Cornelius IAC1030 Service Manual

THE HOTTEST MACHINES ON ICET
I" Series
Ice Cube Machine
SERVICE MANUAL & MAINTENANCE GUIDE
(Includes Installation Instructions)
Revised: 3/4/96
12/1/94166240004
TABLE OF CONTENTS
MODEL AND SERIAL LOCATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
“I” SERIES CUBER 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERIAL NUMBER EXPLANATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPECIFICATIONS 3 – 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FREIGHT DAMAGE CLAIMS PROCEDURE 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION OF EQUIPMENT 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EQUIPMENT SET-UP 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSER INSTALLATION 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IACS/IWCS 227 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLUMBING CONNECTIONS 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION CHECK POINTS 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START-UP AND CHECK OUT 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OWNER -OPERATOR 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
CLEANING PROCEDURES 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREP – CLEANING 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING THE WATER SYSTEM AND EVAPORATOR 16. . . . . . . . . . . . . . .
SANITIZING PROCEDURES 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUMP CYCLE 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING BRIDGE THICKNESS 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TOTAL ICE CAPACITY 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICE PRODUCTION CHECK 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED INDICATORS 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CIRCUIT BOARD DIAGNOSTIC PROCEDURE 22. . . . . . . . . . . . . . . . . . . . . . . . . . . .
RESTORING ICE THICKNESS POTENTIOMETER TO FACTORY SETTING 23. .
MAKING ADJUSTMENTS 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPONENT FUNCTION (CIRCUIT BOARD ETC.) 24. . . . . . . . . . . . . . . . . . . . . . . . . .
TEST PLUG 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SENSORS 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RESET OPERATION 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EVAPORATOR SWITCHES 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HARVEST SAFETY TERMINATION 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VOLTAGE CHECKS 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EVAPORATOR PROXIMITY SWITCH 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VOLTAGE SELECTOR SWITCH 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STACKING CABLE 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SENSOR [THERMISTOR] DIAGNOSIS 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SENSORS 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER FAN CYCLING CONTROL 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THERMOSTATIC EXPANSION VALVES 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STARVING TXV - PRODUCT SYMPTOMS 26. . . . . . . . . . . . . . . . . . . . . . . . . . .
i
TABLE OF CONTENTS (cont’d)
FLOODING TXV - PRODUCT SYMPTOMS 26. . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER REGULATING VALVE 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE STEM VALVES 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOISTURE CONTAMINATION 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR CONTACTOR 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR & STARTING COMPONENT CHECK-OUT PROCEDURE 28. . . .
RELAY 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POTENTIAL – 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CURRENT – 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAPACITORS 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LEAK DETECTION 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSTEM EVACUATION & RECHARGING 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SELF-CONTAINED PRODUCTS 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIGH PRESSURE SAFETY SWITCH 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR RUN-ON 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER NOT OPERATING 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER NOT OPERATING, INDICATOR LIGHTS “OFF”, NO POWER
TO CIRCUIT BOARD 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER NOT OPERATING,
INDICATOR LIGHTS “OFF”, POWER TO THE CIRCUIT BOARD 51. . . . . . . . . . . .
COMPRESSOR DOES NOT RUN, CIRCUIT BOARD
INDICATOR LIGHTS “ON” 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR RUNS BUT DOES NOT COOL, CIRCUIT
BOARD INDICATOR LIGHTS “ON” 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER REMAINS IN THE FREEZE CYCLE 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CUBER REMAINS IN THE HARVEST CYCLE 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SUCTION LINE THERMISTOR OPEN (STARTS IN HARVEST) 52. . . . . . . . . . . . . .
PROXIMITY SWITCH LIGHT “OUT” 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROXIMITY SWITCH LIGHT “ON” 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LONG FREEZE CYCLE WATER FLOW ASSOCIATED 53. . . . . . . . . . . . . . . . . . . . .
LONG FREEZE CYCLE GENERAL 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LONG HARVEST CYCLES 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICE WEIGHT LIGHT AT TOP OF PLATE AND HEAVY AT THE BOTTOM 54. . . . .
SOFT WHITE ICE OR WATER PUMP NOT PUMPING 54. . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS 71. . . . . . . . . . . . . . . .
REMOTE CONDENSER LOCATION 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HEAD PRESSURE CONTROL [HEADMASTER] 77. . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE SYSTEM EVACUATION/RE-CHARGE 78. . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
LIST OF FIGURES
LIST OF TABLES
ii
MODEL AND SERIAL LOCATION
I SERIES CUBER
Condenser Discharge Air Deflector (as required)*
Bin Adapter (as required)*
Model/Serial Number Location
*Bin adapters and condenser discharge air deflector may be equipped depending on your location or the size of the storage bin.
Record the model number and the serial number of your ice equipment. These numbers are required when re­questing information from your local dealer/distributor/service company.
Model Number – Date Installed –
Serial Number – Purchased From -
SERIAL NUMBER EXPLANATION
AA 95 01 BC 0001
Number – 4 digit number, 0001 – 9999
Product Code – 2 digit alpha
Month – 2 digit numerical month designation
Year – 2 digit year designation
Engineering Change Level – 1 or 2 alpha designation
12/1/94 Rev 3/4/96
1
REMOTE CONDENSER SPECIFICATION
MODEL CR800 CR1200 CR1400
Volts 208/230 208/230 208/230 Phase 1 1 1 Hertz 60 60 60 Amps 1.0 1.0 1.0 Output, HP 1/6 1/6 1/6 Max. fuse size, Amps (HVAC circuit breaker
required)
20 20 20
ICE CUBER SPECIFICATION
MODEL
IAC322/330
IAC227
UNIT
Volts 115 115 115 115 Phase 1 1 1 1 Hertz 60 60 60 60 No. Wires 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 20
REFRIGERANT
Type R404A (HP62) R404A (HP62) R404A (HP62) R404A (HP 62) Weight (oz) 17 15 26 23 Weight (g) 482 425 737 652
COMPRESSOR
Volts 115 115 115 115 Phase 1 1 1 1 Hertz 60 60 60 60 LRA 51 51 59 59 RLA 11.5 11.5 11.6 11.6
CONDENSER FAN MOTOR (Air-Cooled Systems only) of AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 115 115 115 115 Phase 1 1 1 1 Hertz 60 60 60 60 Amps Running 1.7 0.38 1.75 0.38 Watts 50 6 50 6
WATER PUMP
Volts 115 115 115 115 Phase 1 1 1 1 Hertz 60 60 60 60 Amps Running 0.88 0.88 0.76 0.88 HP 1/40 1/40 1/40 1/40
IWC322/330
IWCS227
IAC522/530 IWC522/530
2
12/1/94 Rev 3/4/96
12/1/94
Rev 3/4/96
3
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
IAC322E60
MODEL
UNIT
Volts 230 230 230 230 Phase 1 1 1 1 Hertz 60 60 60 60 No. Wires 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 15 15 15 15
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 15 15 15 15
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP 62) Weight (oz) 17 15 26 23 Weight (g) 482 425 737 652
COMPRESSOR
Volts 230 230 230 230 Phase 1 1 1 1 Hertz 60 60 60 60 LRA 24.1 24.1 45 45 RLA 5.7 5.7 9.2 9.2
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 230 230 230 230 Phase 1 1 1 1 Hertz 60 60 60 60 Amps Running 0.89 0.36 0.89 .036 Watts 50 6 50 6
WATER PUMP
Volts 230 230 230 230 Phase 1 1 1 1 Hertz 60 60 60 60 Amps Running 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30
IAC330E60
IACS227E60
IWC322E60 IWC330E60
IWCS227E60
IAC522E60
IAC522E60L
IAC530E60
IAC530E60L
IWC522E60
IWC522E60L
IWC530E60
IWC530E60L
4
12/1/94
Rev 3/4/96
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
MODEL IAC630 IWC630 IRC630 IAC830 IWC830 IRC830
UNIT
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 No. Wires 2+ground 2+ground 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 20 20 20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 20 20 20
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP62) Weight (oz) 43 35 170 55 33 170 Weight (g) 1219 992 4820 1559 936 4820
COMPRESSOR
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 LRA 69 69 69 61 61 61 RLA 8.8 8.8 8.8 12.5 12.5 12.5
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 Amps Running 1.09 0.36 0.36 1.09 0.36 0.36 Watts 75 6 6 75 6 6
WATER PUMP
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 Amps Running 0.5 0.5 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30 1/30 1/30
12/1/94
Rev 3/4/96
5
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
MODEL
UNIT
Volts 230 230 230 Phase 1 1 1 Hertz 60 60 60 No. Wires 2+Ground 2+Ground 2+Ground
MIN. CIRCUIT
Amps 20 20 20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20
REFRIGERANT
Type R404a(HP62) R404a(HP62) R404a(HP62) Weight (oz) 60 42 210 Weight (g) 1701 1191 5954
COMPRESSOR
Volts 230 230 230 Phase 1 1 1 Hertz 60 60 60 LRA 82 82 82 RLA 13.0 13.0 13.0
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 230 230 230 Phase 1 1 1 Hertz 60 60 60 Amps Running 0.892 0.36 0.36 Watts 50W2 6W 6W
WATER PUMP
Volts 230 230 230 Phase 1 1 1 Hertz 60 60 60 Amps Running 0.5 0.5 0.5 HP 1/30 1/30 1/30
IAC1030
IAC1030L
IWC1030
IWC1030L
IRC1030
IRC1030L
6
12/1/94
Rev 3/4/96
SPECIFICATIONS – 60 HZ
ICE CUBER SPECIFICATION
MODEL IAC1230 IWC1230 IRC1230 IAC1448 IWC1448 IRC1448
UNIT
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 No. Wires 2+ground 2+ground 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 25 25 25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 25 25 25
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP 62) R404A(HP 62) R404A(HP 62) Weight (oz) 49 45 210 92 44 250 Weight (g) 1389 1276 5954 2608 1247 7088
COMPRESSOR
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 LRA 96 96 96 95.6 95.6 95.6 RLA 13.5 13.5 13.5 23.9 23.9 23.9
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 Amps Running 0.89 X 2 0.36 0.36 0.4 0.36 0.36 Watts 50 W X 2 6 W 6 W 1/15 HP 6 W 6 W
WATER PUMP
Volts 230 230 230 230 230 230 Phase 1 1 1 1 1 1 Hertz 60 60 60 60 60 60 Amps Running 0.5 0.5 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30 1/30 1/30
12/1/94
Rev 3/4/96
SPECIFICATIONS – 50 HZ
7
IAC322E50
MODEL
UNIT
Volts 220 220 220 220 Phase 1 1 1 1 Hertz 50 50 50 50 No. Wires 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 15 15 15 15
