Cornelius IMD300-15A, IMD300-30W, IMD302-15A, IMD300-30A, IMD301-30A Installation Manual

...
IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (612) 422-3246
Installation Manual
COUNTERTOP ICEMAKER
IMD SERIES
IMPORTANT:
TO THE INSTALLER. It is the responsibility of
the Installer to ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112.1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local Codes.
Part No. 638085277 Revisied October 16, 2000 Revision B
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 94-2000Ó
PRINTED IN U.S.A
TABLE OF CONTENTS
SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RECOGNIZE SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNDERSTAND SIGNAL WORDS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOLLOW SAFETY INSTRUCTIONS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 (CARBON DIOXIDE) WARNING 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHIPPING, STORING, OR RELOCATING UNIT 1. . . . . . . . . . . . . . . . . . . . . . .
SPECIFICATION CHART 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GUIDE TO SERVICE 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICEMAKER CLEANING AND SANITIZING PROCEDURES 9. . . . . . . . . . . . . . . . .
MAINTENANCE 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MONTHLY 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUARTERLY 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SEMI--ANNUALLY 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER LEVEL CONTROL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOW WATER LEVEL CONTROL WORKS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PURPOSE OF WATER LEVEL CONTROL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TO REPLACE WATER LEVEL CONTROL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TO REPLACE WATER LEVEL SAFETY SWITCH 11. . . . . . . . . . . . . . . . . . . . . . . . . .
ICE LEVEL CONTROL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEMPERATURE / PRESSURE CHARTS* 12. . . . . . . . . . . . . . . . . . . . . . . . . . . .
AIR TEMPERATURE 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 LBS. DISCHARGE PRESSURE 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER TEMPERATURE 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMD300--5 & IMD300--15 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMD300--30 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMD600--30, IMD600--90 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERATION SYSTEM ADJUSTMENTS 12.. .. .. .. .. .. .. .. .. .. .. .. .. .. .
EXPANSION VALVE 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENT AND TROUBLESHOOTING 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER MODULATING VALVE 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER MODULATING VALVE REMOVAL 13.. . . . . . . . . . . . . . . . . . . . . . . . .
GEAR MOTOR 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHAFT SEAL INSTALLATION AND REPLACEMENT (SEE FIGURE 7.) 14. . . . .
AUGER & EXTRUDING HEAD REMOVAL 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION AND SHAFT SEAL REPLACEMENT (SEE FIGURE 9.) 15. . . . . .
UPPER NUT AND BEARINGS 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TO REPLACE BEARINGS 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING COMPRESSOR 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL CHECKOUT 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OVERLOAD CHECK -- FIGURE 10. 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR CHECK -- FIGURE 11. 17. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
CAPACITOR CHECK 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
i 638085277
TABLE OF CONTENTS (cont’d)
TROUBLESHOOTING GEAR MOTORS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THE GEARMOTOR WILL NOT RUN 17.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THE GEARMOTOR STAR TS BUTS TRIPS REPEATEDLY ON THE
OVERLOAD PROTECTOR: 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THE MOTOR RUNS BUT OUTPUT SHAFT DOES NOT ROTATE: 17. . . . . . .
OVERLOAD CHECK: 17. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
MOTOR CHECK: 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONTROLS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GUIDE TO GOOD ICE 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING CHART -- ICEMAKER NOT OPERATING 21. . . . . . . . . . . . . . . .
PARTS LIST 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERATION AND FRAME ASSEMBLY IMD 300-15 PARTS LIST 29. . . . . . .
REFRIGERATION AND FRAME ASSEMBLY IMD 300--30 AND IMD 600--30
PARTS LIST 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERATION AND FRAME ASSEMBLY IMD 600--90 PART LIST 33. . . . . . . .
ICE LEVEL CONTROL ASSEMBLY PARTS LIST FOR PAR T NO
32770 IMD 300--15 AND 32770--002 IMD302--15 37. . . . . . . . . . . . . . . . . . . . . . . . . . .
ICE LEVEL CONTROL ASSEMBLY PARTS LIST IMD300--30 AND IMD600--30
PART NUO 31494--001 (115V) PART NO. 31494--002 (208V/220V) 39. . . . . . . . . . .
ICE LEVEL CONATROL ASSEMBLY PARTS LIST IMD 600--90
PART NO. 31892 41. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
BIN AND FRONT END ASSEMBLY PARTS LIST IMD 300-15, IMD 300-30
AND 600-30 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BIN AND FRONT END ASSEMBLY IMD PARTS LIST 600-90 45. . . . . . . . . . . . . . .
