 6) is used to connect drain hose (not provided) to the Dispenser drip tray.
5. FITTING, 90° SWIVEL ELBOW (item 9) is used to connect plain water source line to the carbonator water pump inlet fitting. TAPERED GASKET, BLACK (item 7) is used to seal the connection.TUBING CLAMP (item 8) is used to secure the plain water source inlet line when connected to the 90° swivel elbow installed on the carbonator water pump.
9
312027000
SELECTING LOCATION
CAUTION: This Unit is intended for indoor installation only. Do not install this Unit in an outdoor environment which would expose it to the outside elements.
This Unit may be island-mounted or installed on a front or rear counter. Locate the Unit so the following requirements are satisfied:
DANGER: To avoid possible fatal electrical shock or serious injury to the operator, it is required that a GFCI (ground fault circuit interrupt) be installed in the electrical circuit for the domestic Units. It is required that an ELCB (earth leakage circuit breaker) be
installed in the electrical circuit for the export Units
1. The Unit must be installed near a properly grounded electrical outlet with proper electrical require­ments.The electrical circuit must be properly fused (slow-blow type fuse) or the circuit must be connected through an equivalent HACR circuit breaker.The electrical outlet must be accessible for ease of connecting and disconnecting the Unit power cord. No other electrical equipment should be connected to this circuit.
REFER TO UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE, HZ, AND THE MINIMUM CIRCUIT AMPACITY OF THE UNIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.
CAUTION: Do not place or store anything on top of the Unit.
2. A minimum of 15-inches clearance must be maintained above the Unit to the nearest obstruction (shelf, cupboard, ceiling, etc.) and 6-inches clearance between back-side of the Unit and the wall. The front grille of the Unit must be unobstructed to allow air to enter the hood.
3. Close to a permanent drain to route drip tray drain hose and water tank drain hose.
INSTALLING WATER ONLY LEVER KIT (P/N 3297) ON UF-1 DISPENSING VAL VE
The WATER ONLY LEVER KIT, UF-1 DISPENSING VALVE (item 10) is loose-shipped with all six-flavor Dispensers equipped with UF-1 dispensing valves. Installation of this kit on the dispensing valve allows plain or carbonated (depending on which dispensing valve the kit has been installed on) water only to be dispensed. If desired, the kit may be installed at this time following instructions included with the kit.
INSTALLING UNIT
NOTE: Optional 4-inch Legs (P/N 314744000) that will elevate the Unit 4-inches above the countertop are available. When ordering legs, order a quantity of four.
CUTTING HOLE IN COUNTERTOP
Place Unit in location on the countertop flush with the countertop edge. Mark Unit center line on edge of the countertop, then move Unit off to one side. Starting at center line mark on edge of the countertop, measure back 8-inches for location of the 2-1/2-inch diameter hole to be cut in the countertop. Cut a 2-1/2-inch hole in the countertop where indicated. Place the Unit in position over the hole.
CONNECTING PLAIN W ATER SOURCE LINE(S) TO UNIT
(see applicable Figure 2 or 3 and Figure 4)
NOTE: IMI Cornelius Inc. recommends that a water shutoff valve and water filter be installed in the plain water inlet supply line (see applicable Figure 2 or 3) . A Cornelius Water Filter (P/N 313860000) and Quick Disconnect Set (P/N 313867000) are recommended.
312027000
10
DISPENSING VALVE
RELEASE LATCH
DISPENSING VALVE
BLOCK
SYRUP INLET
TUBES (6)
FIGURE 4. SYRUP INLET SUPPLY LINE CONNECTIONS (SIX-FLAVOR UNIT SHOWN)
11
312027000
IMPORTANT: TO THE INSTALLER. It is the responsibility of the Installer to ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112. 1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local laws.
CAUTION: Check the minimum flow rate and maximum pressure of plain water inlet supply line. MINIMUM FLOW RA TE MUST BE AT LEAST 100-GALLONS PER HOUR. If flow rate is
less than 100-gallons per hour, starving of carbonator water pump will occur. Starving will allow water pump to overheat and will damage the pump. Overheating could occur if plain water inlet supply line flow rate drops below 100-gallons per hour. CARBONATOR CO2OPERA TING PRESSURE MUST EXCEED WATER PRESSURE BY 10 PSI. (Example: CO2operating pressure is 80 psi, maximum water pressure can be no more than 70 psi, etc.) Water over pressure (higher than CO2operating pressure) can cause carbonator flooding, malfunction, and leakage through carbonator relief valve. If water is exceeding maximum pressure specifications, a Water Pressure Regulator Kit (P/N 317589000) or equivalent must be installed in plain water inlet supply line.
Five and Six-Flavor Units (see applicable Figure 2 or 3)
1. Route plain water source line from plain water source up to location under the countertop.
2. Remove Unit front access panel as follows: A. Remove drip tray from the Unit. B. Remove two screws securing front access panel to the Unit. C. Pull front access panel down and out to remove for access to front of the Unit.
3. Route plain water source line up through hole cut in the countertop, up across front of the Unit, to the car­bonator water pump.
4. Install FITTING, 90° SWIVEL ELBOW (item 9) on end of the plain water source line and secure with TUBING CLAMP (item 8).
5. Connect plain water source line 90° elbow to the carbonator water pump inlet fitting. Seal connection with TAPERED GASKET, BLACK (item 7).
Six-Flavor Units (see Figure 3)
NOTE: The six-flavor (see Figure 3) Unit was set up at the factory to dispense a still (noncarbonated) drink from No. 3 dispensing valve and carbonated drinks from the remaining dispensing valves.
1. Route plain water source line up to back side of the Unit.
2. Connect plain water source line to the Unit labeled plain water inlet line protruding out back of the Unit with ADAPTOR FITTING (item 4). This water line provides plain water to the Unit No. 3 dispensing valve which dispenses a still (non-carbonated) drink.
CONNECTING SYRUP SOURCE LINES TO UNIT
(see applicable Figure 2 or 3 and Figure 4)
NOTE: The Unit syrup inlet lines are labeled to identify the dispensing valves they serve. For example, the line labeled “S1” must be connected to the syrup source line that provides syrup to be dispensed from the No. 1 dispensing valve (No. 1 dispensing valve is the valve on the right side when facing front of the Unit).
312027000
12
1. Route syrup source lines from the syrup tanks location up to location under the countertop.
2. Route syrup source lines up through hole cut in the countertop to the barbed and labeled syrup inlet lines on front of the Unit.
3. Connect the syrup source lines to the Unit barbed and labeled syrup inlet lines. Secure connections with tubing clamps.
CONNECTING CO2SOURCE LINE TO UNIT
(see applicable Figure 2 or 3 and Figure 4)
1. Route CO2source line up to back side of the Unit.
2. Connect CO2source line to Unit labeled CO2inlet line. Seal connection with a tapered gasket.
SEALING UNIT BASE TO COUNTERTOP
1. To comply with NSF International (NSF) requirements within the United States, the Unit base must be sealed to the countertop and all access holes to the Unit base must be completely sealed with a silastic sealant such as Dow Corning RTV 731 or equivalent after completing installation of the Unit. Proceed as follows to seal the Unit base to the countertop.
