Cornelius QLT 180 BEVERAGE DISPENSER Installation Manual

INSTALLATION
&
SERVICE
MANUAL
MODEL
QLT180/1000-1,
1002-1, & 1001-1
IMI
CORNELIUS INC.
One Cornelius Place Anoka,
MN
55303
Tel:
1-800-238-3600 / 763-421 -61 20
Fax:
763-422-3226
Part
No.
8531 2001
Revision-
July
C
22,2002
Installation & Service Manual
SEMI-ANNUAL
CAUTION: The following procedures require removal of the dispenser side panel
A
0
1.
2.
3.
4.
0
1.
2.
3.
4.
ing.
Clean Water Inlet Strainer: Remove the left side side panel from the dispense.
Turn
off
the water supply to the dispenser.
Remove the access port from the located on the water inlet in the lower rear portion dispenser.
Clean and reinstall the stainless steel water strainer. Clean Chassis Interior:
Clean the condenser cooling fins. Clean the air inlet grille located at the base Clean the interior base. Wipe the fan blade clean.
"
(8).
Disconnect the power cord from the receptacle prior to proceed-
"Y"
shaped solenoid
of
the
of
the dispenser.
5.
Reinstall the left side panel, turn on the water supply, and plug the dispenser into the power receptacle.
8531
2001
10
Installation & Service Manual
TROU
BLE-SHOOTING
GUIDE
The following pages contain trouble-shooting information intended to aid an experienced service
If
person in diagnosing any operational problems that may occur. problem after several attempts, contact the IMI Cornelius
/
you are unable to resolve the
Wilshire Inc. Technical Services de­partment at 1-800-238-3600 (763-421-6120 outside the United States) between the hours of 8:OO AM and
PM Central Standard Time. You must have the model and serial number
(lo-
300
cated on the right side of the dispenser) prior to calling.
PROBLEM PROBABLE CAUSE REMEDY
Totally Inoperative
No
power to dispenser due to tripped circuit breaker.
0
Reset circuit breaker.
Confirm that breaker is correct size and no other equipment si operating on the same circuit.
Also confirm that supply volt­age is
f
10% of name-
plate specifications.
0
Loose or broken power
0
Repair connection.
supply connection inside dispenser.
Yo
Cooling
Line voltage is not within
f
10%
of
nameplate specifications causing compressor overload to trip.
Both thermostats in
OFF
position.
Defective compressor overload or start capaci­tor.
Defective start relay
lo-
cated on upper rear shelf inside dispenser.
Compressor starts but hums and trips overload.
Compressor starts but does not switch
off
of
start
winding.
0
Contact an electrician.
0
Turn
ON
thermostats and recalibrate the tempera­tures to
0
Replace.
There should
0
40°F f 5
be
age on the black wire of the relay when there is line voltage present
OR
orange Replace relay
yellow wire.
if
test.
0
Seized or shorted com­pressor, replace.
0
Relay or compressor is defective. Test and re­place faulty item.
(45°C).
line volt-
on
the
it fails this
Compressor short cycles on overload.
11 8531 2001
0
Excessively high dis­charge pressure due to restricted condenser or operative condenser fan motor.
in-
Installation & Service Manual
No Cooling (Cont'd)
Yo
water dispensed, concen-
trate only.
0
Refrigerant leak.
0
No
watertodispenser.
0
Water supply line inside refrigerated cabinet dis­connected from pump platform.
Water solenoid located on pump platform clogged or defective.
Main water solenoid strainer located at base of dispenser is clogged, binding or defective.
No
water dispensed, con-
centrate only.
0
Repair leak, evacuate and recharge system.
0
Restore water.
0
Reconnect.
0
Disassemble and clean solenoid. Replace essary.
0
Remove and clean strain­er. Confirm 28VDC is present at solenoid during dispense. Confirm sole­noid coil is not open. Dis­assemble and clean sole­noid.
0
Add external regulator and lower pressure to psi
(3.5
bar).
if
nec-
50
No
water and no concentrate,
refrigeration is working.
Water supply pressure is greater than
100
bar)
0
Freeze-up of water coil or concentrate chamber.