ELECTRICAL BOX ASSEMBLY PARTS LIST, PART NO. 32776 IMD 300--15
AND PAR T NO. 32776-002 IMD 302-15 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL BOX ASSEMBLY PARTS LIST IMD 300--30,
IMD 600--30 AND IMD 600-90 (ALL VOLTAGES) 49. . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSE MECHANISM ASSEMBLY PARTS LIST IMD 300-15, IMD300-30,
IMD 600-30 AND IMD 600-90 PARTS LIST 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GEAR MOTOR ASSEMBLY PARTS LIST 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 60.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
Page
FIGURE 1. DIMENSION DRAWING (15 LB.) IMD 300--15 4. . . . . . . . . . . . . . . . . . .
FIGURE 2. DIMENSION DRAWINGS (30 LBS.) IMD300--30 AND IMD600--30 5.
FIGURE 3. DIMENSION DRAWINGS (90 LBS.) IMD600--90 5. . . . . . . . . . . . . . . . .
FIGURE 4. FLOAT ASSEMBLY 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 5. UPPER BEARING AND AUGER ASSEMBLY 10. . . . . . . . . . . . . . . . . . .
FIGURE 6. ADJUSTMENT SCREW 13.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 7. IMD 300 SHAFT SEAL 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 8. AUGER AND EXTRUDING HEAD REMOVAL 14. . . . . . . . . . . . . . . . . .
FIGURE 9. IMD 600 SHAFT SEAL 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 10. OVERLOAD CHECK 16.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 11. COMPRESSOR CHECK 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
638085277
LIST OF FIGURES
ii
TABLE OF CONTENTS (cont’d)
FIGURE 12. PIN NUMBERS 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 13. GEAR MOTOR OVERLOAD 19.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 14. SCHEMATIC IMD 300--15 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 15. SCHEMATIC IMD 300--30, IMD600--30, IMD601--30, IMD600--90,
AND IMD601--90 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 16. SCHEMATIC IMD302--30, IMD602--30, AND IMD602--90 24. . . . . . . .
FIGURE 17. IMD 300--15 CABINET PARTS ASSEMBLY AND PARTS LIST 25. . . FIGURE 18. IMD300--30 AND IMD600--30 CABINET PARTS ASSEMBLY
AND PAR TS LIST 26.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
FIGURE 19. IMD600--90 CABINET PAR TS ASSEMBLY AND PARTS LIST 27. . . .
FIGURE 20. REFRIGERATION AND FRAME ASSEMBLY IMD 300--15 28. .. .. ..
FIGURE 21. REFRIGERATION AND FRAME ASSEMBLY IMD 300--30
AND IMD 600--30 30.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 22. REFRIGERATION AND FRAME ASSEMBLY IMD 600--90 32. .. .. ..
FIGURE 23. WATER CONTROL ASSEMBLY AND PAR TS LIST PART NO.
04643-04 IMD 300-30 AND IMD 600-30 34.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 24. WATER CONTROL ASSEMBLY AND PARTS LIST
PART NO. 32843 IMD 300--15 32545 IMD 600-90 35. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 25. TOP VIEW ICE LEVEL CONTROL ASSEMBLY
PART NO. 32770 IMD 300-15 AND 32770-002 IMD 302--5 36. . . . . . . . . . . . . . . . . .
FIGURE 26. SIDE VIEW ICE LEVEL CONTROL ASSEMBLY
PART NO. 32770 IMD 300-15 AND 32770-002 IMD 302--5 36. . . . . . . . . . . . . . . . . .
FIGURE 27. TOP VIEW ICE LEVEL CONTROL ASSEMBLY IMD 300-30 AND IMD 600-30PAR T NO. 31494-001 (115V) PART NO. 31494-002 (208V/220V) 38. .
FIGURE 28. SIDE VIEW ICE LEVEL CONTROL ASSEMBLY IMD 300-30 AND IMD 600-30PAR T NO. 31494-001 (115V) PART NO. 31494-002 (208V/220V) 38. .
FIGURE 29. TOP VIEW ICE LEVEL CONTROL ASSEMBLY IMD 600-90
PART NO. 31892 40. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 30. SIDE VIEW ICE LEVEL CONTROL ASSEMBLY IMD 600-90
PART NO. 31892 40. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 31. BIN AND FRONT END ASSEMBLY IMD 300-15, IMD 300-30
AND 600-30 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 32. BIN AND FRONT END ASSEMBLY IMD 600-90 44. . . . . . . . . . . . . . . .