A. Tilt Unit up to expose bottom of the Unit base. B. Connect a length of drain hose (not provided), long enough to reach a permanent drain, to drain fitting
on back side of the drip tray pan. Secure connection with DRAIN HOSE CLAMP (item 6).
C. Liberally apply silastic sealant such as Dow Corning RTV 731 or equivalent on the Unit base bottom
edges.
NOTE: Do not move Unit after positioning or seal from base to countertop will be broken.
D. Route drip tray drain hose down through hole in countertop, then lower Unit into operating position on
the countertop to complete seal from Unit base to the countertop.
E. Apply additional sealant around bottom of the base.The seal must have a minimum radius of 1/2-inch
to prevent crevices and to ensure a complete seal.
NOTE: Connection of drip tray drain hose to a permanent drain is recommended. Drip tray drain hose routed to waste container is not recommended due to sanitation and cleaning problems.
F. Route lower end of drip tray drain hose to and connect to a permanent drain. G. Install DRIP TRAY (item 1) in position on the Unit, then place CUP REST (item 2) in the drip tray .
PREPARING UNIT FOR OPERATION
FILL W ATER TANK AND START REFRIGERATION SYSTEM
(see Figure 5)
1. Make sure plug in the water tank drain hose is secure.
NOTE: Use low-mineral-content water where a local water problem exists.
2. Remove plug from the drop-in refrigeration assembly platform water fill hole. Fill the water tank with clean water until water runs out of the overflow groove on top front of the tank into the drip tray . USE LOW-MIN- ERAL-CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS. When the water tank is full, the water level in the clear plastic water level tube should be approximately one inch from end of the tube.
13
312027000
3. Install plug in water fill hole.
4. 115 VAC, 60 HZUnits. Make sure the main power switch on right side of the Unit (see Figure 5) is in the “OFF” position.
115 VAC, 60 HZUnits and 230 VAC, 50 HZUnits.
Make sure the carbonator water pump motor power switch located on the drop-in refrigeration assembly electrical control box (see Figure 5) is in the “OFF” position.
WARNING: Unit must be electrically grounded to avoid possible fatal electrical shock or serious injury to the operator. Unit power cord is equipped with a three-prong plug. If a three-hole (grounded) electrical outlet is not available, use an approved method to ground
the Unit.
5. Plug Unit power cord into a properly grounded electrical outlet.
6. 115 VAC, 60 HZUnits. A. Plug Unit power cord into an accessible and properly grounded electrical outlet with GFCI (ground
fault circuit interrupt).
B. Place Unit main power switch on right side of the Unit in the “ON” position. The compressor, condens-
er fan motor, and agitator motor will start and begin forming an ice bank. When full ice bank has been formed, the compressor and condenser fan motor will stop but the agitator motor will continue to oper­ate circulating ice water bath in the water tank.
7. 230 VAC, 50 HZUnits. A. Plug Unit power cord into an accessible and properly grounded electrical outlet with ELCB (earth
leakage circuit breaker). The compressor, condenser fan motor, and agitator motor will start and begin forming an ice bank. When full ice bank has been formed, the compressor and condenser fan motor will stop but the agitator motor will continue to operate circulating ice water bath in the water tank.
UNIT OPERATION
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
CAUTION: Before opening CO2cylinder shutoff valve, turn secondary CO2regulators
adjusting screws to the left (counterclockwise) until all tension is relieved from adjusting
screws springs.
1. Open (counterclockwise) the CO2cylinder shutoff valve slightly to allow the lines to slowly fill with gas, then open the valve fully to back-seat the valve. (back-seating the valve prevents leakage around the valve shaft). Check for CO2leaks.
2. Adjust CO2regulator (regulator that controls the Unit built-in cold carbonator CO2pressure) as instructed in the SERVICE AND MAINTENANCE section of this manual. Check for CO2leaks and repair if evident..
312027000
14
3. Open the plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose connections.
4. Place the carbonator water pump motor power switch (located on the refrigeration assembly control box) in the “ON” position. The carbonator water pump will start and continue to operate until the carbonated water tank has been filled, then the water pump motor will stop. Check for CO2, plain water, and carbonated wa­ter leaks and tighten any loose connections.
5. Adjust the syrup tanks CO2regulators as instructed in SERVICE AND MAINTENANCE section of this manual.
6. Install full syrup tanks into the syrup systems.
7. Make sure keyed lock-out switch (left-side facing front of Unit) is in the “ON” (vertical) position.
8. Dispense from each dispensing valve until air is bled from the systems and until syrup and applicable plain or carbonated water are dispensed.
9. Check for syrup and water leaks and repair any leaks.
10. Install the Unit hood and secure with screw.
ADJUST W ATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED PRODUCT
1. Adjust the dispensing valves for water flow rate as instructed in SERVICE AND MAINTENANCE section of this manual.
2. Adjust the dispensing valves for Water-to-Syrup “Ratio” (Brix) of dispensed product as instructed in SERVICE AND MAINTENANCE section of this manual.
3. Seal all access holes to the Unit with a silastic sealant such as Dow Corning RTV 731 or equivalent.
4. Install Unit front access panel and secure with two screws.
5. Install drip tray on the Unit.
15
312027000
THIS PAGE LEFT BLANK INTENTIONALLY
312027000 16
OPERATOR’S INSTRUCTIONS
This section covers operating controls, daily pre-operation check, Unit operation, adjustments, replenishing CO2and syrup supplies, cleaning and sanitizing, checking the drop-in refrigeration assembly condenser coil for restrictions, checking the ice water bath, water pump yearly maintenance, and periodic cleaning of the CO2gas check valves.
WARNING: Disconnect electrical power to the Unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or electrical wiring.
CAUTION: Do not place or store anything on top of the Unit.
OPERATING CONTROLS
(see Figure 5)
DISPENSING VALVE LEVER
The dispensing valve lever, located on bottom of the valve, needs only to be pressed with cup or glass to dis­pense product.
DISPENSING VALVE WITH WATER LEVER
The dispensing valve water lever will dispense only water when actuated.
DISPENSING VALVES KEYED LOCK-OUT SWITCH
The dispensing valves keyed lock-out switch, located on the left side of Unit (see Figure 5), must be in the “ON” (vertical) position to operate the electric dispensing valves. The keyed lock-out switch in the “OFF” (horizontal) position turns off electrical power to the dispensing valves only, but the refrigeration system will continue to operate.
UNIT POWER SWITCH (115 VAC, 60 HZUNITS ONLY)
The Unit power switch, located on the right side of the Unit (see Figure 5), must be in the “ON” position before the Unit will operate.
CARBONATOR W ATER PUMP MOTOR POWER SWITCH
The carbonator water pump motor power switch, located on the refrigeration assembly control box, (see Figure
5), must be in the “ON” position before the carbonator water pump motor will operate. The purpose of the power switch is to turn off the carbonator water pump motor for service and maintenance. THE WATER SUPPLY TO THE CARBONATOR WATER PUMP MUST BE TURNED ON BEFORE RESTAR TING THE CARBONATOR. STARVING THE WATER PUMP OF WATER WILL DAMAGE THE PUMP.