0
Service switch located un­der drip tray in OFF posi­tion.
0
Door switch open.
0
6.25 amp fuse inside front
box
electrical
blown.
psi
(7
0
Unplug dispenser and al-
low 2-4 hours to thaw. Water or concentrate ther­mostat set too low, recali-
f
brate to 40" F
0
Defective water or con-
5
centrate thermostat, re­place. Refrigerant solenoid stuck open or not closing fully. Evacuate system, replace solenoid valve and recharge.
0
Turn on switch.
0
Door switch must be
in
closed
order to operate pump. Check switch op­eration and replace essary.
0
Replace with 6.25 amp, 25OVAC
slow
blow fuse
and test.
(4.5"C).
if
nec-
8531 2001
0
No output from transform-
0
Confirm transformer out-
er located on rear upper put by measuring for shelf. 26VAC at fuse. Replace
transformer
if
necessarv.
12
Installation & Service Manual
No water and no concentrate,
refrigeration is working
0
Defective voltage regula-
tor board (VRB) located
0
Measure across the blue
and black wire located in
(Cont'd). inside front electrical box. the upper left corner of
the board. There should be 28VDC present when the dispense button is pressed. Replace VRB necessary.
0
Defective portion control
board.
0
Disconnect wire harness from rear of portion con­trol, close door switch and short the orange and black wires together on
If
the harness.
unit dis-
penses portion control
board
is
defective.
If
does not dispense the voltage regulator board is defective.
No
concentrate dispensed,
water only.
0
Dispense tube not fully
engaged into receptacle
0
Refer to
Loading
Concentrate
section of this
on concentrate pouch. manual.
if
it
0
Dispense tube discon­nected from mixing cham­ber. manual.
0
Slide block on pump in open position.
'
Switch on pump platform in FLUSH position. tion.
0
Concentrate too cold, no properly thawed. 3540°F (1.74.5"C) prior
I
Excessive remnant left in
0
Defective pump motor.
0
Concentrate pouch im-
empty concentrate pouch. properly thawed.
0
Concentrate pouch and/or dispense tube improperly installed. manual.
0
Refer to Concentrate Loading section of this
0
Close and lock the slide block. Refer to Concen­trate Loading section of this manual.
0
Move switch to RUN posi-
0
Concentrate should be to loading.
0
Replace pump motor.
0
Concentrate should be 3540°F (1.7-4.5"C) prior to loading.
0
Refer to
Loading
Concentrate
section of this
Concentrate refill light comes on prematurely.
0
Concentrate pouch im-
0
Concentrate should
properly thawed. 3540°F (1.7-4.5"C) prior
to loading.
0
Concentrate pouch andlor dispense tube improperly installed. manual.
_____
0
Refer to
Loading
Concentrate
section of this
13 8531 2001
be
Installation & Servicg Manual
Concentrate refill light comes on prematurely (Cont'd).
I
Concentrate refill light does not come on at all.
Warm Drink
I
0
Loose wiring.
0
Check wiring connections between the pump motor and the VRB board.
0
Bad VRB board.
0
Bad pump motor.
0
Pump improperly locked
0
Replace VRB board.
0
Replace pump motor.
0
Close and lock pump.
or pump is open.
0
Run/flush switch is in the
0
Move switch to the RUN
FLUSH position. position.
0
Improperly loaded tube.
0
Refer to concentrate load­ing section of this manual.
0
Bad VRB board.
0
Bad portion control.
0
Incoming water supply too
0
Replace VRB board.
0
Replace portion control.
0
Optimum performance is
warm. achieved when the dis-
penser utilizes water from a pre-cooler.
0
Ambient air too warm.
0
Excessive demand on dis-
penser.
0
Relocate dispenser.
0
Add water pre-cooler or second dispenser.
I
I
Water continuously drips from
nozzle when in OFF mode.
No
Flush Cycle
0
Dirty condenser coil.
0
Inoperative condenser
0
0
fan. motor.
0
Defective water thermo-
0
stat.
0
Loss of refrigerant charge
0
due to leak in system.