FIGURE 33. ELECTRICAL BOX ASSEMBLY PART NO. 32776 IMD 300--15
AND PAR T NO. 32776-002 IMD 302-15 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 34. ELECTRICAL BOX ASSEMBLY IMD 300--30
AND IMD 600--30 IMD 600-90 (ALL VOLTAGES) 48. . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 35. COMPRESSOR ELECTRICAL BOX ASSEMBLY AND PAR TS LIST
IMD 300-30, 600-30 AND 601-30 50.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 36. COMPRESSOR ELECTRICAL BOX ASSEMBLY AND PAR TS LIST
IMD 302-30 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 37. COMPRESSOR ELECTRICAL BOX ASSEMBLY AND PAR TS LIST
IMD 602-30 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 38. COMPRESSOR ELECTRICAL BOX ASSEMBLY AND PAR TS LIST
IMD 600-90 AND IMD 601--90 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 39. COMPRESSOR ELECTRICAL BOX ASSEMBLY IMD 602-90
EXPLODED VIEW AND PARTS LIST 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 40. DISPENSE MECHANISM ASSEMBLY IMD 300-15, IMD300-30, IMD 600-30 AND IMD 600-90
EXPLODED VIEW 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii 638085277
Page
TABLE OF CONTENTS (cont’d)
FIGURE 41. GEAR MOTOR ASSEMBLY 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 42. GEAR MOTOR ASSEMBLY WIRING DIAGRAM (ALL VOLTAGES)
EXPLODED VIEW 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF TABLES
SPECIFICATION CHART 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEMPERATURE/PRESSURE CHARTS 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
638085277
iv
SAFETY INFORMATION
Recognize Safety Information
This is the safety-alert symbol. When you see this symbol on our machine or in this manual, be alert to the potentially of personal injury.
Follow recommended precautions and safe operating practices.
Understand Signal Words
A signal word - DANGER, WARNING, OR CAUTION is used with the safety-alert symbol. DANGER identi­fies the most serious hazards.
DANGER
Safety signs with signal word DANGER or WARNING are typically near specific hazards.
General precautions are listed on CAUTION safety signs. CAUTION also calls attention to safety mes­sages in this manual.
WARNING
CAUTION
Follow Safety Instructions
Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to use the controls properly . Do not let anyone operate the machine without instructions. Keep your machine in proper working condition. Unauthorized modifications to the machine may impair function and/or safety and affect the machine life.
CO2(Carbon Dioxide) Warning
CO2Displaces Oxygen. Strict Attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Person­nel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
Shipping, Storing, Or Relocating Unit
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient temperature will cause residual water remaining inside the Unit to freeze resulting in damage to internal components of the Unit.
CAUTION: Very high discharge pressure is present in system. Quick disconnects on your gauges will minimize Danger and loss of refrigerant.
1
638085277
CAUTION: Unit requires a separate electrical line. See Manual for proper fuse size.
WARNING: There Must Be Adequate Clearance Around Ice Maker. Allow Minimum 6” Air Intake and 4” For Air Exhaust on all sides and open to the front.
NOTICE Unit must be installed per local plumbing and electrical codes. See Installation Manual for unit requirements. Failure to do so may cause damage to unit, which would void the warranty.
NOTICE Using Any Parts Other Than Genuine Factory Manufactured Parts Relieves the Manufacturer of all Liability.
NOTICE Manufacturer Reserves The Right To Change Specifications At Any Time.
638085277
2
SPECIFICATION CHART
Models Condensing
Unit
IMD300--15A Air Cooled 115 60 1 6 0.82 2 12 R134a 15 IMD302--15A Air Cooled 220/240 50 1 3 0.5 1.6 12 R134a 15 IMD300--30A Air Cooled 115 60 1 10.1 1 2 28 R404A 20
IMD300--30W Water Cooled 115 60 1 10.1 N/A 2 13 R404A 20
IMD301--30A Air Cooled 208/230 60 1 5.7 1 1.6 28 R404A 20
IMD301--30W Water Cooled 208/230 60 1 5.7 N/A 1.6 13 R404A 20
IMD302--30A Air Cooled 220/240 50 1 5.3 0.5 1.6 28 R404A 20
IMD302--30W Water Cooled 220/240 50 1 5.3 N/A 1.6 13 R404A 20
IMD600--30A Air Cooled 115 60 1 12 1 2 28 R404A 20
IMD600--30W Water Cooled 115 60 1 12 N/A 2 14 R404A 20
IMD601--30A Air Cooled 208/230 60 1 7.7 1 1.6 28 R404A 20 IMD601--30W Water Cooled 208/230 60 1 7.7 N/A 1.6 14 R404A 20 IMD602--30W Water Cooled 220/240 50 1 8.2 N/A 1.6 14 R404A 20
IMD600--90A Air Cooled 115 60 1 12 1 2 24 R404A 20 IMD600--90W Water Cooled 115 60 1 12 N/A 2 14 R404A 20
IMD601--90A Air Cooled 208/230 60 1 7.7 1 1.6 24 R404A 20 IMD601--90W Water Cooled 208/230 60 1 7.7 N/A 1.6 14 R404A 20
IMD602--90A Air Cooled 220/240 50 1 8.2 0.5 1.6 24 R404A 20 IMD602--90W Water Cooled 220/240 50 1 8.2 N/A 1.6 14 R404A 20
NOTE: FOR UNITS NOT LISTED IN ABOVE CHART, REFER TO NAMEPLATE OR CONTACT FACTORY SERVICE.