DAILY PRE -OPERATION CHECK
1. Check CO2cylinder regulator assembly 1800-psi gage and if the gage indicator is in the shaded (“change CO2cylinder”) portion of the dial, the CO2cylinder is almost empty and must be replaced.
31202700017
2. Make sure there is a sufficient syrup supply . If not, replenish the syrup supply as instructed in SERVICE AND MAINTENANCE section in this manual.
3. Make sure drip tray and cup rest are clean and are properly installed on the Unit.
UNIT OPERATION
1. Make sure dispensing valves keyed lock-out switch on left side of the Unit is in the “ON” (vertical) position.
2. Press cup or glass against the dispensing valve lever and dispense until the cup or glass is full of product, then release the lever.
3. If water only is desired, hold cup or glass under the dispensing valve with lever on its side, then actuate the lever to dispense water.
ADJUSTMENTS
ADJUSTING CO2REGULATORS
The CO2regulators should be checked periodically for proper pressure settings and be adjusted if necessary . Refer to SERVICE AND MAINTENANCE section in this manual for adjustment instructions.
ADJUSTING DISPENSING VALVE WATER FLOW RATE
The water flow rate of the dispensing valves may be adjusted. Refer to SERVICE AND MAINTENANCE section in this manual for adjustment instructions.
ADJUSTING W ATER-TO-SYRUP “RATIO” OF DISPENSED PRODUCT
The Water-to-Syrup “Ratio” (Brix) of the dispensed product should be checked periodically and adjusted if necessary . Refer to SERVICE AND MAINTENANCE section in this manual for adjustment instructions.
REPLENISHING CO2SUPPLY
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
The CO2supply should be checked daily and replenished if necessary. Refer to SERVICE AND MAINTE­NANCE section in this manual for replenishing procedure.
REPLENISHING SYRUP SUPPLY
The syrup supply should be checked daily and replenished if necessary . Refer to SERVICE AND MAINTE­NANCE section in this manual for replenishing instructions.
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT
The daily cleaning procedure for the Unit should be performed at the end of the daily operation. Refer to SER­VICE AND MAINTENANCE section in this manual for daily cleaning procedure.
312027000 18
SANITIZING SYRUP SYSTEMS
The syrup systems should be sanitized as instructed every 90-days. Refer to SERVICE AND MAINTENANCE section in this manual for sanitizing instructions.
CHECKING DROP -IN REFRIGERATION ASSEMBLY CONDENSER COIL FOR RESTRICTIONS
NOTE: Circulating air required to cool the refrigeration assembly condenser coil is drawn in through the grille on front and is exhausted through grille on top of the hood. Restricting air in or out of the Unit will decrease its cooling efficiency.
Area on top of the hood must be kept free of obstructions at all times. Make sure nothing is stored on top of the hood. The refrigeration assembly condenser coil should be periodically cleaned to maintain cooling efficiency as instructed in the SERVICE AND MAINTENANCE section of this manual.
CHECKING ICE WATER BATH
A “gurgle” heard from the Unit indicates the water level in the water tank is low and more water should be added for maximum product cooling. The water adding procedure may be found in the SERVICE AND MAINTE­NANCE section of this manual.
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER SYSTEM DISRUPTIONS
The water pump water strainer screen and the double-liquid check valve must be inspected and cleaned as instructed at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.). Refer to SERVICE AND MAINTENANCE section of this manual for inspecting and cleaning procedure.
CLEANING CO2GAS CHECK VALVES
The CO2gas check valves must be inspected and serviced as instructed at least once a year under normal conditions and after any CO2system servicing or disruption. Servicing of the CO2gas check valves should be performed by qualified Service Person. Refer to SERVICE AND MAINTENANCE section in this manual for inspecting and servicing procedures.
31202700019
THIS PAGE LEFT BLANK INTENTIONALLY
312027000 20
SERVICE AND MAINTENANCE
This section describes service and maintenance procedures to be performed on the Unit.
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
WARNING: Disconnect electrical power to the Unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or electrical wiring.
PREPARING UNIT FOR SHIPPING, STORING, OR RELOCATING
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must
also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
HOOD AND FRONT PANEL REMOVAL
(see Figure 5)
HOOD REMOVAL
CAUTION: Do not place or store anything on top of the Unit.
Loosen screw on top of hood, then lift hood straight up and off Unit.
FRONT ACCESS PANEL REMOV AL
1. Remove drip tray from the Unit.
2. Remove two screws securing the front access panel to the Unit.
3. Pull the front access panel down and out to remove.
PERIODIC INSPECTION
1. Check the refrigeration condenser coil for obstructions and dirt. DO NOT place objects in front of or on top of the hood. Restricting circulating air in or out of the Unit will decrease its cooling efficiency.
2. Check the dispensing valves for dripping that indicates leaking and repair as necessary .
ADJUSTMENTS
ADJUSTING CO2REGULATORS
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
21
312027000
DISPENSING VALVE
CONDENSER COIL
WATER FILL
HOLE PLUG
DISPENSING VALVES
KEYED-LOCK SWITCH
DISPENSING VALVE
SYRUP FLOW
REGULAT OR
DISPENSING VALVE
LEVER
COVER WITH
WATER LEVER
CUP REST
HOOD RETAINING
SCREW (1)
CONDENSER FAN
MOTOR
AGITATOR MOTOR
COMPRESSOR
BUILT -IN COLD CARBONAT OR
POWER CORD
CONTROL
BOX
DRIP TRAY
FRONT PANEL
WATER PUMP
MOTOR
WATER PUMP
SHIPPING NUT (4)
MAIN POWER SWITCH
(115VAC UNIT ONLY)
DISPENSING VALVE
RELEASE LATCH
MOUNTING BLOCK
FIGURE 5. DISPENSER COMPONENTS
312027000 22
NOTE: To readjust CO2regulator to a lower setting, loosen adjusting screw lock nut, then turn screw to the left (counterclockwise) until pressure gage reads 5 psi lower than new setting will be. Turn the ad­justing screw to the right (clockwise) until the gage registers new setting, then tighten the lock nut.
Adjusting Carbonator CO2Regulator.
Adjust primary CO2regulator (regulator controls Unit built-in cold carbonator CO2pressure) to a nominal 80 psig. Check for CO2leaks and repair if evident. INLET CO2PRESSURE TO CARBONATOR MUST NOT EXCEED 125 PSIG.
Sugar Syrup Tanks Secondary CO2Regulator.
Adjust sugar syrup tanks secondary CO2regulator with 100 psi gage at 40 psig for syrup lines up to 10 feet in length plus one pound for each additional length of 10 feet, plus one pound for each 2 feet of vertical lift. For example; if syrup line total length is 30 feet and total vertical lift is 6 feet, then 40 psig + 2 psig (1-pound for ev­ery 10 feet of length over 10 feet which is 20 feet) + 3 psig (1 pound for every 2 feet of vertical lift which is 6 feet); total equals 40 + 2 + 3 = 45 psig CO2regulator setting. Loosen lock nut on CO2regulator adjusting screw, turn adjusting screw to the right (clockwise) until gage registers desired pressure, then tighten lock nut.