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 15 15 15 15
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP 62) Weight (oz) 17 15 26 23 Weight (g) 482 425 737 652
COMPRESSOR
Volts 220 220 220 220 Phase 1 1 1 1 Hertz 50 50 50 50 LRA 26 26 33 33 RLA 5.3 5.3 8.2 8.2
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 220 220 220 220 Phase 1 1 1 1 Hertz 50 50 50 50 Amps Running 0.75 0.3 0.75 0.3 Watts 50 6 50 6
WATER PUMP
Volts 220 220 220 220 Phase 1 1 1 1 Hertz 50 50 50 50 Amps Running 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30
IAC330E50
IACS277E50
IWC322E50 IWC330E50
IWCS227E50
IAC522E50
IAC522E50L
IAC530E50
IAC530E50L
IWC522E50
IWC522E50L
IWC530E50
IWC530E50L
SPECIFICATIONS – 50 HZ
8
12/1/94
Rev 3/4/96
MODEL
UNIT
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 No. Wires 2+ground 2+ground 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 20 20 20
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 20 20 20
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP 62) R404A(HP 62) R404A(HP 62) Weight (oz) 43 35 170 55 33 170 Weight (g) 1219 992 4820 1559 936 4820
COMPRESSOR
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 LRA 53 53 53 58 58 58 RLA 8 8 8 12 12 12
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 Amps Running 1.06 0.3 0.3 1.06 0.3 0.3 Watts 75 6 6 75 6 6
WATER PUMP
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 Amps Running 0.5 0.5 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30 1/30 1/30
IAC630E50
IAC630E50L
IWC630E50
IWC630E50L
IRC630E50 IRC63050L
IAC830E50
IAC830E50L
IWC830E50
IWC830E50L
IRC830E50
IRC830E50L
12/1/94
Rev 3/4/96
SPECIFICATIONS – 50 HZ
9
MODEL
UNIT
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 No. Wires 2+ground 2+ground 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 25 25 25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 25 25 25
REFRIGERANT
Type R404A(HP62) R404A(HP62) R404A(HP62) R404A(HP 62) R404A(HP 62) R404A(HP 62) Weight (oz) 49 45 210 92 44 250 Weight (g) 1389 1276 5954 2608 1247 7088
COMPRESSOR
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 LRA 64 64 64 75.9 75.9 75.9 RLA 12.5 12.5 12.5 13 13 13
CONDENSER FAN MOTOR (Air-Cooled Systems only) or AIR CIRCULATION FAN MOTOR (Water-Cooled and Remote Systems only)
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 Amps Running 0.752 0.3 0.3 0.752 0.3 0.3 Watts 0.50W2 6W 6W 0.75W2 6W 6W
WATER PUMP
Volts 220 220 220 220 220 220 Phase 1 1 1 1 1 1 Hertz 50 50 50 50 50 50 Amps Running 0.5 0.5 0.5 0.5 0.5 0.5 HP 1/30 1/30 1/30 1/30 1/30 1/30
IAC1030E50
IAC1030E50L
IWC1030E50
IWC1030E50L
IRC1030E50 IRC103050L
IAC1230E50
IAC1230E50L
IWC1230E50
IWC1230E50L
IRC1230E50
IRC1230E50L
10
SPECIFICATIONS – 50 HZ, REMOTE CONDENSER
MODEL CR800E50 CR1200E50 CR1400E50
UNIT
Volts 220 220 220 Phase 1 1 1 Hertz 50 50 50 Amps 1.1 1.1 1.1 Output H.P. 1/6 1/6 1/6 MAX fuse size, Amps
(HVAC circuit breaker required
20 20 20
12/1/94
Rev 3/4/96
GENERAL
FREIGHT DAMAGE CLAIMS PROCEDURE
The deliverer of your equipment (freight company, distributor or dealer) is responsible for loss or damage of your shipment. All claims must be filed with the deliverer of your equipment. Please follow the steps below to deter­mine if your shipment is satisfactory or if a claim must be filed:
1. Check the number of products delivered against the number of products listed on the delivery receipt. Should the totals not match, have the driver note all errors on both copies and both you and the driver sign and date said notation.
2. Inspect all cartons for visible damage. Open and inspect as required before the driver leaves and have him or her note any damage on the receipts. All damaged claims must be inspected within 15 days of delivery. Notify your carrier immediately if concealed damage is found after delivery.
3. Should concealed damage be found when product is unpacked, retain the packing material and the product and request an inspection from the deliverer.
4. All claims for loss or damage should be filed at once. Delays in filing will reduce the chance of achieving a satisfactory resolution to the claim.
12/1/94 Rev 3/4/96
11
INSTALLATION INSTRUCTIONS
Installation and start-up of the equipment should be performed by the distributor or the dealer’s professional staff.
LOCATION OF EQUIPMENT
For maximum performance the location should be away from heat sources such as ovens, direct sunlight, hot air discharge, etc.
To reduce cost of maintenance and loss of efficiency, avoid placing air-cooled equipment in areas where grease, flour and other airborne contaminants are present. Allow a minimum of 6I (15.24 cm) clearance on all sides and top for proper air circulation. Restricted air circulation will affect the efficiency and required maintenance of the product.
IMPORTANT: Never operate your equipment in room temperature below 50_F (10_) or above 100_ F (38_C). Should the location of your product ever be exposed to freezing temperatures, it must be shut down and winterized.
EQUIPMENT SET-UP
The following steps refer to the set-up of the ice bin and the cuber:
1. Remove the bin from its carton, place it on its back and install the legs into the bottom of the bin. Bins must be installed on legs or sealed to the floor with RTV-732 sealant.
2. Set the bin up on its legs. Place the bin in its final location and level it with the adjustable feet in the legs.
3. Unpack the cuber from its carton, and set in place on the bin and adjust as required. Leave all panels on the cuber until it is set in place on the dispenser or bin.
4. Remove all internal packing from the cuber.
THREAD LEVELING LEG INTO BASE
NOTE: Bin adapter andcondenser air baffles may be required in certain installations.
DISPENSER INSTALLATION
The proper cuber/dispenser installation package should be ordered. This package will include gasket material and hold-down bracket.
12
12/1/94 Rev 3/4/96
R
D
A
(
E
0
0
R
IACS/IWCS 227
C
25.06
6.0 MIN
15.25
27.00
28.00
33.00
31.38
21.38
31.38
21.38
7.06
7.06
A
B
D
1.00(3)
IACS 227 REAR VIEW
C
A
B E F
2.06
1.00(5) IWCS 227
REAR VIEW
1. LAY CABINET ON BACK OR SIDE USING BLANKET O
2. REMOVE CRATE SKID FROM UNIT BOTTOM.
3. SCREW ADJUSTABLE LEGS INTO RECESSED THREA
4. LEVEL UNIT USING FEET FOR ADJUSTMENT.
8.75
D
8.75
INSTRUCTIONS FOR ATTACHING SUPPORT LEGS
PADDING TO AVOID MARRING.
A ELECTRICAL CORD ATTACHED (2 B 3/4 DRAIN – TUBING SIZE 5/8 I.D. C 3/8 WATER INLET (SEA MALE FLA D 3/4 BIN DRAIN – STD PIPE SAE
2.25
A ELECTRICAL CORD ATTACHED (2 B 3/4 DRAIN – TUBING SIZE 5/8 I.D. C 3/8 RESERVOIR WATER INLET (SA D 3/4 BIN DRAIN – STD PIPE SAE E 5/8 CONDENSER WATER OUTLET F 5/8 CONDENSER WATER INLET (M
2.25
12/1/94 Rev 3/4/96
13
LEGS (4)
BLANKET
Electrical Service
Line
Manual Disconnect
Switch
Shut-Off
Water Filter
Valve
Electrical Service
Line
Manual Disconnect
Switch
Shut-Off Valve
Water Filter
Bin Drain
Tube
AIR-COOLED MODELS
STRAIN RE-
LIEF
MUST BE
USED
Dump Valve
Drain Tube
Floor Drain
Bin Drain
Tube
WATER-COOLED MODELS
Shut-Off Valve
Condenser Water Inlet
Strain Relief
must be used
Dump Valve
Drain Tube
Condenser Water
Drain Tube
Floor Drain
Note: Leave all panels on the cuber until it is in place on the bin.
PLUMBING CONNECTIONS
1. All plumbing lines and connections must conform to local and national plumbing codes.
2. Line shut-off valves must be located in supply water lines for cuber and condenser if product is water­cooled. Water supply to water-cooled condenser must include a stand-pipe to prevent “water hammer.
3. Should your local water supply quality require the installation of a water filter system, consult your local dis­tributor or dealer for proper size required.
4. Water supply pressure must not be lower than 20 PSI (1.37 BAR), nor should it exceed 120 PSI (8.16 BAR).
NOTE: Water filters larger then 5 microns do not give proper protection. Water pressures above 80
PSI (5.44 BAR) will destroy the filter.
DRAIN LINES: Bin and cuber drain lines must never be connected together and must be vented. NOTE: All HP-62 (R404A) ice machines have a voltage range of –5%, +10% from the serial palte rating.
ELECTRICAL
1. All wiring and connections must conform to national and local electrical codes.
2. Wire size and circuit protection must conform to specifications and cuber must be on a separate electrical circuit.
3. Strain relief connectors must be used at the junctions box of the control box and the cuber.
4. Cuber must be grounded by the control box ground screw or other method for intentional safety grounding that meets code requirements.
5. A manual disconnect in a convenient location to the cuber must be installed.
INSTALLATION CHECK POINTS
1. Has bin and cuber been leveled and sanitized?
2. Does electrical and plumbing meet code requirements?
3. Check correct operating water level in the water pan.
14
12/1/94 Rev 3/4/96
operating water level Single Evaporator Units
3/8I
WATER PAN RIGHT SIDE VIEW
operating water level
Dual Evaporator Units
4. If water-cooled, are inlet and drain connections to condenser correct to prevent water hammer”?
5. Are drain lines separate and vented?
6. Is there 6I clearance on all sides and top for proper air circulation?
7. Does the water curtain move freely, and does the float valve shut off incoming water to the water pan?
START-UP AND CHECK OUT
1. Turn the Cuber’s power switch to the clean (pump only) position. The water pump only should be opera- tional. Wipe the top extrusion briskly with a ScotchBrite pad. Check for an even, steady flow of water over evaporator top extrusion and down over evaporator surface. Check that all ports of the water distribution tube are open for even water discharge. The water pan should refill and the float should stop the incoming water sup­ply.
Power Switch
NOTE: On the IACS222/IWCS227 to service the float valve:
1. Compress the John Guess fitting remove the 1/4 tubing.
2. Remove the screws that hold the float bracket to the liner wall.
3. Carefully remove float strainer and bracket as one assembly.
4. Reverse procedure to reinstall. Should service be required on the float valve or strainer, turn the water supply off, loosen the float, hold down nut and remove the float and strainer as an assembly for ease of service.
2. Place the Cubers power switch in the ON position. After a 2-second delay the compressor will start. The
condenser fan will operate when the condenser sensor signals the circuit board its temperature is 100_F (38_C). The water pump will operate when the evaporator cools to 25_F (–3.9_C). Depress the manual harvest switch (on the circuit board). The fan motor will stop and the water dump valve will open. In 3 se­conds the hot gas solenoid will open and 15 seconds after depressing the manual harvest switch, the water pump and dump valve will close terminating the dump cycle.
3. Hold the water curtain open for a maximum of 30 seconds; the Cuber should shut down. Release the water curtain(s). When the curtain(s) closes, there will be a 2-second delay, then the compressor will start and the start-up process should begin for the next ice-making mode.
4. If all Cuber operation is as stated, allow product to operate and produce one slab of ice, then discard the ice. Allow the Cuber to continue operation to fill the storage bin.