0
Main water solenoid at
0
base of unit or water sole­noid on pump platform not
off
shutting
0
Run/Flush switch on pump platform
tightly.
in
Run position.
0
mode.
0
Defective Run/Flush
0
switch on pump platform switch. (concentrate continues to dispense while in Flush mode).
Clean condenser coil.
Replace condenser fan
Replace thermostat.
Repair leak and recharge system.
Clean solenoid(s), replace parts as necessary.
Move switch to Flush
Replace Run/Flush
Concentrate warm, water cold
0
Concentrate thermostat is
off
turned
or not calibrated
properly.
8531 2001 14
0
Calibrate to be 3540°F (1 -7-4.5"C).
Installation & Service Manual
Concentrate warm, water cold (Cont'd).
Brix Problem
0
Concentrate thermostat
0
Replace thermostat and
defective (stuck open). calibrate to 3540°F
(1.7-4.5"C).
0
Defective start relay cated on upper rear shelf inside dispenser.
lo-
0
There should be line volt­age on the black wire of the relay when there is line voltage present on the orange
OR yellow wire.
Replace relay test.
0
Loss of refrigerant charge
0
Repair leak and recharge system. due to leak in system.
0
Water supply pressure too low, less than 40 psi (2.8 bar) flowing or water pres­sure fluctuates sharply.
0
Water flow control binding or spring is defective.
0
Improperly thawed con­centrate. Brix changes as
0
Correct water supply problem to ensure a constant
40
flowing to the dispenser.
0
Clean and/or replace parts as necessary.
0
Concentrate should be
3540°F (1.74.5"C) prior the concentrate tempera- to loading. ture changes (concentrate
becomes thinner as tem-
perature rises).
if
it fails this
psi (2.8 bar)
Pump Inoperative
0
Pump motor defective. 28VDC should be present
at pump motor during dis-
pense.
If
voltage is pres­ent and motor does not start, replace pump motor.
0
No power to transformer or no 28VAC output from
transformer.
Confirm transformer has line voltage present on primary side. If no 28VAC output from the secondary replace transformer.
0
Defective voltage regula-
tor board (VRB) located
inside front electrical box.
Measure across the blue and black wire located
the upper
left
corner of the board. There should be 28VDC present when the dispense button is pressed. Replace VRB necessary.
in
if
15
8531 2001
Installation & Service Manual
Pump Inoperative (Cont’d).
Machine continues to dis­pense after dispense button is released or dispenses without operator input.
0
Defective portion control
board.
0
Portion control pad stuck in on position.
0
Relay on voltage regulator board (VRB) stuck on.
0
Disconnect wire harness from rear of portion con­trol, close door switch and short the orange and black wires together on
If
the harness.
unit dis­penses portion control board is defective. does not dispense the voltage regulator board is defective.
0
Disconnect the wire har­ness from the rear of the portion control and close the door. If unit does not dispense on its own the portion control is bad (stuck on).
0
Disconnect the &wire
harness from the lower
right corner of the VRB.
the unit continues to dis-
pense on its own the VRB is defective (relay stuck
on).
If
it
If
8531
2001
16
Installation
&
Service
Manual
System
Wiring
Diagram
17
8531
2001
Installation & Service Manual
0
0
0
0
Main Electrical
Box
Wiring Diagram
0
0 0
0
0
8631 2001
18
Installation & Service Manual
I
Item Number
I
I
1
6
Part Number
45551 455381 455091 451 55001
451 29001 451 52
491 57 49155 49154 45087 45088
00 000
Final
Assembly
P/N
45100401. (115VAC)
P/N
451 00402 (23OVAC)
I
Description
Pouch Holder, Plastic Shelf, Plastic Platform Grill, Drip Pan
I
Drip Pan Bracket, Drip Pan
Bushing
I
I
Shoulder Bolt - 1/4-20 X 1 3/16 S.S.
I
I
Upper Hinge Plate
..
I
Hinge - Top Cover
I
Hinge - Bottom Cover
Assembly,
-
-
19 85312001
QLT
Upper Hinge
180
w/Sold
I
Out Feature
I
1
I
I
I
Loading...
+ 24 hidden pages