Low-Calorie (Diet) Syrup Tank Secondary CO2Regulator
Adjust low-calorie (diet) soft drink tank secondary CO2regulator with 30 psi gage to 10 psig for syrup lines up to 30 feet in length. Syrup lines longer than 30 feet in length may require a slightly higher CO2regulator setting of 12 psig maximum. Excessive CO2pressure may cause low-calorie syrup carbonation resulting in foam.
ADJUSTING DISPENSING VALVES WATER FLOW RATE
SF-1 Dispensing Valve.
(see Figure 6)
1. Remove acorn nut securing the dispensing valve cover, then remove the cover to expose the valve water and the syrup flow controls.
2. Remove dispensing valve nozzle by turning nozzle counterclockwise and pulling down.
3. Remove syrup diffuser by pulling straight down.
ADJUSTABLE WATER
FLOW REGULATOR
NOZZLE
WATER
CHAMBER
ADJUSTABLE SYRUP
FLOW REGULATOR
SYRUP DIVERSION
TUBE ASS’Y
(P/N 319540000)
RATIO CUP
(P/N 31 1100000)
FIGURE 6. SF -1 DISPENSING VALVE
23
312027000
4. Install syrup separator on dispensing valve in place of the nozzle.
5. Measure the water flow rate by dispensing water into a graduated cup for a set period of time. Factory-set flow rate is approximately 1.25 ounces per second.
6. Adjust the water flow control adjusting screw clockwise for a greater flow or counterclockwise for lesser flow. Limit your adjustment to 1/4 turn at a time, then recheck the flow rate. Only the water flow rate is to be adjusted now. Syrup flow rate is adjusted in the Water-to Syrup “Ratio” (Brix) Adjustment section.
UF-1 Dispensing Valve
(see Figure 7)
1. Remove cover from the dispensing valve by lifting the front cover up 1/4 inch and pulling forward.
2. Install syrup diversion tube assembly on the dispensing valve by pushing rubber end of the syrup diversion tube onto the syrup outlet of the inner nozzle.
3. Measure the water flow rate by dispensing water into a graduated cup for a set period of time.
NOTE: Adjusting screw stops are built into the valve to prevent leakage when the screws are adjusted too far clockwise. Stop adjusting clockwise when turning resistance increases. Turn the screw coun ­terclockwise 1--1/2 turns after the stop are contacted.
4. Turn the water flow regulator adjusting screw to the left (counterclockwise) to decrease the water flow rate or turn the adjusting screw to the right (clockwise) to increase the water flow rate, then recheck the flow rate. Adjustments should be no more than 1/4 turn at a time.
5. Remove syrup diversion tube from the dispensing valve, then install cover on the dispensing valve.
WATER FLOW
REGULAT OR
SYRUP FLOW
REGULAT OR
INNER NOZZLE
Counterclockwise
to Decrease
Clockwise
to Increase
NOZZLE
SYRUP DIVERSION
TUBE
FIGURE 7. UF -1 DISPENSING VALVE
312027000 24
RATIO CUP
ADJUSTING W ATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED PRODUCT
SF-1 Dispensing Valve.
(see Figure 6)
NOTE: Make sure the dispensing valve water flow rate is as desired before adjusting the valve for Wa­ter-to-Syrup ‘‘Ratio’’ (Brix) of the dispensed product.
Adjust Water-to-Syrup ‘‘Ratio’’ of dispensed product by using Ratio Cup (P/N 311100000) and Syrup Diversion Tube Assembly (P/N 319540000) as follows.
1. Remove acorn nut securing the dispensing valve cover, then remove cover from the valve.
2. Install the syrup diversion tube assembly on the dispensing valve by pushing the rubber end of the syrup diversion tube up on the baffle inside the nozzle.
NOTE: Refer to syrup manufacturer’s recommendations on syrup package for Water-to-Syrup ‘‘Ratio’’.
3. Hold container under the dispensing valve. Open the dispensing valve and dispense just enough to fill the syrup diversion tube with syrup.
4. Hold large chamber of the ratio cup under the dispensing valve nozzle. Place free end of the syrup diver­sion tube into syrup chamber marked for proper ratio. Open the dispensing valve and dispense approxi­mately five ounces of water into the ratio cup. Water and syrup levels should be even in the ratio cup.
5. Adjusting Syrup Flow Regulator. If water and syrup levels are not even in ratio cup, turn dispensing valve syrup flow regulator labeled ‘‘SYRUP’’ adjusting screw to the left (counterclockwise) no more than 1/4-turn at a time for less syrup or to the right (clockwise) no more than 1/4-turn at a time for more syrup.
6. Repeat Water-to-Syrup ‘‘Ratio’’ test and adjust the syrup flow regulator as many times as necessary until proper ratio of the dispensed drink is achieved.
7. Remove syrup diversion tube assembly from the dispensing valve.
8. Install the dispensing valve cover and secure with acorn nut.
UF-1 Dispensing Valve
(see Figure 7)
NOTE: Make sure the dispensing valve water flow rate is as desired before adjusting the valve for Wa­ter-to-Syrup ‘‘Ratio’’ (Brix) of the dispensed product.
Adjust Water--to--Syrup “Ratio” (Brix) of the dispensed product by using ratio cup (P/N 311100000) and syrup diversion tube assembly (P/N 319540000) as follows:
1. Remove cover from the dispensing valve by lifting front cover up 1/4 inch and pulling forward.
2. Install syrup diversion tube assembly on the dispensing valve by pushing the rubber end of the syrup diver­sion tube onto the syrup outlet of the inner nozzle.
Notice: Refer to syrup manufacturer’s recommendations on syrup package for water-to-syrup ratio.
3. Dispense enough to fill syrup diversion tube with syrup.
4. Hold large chamber of the ratio cup under the dispensing valve nozzle. Place free end of the syrup diver­sion tube into the syrup chamber marked for the proper ratio. Dispense approximately 6 ounces of water into the ratio cup. Water and syrup levels should be even in cup.
Note: Adjusting screw stops are built into the valve to prevent leakage when the screws are adjusted clockwise too much. Stop adjusting clockwise when turning resistance increases. Turn the screw counterclockwise 1--1/2 turns after the stop are contacted.
25
312027000
5. Adjusting Syrup Flow Regulator -- If water and syrup levels are uneven in the ratio cup, adjust by turning the dispensing valve syrup flow regulator adjusting screw labeled SYRUP as follows.
A. For less syrup, turn the adjusting screw counterclockwise no more than 1/4 turn at a time. B. For more syrup, turn the adjusting screw clockwise no more than 1/4 turn at a time.
6. Repeat water-to-syrup ratio test and adjust syrup flow regulator as many times as necessary until proper ratio of dispensed drink is achieved.
7. Remove syrup diversion tube assembly from dispensing valve.
8. Install dispensing valve front cover.
CLEANING DROP -IN REFRIGERATION ASSEMBLY CONDENSER COIL
(see Figure 5) Excessive accumulation of dust, lint, and grease on the drop-in refrigeration assembly condenser coil will restrict
air flow through the coil and cause a loss of cooling. Perform the following procedure to clean the condenser coil.