12/1/94 Rev 3/4/96
15
OWNER -OPERATOR
The installation is not complete until you are sure the owner-operator understands the cuber operation and his or her responsibility of preventative maintenance.
Does the owner-operator know:
1. Location of electrical disconnect switch and water shut-off valves?
2. How to start and/or shut down the product, clean and sanitize it?
3. Bin full operation and reset operation of high pressure cutout (water-cooled and remote products only)?
4. How to clean the condenser and fan blade?
5. Whom to call for product information and/or service?
CLEANING PROCEDURES
Approved ice machine cleaners by brand names:
S Lime–A–Way S Calgon Nickel Safe (green color only)
NOTE: All ice machine cleaners labeled safe for nickel ARE NOT the brand CALGON NICKEL SAFE.
CAUTION: Ice machine cleaners are acidic-based chemicals. Before beginning any cleaning of the cuber, the ice in the storage bin or dispenser must be removed.
WARNING: When using any chemical, rubber gloves and eye protection should be worn.
PREP – CLEANING
Use full-strength ice machine cleaner on a coarse-surface cloth material (such as terry cloth) and wipe down the inside wall of the evaporator area, the water pan, the water curtain and evaporator plastic extrusions. If the wa­ter distributor tube has heavy scale build-up, remove and soak it in full-strength ice machine cleaner (or ex­change the tube and clean the scaled tube at a later date).
Cleaning the Water System and Evaporator
1. Set the switch to Clean and allow any ice on the evaporator to release and melt away.
2. Remove all ice from the storage bin.
3. Remove the water curtain(s), pour 1/2 oz. of ice machine cleaner down the rear key-slot openings. The cleaner will drain into the water pan.
4. Return the water curtain(s) to their proper operating positions.
5. Add 3 oz. for a single evaporator, or 5 oz. for a dual evaporator of Calgon Nickel Safe or “Lime-A-Way ice machine cleaner directly into the water pan. The float will balance with inlet water. Set switch to CLEAN, circulate for a maximum of 15 minutes.
6. Depress and hold the dump switch to allow the cleaner to drain away.
7. Fill the water pan with clean fresh water, circulate for approximately 3 minutes. Depress and hold the DUMP switch and allow the water to drain away. Repeat the procedure 3 times.
8. After third rinse cycle, place product power switch in ice position. Allow Cuber to produce one slab of ice – DISCARD THE ICE.
9. When the clean cycle is complete, return cuber to normal operating mode.
NOTE: Please Take Note of the Following:
S Ice machines should only be cleaned when needed, not by a timed schedule of every 60 days, etc. S Should your ice machine require cleaning more than twice a year, consult your distributor or dealer about
proper water treatment.
16
12/1/94 Rev 3/4/96
Power Switch
SANITIZING PROCEDURES
NOTE: To be performed only after cleaning the ice machine:
1. Add 1/4 ounce (7.08 g) sodium hypochlorite solution (common liquid laundry bleach) to the water pan and allow the pump to circulate the solution for 5 minutes. You may also use a commercial sanitizer such as Calgon Ice Machine Sanitizer following the directions on the product label.
2. Turn the Cuber power switch off and depress and hold the dump switch to drain the water pan.
3. To sanitize the bin and other surface areas, use 1 ounce of liquid bleach per gallon of water and wipe all areas with the solution. Or use a commercial sanitizer.
4. Place the Cuber power switch in the ice position. Discard the first batch of ice produced.
5. Cleaning and sanitizing are now complete. Cuber may be returned to normal service.
DUMP CYCLE
OPERATING WATER LEVEL
SINGLE EVAPORATOR UNITS
3/8I
WATER PAN RIGHT SIDE VIEW
1. With the proper water level in the water pan, start the water pump to circulate the water. Check that the float will return water level to original setting and stop inlet water.
2. There is a flow washer in the inlet side of the float assembly that will control inlet water pressure from 20/120 PSI (3.4/8.16 Bars). This will prevent float flutter. In low water pressure conditions, 20 PSI (1.37 Bars) or less, the flow washer may have to be removed from the float assembly for proper volume.
OPERATING WATER LEVEL DUAL EVAPORATOR UNITS
FLOW CONTROL WASHER FLAT SIDE UP
3. Push the manual dump switch – allow dump action to drain the water pan. When you release the momen­tary switch, the pump will stop and the float will return the water level back to its original setting and shut off the water supply.
12/1/94 Rev 3/4/96
17
4. You have the option of selecting dump cycle intervals of:
)
S every cycle; (Standard setting from factory) S every 3rd cycle; S every 5th cycle; S every 7th cycle.
Remember, the higher the mineral content in the water supply the more often it will be required to dump the wa­ter and/or clean the product if proper water treatment is not used.
Water
YL
RH Evap.
LH Evap.
Condenser plug
Suction plug
RD
Error
Adjustable Ice Thickness Pot.
DĆ15
DĆ14
DĆ12
DĆ5
Dump Valve
GR
Fan
GR
Manual Harvest Switch
Contactor
Water Pump
Hot Gas
DĆ11
DĆ6
7
5
3
1
Transformer
8
6
4
2
Voltage Selector Switch
230v
neutral
115v
Sleeve Connector
Dump Every
Cycle
Options Plug
Dump Every
3rd
Cycle
Dump Every
5th
Cycle
Dump Every
7th
Cycle
RH Evap. Switch
Suction Line Sensor
N S
LH Evap. Switch
N S
Condenser Sensor
White
Brown
To Stacked
Unit
(if required
DĆ13
YL
DĆ10
Test Plug
Options Plug
Micro Processor
Stacking Cable Plug
18
12/1/94 Rev 3/4/96
ADJUSTING BRIDGE THICKNESS
TOP ROW 3/8I - 5/8I DIMPLE
CENTER 1/8I BRIDGE
BOTTOM 2 ROWS 3/16I - 1/4I BRIDGE
For optimum ice production and maximum cube separation, the ice connecting the individual cubes should be a minimum of 1/8I (.32cm) thick at the center area of the ice waffle.
BRIDGE 1/8I (0.32 cm)
It is normal for the ice slab to be slightly thicker at the bottom and taper off in a slight wedge pattern at the top. The top row of cubes must have a complete pattern of ice on all four sides and the back wall. Remem­ber, when you operate the product with the panels off during testing the additional heat at the top of the evaporator will cause thinner ice at the top than when the panels are in place.
Should a different thickness of the bridge be desired, it will be required to adjust the ice thickness “POT”, located on the circuit board, as fol­lows:
1. Thinner Bridge – turn the ice thickness “pot” adjustment screw CW one full turn. Allow two cycles before determining if
additional adjustments are required.
2. Thicker Bridge – turn the ice thickness “pot” adjusting screw CCW
one full turn. Allow two cycles before determining if additional ad­justments are required.
NOTE: Never judge the thickness of the ice from the first batch of the ice produced – the first cycle is a balance cycle. Always wait for the second cycle before making any adjustments.
TOTAL ICE CAPACITY
Ice capacity of any ice maker is affected by many operating conditions, such as water and air temperature and location factors. Please review the capacity tables in this manual for average 24-hour capacity under various conditions.
NOTE: All printed capacity ratings are 10% except 50 HZ units. These products have 12% increase in cycle time and capacity decrease of approximately 17%.
ICE PRODUCTION CHECK
If air cooled, take air temperature at the intake of the condenser, 2I from the condenser fins, and Incoming wa­ter temperature at the outlet of the “float” valve.*
Cycle time (CT) = freeze time plus harvest time, in minutes and seconds. 1440 divided by CT = number of cycles per 24 hours.
Measure weight of ice from one cycle in pounds and fractions of a pound.
EXAMPLE: Weight/cycle x cycles/day = total production/24 hrs. Compare to the production tables.
* If water cooled, be certain water regulator valve is set to maintain 300/310 PSI head pressure.
12/1/94 Rev 3/4/96
19
RH Evap. Switch
N S
LH Evap. Switch
N S
Condenser Sensor
Suction Line Sensor
White
Brown
DĆ13
YL
RH Evap.
YL
DĆ10
LH Evap.
Condenser
plug
Suction plug
Test Plug
Options
Plug
Micro Processor
DĆ15
DĆ14
DĆ12
RD
DĆ5
Error
Adjustable Ice Thickness Pot.
Water Dump Valve
Contactor
Water Pump
GR
DĆ11
Fan
GR
DĆ6
Hot Gas
7
5
3
1
Transformer
8
6
4
2
Voltage
Selector
Switch
230v
neutral
115v
Stacking
Cable
Plug
To Stacked Unit
(if required)
Manual
Harvest
Switch
LED INDICATORS
The LEDs are board circuit indicators. If the LED in the functional board circuit is complete, check component. Example: Contactor does not energize and LED is “ON”, board circuit is OK. Check contactor, coil, leads, &
connections. Yellow:
S Evaporator switch(s) (proximity)
Green:
S Water dump valve S Compressor contactor S Water Pump S Hot Gas Valve S Condenser Fan (cycles on & off with fan)
Red: Error in system operation. Product shut down.
20
12/1/94 Rev 3/4/96
STATUS INDICATOR
D6 Green LED Condenser Fan D10 Yellow LED Left Water Curtain D11 Green LED Hot Gas Valve D12 Green LED Water Pump D13 Yellow LED Right Water Curtain D14 Green LED Compressor Contactor D5 Red LED Error D15 Green LED Dump Valve
Curtain Open
D13 Yellow LED off Right evaporator curtain open.
D10 Yellow LED off Left evaporator curtain open.
Pre-Chill Mode
D6 Green LED (on or off) Condenser fan cycles on & off depending upon condenser temperature.
D14 Green LED (on) Compressor contactor active - Compressor running.
D13 Yellow LED (on) Right evaporator curtain closed.
D10 Yellow LED (on) Left evaporator curtain closed (only if unit has two evaporators).
Ice-Making Mode
D6 Green LED (on or off) Condenser fan cycles on and off depending upon condenser temperature.
D12 Green LED (on) Water pump active.
D14 Green LED (on) Compressor contactor active - compressor running.
D13 Yellow LED (on) Right evaporator curtain closed.
D10 Yellow LED (on) Left evaporator curtain closed (only if unit has two evaporators).
Harvest Mode
D11 Green LED (on) Three seconds after water dump valve becomes active, the hot gas valve becomes active.
D12 Green LED (on) 15 sec. Fifteen seconds after water dump valve becomes active, the water pump deactivates.
D14 Green LED (on) Compressor contactor active - compressor running.
D15 Green LED (on) 15 sec. Water dump valve becomes active at the start of harvest. Water dump valve is active for
D13 Yellow LED (on) Right evaporator curtain closed. When the ice falls and the curtain opens, the LED will turn off.
D10 Yellow LED (on) Same as D13 if there is a second (left) evaporator.
15 seconds.
Error LED
D5 Red LED (on) EVAPORATOR OPEN THERMISTOR CIRCUIT Ć thermistor open / broken wire / poor connection.
D5 Red LED (on) EVAPORATOR HIGH TEMP. ERROR: Six minutes into the Freeze cycle the suction line temperaĆ
D5 Red LED (on) TWO REPEATED FAILED HARVEST CYCLES Ć No ice drop.