VAC Hz Ph Comp
RLA
Fan
Amps
Grmtr Amps
Refrigerant Oz. Type
Circuit
Fuse
3
638085277
SHIPPING WT. 189 LBS. (APPROX.)
FIGURE 1. DIMENSION DRAWING (15 LB.) IMD 300--15
638085277
4
SHIPPING WT. (IMD300--30) 220 LBS. (APPROX.) SHIPPING WT. (IMD600--30) 240 LBS. (APPROX.)
FIGURE 2. DIMENSION DRAWINGS (30 LBS.) IMD300--30 AND IMD600--30
FIGURE 3. DIMENSION DRAWINGS (90 LBS.) IMD600--90
SHIPPING WT. 225 LBS. (APPROX.)
5
638085277
INSTALLATION INSTRUCTIONS
A.. REMOVE ICEMAKER FROM CARTON:
1. Keep unit in the upright position, remove carton and pallet from unit and inspect unit for damage. Upon inspection of unit, if any damage is found, file a claim with carrier immediately.
2. Locate Startup Card either on outside of container or on plastic liner. Fill in proper information and send one copy to factory, and other copy to Distributor. Postage is prepaid.
B.. CABINET REMOVAL
1. Locate and remove the (2) screws from under the front cover. Lift cover forward and up to remove.
2. Lift up front edge of top cover. Slide back about 1/2 inch and remove.
3. Remove (6) screws from the front of the machine.
4. Remove side panels by sliding the front edge out and then back slightly to disengage.
5. Remove the front splash panel by lifting slightly to disengage the front, then tilt forward and remove.
6. Remove bin top and remove shipping insert.
C.. PREPARATION OF INSTALLATION SITE
1. The refrigeration system on air cooled units requires airflow, so a well ventilated area should be cho­sen. A minimum of (6) inches must be maintained, free of any obstruction, for air intake. A minimum of (4) inches clearance is required for air exhaust.
2. With template provided make the necessary provisions in the counter for water, drain and the electrical hook--up. Provisions are available for rear and bottom connections of water and electrical. Use hole plugs provided to plug unused holes.
D.. WATER INLET HOOK--UP:
1. Water Inlet -- Fitting is a 1/4” SAE male flare located at the rear of the unit. Connect water supply with a 1/4”or larger copper or flexible tubing.
2. Water Pressure -- Unless otherwise specified, the unit is designed to operate on water pressures be­tween 10 P.S.I. and 90 P.S.I. (NOTE: for pressures above 90 P.S.I. a regulator must be installed).
3. Water Cooled Condensers a.. Inlet to modulating valve uses 3/8” FPT. Use separate 3/8” or larger water line. b.. Outlet is 3/8” FPT.
4. Filter Conditioners are recommended on supply lines to icemakers. Never run the water supply to wa­ter cooled Condenser through Filter/Conditioner, it uses up the cartridge unnecessarily and a saturated cartridge can starve the icemaker causing premature component damage. Separate water supplies are recommended.
NOTE: Unit must be installed per local plumbing code. E.. ELECTRICAL SUPPLY
1. Power Access -- Is provided by way of a 7/8” dia. hole in both the base and the rear panel. Route in­coming power in conduit, to icemaker electrical control box. Make connections to wires provided in control box and ground lug/screw. Plug unused hole.
2. Fused Line -- Should be a dedicated circuit checked and sized according to electrical rating shown on unit nameplate.
638085277
6
NOTE: Unit must be installed per local electrical code.