1. Unplug Unit power cord from electrical outlet.
2. Remove hood by loosening screw on top of the hood, then lift the hood straight up off the Unit.
3. Vacuum or use a soft brush to clean the condenser coil. If available, use compressed air to blow dust and debris out of the condenser coil.
4. Clean dust and dirt from around top of the refrigeration assembly.
5. Install hood on the Unit and secure with one screw.
6. Plug Unit power cord into electrical outlet.
CHECKING ICE WATER BATH
(see Figure 5) A “gurgle” heard from the Unit indicates water level in the water tank is low and more water should be added to
the tank for maximum cooling. Before adding more water, ice water bath and ice bank should be checked for cleanliness and the water tank coils checked for excessive mineral deposit build-up.
1. Unplug Unit power cord from electrical outlet.
2. Remove Unit hood by loosening one screw on top of the hood, then lift the hood straight up off the Unit.
3. Remove plug from the drop-in refrigeration assembly platform water fill hole.
4. Using a flashlight, inspect the ice water bath and the ice bank for cleanliness. The ice water bath should be clear and the ice bank should be free of foreign particles.
5. If cleaning of the water tank is necessary, refer to CLEANING WATER TANK in this section.
6. Fill the water tank with clean water until water runs out of the overflow groove on top front of the tank into the drip tray. USE LOW-MINERAL-CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS When the water tank is full, the water level in the clear plastic water level tube should be approximately one inch from end of the tube.
7. Install plug in the water fill hole.
8. Install the Unit hood and secure with screw.
9. Plug Unit power cord into electrical outlet.
312027000 26
CLEANING WATER TANK
(see Figure 5 and 8)
1. Unplug Unit power cord from electrical outlet.
2. Shut off plain water supply to the Unit.
3. Note pressure setting on the primary CO2regulator for the carbonator, then turn the regulator adjusting screw to the left (counterclockwise) until gage reads 0-psig.
4. Remove the Unit hood by loosening screw on top of the hood, then lift the hood straight up off the Unit.
5. Disconnect the drop-in refrigeration assembly power cord from the Unit power cord.
6. Disconnect the dispensing valves power cord from the drop-in refrigeration assembly mating power cord.
7. Disconnect the carbonated water tank sensor leads power cord from the drop-in refrigeration assembly mating power cord.
8. Remove screw securing the carbonated water tank access hole cover, then remove the cover for access to the carbonated water tank relief valve.
9. Pull up on the carbonated water tank relief valve to release CO2gas pressure from the tank and the car­bonated water system.
10. Disconnect the plain water inlet and the carbonated water outlet lines from the carbonator water pump.
11. Remove four hex nuts securing the drop-in refrigeration assembly in the Unit lower housing.
12. Very carefully, lift the drop-in refrigeration assembly up and out of the Unit lower housing.
CAUTION: Never use an ice pick or other instrument to remove ice from the drop -in refrigeration assembly evaporator coils. Such practice can result in a punctured refrigeration circuit.
13. Allow ice bank to melt. Hot water may be used to speed melting.
14. Use a fiber brush and carefully clean mineral deposit build-up from the agitator motor shaft and the ice bank sensing bulb.
15. Route the water tank drain hose to a drain. Remove plug from end of the drain hose and allow the water tank to drain.
16. Wash inside of the water tank and the drop-in refrigeration assembly evaporator coils, then rinse with clean water.
17. Install plug in end of the water tank drain hose.
18. Install the drop-in refrigeration assembly in the Unit by reversing the removal procedure.
19. Remove plug from the drop-in refrigeration assembly platform water fill hole.
20. Fill the water tank with clean water until water runs out of the overflow groove on top front of the tank into the drip tray. USE LOW-MINERAL-CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS When the water tank is full, the water level in the clear plastic water level tube should be approximately one inch from end of the tube.
21. Install plug in the drop-in refrigeration assembly platform water fill hole.
22. Turn the primary CO2regulator adjusting screw to the right (clockwise) until the gage indicates pressure setting noted in step 3 preceding.
23. Restore plain water supply to the Unit. Check for CO2and water leaks and repair if evident.
27
312027000
24. Plug Unit power cord into electrical outlet.
25. Dispense from one of the carbonated drink dispensing valves to bleed all air from the Unit carbonated water tank and the carbonated water system.
26. Check for leaks and repair if evident.
27. Install hood and secure with screw.
CARBONAT OR
SENSOR LEADS
CARBONAT OR
TANK
RELIEF
VALVE
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT
FIGURE 8. WA TER TANK
1. Remove cup rest from the drip tray .
2. Wash drip tray in place on the Unit, then rinse drip tray with hot water allowing water to drain out through the drain hose.
3. Wash cup rest, then rinse the cup rest with clean water. Install cup rest in the drip tray.
4. Clean all external surfaces of the Unit with a sponge. Rinse out the sponge with clean water, then wring excess water out of the sponge and wipe off all external surfaces on the Unit. Wipe Unit dry with a clean soft cloth. DO NOT USE ABRASIVE CLEANERS.
312027000 28
5. Remove nozzle and syrup diffusers from the dispensing valves. Place nozzles and syrup diffusers in sani­tizing solution.
6. Wash the nozzles and syrup diffusers in sanitizing solution, then rinse them with potable water.
7. Re-install nozzles and syrup diffusers back on the dispensing valves.
SANITIZING POST-MIX SYRUP SYSTEMS
IMPORTANT: Only qualified Service Personnel should perform sanitizing procedure on the post-mix syrup systems.
The post-mix syrup systems should be sanitized every 90-days using a non-scented household liquid bleach containing a 5.25 % sodium hypochlorite concentration. Proceed as follows to sanitize the post-mix syrup sys­tems.
1. Disconnect syrup supplies from syrup systems.
2. Rinse quick disconnects (syrup tanks systems) or bag-in-box connectors (syrup bag-in-box systems) in warm potable water.
STEP 1. WASH SYRUP SYSTEMS
3. Using a clean syrup tank (syrup tank system) or a five-gallon container (bag-in-box system), prepare a full tank or container of liquid dishwasher detergent by using 70_ F (21_ C) to 100_ F (38_ C) potable water and 0.5 oz. (15 ml) of liquid dishwasher detergent to one gallon of potable water. Stir detergent solution to thoroughly mix the solution.
4. Syrup Tank Systems. A. Observe and note CO2pressure setting on the syrup tanks CO2regulator, then re-adjust CO2regula-
tor to 60 to 80-psi. Pressurize syrup tank containing detergent solution to 60 to 80-psi.
B. Connect detergent solution tank, pressurized at 60 to 80-psi, into one of the syrup systems.
Bag-in Box Syrup Systems.
C. Install bag valves, cut from empty bag-in-box syrup containers, on ends of syrup containers syrup
outlet tubes connectors.
D. Place all syrup outlet tubes, with bag valves on their ends, in container containing detergent solution.
5. Flush the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all syrup and flush out the syrup system. C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
6. Connect detergent solution to the remaining syrup systems and flush syrup out of the syrup systems as instructed in step 5 preceding.