D5 Red LED Flashing, 1/sec CONDENSER OPEN THERMISTOR CIRCUIT (Air Cooled only) Ć Thermistor open / broken wire /
D5 Red LED Flashing, 1/sec CONDENSER LOW TEMPERATURE CONDITION. Ć Condenser midpoint reaches 36°F Ć Ice
D5 Red LED Flashing, 1/sec CONDENSER HIGH TEMPERATURE SAFETY SHUT DOWN.
Ice maker is SHUT DOWN. Consult service manual (Diagnostic Section) for troubleshooting guide.
ture failed to reach 40°F or below. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic Section) for troubleshooting guide.
poor connection. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic Section) for troubleshooting guide.
Maker is SHUT DOWN.
12/1/94 Rev 3/4/96
21
CIRCUIT BOARD DIAGNOSTIC PROCEDURE
Turn the power switch to the “ON” position. The D-5 red LED (error indicator) will be illuminated for 2 seconds. After the D-5 red LED goes out, short across the bottom two terminals of the Test Plug with a jumper wire or a pocket screwdriver and then remove the jumper. The circuit board is now in the test mode.
One of these two conditions will exist:
S If the Ice Thickness Potentiometer is within the factory setting the D-5, red LED will flash continiously. S If the Ice Thickness Potentiomater is not
In either case the Green LED indicators will illuminate for 2 seconds each in the sequence shown below. They will continue to sequence until you turn the power off and stop the procedure.
D-11 Green Hot Gas D-12 Green Water Pump D-14 Green Contactor D-6 Green Fan D-15 Green Dump Valve
Failure of the green LEDs to cycle in this sequence indicates a defect in the circuit board.
LED Indicators
Test Plug
within the factory setting, the D-5 red LED will not be illuminated.
Water
RH Evap. Switch
N S
LH Evap. Switch
N S
Condenser Sensor
Suction Line Sensor
White
Brown
DĆ13
YL
YL
DĆ10
Test Plug
Options Plug
DĆ14
RH Evap.
LH Evap.
Condenser plug
Suction plug
RD
Error
Adjustable Ice Thickness Pot.
DĆ15
DĆ12
DĆ5
Dump Valve
Contactor
Water Pump
GR
DĆ11
Fan
GR
DĆ6
Hot Gas
Transformer
7
5
3
1
8
6 4
2
Voltage Selector Switch
To Stacked Unit (if required)
22
Micro Processor
Stacking Cable Plug
Manual Harvest Switch
12/1/94 Rev 3/4/96
RESTORING ICE THICKNESS POTENTIOMETER TO FACTORY SETTING
1. Turn cuber power switch to the OFF (center) position.
2. Unplug the proximity switch(es) and the thermistor(s) from the circuit board.
3. Turn the cuber power switch to the ON position. The red LED D-5 will illuminate for 2 seconds and then go out.
4. Short across the bottom 2 pins of the Test Plug using a wire jumper or a pocket screwdriver. Immediately remove the jumper.
One of these two conditions will exist:
S If the Ice Thickness Potentiometer is within the factory setting the D-5, red LED will flash continiously. S If the Ice Thickness Potentiomater is not within the factory setting, the D-5 red LED will not be illuminated.
In either case the Green LED indicators will illuminate for 2 seconds each in the sequence shown below. They will continue to sequence until you turn the power off and stop the procedure.
D-11 Green Hot Gas D-12 Green Water Pump D-14 Green Contactor D-6 Green Fan D-15 Green Dump Valve
Making Adjustments
When making adjustments, turn the Ice Thickness Potentiometer screw slowly to allow the circuit board time to react. Always turn the screw one full 360_ turn, rest several seconds, then adjust another 360_ turn.
Turn the Ice Thickness Potentiometer screw 10 (ten) turns clockwise or until the red LED D-5 starts to flash – should the LED not start to flash after 10 (ten) turns clockwise – reverse the direction and turn the screw slowly counterclockwise until the red LED D-5 starts to flash.
When the LED starts to flash, stop turning. You have reached the original factory setting.
Important: Erratic component operation (water pump, condenser fan, hot gas valves, etc.) are usually a result of a poor connection at the 8-pin connector. Before doing any diagnostic test on the control board, be sure to check the 8-pin connector to ensure that all wires are properly installed and the connector is securely in place.
12/1/94 Rev 3/4/96
23
COMPONENT FUNCTION (CIRCUIT BOARD ETC.)
TEST PLUG
Board manufactures check point. DO NOT ATTEMPT ANY VOLTAGE CHECKS AT THESE PINS.
SENSORS
Condenser sensor (WHITE) and suction line sensor (BROWN) are thermistors rated 1k ohm at room tempera­ture.
S Condenser sensor signals the circuit board for fan cycling and also serves as the high temperature safety
shut down. The red Error LED will flash on and off every second, during high temperature safety shut down. Product is functionally shut down. Reset procedure must be performed to restart product operation.
S Suction line sensor signals the circuit board the suction line temperature, to control ice bridge thickness.
Also the sensor serves as suction line high temperature signal (Cuber has 6 minutes to reduce suction line temperature to 40°F (4.4°C) in the freeze mode). The red Error LED will be steady on. Should this time frame not be met, product is functionally inoperative during this safety shut down. Reset procedure must be performed to restart product operation.
RESET OPERATION
When Cuber is functionally shut down and red “Error LED” is operational, the Cuber power switch must be turned off for 5 seconds and returned to the ON position to reset the circuit board and allow the Cuber to restart operation.
Evaporator Switches
Proximity Switches are half mounted to the water curtain, and the other half mounted to the evaporator side rail.
Switch Notes
1. Manually holding the curtain open during freeze mode will shut the Cuber down in 5 seconds.
2. During harvest cycle, if curtain is open for 10 seconds, the water pump will stop. The compressor will oper­ate for 20 additional seconds before Cuber shut down takes place. When the water curtain is closed, the Cuber will begin the normal start-up process.
3. In single evaporator machines, the proximity switch connection must be on the top (RH) connection on the circuit board.
4. In dual evaporator machines, both RH and LH switches must open and reset to start the next freeze mode.
Harvest Safety Termination
After 4 minutes in the harvest mode, the safety timer in the circuit board will terminate the harvest mode and place the Cuber back into a freeze mode. This safety cycle will protect the evaporator, etc. should the product fail to terminate the harvest mode for any reason.
VOLTAGE CHECKS
Evaporator Proximity Switch
Turn Cuber power switch OFF. Disconnect proximity switch plug(s) from the circuit board. Use a digital multime­ter set for D.C. Voltage; turn power switch ON, connect leads of meter across the top two terminal pins on the board, (for the switch being tested), meter should read 5VDC ± 0.2 output voltage. If not, replace the circuit board.
NOTE: The proximity switch on the IACS 227 or the IWCS 227 is mounted inside the right hand evaporator side rail. To test the switch, make the voltage test at the circuit board. To replace the switch, remove the upper right hand side service panel. Carefully remove the Mylar shield to gain access to the two nylon screws that hold the proximity switch. Remove the screws and the switch through the service opening. After installing the new switch, replace the Mylar shield and seal with a bead of silicone sealant.
24
12/1/94 Rev 3/4/96
VOLTAGE SELECTOR SWITCH
1. Selector bar in center position, switch is open. Product is inoperative.
2. Selector bar in down position, selection is for 115 VAC.
3. Selector bar in up position, selection is for 230 VAC.
STACKING CABLE
When stacking the “I” series cuber the connecting cable (connecting the two (2) circuit boards) will allow: the bottom Unit to shut off on the full bin signal (or any error code), the top Unit will then finish the cycle it is in and shut down. The “I” series should never be stacked more than two high.
Sensor [Thermistor] Diagnosis
Sensors
Condenser or suction line – Turn Cuber power switch OFF. Disconnect sensor plug from board. Use digital multimeter set for D.C. Voltage. Turn power switch ON. Connect leads of meter across the two pins of the sen­sor being checked. Meter should read 2.5 VDC0.2 output voltage from the board. If voltage is not correct, re­place the circuit board.
Should the cuber operation indicate there may be a fault in the sensor [thermistor] or the control board cir­cuit proceed as follows.
1. Using a good multimeter, check the control board sensor output voltage.
2. If voltage checks are correct do the following: A. Disconnect the suction line sensor (brown lead) from the control board. B. Install the special test cord* to the control board and reinstall the sensor to the test cord terminals. C. Connect the multimeter (set on VDC - milli-volts) to the test cord leads. D. Operate the cuber in the freeze cycle.
3. As the suction line temperature decreases the milli-volt reading will increase.
4. Sensor Shorted – milli-volt reading will cease to increase and will remain steady indicating a shorted sen­sor.
5. Sensor Open – The voltage reading will indicate the control board output voltage of 2.5 VDC.
6. Should step 4 or 5 occur during this test, the sensor will require replacement. * Special test cord, part # 164984009, may be ordered through the Service Department.
7. Condenser Sensor (white leads) – self-contained air-cooled only – water cooled and remote systems
use a resistor plug on the control board.
Complete the sensor and multimeter connections as described in 2- B, C, D
8. Shorted sensor – a steady low milli-volt reading will be recorded. The reading will not change.
9. Open sensor – the multimeter will record control board output voltage of 2.5 VDC.
10. Should sensor (thermistor) pass the voltage test proceed to the control board diagnosis for LED sequence (see page 22).
NOTE: The sensor controls the condenser fan cycling from 88/100 degree Fahrenheit. Thus any de­fects in the condenser circuit will effect the fan cycling rate.
CONDENSER FAN CYCLING CONTROL
The condenser fan on air-cooled cubers is cycled by the circuit board. The condenser sensor signals the circuit board when the condenser temperature reaches 100°F (38°C) the fan starts and continues to run until the tem­perature is reduced to 88°F (31°C).
NOTE: There is no pressure control used to cycle the fan motor on intergal condensor unit.
THERMOSTATIC EXPANSION VALVES
The following suggestions for diagnosis of automatic Thermostatic Expansion Valve (TXV) are given with the understanding that the following have been checked and are correct and/or have been corrected prior to pro­ceeding.
1. The condenser and fan blade are clean and have proper operating conditions.
12/1/94 Rev 3/4/96
25
2. Water supply to the product is correct and flow over the evaporator is correct.
3. Cuber refrigerant charge is correct.
4. TXV sensing bulb is properly located and secured to the suction line and correctly insulated.
5. Hot gas valve(s) are not leaking and/or seeping through.
Starving TXV - Product Symptoms
1. Suction pressure lower than normal for the operating conditions.
2. Ice production lower than normal and/or none.
3. Ice pattern on evaporator (if any) thin at top and thick at bottom.
Flooding TXV - Product Symptoms
1. Ice production lower than normal and/or none.
2. Suction pressure stabilizes at higher than normal pressure for operating conditions. Suction pressure does not modulate and may start to slowly rise.
3. Ice pattern will be very heavy at the bottom and thin at the top of the evaporator. Product may not enter harvest cycle because of higher than normal suction line temperature.