F.. DRAIN CONNECTION
1. Install splash panel on machine and hold in place with (2) screws. Do not tighten at this time.
2. Remove drain tray mounting bracket from their shipping carton.
3. Clip the drain tray mounting bracket onto the bottom of the splash panel in the brackets provided.
4. Hook the drain tray into the splash panel and onto the mounting bracket.
5. Push the drain elbow securely onto the drain tray. Do not glue in place.
6. Complete the drain hookup according to the instructions provided with unit
FIGURE 4. FLOAT ASSEMBLY
NOTE: Steps 7 and 8 to be completed only after all start up checks and adjustments are performed.
7. Replace side panels tightening all (6) screws (including splash panel screws left loose).
8. Replace top panel and front cover and secure with (2) screws.
NOTE: In those cases where the unit is base mounted and not on legs it should be sealed all around the base with NSF listed sealant. (IMI Wilshire P/N 04815--B).
G.. AUGER ENGAGEMENT
Be certain that auger is fully engaged to lower drive and that extruding head is fully engaged to evaporator.
H.. INITIAL START UP, CHECKS & ADJUSTMENT INSTRUCTIONS NOTE: Do not start unit before completing Installation steps A--G.
Turn on water supply and main power switch (located on top of electrical box). All IMD 30 lb. and 90 lb. series units are equipped with a 45 second delay timer. This means that the refrigeration system will not start until 45 seconds of dispense are accumulated in the timer. Start the refrigeration system by depressing the ice dis-
pense button for 45 seconds. Make the following system checks: NOTE: If unit will not start be sure water reservoir is full. Low water safety control must be properly adjusted to
start and shut down unit. If water level drops below bottom of reservoir, unit must shut down. Adjustment is made by moving magnet up or down.
Water Level -- If necessary adjust Float by bending float arm up or down as needed, push float assembly down until unit stops running. Release float and unit will restart. Keep water in reservoir at level line while unit is in op­eration. See Figure 1.
7
638085277
Low Water Safety Control -- Adjust magnet by bending magnet arm as shown in figure 1 to shut down unit if the water level drops below the line on the side of the reservoir.
Bin Control -- Remove four screws from top of bin cover and lift cover so bin control plate can be manually lifted until unit shuts down. Release plate and unit will restart (On IMD300--30, IMD600--30 and IMD600--90 the dis­pense button must be depressed for 45 seconds before unit will start). Replace screws.
Dispense Switch and Mechanism -- By depressing the dispense switch, the dispense mechanism door on the storage bin will open, and chain, sprockets, and agitator will rotate counterclockwise.
NOTE: If any of these checks or adjustments cannot be achieved, refer to Troubleshooting Section of this
manual or call our technical support center for assistance at 1--800--238--3600.
638085277
8
GUIDE TO SERVICE
ICEMAKER CLEANING AND SANITIZING PROCEDURES
Do not use any of the ice made during cleaning operations. Clean and sanitize ice storage area when cleaning icemaker.
1. Turn machine off.
2. Shut off water supply.
3. Remove ice from storage bin.
4. Mix approved cleaner (2 gallons as directed). Recommended cleaner: Calgon Corp. of Virginia Chemi­cals, ice machine cleaner. Mixture: 3-1/3 ounces per gallon of water. Do not use nickel safe cleaners.
5. Turn machine on and add cleaner solution to water level control (float reservoir) until 2 gallons have been used.
6. Turn on water supply and run machine for 15 minutes.
7. Turn off machine and remove and discard all ice.
8. Sanitize using household liquid bleach (50 ppm chlorine). Mixture: 1 fluid ounce per gallon room tempera­ture water. 2 minute exposure time.
9. Sanitize pre--cleaned inside areas of storage bin liner, door frame, door, as well as exposed surfaces of the evaporator assembly and bin shutoff assembly with sanitizing solution and allow to air dry .
MAINTENANCE
Preventive maintenance can increase the trouble free life of your icemaker. Many authorized service agencies offer service contracts for your icemaker. Contact your local distributor for further information.
MONTHLY
1. Clean the condenser. Use a brush, vacuum cleaner or blow from inside with air or CO2gas. If unit is pro­vided with and air filter, clean or replace.
2. Inspect water feed reservoir at lease once a month until a definite pattern for cleaning and sanitizing has been established.
QUARTERLY
This is the maximum period of time between cleaning and sanitizing the icemaker. In addition to recommended monthly procedure, and if a more frequent cleaning and sanitizing pattern has not been established, unit must be cleaned and sanitized.