7. Remove detergent solution source from the syrup system.
STEP 2. FLUSH SYRUP SYSTEMS
8. Syrup Tank Systems. Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems.
Bag-in-Box Syrup System.
29
312027000
Fill five-gallon container with potable water, then place all bag-in-box syrup containers syrup outlet tubes in
container containing potable water.
9. Flush detergent solution out of the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all detergent solution and flush out the syrup
system.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
10. Connect potable water source to the remaining syrup systems and flush detergent solution out of the syrup systems as instructed in step 9 preceding.
11. Remove potable water source from the syrup system.
STEP 3. SANITIZE SYRUP SYSTEMS
12. Using a clean syrup tank (syrup tanks system) or a five-gallon container (bag-in-box system), prepare sani­tizing solution using 70_ F (21_ C) to100_ F (38_ C) potable water and 0.5 oz. (15 ml) of non-scented household liquid bleach that contains a 5.25 % sodium hypochlorite concentration to one gallon of potable water. This mixture must not exceed 200 PPM of chlorine. Stir sanitizing solution to thoroughly mix.
13. Syrup Tank Systems.
Connect sanitizing solution tank, pressurized at 60 to 80-psi, into one of the syrup systems. Bag-in-Box Syrup System. Place all bag-in-box syrup containers syrup outlet tubes in container containing sanitizing solution.
14. Sanitize the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all water from and install sanitizing solution in
the syrup system and dispensing valve.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
15. Repeat steps13 and 14 to flush water out of and install sanitizing solution in the remaining syrup systems and dispensing valves.
16. Remove sanitizing solution source from the syrup system.
17. Allow sanitizing solution to remain in the syrup systems for not less than 10 or no more than 15-minutes (max.) contact time.
STEP 4. WATER FLUSH SYRUP SYSTEMS
WARNING: Flush sanitizing solution from the syrup systems as instructed. Residual sanitizing solution left in the syrup systems could create a health hazard.
18. Fill syrup tank (syrup tank system) or a five-gallon container (bag-in-box system) with potable water.
19. Syrup Tank Systems.
Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems. Bag-in-Box Syrup System.
312027000 30
Place all bag-in-box syrup containers syrup outlet tubes in container containing potable water.
20. Flush sanitizing solution from the syrup system and the dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all sanitizing solution out of the syrup system
and the dispensing valve.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
21. Repeat steps 19 and 20 preceding to purge sanitizing solution out of the remaining syrup systems and dispensing valves.
22. Remove potable water source from the syrup system.
STEP 5. PURGE WATER OUT OF SYRUP SYSTEMS (RESTORE OPERATION)
23. Syrup Tank Systems. A. Noting syrup tanks CO2regulator pressure setting observed in step 4 preceding, readjust CO2regula-
tor to the observed pressure setting,
B. Connect tanks containing syrup into syrup systems.
Bag-in-Box Syrup System. C. Remove all bag valves from bag-in-box syrup containers outlet tubes connectors. D. Connect bag-in-box syrup containers into the syrup systems.
24. Place waste container under dispensing valves. Dispense from all dispensing valves to permit syrup to purge all potable water from the syrup systems and the dispensing valves. Continue to dispense from the dispensing valves until only syrup is dispensed from the syrup systems and valves.
WARNING: To avoid possible personal injury or property damage, do not attempt to remove the syrup tank cover until CO2pressure has been released from the tank.
25. Dispose of waste sanitizing solution in a sanitary sewer, not in a storm drain, then thoroughly rinse the in­side and the outside of the container that was used for sanitizing solution to remove all sanitizing solution residue.
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER SYSTEM DISRUPTIONS
WARNING: The carbonator water pump water inlet strainer screen and the double-liquid check valve must be inspected and cleaned at least once a year under normal
circumstances, and after any disruptions (plumbing work, earthquake, etc.) to the water supply system that might cause turbulent (erratic) flow of water through the system. A carbonator water pump with no screen or a defective screen in the strainer would allow foreign particles to foul the double-liquid check valve. CO2gas could then back flow into the water system and create a health hazard.
The carbonator water pump water inlet strainer screen and the double-liquid check valve must be inspected and cleaned at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.) as follows:
31
312027000
Servicing Water Pump Water Inlet Strainer Screen
(see Figures 5 and 9)
1. Unplug Unit power cord from electrical outlet.
2. Remove the Unit hood by loosening one screw on top of the hood, then lift the hood up and off the Unit.
3. Close the water inlet supply line shutoff valve.
4. Note pressure setting on the carbonator primary CO2regulator, then turn the regulator adjusting screw to the left (counterclockwise) until the gage reads 0-psig.
5. Remove screw securing the carbonated water tank access hole cover, then remove the cover for access to the carbonated water tank relief valve.
6. Pull up on the carbonated water tank relief valve to release CO2gas pressure from the tank and the car­bonated water system.
7. Loosen the screen retainer, then pull the screen retainer and the strainer screen from the water pump.
8. Pull the screen from the screen retainer. Clean any sediment from the screen retainer and the water pump screen retainer port.
9. Inspect the screen for holes, restrictions, corrosion, and other damage. Replace the screen if damaged (P/N 315348000).
10. Check O-Ring on the screen retainer. Replace the worn or damaged O-Ring (P/N 315349000).
NOTE: A screen should always be used, otherwise particles could foul the double-liquid check valve.
11. Install screen (P/N 315348000) in the screen retainer, then screw the retainer into the water pump and tighten securely.
12. Service the double-liquid check valve, (refer to next paragraph Servicing Double-Liquid Check Valve) as instructed.
Servicing Double-Liquid Check Valve.
(see Figures 5, 9, and 10)
1. Service the water inlet strainer screen as instructed in previous paragraph before servicing the double-liq­uid check valve.
2. Disconnect the carbonated water line from the double-liquid check valve, then remove the double-check valve from the water pump outlet port.
3. Disassemble each check valve as shown in Figure 10.
4. Wipe each part with a clean lint-free cloth. Inspect each part, especially the ball for burrs, nicks, corrosion, deterioration, and other damage. Discard the ball seat and any damaged or suspicious parts and replace with new parts during reassembly.
5. Reassemble check valves as shown in Figure 10. ALWAYS INSTALL A NEW BALL SEAT (QUAD RING) P/N 312418000.
NOTE: Make sure when assembling the check valves together, the check valve female end with a white tapered gasket inside is on the inlet side of the double-liquid check valve assembly.
6. Assemble the check valves together as shown in Figure 10.
7. Install the double-liquid check valve in the water pump outlet port.
312027000 32
PUMP TO MOTOR COUPLING
WATER PUMP
WATER
STRAINER SCREEN
(P/N 315348000)
O-RING (P/N 315349000)
WATER LINE TO TANK
WHITE TAPERED GASKET
DOUBLE-LIQUID
CHECK VALVE
ELBOW
SCREEN RETAINER
FIGURE 9. WA TER STRAINER SCREEN AND DOUBLE-LIQUID CHECK VALVE
8. Connect the carbonated water line to the double-liquid check valve.
9. Turn the carbonator primary CO2regulator adjusting screw to the right (clockwise) until it’s gage indicates pressure setting noted in step 4 of Servicing Water Pump Water Inlet Strainer Screen.