IMPORTANT: Frost on the suction line may be normal on medium temperature refrigeration equipment. Frost should be considered a red flag, long run times will normally produce some type of frost pattern. Before checking the sealed refrigeration system, the external conditions that could lead to frost follow:
1. Dirty condenser
2. Dirty condenser fan blade
3. Improper air clearance around Cuber
4. Loose TXV bulb mount
5. Poor water flow over evaporator
6. Ventilation problems
The expansion valves used on Cornelius “I” series ice equipment have special super heat settings and bulb charge designed for the product load and HP 62 refrigerant. Should the need arise to replace this or any refrig­erant components, be certain to use only components recommended by Cornelius for the model of the Cuber being serviced. Use of nonapproved components will compound system difficulties and may void product war­ranty.
WATER REGULATING VALVE
The water regulating valve is used on water-cooled cubers only. The valve is installed in the condenser outlet water line. Its function is to control the proper operating head pressure by regulating the amount of water flow­ing through the condenser. The valve is adjustable and factory set to maintain condenser discharge water tem­perature @ 108/112_F (42-44_C). Setting the water regulating valve to maintain discharge water temperature eliminates the need to enter the sealed refrigeration system. When checking the valve, the water temperature should be taken as close to the condenser discharged as possible. The water temperature will equate to operat­ing head pressure of approximately 310 PSI (21.1 BAR).
Should adjustment be required, the valve has an adjustment stem on the top of the valve. After allowing the cuber to operate for 10 minutes in the ice– making mode to balance the system, turning the adjusting stem CW
will increase the discharge water temperature, and CCW will decrease the discharge water temperature.
The water regulating valve must close off condenser water flow completely during the hot gas harvest cycle. There should be no discharge water flowing out of the condenser during the harvest cycle. Should the valve fail to close during the harvest mode, the condenser will continue to condense the compressor discharge vapor needed for the harvest cycle and this will result in long harvest times.
Also discharge water temperature below 108_F /112_F will result in long harvest times.
Leaking (bypassing) water regulating valves are normally the result of scale build-up on the valve diaphragm and the valve should be flushed, not replaced. To flush the valve, open the adjusting stem wide open CCW (or force the valve spring up with a screwdriver), open and close the water supply to the condenser resulting in the flushing action. Should this not correct the problem, replace the valve diaphragm. This can be done without en­tering the sealed refrigeration system.
Damage to the water regulating valve may also be caused by water hammer. Water hammer will result from the condenser inlet and outlet water lines being reversed or defective valve stops in the water supply line. Proper installation of water–cooled equipment should always include an anti-water hammer standpipe in the supply inlet line as close to the cuber as possible.
26
12/1/94 Rev 3/4/96
SERVICE STEM VALVES
When closing the service stem valves to remove your gauge and manifold set always close the high side stem valve first. Following this procedure will allow the system to “PULL” the refrigerant vapor from your manifold set to reduce refrigerant loss. When the pressure has been reduced, close the low side stem valve.
MOISTURE CONTAMINATION
With the major changes in refrigerants in todays marketplace and the use of hydroscopic oils the control of moisture and contaminates have become more critical to safeguard against than ever before in the history of mechanical refrigeration.
Contaminates are also the most difficult of all problems to determine. A Meg-Ohm meter “Megger” can be a valuable tool to aid in the analysis of this problem. A Meg-Ohm reading log may be started any time after 90 days of operation of the product. To perform the test, proceed as listed.
Disconnect all three (3) compressor leads, take a Meg-Ohm meter reading from each compressor terminal to a good chassis ground. Compare reading to chart below:
Meter Reading
MegĆOhm
100 Ć
50 to 100 Moisture present Replace drier.
20 to 50 Severe moisture & possible contaminated oil
.5 to 20 System has severe contamination Remove compressor oil and refrigerant charge.
Okay None needed.
with acid present
Compressor Condition Maintenance Required
Replace drier with acid hold type. Run 24 hours, change to regular drier.
Evacuate, install liquid and suction line driers (acid hold type). Recharge with new oil and reĆ frigerant. Run 24 hours. Discharge system, disĆ card suction line drier, replace the liquid line drier. Evacuate and recharge.
Readings in the range listed below 100 Meg-Ohm would be an indicator that the system being tested may have a contamination problem. Where does the problem come from? As an example, the filter drier may become sat­urated and hold large percentages of moisture and the system function without a problem until such time as the product operating conditions change. Should the room temperature increase, or the condenser plug-up etc., the higher operating pressures and temperatures may cause the drier filter to release a portion of its held moisture. It is also imperative to avoid opening the sealed refrigeration system whenever possible and when it is done to be certain the true problem is correctly diagnosed and repaired. Remember, service gauge sets should only be installed after all external checks have been performed.
CAUTION: Megger checks should NEVER be performed on any compressor that is under a vacuum.
COMPRESSOR CONTACTOR
The contactor serves as the voltage supply switch for the compressor circuit. Voltage to the coil of the contactor is supplied by the circuit board.
Check Out: The two (2)* line supply screws of the contactor should always have supply voltage present when voltage is on
to the product. The other two (2)* screws (load) should have line voltage when the contactor is energized. The contactor coil
receives its supply voltage from the circuit board. Should the contactor fail to energize:
12/1/94 Rev 3/4/96
27
Check for supply voltage from circuit board, lead connections to contactor coil, and ohms value of coil. * (3) if the product is 3 phase
Note: See compressor run-on condition check procedure on page 31.
COMPRESSOR & STARTING COMPONENT CHECK-OUT PROCEDURE
When compressors fail to start or run properly, it is normally the external electrical supply or the compressor start components that are defective – the overload protector, start and/or run capacitor, relay, circuit board, safety controls, etc.
1. Check voltage at compressor terminals. NO voltage will require checking the electrical circuit working back from the compressor to determine where the voltage supply is interrupted and correct as required. The load voltage, while compressor is trying to start, should not be less than 90% of rated required voltage.
Line voltage and wire size effect the life expectancy of the electrical components, compressor, motor winding, solenoid coils, etc.
Poor line quality voltage will cause many erratic electrical problems. Remember every electrical product, ice ma­chine, dispenser, walk-in, reach-in, air conditioner, etc. required proper power supply to operate. Be certain when voltage checks are performed that you are measuring load voltage, not line voltage.
2. A defective capacitor or start relay may prevent the compressor from starting. Should the compressor at­tempt to start, but is unable to do so, or if the compressor hums or trips off on the over protector, check the following:
NOTE: For 50 HZ application on dual rated 50/60 HZ models, load voltage while compressor is start­ing must not be less than 90% of 50 HZ rating.
Relay
Potential –
For the potential type, contacts are normally closed. The start contacts open by C.E.M.F. generated by the com­pressor at approximately 80% of the normal operating speed. As the contacts open, only the start capacitor is removed from the start circuit. Both the start and run winding and the run capacitor remain in the circuit. This
relay may or may not be directional in mounting.
Current –
For the current type, contacts are normally open. The start contacts close by the high current draw from the locked rotor condition with only the run winding in the circuit. As the contacts close, the start capacitor and the start winding is energized and the compressor starts. At approximately 80% of its operating speed the current draw drops off, the relay contacts open removing the start winding and start capacitor from the circuit. (Remem-
ber, current relays are directional in their mounting to allow contacts to lift and close).
Capacitors
A quick check is to replace suspected defective capacitors with known good capacitors being careful to stay within the range for substitute values. Should those values be unknown, a basic rule for capacity is: for start ca­pacitors 10% and run capacitors 5% of the rating on the defective original capacitor being replaced. Voltage should always try and be matched; if it cannot be, it is acceptable to increase up to 10% higher than the voltage listed on the capacitor being replaced. NEVER put a capacitor on a product with a voltage rating lower than the original being replaced. If a capacitor analyzer is not available, an ohm meter may be used to check a capacitor for short or open circuits. Set the ohm meter to its highest scale and connect its leads to the capacitor terminals.
1. With a capacitor, without plate defect, the indicator should first move to zero (0) and then gradually in­crease to infinity.
2. If there is no movement of the ohm meter indicator, an open circuit is indicated.
3. If the ohm meter indicator moves to zero (0) and remains there, or on a low resistance reading, a short cir­cuit is indicated.
4. Please note this check does not determine if the capacitor will deliver the proper rated MFD/UFD required, it only shows if the capacitor has shorted or open circuits.
5. Capacitors that show any signs of leakage of electrolyte, or damage of the can, should be replaced. DO NOT TEST!
Compressor
1. Using an ohm meter, check for continuity from compressor terminal C to R and C to S. If the compressor is hot, wait one (1) hour for compressor to cool and recheck. An open internal overload protector can cause a lack of continuity. If continuity cannot be measured through all windings, the compressor must be replaced.
28
12/1/94 Rev 3/4/96
2. To check the compressor motor for accidental ground, perform a continuity check between terminals C, R and S to the compressor shell or a copper line of the refrigeration system (do not use a painted surface). Continuity present, the compressor windings are grounded and the compressor must be replaced.
If the compressor starts, but trips repeatedly on the overload protector, remember that the overload is both tem­perature and current activated. Be sure to check:
S Low voltage S Undersized supply lines S High head pressure S High suction pressure S Defective capacitors S Compressor mechanical problems S Low refrigerant charge
LEAK DETECTION
The new non-chlorine based refrigerants such as [HP - 62/R 404A] require special leak detection devices other than what has been standard for the CFC’s.
While the instruments for leak detection are different, the processes have not changed. Basics to remember:
1. Look for signs of oil when you visually start your leak check process. Oil is carried with the refrigerant. If the oil has leaked out so will the refrigerant.
2. Refrigerant vapor is heavier than air. When leak checking suspect areas, probe below the joints or connec­tions.
A. Always check the high-side of the system with the compressor operational. B. Check the low-side of the system, with the system idle. C. Following a & b will normally allow the highest pressure on each portion of the system for the best
detection.
3. Systems short of refrigerant will show improper operational results in both the freeze and harvest cycles. Many systems will appear normal in higher operating temperatures and change drastically in cooler con­denser temperatures.
4. Many new and reworked leak detection instruments have the ability to detect CFCs, HCFCs and the new HFCs by making a simple switch selection. This type of detector will be more sensitive on one setting than the other. This results in finding some leaks that are so small it may take years before the actual leak rate would create adverse operating conditions in the product.
A bubble test and/or additives with UV lamp may be the best team for the most positive leak testing results.
5. Never pressurize a system with oxygen or a mixture of refrigerant and air. Either of these methods may
cause a system explosion to occur.
6. Pressurizing systems to leak test should only be done with dry nitrogen. Be sure the regulator setting does not exceed the recommended system pressure.
CAUTION: A full cylinder of nitrogen will have pressure of approximately 2700 PSI.
7. Failure to correct leaks will also cause shorter compressor life as a result of the higher operating tempera­tures. Always leak check the total system as one located leak may not be the only leak.
SYSTEM EVACUATION & RECHARGING
Should service work ever be required on a product where the sealed refrigeration is opened for any reason, the refrigerant must be recovered, drier/filter replaced, evacuated and recharged. The old method of “purging” is NOT ACCEPTABLE. Always evacuate the system through both the high and low side service valves. Be certain both valves are completely open when evacuating and the drier/filter has been replaced.
SELF-CONTAINED PRODUCTS
With the new POE [Polyol Ester] oils, the refrigeration system is more prone to moisture problems than the CFC systems. Every effort should be made to never have the system open to the atmosphere for longer than 15 min­utes, and the replacement of the drier/filter is no longer an option, [IT IS MANDATORY].