SEMI--ANNUALLY
Semi-Annually in addition to all previously established service procedures perform the following:
1. Check for water leaks in tube connections, water fittings and lower icemaker water seal.
2. Check drain tubes for clogs and “aged” tubes. Replace if tubes are stained or brittle.
3. Check for signs of condensation. Clean where necessary and replace insulation properly.
9
638085277
4. Check safety circuits for proper operation.
5. Check refrigeration system (see page12 12).
6. Check unit for abnormal noise. Tighten machine and cabinet screws, if necessary .
7. Check white upper bearings on auger assembly . If bearings are less than 1/16? thick, replace. See Figure 5
REPLACE
OK
1/16?
REPLACE
1/16?
OK
FIGURE 5. UPPER BEARING AND AUGER ASSEMBLY
NOTE: preventive maintenance can increase the trouble--free life of your ice maker. Failure to perform
preventive maintenance could void your equipment warranty
638085277
10
WATER LEVEL CONTROL
HOW WATER LEVEL CONTROL WORKS
When water is introduced through the inlet fitting the float rises. the float pushes against a lever which in turn forces the poppet assembly against the inlet fitting valve seat which seals the water off, (See Figure 4). Before the water inlet is sealed the safety switch is operated. In the event of a water failure the float would drop down and operate the safety switch to shut off the machine.
If water level control will not shut off and seal at level as indicated, be sure inlet pressure does not exceed rec­ommended factory operating range.
Under ordinary circumstances adjustment should not be necessary providing it was properly adjusted when unit was installed or relocated. If, however, the control becomes inoperative, repair or replace. See Start-Up Adjust­ment, page 7 .
PURPOSE OF WATER LEVEL CONTROL
1. To automatically maintain proper water level in the evaporator when unit is running and making ice.
2. A safety switch is operated in the event of an interruption in water supply. The switch shuts off the electrical power to the icemaker and its refrigeration system. Switch will reset as soon as cause of water failure has been corrected and proper water level in icemaker has again been reached.
3. The transparent bowl not only provides a visible check of water level, but also is a good guide to the inter­nal conditions which exist within the icemaker assembly itself. (See Cleaning Procedure.)
TO REPLACE WATER LEVEL CONTROL
1. Shut off the water supply . Shut off the main power switch or unplug the ice dispenser from electrical outlet.
2. Remove the flexible tubing from bottom of water level control and drain water from water level control and evaporator.
3. Remove flexible tubing at bottom of water level bowl connected to the overflow.
4. Hold water inlet fitting with proper tool to prevent it from rotating when disconnecting the water inlet.
5. Remove wing nut holding water control to its mounting bracket. Control can be removed by lifting straight up.
TO REPLACE WATER LEVEL SAFETY SWITCH
1. Shut off main power switch or unplug the ice dispenser from electrical outlet.
2. Unplug molex connector connecting switch to electrical box.
3. Remove the 2 screws anchoring the water level safety switch to the bottom of the water level control mounting bracket.
ICE LEVEL CONTROL
The ice level control assembly is secured to the top of the ice storage container cover. The cover is secured to the storage container with four screws. The level control switch is operated by a plate assembly located beneath the diaphragm. When the plate assembly is down due to lack of ice in storage container, electrical impulse is sent to compressor, starting the ice making cycle. As ice level increases in storage container, the plate assembly is pushed up. When storage container is full, it de--actuates the switch, stopping the compressor and ice making cycle.
11
638085277
The operating positions of the switch are fixed, no adjustments are necessary. If switch replacement becomes necessary , simply disconnect cable at connector, remove wires from switch.
TEMPERATURE / PRESSURE CHARTS*
±10 lbs. Discharge Pressure
Water Temperature
IMD300 --5 & IMD300--15 IMD300--30
IMD600 --30, IMD600--90
40_ 65_ 90_ 40_ 65_ 90_
162
188 214
245 275 309
166 192 218
249
279 313
168 194
220 251 281
315
174 202
230
265 300 328
177
205
233 269
304 334
180
208
236
272 307
340
50_
60_
70_
80_ 90_
Air Temperature
100_
40_ 65_ 80
92
114 124 161 187
NOTE: The thermostatic expansion valve is non--adjustable on all models.
85
97
120 120 167 193
90_
90 102 124 147
171
195
REFRIGERATION SYSTEM ADJUSTMENTS
A complete understanding of the icemaker and hermetic refrigeration system is necessary before any adjust­ments are made. The refrigeration technician must use high and low side pressure readings, water and air tem­peratures, plus general conditions of cleanliness to assess the refrigeration system status when making any adjustments.
All icemaker products are tested and adjusted at the factory prior to shipment where the ambient temperature ranges from 65_F to 90_F, depending on the season of the year.