10. Open the water inlet supply line shutoff valve.
11. Pull up on the carbonated water tank relief valve to purge all air from the tank.
12. Install the carbonated water tank access hole cover and secure with screw.
13. Install the Unit hood and secure with screw.
14. Plug Unit power cord into electrical outlet.
15. Test dispense Unit for proper operation.
REPLENISHING CO2SUPPLY
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
33
312027000
4
3
1
4
2
3
1
2
Item
No. Part No. Name
1 5470E Flat Washer 2 312418000 Ball Seat (Quad Ring) 3 312419000 Ball 4 5470D Spring
FIGURE 10. LIQUID CHECK VALVE ASSEMBLY
NOTE: When indicator on the CO2cylinder primary CO2regulator assembly 1800-psi gage is in the shaded (‘‘change CO2cylinder’’) portion of the dial, the CO2cylinder is almost empty and should be changed.
1. Fully close (clockwise) the CO2cylinder main shutoff valve.
2. Slowly loosen primary the CO2regulator assembly coupling nut allowing CO2pressure to escape, then remove the regulator assembly from the empty CO2cylinder.
3. Unfasten safety chain and remove the empty CO2cylinder.
WARNING: To avoid personal injury and/or property damage, always secure the CO
2
cylinder in an upright position with a safety chain to prevent it from falling over. Should the valve become accidentally damaged or broken off, the CO2cylinder can cause serious
personal injury.
4. Position full CO2cylinder in an upright position and secure with a safety chain.
5. Make sure a gasket is in place inside the primary CO2regulator coupling nut, then install regulator on the CO2cylinder.
6. Open (counterclockwise) the CO2cylinder main shutoff valve slightly to allow the lines to slowly fill with gas, then open the valve fully to back-seat the valve. (Back-seating the valve prevents leakage around the valve shaft).
7. Check all CO2connections for leaks. Tighten any loose connections and repair any leaks.
REPLENISHING SYRUP SUPPLY
NOTE: The following instructions are applicable only when replenishing same flavor syrup. Refer to SYRUP FLAVOR CHANGE when changing syrup flavor.
312027000 34
SYRUP TANK SYSTEM
1. Disconnect empty syrup tank from syrup system.
2. Check syrup drink quick disconnects for sticky or restricted operation. Wash disconnects in warm water.
3. Connect full tank of syrup into syrup system.
BAG-IN-BOX SYRUP SYSTEM
1. Disconnect empty bag-in-box container from syrup system.
2. Check bag-in-box connecter for sticky or restricted operation. Wash bag-in-box connecter in warm water.
3. Connect full bag-in-box container into syrup system.
SYRUP FLAVOR CHANGE
1. Perform sanitizing procedure (as instructed in this section of the manual) on the syrup system syrup flavor change will be made on.
2. Connect a new flavor syrup into the syrup system.
CLEANING CO2SYSTEM CO2GAS CHECK VALVES
(see applicable Figure 2 or 3 and 11) The CO2regulators and CO2manifold CO2gas check valves must be inspected and serviced at least once a
year under normal conditions and after any servicing or disruption of the CO2system. ALWAYS REPLACE BALL SEAT (QUAD RING SEAL) EACH TIME GAS CHECK VALVES ARE SERVICED.
FIGURE 11. CO2GAS CHECK VALVE ASSEMBLY
35
312027000
THE GERMAN ICE BANK CONTROL IS FOR
INTERNATIONAL USE ONLY.
FIGURE 12. WIRING SCHEMA TIC FOR ELECTRONIC ICE BANK CONTROL (OPTIONAL)
312027000 36
560001023
37
FIGURE 13. WIRING DIAGRAM (50 AND 60 HZ UNIT WITH 1/3 H.P. REFRIGERATION ASSEMBLY)
312027000
301112002
312027000
FIGURE 14. WIRING DIAGRAM (60 HZ UNIT WITH 1/4 H.P. REFRIGERATION ASSEMBLY AND BUILT-IN COLD CARBONATOR)
38
301112002
39
FIGURE 15. WIRING DIAGRAM (50 HZ UNIT WITH 1/4 H.P. REFRIGERATION ASSEMBLY AND BUILT-IN COLD CARBONATOR)
312027000
FRONT
SOLENOID
TOP VIEW
WHITE
BLACK
BLACK
SWITCH
C
N.O.
N.C.
RIGHT SIDE VIEW
1 2
FIGURE 16. WIRING DIAGRAM (SF-1 DISPENSING VALVE)
SOLENOID
WHITE
TWO - PIN
CONNECTOR
BLACK
RED
C
NO
SWITCH ASS’Y
P/N 1932
LEVER
P/N 1925
FIGURE 17. WIRING DIAGRAM (UF-1 DISPENSING VALVE)
312027000 40
2 1
P/N 1933
312027000
THIS PAGE LEFT BLANK INTENTIONALLY
TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
WARNING: If repairs are to be made to a product system, remove quick disconnects from the applicable product tank, then relieve the system pressure before proceeding. If repairs
are to be made to the CO2system, stop dispensing, shut off the CO2supply , then relieve the system pressure before proceeding. If repairs are to be made to the refrigeration system, make sure electrical power is disconnected from the unit.
TROUBLESHOOTING POST-MIX SYSTEM SYSTEM
Trouble Probable Cause Remedy
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
A. Dispensing valve syrup flow
control not properly adjusted.
B. Syrup Tanks System.
CO2gas pressure to syrup tanks insufficient to push syrup out of tanks.
Bag-in-Box Syrup System.
CO2gas pressure to syrup pumps insufficient to operate pumps.
A. No syrup supply. A. Replenish syrup supply as
B. Syrup Tanks System.
Syrup tanks CO2regulator out of adjustment.
Syrup Bag-in-Box System.
Syrup pumps CO2regulator out of adjustment.
A. Adjust Water-to-Syrup “Ratio” as
instructed.
B. Adjust CO2regulator for syrup
tanks as instructed.
Adjust CO2regulator for syrup pumps as instructed.
instructed.
B. Adjust CO2regulator for syrup
tanks as instructed.
Adjust syrup pumps CO regulator as instructed.
2
312027000
C. Dispensing valve syrup flow
control syrup or syrup line restricted.
D. Improper syrup Baume. D. Replace syrup supply as
E. Inoperative dispensing valve
syrup flow control.
F. Tapered gasket inside tube
swivel nut connection distorted from being overtightened restricting syrup flow.
42
C. Sanitize syrup system as
instructed.
instructed.
E. Repair dispensing valve syrup
flow control.
F. Replace tapered gasket. Make
sure it is properly seated.
312027000
Trouble Probable Cause Remedy
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
DISPENSED PRODUCT CARBONATION TOO LOW.
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP OR GLASS.
A. Dirty or inoperative dispensing
valve syrup flow control.
A. Disassemble and clean
dispensing valve syrup flow control.