12/1/94 Rev 3/4/96
29
A good vacuum is not always easy to measure, however the goal is to have less then 1% non-condensible va­pors in the system at the completion of the evacuation. Basic guidelines with a good pump would be to evacu­ate a selfcontained product 30 to 45 minutes and a remote product no less than 60 minutes.
The system should be evacuated to approximately 200/250 microns. Then perform a 5 minute holding test. You may expect a low grade loss of the vacuum as normal. However, a rapid rise to normal atmospheric pressure would signal a system leak is present and must be located and repaired before recharging the product. A slower pressure rise to approximately 1500 microns would signal moisture still present in the refrigeration system.
On a “WET” system, it would be beneficial to use heat lamps to raise the temperature of the compressor dome and evaporator surface area during the evacuation.
To assure a properly recharged product, the refrigerant charge must be weighed into the product using an elec­tronic charging scale or dial-a-charge. On air- and water-cooled products the charge should be introduced into the high side service valve. On remote systems, the charge should be introduced into the product receiver.
MANIFOLD SET
MANIFOLD SET
OPEN
OPEN
OPEN
CLOSED
OPEN
CHARGING
CYLINDER
OPEN
VACUUM
PUMP
CLOSED
HIGH SIDE
SERVICE
VA LV E
LOW SIDE
SERVICE
VA LV E
CLOSED
ELECTRONIC
SCALE
CLOSED
HIGH SIDE
SERVICE
VA LV E
LOW SIDE
SERVICE
VA LV E
OPEN
CHARGING
CYLINDER
CLOSED
VACUUM
PUMP
OPEN
ELECTRONIC
SCALE
IMPORTANT: Service personnel are held responsible for ALL ASPECTS OF THE CLEAN AIR ACT OF JULY, 1992.
REFRIGERANT DEFINITIONS
(ASHRAE 3-1990)
RECOVERY To remove refrigerant in any condition from a system and store it in an external container without necessarily testing or processing it in any way.
RECYCLING To clean refrigerant for reuse by oil separation and single or multiple passes through devices, such as replace­able core filter-driers, which reduce moisture, acidity, and particulate matter. This term usually applies to proce­dures implemented at the field job site or at a local service shop.
RECLAIM To reprocess refrigerant to new product specifications by means which may include distillation. Will require chemical analysis of the refrigerant to determine that appropriate product specifications are met. This term usu­ally implies the use of processes or procedures available only at a reprocessing or manufacturing facility.
NOTES REGARDING RECLAIM: New product specifications currently means ARI standard 700-88. Note that chemical analysis is required to assure that this standard is met.
30
12/1/94 Rev 3/4/96
Chemical analysis is the key requirement to the definition of “Reclaim”. Regardless of the purity levels reached by a re-processing method, the refrigerant is not “reclaimed” unless it has been chemically analyzed and meets ARI Standard.
HIGH PRESSURE SAFETY SWITCH
All water-cooled and remote products contain a high pressure safety cut-out switch. The function of this switch is to shut down the cuber should excessive pressure develop in the high side of the refrigeration system. This switch will open the power supply at 450 PSI (30.61 BAR) high side pressure. Should this control open, it must be reset manually and the cause for the increase in pressure determined.
COMPRESSOR RUN-ON
Contactor remains energized when curtains are in a full bin condition – compressor runs but water pump and condenser fan (AC) are off.
1. Check VAC at contactor coil with an analog voltmeter (dial type, not digital). A. Voltage at the contactor coil 12 VAC or higher may hold the coil energized. Turn the power switch
OFF, if contactor de-energizes, replace the circuit board, the snubber circuit is leaking. B. Should you find 1/2 normal line voltage, replace the circuit board, the triac is shorted. C. If no voltage or very low voltage (6 VAC or less) is present and plunger is still closed, replace the con-
tactor.
12/1/94 Rev 3/4/96
31
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IACS227/IAC322/IAC330
IP Units
FREEZE CYCLE HARVEST CYCLE
AVERAGE
AMBIENT
TEMP
_F
70 50 200 39 9:5 150 105 1:1 2.4 325
80 70 228 42 12:4 160 110 0:9 2.4 260
90 70 267 44 14:3 183 133 0:7 2.5 240
90 80 270 45 15.1 181 130 0.7 2.4 220
100 70 299 47 19:8 199 142 0:6 2.8 200
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
AVERAGE
ICE
WEIGHT
lb/Day
32
12/1/94
Rev 3/4/96
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1379 269 9:5 1034 724 1:1 1.1 147
27 21 1572 290 12:4 1103 758 0:9 1.1 118
32 21 1841 303 14:3 1262 917 0:7 1.1 109
32 27 1862 310 15.1 1248 896 0.7 1.1 100
38 21 2062 324 19:8 1372 979 0:6 1.3 91
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
kg/Day
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IWCS227/IWC322/IWC330
IP Units
FREEZE CYCLE HARVEST CYCLE
33
AMBIENT
TEMP
_F
70 50 300 40 12:1 143 103 0:9 2.8 310
80 70 300 42 15:3 160 116 1:1 2.8 245
90 70 300 43 16:2 160 118 1:2 2.9 240
90 80 303 44 16.4 173 120 1.1 2.8 230
100 70 300 44 16:3 160 117 1:3 2.6 215
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2068 276 12:1 986 710 0:9 1.3 141
27 21 2068 290 15:3 1103 800 1:1 1.3 111
32 21 2068 296 16:2 1103 814 1:2 1.3 109
32 27 2089 303 16.4 1193 827 1.1 1.3 104
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2068 303 16:3 1103 807 1:3 1.2 98
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IAC522/IAC530
IP Units
FREEZE CYCLE HARVEST CYCLE
34
AMBIENT
TEMP
_F
70 50 220 38 12:5 155 95 1.0 5.1 540
80 70 250 42 14:6 175 111 0:9 4.8 450
90 70 275 41 17:4 195 120 0:7 5.1 405
90 80 290 45 17.9 200 120 0.6 5.0 387
100 70 320 46 20:9 220 120 0:6 5.2 350
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1517 262 12.5 1069 655 1:0 2.3 245
27 21 1724 290 14.6 1207 765 0.9 2.2 204
32 21 1896 283 17.4 1344 827 0.7 2.3 184
32 27 1999 310 17.9 1379 827 0.6 2.3 176
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2206 317 20.9 1517 827 0.6 2.4 159
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IWC522/IWC530
IP Units
FREEZE CYCLE HARVEST CYCLE
35
AMBIENT
TEMP
_F
70 50 323 44 11:3 156 106 1:3 4.3 490
80 70 327 45 13:7 168 115 1.2 4.4 425
90 70 326 45 13:8 173 117 1:1 4.3 420
90 80 328 47 15.2 184 127 1:1 4.3 384
100 70 327 45 13:9 175 119 1:1 4.3 415
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2227 303 11:3 1076 731 1:3 1.9 222
27 21 2255 310 13:7 1158 793 1:2 2.0 193
32 21 2248 310 13:8 1193 807 1:1 2.0 191
32 27 2261 324 15:2 1269 876 1:1 2.0 174
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2255 310 13:9 1207 820 1:1 2.0 188
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IAC630
IP Units
FREEZE CYCLE HARVEST CYCLE
36
AMBIENT
TEMP
_F
70 50 225 34 8:4 148 88 1:5 5.4 755
80 70 261 37 11:3 166 101 1.2 5.6 640
90 70 296 40 12:6 183 113 1:1 5.6 590
90 80 297 40 13:2 184 113 1:0 5.5 560
100 70 333 43 17:1 200 125 1:1 6.0 475
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1551 234 8:4 1020 607 1:5 2.4 342
27 21 1800 255 11:3 1145 696 1:2 2.5 290
32 21 2041 276 12:6 1262 779 1:1 2.6 268
32 27 2048 276 13:2 1269 779 1:0 2.5 254
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2296 296 17:1 1379 862 1:1 2.7 215
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IWC630
IP Units
FREEZE CYCLE HARVEST CYCLE
37
AMBIENT
TEMP
_F
70 50 299 35 10:1 143 86 1:6 5.8 715
80 70 299 38 12:4 152 92 1.4 6.0 622
90 70 300 38 12:3 153 93 1:4 5.9 620
90 80 304 39 14:0 166 100 1:2 6.0 570
100 70 300 38 12:2 152 93 1:4 5.8 615
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2062 241 10:1 986 593 1:6 2.6 324
27 21 2062 262 12:4 1048 634 1:4 2.7 282
32 21 2068 262 12:3 1055 641 1:4 2.7 281
32 27 2096 269 14:0 1145 689 1:2 2.7 259
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2068 262 12:2 1048 641 1:4 2.6 279
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IRC630
IP Units
FREEZE CYCLE HARVEST CYCLE
38
AMBIENT
TEMP
_F
70 50 225 34 8:4 148 88 1:5 5.2 755
80 70 261 37 11:3 166 101 1.2 5.6 640
90 70 296 40 12:6 183 113 1:1 5.6 590
90 80 297 40 13:2 184 113 1:0 5.5 560
100 70 333 43 17:1 200 125 1:1 6.0 475
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1551 234 8:4 1020 607 1:5 2.4 342
27 21 1800 255 11:3 1145 696 1:2 2.5 290
32 21 2041 276 12:6 1262 779 1:1 2.6 268
32 27 2048 276 13:2 1269 779 1:0 2.5 254
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2296 296 17:1 1379 862 1:1 2.7 215
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IAC830
IP Units
FREEZE CYCLE HARVEST CYCLE
39
AMBIENT
TEMP
_F
70 50 253 29 7:6 163 83 1:5 5.3 840
80 70 293 33 9:0 187 97 1.0 5.2 745
90 70 335 36 11:5 210 111 0:9 5.8 680
90 80 339 37 12:0 209 111 0:9 5.8 645
100 70 379 40 13:8 232 126 0:8 6.0 595
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1744 200 7:6 1124 572 1:5 2.4 381
27 21 2020 228 9:0 1289 669 1:0 2.3 338
32 21 2310 248 11:5 1448 765 0:9 2.7 308
32 27 2337 255 12:0 1441 765 0:9 2.6 293
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2613 276 13:8 1600 869 0:8 2.7 270
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IWC830
IP Units
FREEZE CYCLE HARVEST CYCLE
40
AMBIENT
TEMP
_F
70 50 298 32 8:6 154 81 1:5 5.6 795
80 70 296 34 10:2 163 86 1.3 5.7 715
90 70 295 34 10:7 164 87 1:3 5.9 710
90 80 298 37 12:1 166 88 1:2 6.0 650
100 70 295 34 11:1 175 93 1:3 5.9 690
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2055 221 8:6 1062 558 1:5 2.5 361
27 21 2041 234 10:2 1124 593 1:3 2.6 324