Whenever a new icemaker is initially installed and started--up, it is imperative that the start --up operator make the following checks and readjustments for local conditions.
EXPANSION VALVE
You will find a thermal expansion valve on ice makers, which is used to control the amount of refrigerant flowing through the evaporator. Improperly installed or defective expansion valves may cause low production, soft ice, squeaking from evaporator and excessive load inside evaporator.
By using general refrigeration trouble shooting along with the pressure charts, you can easily determine whether or not the expansion valve is working properly.
ADJUSTMENT AND TROUBLESHOOTING
When troubleshooting the expansion valve, you must;
1. Be sure you have adequate water flowing into the evaporator, a clean and properly ventilated condenser, and the system is properly charged and free of any restrictions. Also be sure compressor is operating prop­erly .
2. Take reservoir water temperature and air temperature from condenser inlet and determine at what pressure unit should be running. On machines equipped with thermostatic valve there is NO adjustment. If correct pressure cannot be obtained, be sure system has time to stabilize, 10--15 minutes.
3. Be sure sensing bulb is located at outlet side of evaporator about 3--4 inches away from evaporator and be sure to insulate well and clamp tightly to tubing. If system pressures are still not adequate, take a second water and air temperature reading and go over other parts of the system for possible problems. If proper charge is questionable evacuate and recharge to nameplate and leak check. If valve still malfunctions re­place valve.
638085277
12
Use general refrigeration system practices when replacing and recharging unit. After new valve is in place, go through previous monitored adjustments and troubleshooting to be sure valve is functioning properly .
NOTE: On water cooled units adjust condenser modulating valve before troubleshooting expansion valve.
CAUTION: Very high discharge pressure is present in system. Quick disconnects on your gages will minimize Danger and loss of refrigerant. Comply with federal regulations for reclaiming refrigerant.
CONDENSER MODULATING VAL VE
The reason for using a water modulating valve is to supply the correct amount of water to the condenser to maintain the proper operating pressure in the refrigeration system high side. The flow of water through the valve is increased as the high side pressure rises and decreases as high side pressure lowers.
To calibrate the amount of water flow with the refrigeration system high side pressure, turn adjustment screw located on end of valve opposite of bellows See Figure 4. Turn screw counterclockwise to raise opening point. Opening point of valve should be set to maintain proper operating pressure in refrigeration system high side. Refer to Pressure Chart on Page 11. Closing point of valve should be set low enough to close valve during com­pressor stand by periods.
NOTE: Cold water will absorb more heat faster than warm water. The water flow will therefore
automatically increase as inlet temperature increases.
CONDENSER MODULATING VAL VE REMOVAL
1. Disconnect power to unit, then shut off water supply to condenser and reclaim refrigerant from system.
2. Remove inlet water line from Condenser modulating Valve. Also remove tube from refrigerant high side line.
3. Remove Condenser Modulating Valve and bracket.
4. Remove valve from bracket.
5. Replace Condenser Modulating Valve by reversing Steps 2 thru 4. Then pull system into vacuum.
FIGURE 6. ADJUSTMENT SCREW
13
638085277
6. Recharge unit with refrigerant per nameplate.
7. Turn power and water On to unit.
8. With unit running adjust modulating valve to proper setting.
9. Go through a complete system check.
GEAR MOTOR
The gear motor is equipped with a start relay and a manual reset overload. When current is applied, the relay energizes and completes the circuit to the start winding. The motor reaches a predetermined speed and the relay drops out, disconnecting the start winding. The run winding remains in the circuit as long as current is ap­plied.
The purpose of the overload is to automatically shut off the motor in the event of a mechanical bind of the trans­mission, an overload condition within the evaporator or an electrical malfunction. It does this by sensing amper­age draw. If the motor stalls the start relay would energize and stay energized. The amperage would surge to 5 to 6 times greater than normal draw. In this event the overload would shut off the transmission in 4 to 8 seconds.
If the motor is subjected to an abnormal load, but does not reach stall condition, the overload will react, but over a greater period of time. The reaction time depends upon the amperage to which it is subjected.
The overload, through the safety circuit, also shuts off the compressor. Refer to Troubleshooting Guide.
E--RING
WASHER, PLAIN FLAT
SHAFT SEAL
LOCATOR SEAL
GEARMOTOR
FIGURE 7. IMD 300 SHAFT SEAL
BEARING DELRIN
COLLAR WITH
ANTI--ROTATION RIB
FIGURE 8. AUGER AND EXTRUDING HEAD REMOVAL
AUGER NUT
BEARING NYLON
GROOVE
EXTRUDING
HEAD
AUGER
D DRIVE
SHAFT SEAL INSTALLATION AND REPLACEMENT (SEE FIGURE 7.)