A. Carbonator CO2regulator out
of adjustment for existing
A. Adjust carbonator CO2regulator
as instructed. water conditions or temperature.
B. Air in carbonated water tank. B. Vent air from carbonated water
tank by dispensing from No. 1
dispensing valve to make
carbonator pump motor cycle on.
C. Water, oil, or dirt in CO
supply .
2
C. Remove contaminated CO2.
Clean CO2system (lines,
regulators, etc.) using mild
detergent. Install clean CO
2
supply .
A. Oil film or soap scum in cups
A. Use clean cups or glasses.
or glasses.
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE.
B. Ice used for finished drink is
subcooled.
B. Do not use ice directly from
freezer. Allow ice to become “wet”
before using. (Refer to following
NOTE.)
NOTE: Crushed ice also causes dispensing problems. When dispensed drink hits sharp edges of ice, carbonation is released from drink.
A. Recovery rate of refrigeration
A. Allow ice bank to recover. unit exceeded, ice bank depleted.
CAUTION: The drop -in refrigeration assembly condenser coil must be cleaned every 30-days. Excessive accumulation of dust, lint, and grease on the coil will restrict cooling air flow through the coil and cause the refrigeration system to overheat.
B. Condenser coil plugged. B. Clean condenser coil as
instructed.
C. Carbonator CO2regulator
pressure adjusted too high for
C. Adjust carbonator CO2regulator
as instructed. existing water conditions or temperature.
D. Dispensing valve restricted or
dirty .
D. Sanitize syrup system as
instructed.
E. Tapered gasket inside
carbonated water line swivel
E. Replace tapered gasket. Make
sure gasket is properly seated. nut connector distorted restricting carbonated water flow.
Trouble Probable Cause Remedy
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE.(CONT’D)
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES.
F. Dirty water supply . F. Check water filter. Replace
cartridge (see NOTE).
NOTE: If water supply is dirty, be sure to flush lines and carbonator completely . It may be necessary to remove lines to carbonator tank, invert tank, and flush the tank and all inlet lines to remove any foreign particles or dirt.
A. Dispensing valves keyed
lock-out switch in “OFF”
A. Place keyed lock-out switch in
“ON” position.
position.
B. Power switch (if applicable) in
“OFF” position.
B. Place power switch in “ON”
position.
C. No electrical power to Unit. C. Plug in Unit power cord or check
for blown power fuse or tripped circuit breaker.
D. Inoperative power switch (if
D. Replace power switch.
applicable).
E. Dispensing valves power cord
disconnected.
F. Disconnected or broken wiring
E. Connect dispensing valves power
cord.
F. Connect or replace wiring.
to dispensing valve.
G. Inoperative transformer or
valve solenoids.
ONLY CARBONATED WATER
A. Out of syrup. A. Replenish syrup supply as
DISPENSED.
B. Inoperable dispensing valve.. B. Repair dispensing valve. C. Dispensing valve syrup flow
control not properly adjusted.
D. Dispensing valve syrup flow
control or syrup lines restricted.
ONLY SYRUP DISPENSED. A. Water inlet supply line shutoff
valve closed.
B. Carbonator power cord (under
hood) unplugged.
C. Carbonator CO2regulator not
properly adjusted.
D. Inoperative carbonated water
tank liquid level control assembly .
E. Inoperative water pump, water
pump motor, or water pump power switch.
G. Replace inoperative part.
instructed.
C. Adjust dispensing valve syrup
flow control as instructed.
D. Sanitize syrup system as
instructed.
A. Open water inlet supply line
shutoff valve.
B. Remove hood and plug in
carbonator power cord.
C. Adjust carbonator CO2regulator
as instructed.
D. Replace carbonated water tank
liquid level control assembly .
E. Replace inoperative component.
312027000
44
312027000
TROUBLESHOOTING REFRIGERATION SYSTEM
Trouble Probable Cause Remedy
COMPRESSOR DOES NOT OPERATE.
A. Ice bank sufficient. A. Refrigeration not called for.
B. Unit power cord unplugged,
power switch (if applicable) in “OFF” position, or drop-in
B. Plug in power cord(s) or place
Unit power switch in “ON”
position. refrigeration assembly power cord unplugged.
C. No power source (blown fuse
or tripped circuit breaker).
C. Replace fuse or reset circuit
breaker. (NOTE: Fuse or circuit
breaker are not part of unit).
D. Inoperative Unit power switch
(if applicable) or power cord
D. Replace power switch or plug Unit
power cord into electrical outlet. unplugged.
E. Low voltage. E. Voltage must be at least 103 volts
(115 VAC unit) or 208 (230 VAC
unit) at compressor terminal when
compressor is trying to start.
F. Loose, disconnected, or
broken wiring.
G. Overload protector cut out;
overheated compressor. Condenser fan motor not operating as required.
F. Tighten connections or replace
broken wiring.
G. Compressor will cool enough to
restart. Do not overdraw cooling
capacity of Unit. Refer to
“CONDENSER FAN MOTOR
NOT OPERATING” in this
section.
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS PRODUCED. (NOTE: ICE BANK SHOULD JUST COVER CONTROL BULB).
H. Inoperative overload protector
H. Replace inoperative part.
or start relay.
I. Inoperative ice bank control
I. Replace ice bank control.
probe.
J. Inoperative compressor. J. Call service person. A. Ice bank control cap tube
A. Replace ice bank control.
kinked or broken.
B. Ice bank control stuck in
B. Replace ice bank control.
closed position.
Trouble Probable Cause Remedy
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM SUFFICIENT ICE BANK.
AGITATOR MOTOR NOT OPERATING.
A. Cooling capacity is exceeded
by over-drawing.
B. Unit located in excessively hot
area or air circulation through condenser coil is restricted.
A. Reduce amount of drinks drawn
per given time.
B. Relocate unit or check and if
necessary , clean condenser coil as instructed.
NOTE: Ice bank freezes from bottom of evaporator upward. A refrigerant leak or insufficient charge might show an ice bank at bottom and not at top of evaporator.
A. Power switch (if applicable) in
“OFF” position.
B. Unit power cord or
A. Place power switch in
“ON” position.
B. Connect power cord(s). refrigeration assembly power cord unplugged.
C. No power source (blown fuse
or tripped circuit breaker).
C. Replace fuse or reset circuit
breaker. (NOTE: Fuse or circuit breaker are not part of Unit).
D. Agitator motor propeller
D. Remove obstruction. obstructed.
E. Low voltage. E. Voltage must be at least 103 volts
(115 VAC unit) or 208 (230 VAC unit) at compressor terminals when compressor is trying to start.
F. Loose, disconnected, or
broken wiring.
F. Tighten connections or replace
broken wiring.
G. Inoperative agitator motor. G. Replace agitator motor.
312027000
46
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workman­ship under normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire product, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number, serial number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166 AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930 BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307 BRAZIL D RUA IT AOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829 ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644 FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201 GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438 GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491 HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222 ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814 NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361 SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604 SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379 USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255
LD004
4/21/98
312027000
47
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place Anoka, Minnesota 55303-6234 (612) 421-6120 (800) 238-3600
Loading...