32 21 2034 234 10:7 1131 600 1:3 2.7 322
32 27 2055 255 12:1 1145 607 1:2 2.6 295
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2034 234 11:1 1207 641 1:3 2.7 313
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IRC830
IP Units
FREEZE CYCLE HARVEST CYCLE
41
AMBIENT
TEMP
_F
70 50 253 29 7:6 163 83 1:5 5.3 840
80 70 293 33 9:0 187 97 1.0 5.2 745
90 70 335 36 11:5 210 111 0:9 5.8 680
90 80 339 37 12:0 209 111 0:9 5.8 645
100 70 379 40 13:8 232 126 0:8 6.0 595
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1744 200 7:6 1124 572 1:5 2.4 381
27 21 2020 228 9:0 1289 669 1:0 2.3 338
32 21 2310 248 11:5 1448 765 0:9 2.7 308
32 27 2337 255 12:0 1441 765 0:9 2.6 293
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2613 276 13:8 1600 869 0:8 2.7 270
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IAC1030
IP Units
FREEZE CYCLE HARVEST CYCLE
42
AMBIENT
TEMP
_F
70 50 240 33 13:5 164 75 1:7 11.6 1101
80 70 276 36 14:2 177 83 1.4 10.5 969
90 70 312 38 15:9 196 91 1:1 10.5 890
90 80 313 38 16:8 198 91 1:1 10.5 840
100 70 349 41 18:7 215 100 1:0 10.8 793
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1655 228 13:5 1131 517 1:7 5.3 499
27 21 1903 248 14:2 1220 572 1:4 4.8 440
32 21 2151 262 15:9 1351 627 1:1 4.8 404
32 27 2158 262 16:8 1365 627 1:1 4.7 381
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2406 283 18:7 1482 689 1:0 4.9 360
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IWC1030
IP Units
FREEZE CYCLE HARVEST CYCLE
43
AMBIENT
TEMP
_F
70 50 296 34 13:0 155 73 1:8 10.7 1046
80 70 297 35 15:3 161 75 1.7 10.9 925
90 70 297 36 15:7 161 77 1:5 11.0 920
90 80 300 36 17:9 175 81 1:4 11.0 823
100 70 297 36 15:8 164 77 1:5 11.0 915
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2041 234 13:0 1069 503 1:8 4.9 474
27 21 2048 241 15:3 1110 517 1:7 4.9 420
32 21 2048 248 15:7 1110 531 1:5 5.0 417
32 27 2068 248 17:9 1207 558 1:4 5.0 373
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2048 248 15:8 1131 531 1:5 5.0 415
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IRC1030
IP Units
FREEZE CYCLE HARVEST CYCLE
44
AMBIENT
TEMP
_F
70 50 240 33 13:5 164 75 1:7 11.6 1101
80 70 276 36 14:2 177 83 1.4 10.5 969
90 70 312 38 15:9 196 91 1:1 10.5 890
90 80 313 38 16:8 198 91 1:1 10.5 840
100 70 349 41 18:7 215 100 1:0 10.8 793
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1655 228 13:5 1131 517 1:7 5.3 499
27 21 1903 248 14:2 1220 572 1:4 4.8 440
32 21 2151 262 15:9 1351 627 1:1 4.8 404
32 27 2158 262 16:8 1365 627 1:1 4.7 381
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2406 283 18:7 1482 689 1:0 4.9 360
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IAC1230
IP Units
FREEZE CYCLE HARVEST CYCLE
45
AMBIENT
TEMP
_F
70 50 231 30 8:8 175 75 1:5 8.9 1249
80 70 266 33 11:4 191 84 1.1 9.5 1090
90 70 296 35 13:6 211 95 1:0 10.1 1000
90 80 295 36 14:5 211 93 0:9 10.1 948
100 70 331 38 16:3 232 105 0:9 10.3 865
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1593 207 8:8 1207 517 1:5 4.1 567
27 21 21834 228 11:4 1317 579 1:1 4.3 494
32 21 2041 241 13:6 1455 655 1:0 4.6 454
32 27 2034 248 14:5 1455 641 0:9 4.6 430
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2282 262 16:3 1600 724 0:9 4.7 392
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IWC1230
IP Units
FREEZE CYCLE HARVEST CYCLE
46
AMBIENT
TEMP
_F
70 50 336 30 10:1 187 73 1:4 9.8 1221
80 70 324 30 13:2 177 76 1.3 10.7 1065
90 70 330 33 14:0 180 76 1:3 10.9 1030
90 80 323 32 14:8 180 78 1:3 10.9 973
100 70 324 30 14:0 180 76 1:3 10.9 1025
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2317 207 10:1 1289 503 1:4 4.4 554
27 21 2234 207 13:2 1220 524 1:3 4.9 483
32 21 2275 228 14:0 1241 524 1:3 5.0 467
32 27 2227 221 14:8 1241 538 1:3 4.9 441
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2234 207 14:0 1241 524 1:3 4.9 465
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IRC1230
IP Units
FREEZE CYCLE HARVEST CYCLE
47
AMBIENT
TEMP
_F
70 50 231 30 8:8 175 75 1:5 8.9 1249
80 70 266 33 11:4 191 84 1.1 9.5 1090
90 70 296 35 13:6 211 95 1:0 10.1 1000
90 80 295 36 14:5 211 93 0:9 10.1 948
100 70 331 38 16:3 232 105 0:9 10.3 865
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1593 207 8:8 1207 517 1:5 4.1 567
27 21 1834 228 11:4 1317 579 1:1 4.3 494
32 21 2041 241 13:6 1455 655 1:0 4.6 454
32 27 2034 248 14:5 1455 641 0:9 4.6 430
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2282 262 16:3 1600 724 0:9 4.7 392
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IAC1448
IP Units
FREEZE CYCLE HARVEST CYCLE
48
AMBIENT
TEMP
_F
70 50 246 31 10:1 185 79 1:3 12.1 1525
80 70 280 34 11:8 201 88 1.3 12.3 1355
90 70 315 35 13:2 220 97 1:1 12.6 1275
90 80 317 37 13:7 222 98 1:1 12.4 1205
100 70 352 38 15:8 242 106 0:8 13.1 1140
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1696 214 10:1 1276 545 1:3 5.5 692
27 21 1931 234 11:8 1386 607 1:3 5.6 615
32 21 2172 241 13:2 1517 669 1:1 5.7 578
32 27 2186 255 13:7 1531 676 1:1 5.6 547
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2427 262 15:8 1669 731 0:8 6.0 517
12/1/94
AVERAGE
AVERAGE
AVERAGE
AVERAGE
Rev 3/4/96
AVERAGE OPERATING CHARACTERISTICS
IWC1448
IP Units
FREEZE CYCLE HARVEST CYCLE
49
AMBIENT
TEMP
_F
70 50 316 32 9:9 180 73 1:7 12.1 1505
80 70 318 35 11:9 188 77 1.4 12.7 1370
90 70 318 36 12:2 190 78 1:3 12.8 1360
90 80 317 37 13:0 194 80 1:3 12.6 1270
100 70 316 36 12:7 189 77 1:4 13.1 1335
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 2179 221 9:9 1241 503 1:7 5.5 683
27 21 2193 241 11:9 1296 531 1:4 5.8 621
32 21 2193 248 12:2 1310 538 1:3 5.8 617
32 27 2186 255 13:0 1338 552 1:3 5.7 576
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
38 21 2179 248 12:7 1303 531 1:4 5.9 606
AVERAGE
AVERAGE
AVERAGE
AVERAGE
AVERAGE OPERATING CHARACTERISTICS
IRC1448
IP Units
FREEZE CYCLE HARVEST CYCLE
50
AMBIENT
TEMP
_F
70 50 246 31 10:1 185 79 1:3 12.1 1535
80 70 280 34 11:8 201 88 1.3 12.4 1365
90 70 315 35 13:2 220 97 1:1 12.7 1285
90 80 317 37 13:7 222 98 1:1 12.5 1215
100 70 352 38 15:8 242 106 0:8 13.3 1150
WATER
TEMP
_F
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
Psig
SUCTION
PRESSURE
Psig
CYCLE
TIME
Min:Sec
ICE
WEIGHT
lb/Cycle
SI Units
FREEZE CYCLE HARVEST CYCLE
AMBIENT
TEMP
_C
21 10 1696 214 10:1 1276 545 1:3 5.5 696
27 21 1931 234 11:8 1386 607 1:3 5.6 619
32 21 2172 241 13:2 1517 669 1:1 5.8 583
32 27 2186 255 13:7 1531 676 1:1 5.7 551
WATER
TEMP
_C
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
HEAD
PRESSURE
kPa
SUCTION
PRESSURE
kPa
CYCLE
TIME
Min:Sec
ICE
WEIGHT
kg/Cycle
ICE
WEIGHT
lb/Day
ICE
WEIGHT
kg/Day
12/1/94
Rev 3/4/96
38 21 2427 262 15:8 1669 731 0:8 6.0 522
TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
Trouble Probable Cause Remedy
CUBER NOT OPERATING A. Power switch in center “OFF”
position.
CUBER NOT OPERATING, INDICATOR LIGHTS “OFF”, NO POWER TO CIRCUIT BOARD
CUBER NOT OPERATING, INDICATOR LIGHTS “OFF”, POWER TO THE CIRCUIT BOARD
A. Test power switch and leads. A. If defective, replace.
B. High pressure cut-out open.
(water cooled or remote systems)
A. Magnet not in proximity switch
field.
B. No curtain movement. B. Adjust proximity switch.
C. Faulty proximity switch. C. Replace proximity switch.
A. Place switch in “ON” position.
B. Press manual reset.
Determine cause: Water supply shut off; water pressure too low; water valve defective or out of adjustment; water condenser dirty or corroded; unit overcharged; water inlet pressure too high. Replace defective component as needed.
A. Water curtain drifting out of switch
range. Reduce clearance between curtain and proximity switch.
COMPRESSOR DOES NOT RUN, CIRCUIT BOARD INDICATOR LIGHTS “ON”
12/1/94 Rev 3/4/96
D. Unit OFF due to bin full. D. Remove ice from curtain.
Eliminate curtain restriction.
A. Check contactor and leads. A. Replace if defective.
B. Compressor overload “open”. B. Permit overload to cool and reset
or replace.
C. Check compressor and start
components.
51
C. Replace as needed.
Trouble Probable Cause Remedy
COMPRESSOR RUNS BUT DOES NOT COOL, CIRCUIT BOARD INDICATOR LIGHTS ON
CUBER REMAINS IN THE FREEZE CYCLE
CUBER REMAINS IN THE HARVEST CYCLE
A. Low charge. A. Leak check – Recharge.
B. Hot gas solenoid leaking. B. Replace.
C. Defective expansion valve. C. Replace.
D. Inefficient compressor. D. Replace.
E. Internal by-pass open,
E. Permit pressures to equalize.
compressor noisy.
A. Check suction line thermistor
A. Tighten, reattach. (sensor) lead wire connection at the circuit board.
B. Evaporator thermistor shorted. B. Replace.
C. Check thermistor (1K ohm). C. Replace if out of range.
D. Ice bridge setting too low. D. Adjust per bridge adjustment
instructions.
E. Expansion valve failure (will
not pull down).
E. Tighten bulb, replace as needed.
See check-out procedure.
SUCTION LINE THERMISTOR OPEN (STARTS IN HARVEST)
A. Loose connection at the circuit
A. Tighten or reconnect. board.
B. Test thermistor. B. Replace if out of range.
PROXIMITY SWITCH LIGHT OUT
C. Loose wire connection at
C. Tighten, reattach wire. circuit board.
D. Proximity switch defective, see
D. Replace as needed. check-out procedure.
E. Water curtain stuck, curtain
E. Check and adjust as needed. frozen to ice on evaporator. Curtain hung on water pan, proximity switch out of range.
PROXIMITY SWITCH LIGHT “ON”
F. Circuit board failure. Check
F. Replace as needed. voltage output.
G. Ice weight too light. G. Adjust bridge per Bridge
Adjustment instructions.