1. Place shaft seal locator seat over gear motor output shaft, embossed side down, and push down until shaft seal seat rests flush on top of gear motor.
2. Place rubber coated ceramic seal (important: ceramic face up) over output shaft and push down until seal rests on top of the shaft seal seat. (Lubricate rubber on ceramic seal with [#06195] rubber lubricant.)
3. Place shaft seal with carbon face down(spring up) over output shaft and push (gently) downward until seal rests on carbon face of the output shaft seal.
4. Push down on the washer compressing the spring on the output shaft seal. While holding the seals (down) in place slide the E--ring into the groove on the output shaft.
638085277
14
AUGER & EXTRUDING HEAD REMOVAL
1. Disconnect unit from power supply.
2. Remove storage container cover and put aside.
3. Turn off water supply to icemaker.
4. After ice has melted from head take hold of the auger nut and lift straight up to disengage from icemaker.
5. When replacing the auger assembly, make certain that both the auger engages the output shaft drive and the extruding head ribs engage the evaporator tube collar. See Figures 8.
E--RING
WASHER, PLAIN FLAT
SHAFT SEAL
MOUNT ,SHAFT SEAL
LOCATOR SEAT
GEARMOTOR
FIGURE 9. IMD 600 SHAFT SEAL
INSTALLATION AND SHAFT SEAL REPLACEMENT (SEE FIGURE 9.)
1. Place shaft seal locator seat over gear motor output shaft, embossed side down, and push down until shaft seal seat rests flush on top of gear motor.
2. Place rubber coated ceramic seal (important: ceramic face up) over output shaft and push down until seal rests on top of the shaft seal seat. (Lubricate rubber on ceramic seal with [#06195] rubber lubricant.)
3. Place shaft seal with carbon face down(spring up) over output shaft and push (gently) downward until seal rests on carbon face of the output shaft seal.
4. Place flat washer over output shaft and let rest on the output shaft seal. Push down on the washer com­pressing the spring on the output shaft seal. While holding the seals (down) in place slide the E--ring into the groove on the output shaft.
UPPER NUT AND BEARINGS
The upper bearings located on top of the auger is used to absorb the force between the auger and extruding head.
The bearings are 3/32” thick. When they wear below 1/16” they should be replaced. Bearings to be inspected for wear during quarterly maintenance. See Figure 5.
15
638085277
TO REPLACE BEARINGS
1. Dispense all ice from unit.
2. Disconnect unit from electrical power.
3. Remove panels.
4. Unplug Dispense Motor and Ice Level Switch.
5. Remove four screws holding dispense cover in place.
6. Remove dispense cover assembly .
7. Use an open end wrench on auger nut connected to bearing and turn and turn counterclockwise to remove assembly .
8. Remove worn bearings. Replace with new bearings and then reinstall assembly.
NOTE: If auger turns with nut, remove cover on top of gear motor stator and hold rotor while loosening nut.
9. Reconnect power to icemaker.
TROUBLESHOOTING COMPRESSOR
Basically the compressor problems can be narrowed down to three areas of checkout--
1. THE COMPRESSOR WILL NOT RUN
No voltage to the compressor terminals -- check circuit. Low voltage -- below 90% of nameplate rated voltage. Problems in the compressor electrical circuit. See Electrical Checkout instructions.
2. THE COMPRESSOR STARTS BUT TRIPS REPEATEDLY ON THE OVERLOAD PROTECTOR
Check for proper fan operation and clean condenser. Check the compressor suction and discharge pressures. Voltage -- The voltage should be within 10% of the rated nameplate voltage. High compressor amperage draw, it should never exceed 120% of the rated nameplate amperage. See
Electrical Checkout Instructions.
3. THE COMPRESSOR RUNS BUT WILL NOT REFRIGERATE
Check the compressor suction and discharge pressures. See Chart on Page 12.
ELECTRICAL CHECKOUT
1. Be sure the unit is disconnected from the power source. Remove the compressor electrical box cover. Check for obvious damage and loose wires.
2. Disconnect the fan motor leads. Since capacitors store energy, short the capacitor with a screwdriver. This will prevent shocks.
3. Disconnect the compressor terminal wires.
FIGURE 10. OVERLOAD CHECK FIGURE 11. COMPRESSOR CHECK
638085277
16
Loading...
+ 49 hidden pages