H. Potentiometer set too high. H. Adjust bridge per Bridge
Adjustment instructions.
I. Water curtain stuck, curtain
frozen to ice on evaporator. Curtain hung on water pan, proximity switch out of range.
52
I. Check and adjust as needed.
12/1/94 Rev 3/4/96
Trouble Probable Cause Remedy
LONG FREEZE CYCLE WATER FLOW ASSOCIATED
LONG FREEZE CYCLE GENERAL
A. Float set too high. A. Adjust.
B. Float stuck. B. Clean or replace.
C. Flow control washer missing or
C. Replace or re-install. upside down (number must be facing up).
A. Water leaking around pan or
A. Adjust as needed. curtain.
B. Dirty condenser or fan blade. B. Clean as required.
C. Louvers at condenser
C. Remove obstruction. obstructed.
D. Ambient air or water
D. Advise customer. temperature too high.
E. Condenser discharge air
E. Install condenser baffle. re-circulating.
F. Low charge. F. Check for leak, correct, evacuate
and recharge.
G. Hot gas solenoid valve leaking
G. Replace. (not seating).
H. Water regulator valve set too
high or stuck (water cooled
H. Adjust, clean or replace (setting to
be 300 to 310 PSI).
units only).
LONG HARVEST CYCLES A. Ice weight set too light. A. Adjust bridge per adjustment
instructions.
B. Unit not level. B. Level the unit.
C. Water curtain movement
C. Remove restriction. restricted.
D. Low head pressure: ambient
too low.
E. Low head pressure; water
valve set too low (water cooled
D. Minimum ambient temperature
50_F (10_C).
E. Adjust water regulator valve or
replace (300 to 310 PSI). units only) or leaking during harvest.
F. Scale build-up on evaporator. F. Clean per instructions.
G. Hot gas solenoid valve not
G. Replace valve. opening. Slow rise of low side pressure.
H. Expansion valve leaking. H. Replace valve.
12/1/94 Rev 3/4/96
53
Trouble Probable Cause Remedy
ICE WEIGHT LIGHT AT TOP OF PLATE AND HEAVY AT THE BOTTOM
NOTE: REVIEW DRAWING ON PAGE 19 OF THIS MANUAL FOR NORMAL ICE SLAB.
A. Float stuck open. A. Replace the float valve.
B. Flow control washer missing
B. Replace or re-install as needed. from the float or installed upside-down (numbers must be facing up).
C. Water flow rate over the
evaporator too fast.
D. Water leaking around curtain
C. Check position of distribution tube
(inner & outer).
D. Correct. and pan; curtain frozen in the ice.
E. Expansion valve flooding. E. Tighten and seal bulb. Replace
TXV if required.
F. Condenser air re-circulating. F. Install baffle.
G. Low charge. G. Leak check, evacuate & recharge.
H. Hot gas solenoid valve leaking. H. Replace.
I. Evaporator wall gasket torn or
I. Replace. missing, allowing condenser air to reach top of evaporator.
SOFT WHITE ICE OR WATER PUMP NOT PUMPING
A. Distribution tube or water
system scaled.
A. Clean distribution system as
required.
B. Water temperature too cold. B. 50_F (10_C) minimum.
C. Inadequate water system;
C. Correct. water pressure too low (below 20 PSI).
D. Inadequate water system; float
D. Replace. plugged or damaged.
E. Distributor tubes – old style E. Replace with new style, 47 hole,
distributor tube. High flow tubes require new style water curtains to contain water.
54
12/1/94 Rev 3/4/96
WH
UNIT
SWITCH
BL
BK
2
RH Evap.
Switc h
N S
(White Lead)
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
Unit
(if required)
GR
CONTACTOR
BK
1
3
BR
Options
BL
D-13
YL
RH Evap.
YL
D-10
LH Evap.
Condenser
Plug
Suction Plug
Test Plug
Plug
Micro
Processor
Stacking Cable Plug
WH
CO
450 PSIG
BR
D-15
GR
D-14
GR
GR
D-12
Error
Adjustable Ice
Thickness Pot.
RD
Water
Dump
Valve
Relay
Water Pump
D-11
GR
D-6
GR
D-5
Manual Harvest Switch
BR
BK
M
BK
CONDENSATION FAN (W/C ONLY)
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C ONLY)
BL
YL
Hot Gas
Valve
Condenser
Fan
Transformer
3
7 5
3
1
BK
1
230V
Voltage
Selector
Switch
115V
COMPRESSOR
BR
WATER DUMP SWITCH
2
8 6
4 2
RD
R
C
S
COMPRESSOR
BK
WH
BL
EXTERNAL
OVERLOAD
CURRENT START RELAY
BL
HOT GAS SOLENOID
RD
YL
WATER DUMP
VALVE
CONDENSER FAN MOTOR
(A/C ONLY)
M
COMPRESSOR
START
CAPACITOR
243-292 mfd
115 VAC
OR
2
5
1
WH
WH
WH
BK
WH
WH
PUMP CORD
WH
M
WATER PUMP
12/1/94 Rev 3/4/96
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
55
IAC 322 & IWC 322
IAC 330 & IWC 330
POWER CORD
BK
GR
CONTACTOR
BK
WH
WH
COMPRESSOR
START
CAPACITOR
BK
BR
COMPRESSOR
R
C
S
RD
YL
243-292 mfd
115 VAC
EXTERNAL
COMPRESSOR
M
OVERLOAD
OR
UNIT
SWITCH
BL
2
RH Evap.
Switch
N S
(White Lead)
Condenser
Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
Unit
(if required)
BR
BK
1
BL
CONDENSATION FAN (W/C ONLY)
POTENTIAL START RELAY
3
2
5
1
WH
MANUAL RESET
HIGH PRESSURE
BR
CO
450 PSIG
BR
CONTROL(W/C ONLY)
BL
BK
1
3
2
WATER DUMP SWITCH
WATER DUMP
VALVE
WH
CONDENSER
WH
FAN MOTOR
M
(A/C ONLY)
BK
BK
PUMP CORD
WATER PUMP
WH
WH
M
D-13
YL
RH Evap.
YL
D-10
LH Evap.
Condenser Plug
Suction Plug
Test Plug
Options
Plug
Micro
Processor
Stacking Cable Plug
D-15
GR
D-14
GR
GR
D-12
Adjustable Ice
Thickness Pot.
Error
RD
Water Dump
Valve
Relay
Water Pump
D-11
GR
D-6
GR
D-5
Manual Harvest Switch
YL
Hot Gas
Valve
Condenser
Fan
Transformer
7
5
3 1
230V
Voltage
Selector
Switch
115V
BK
8
6
4
2
RD
WH
BL
HOT GAS
SOLENOID
BL
BL
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
12/1/94 Rev 3/4/96
IACS 227 & IWCS 227 115 Volts 60 HZ
56
ILL339
POWER
CORD
BK
RD
RD
SWITCH
BL
N S
N S
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
(if required)
RD
UNIT
RH Evap.
Switch
LH Evap.
Switch
(White Lead)
Unit
GR
BK
BR
BR
Test Plug
Options
Stacking Cable Plug
CONTACTOR
RD
BL
450 PSIG
BR
D-15
GR
D-13
D-14
YL
GR
RH Evap.
GR
D-10
D-12
YL
LH Evap.
Condenser Plug
Suction Plug
RD
Error
Plug
Adjustable Ice
Thickness Pot.
Micro
Processor
BR
BK
M
BK
CONDENSATION FAN (W/C ONLY)
HIGH PRESSURE CONTROL
CO
BL
YL
Water Dump
Valve
Relay
Water Pump
D-11
Hot Gas
GR
Valve
D-6
Condenser
GR
Fan
D-5
Transformer
Manual Harvest Switch
MANUAL RESET
(W/C ONLY)
BK
WATER DUMP
1
2
8
6
4
21
SWITCH
3
7 5
3
230V
Voltage
Selector
Switch
115V
RD
COMPRESSOR
R
C
S
EXTERNAL
COMPRESSOR
OVERLOAD
BK
RD
RD
HOT GAS
SOLENOID
BL
RD
RD
YL
WATER DUMP
CONDENSOR FAN MOTOR (A/C ONLY)
BL
COMPRESSOR
START
CAPACITOR
43-52 mfd 220 VAC
VALVE
M
WH
BK
WH
PUMP CORD
WATER PUMP
WH
M
CURRENT
RELAY
S
M
RD
WH
WH
L
RD
12/1/94 Rev 3/4/96
BL
IACS227E60, IWCS227E60, 208/230V 60HZ
57
Artwork 50910
WH
UNIT
SWITCH
BL
BK
2
RH Evap.
Switch
N S
(White Lead)
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
Unit
(if required)
GR
CONTACTOR
BK
1
3
BR
BL
D-13
YL
RH Evap.
YL
D-10
LH Evap.
Condenser
Plug
Suction Plug
Test Plug
Options
Plug
Micro
Processor
Stacking Cable Plug
WH
CO
450 PSIG
BR
D-15
GR
D-14
GR
GR
D-12
Adjustable Ice
Thickness Pot.
Error
RD
Water Dump
Valve
Relay
Water Pump
D-11
GR
D-6
GR
D-5
Manual Harvest Switch
BR
BK
M
BK
CONDENSATION FAN (W/C ONLY)
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C ONLY)
BL
YL
Hot Gas
Valve
Condenser
Fan
Transformer
3
7 5
3 1
BK
1
230V
Voltage
Selector
Switch
115V
COMPRESSOR
BR
WATER DUMP SWITCH
2
8 6
4 2
C
BK
RD
BL
BL
R
S
EXTERNAL
COMPRESSOR
OVERLOAD
POTENTIAL START RELAY
BL
WH
HOT GAS
SOLENOID
COMPRESSOR
RD
30 mfd
440 VAC
YL
WATER DUMP
VALVE
CONDENSER FAN MOTOR
(A/C ONLY)
M
IAC 522 & IWC 522
IAC 530 & IWC 530
RUN
CAPACITOR
YL
2
5
1
WH
BK
RD
72-86 mfd
330 VAC
WH
PUMP
CORD
WATER PUMP
COMPRESSOR
START
CAPACITOR
OR
WH
WH
WH
WH
M
12/1/94 Rev 3/4/96
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C UNITS.
58
RD
BK
CRANKCASE HEATER
(RC ONLY)
RD
RD
GR
BK
BK
BR
BR
LIQUID LINE SOLENOID
(R/C ONLY)
CONTACTOR
RD
BL
450 PSIG
RD
BR
BK
BK
M
BK
CONDENSATION FAN (W/C & R/C ONLY)
HIGH PRESSURE CONTROL
CO
BL
BK
BR
MANUAL RESET
(W/C & RC ONLY)
BK
RD
COMPRESSOR
R
C
S
EXTERNAL
COMPRESSOR
OVERLOAD
RD
RD
YL
POTENTIAL START RELAY
WATER DUMP
COMPRESSOR
RUN
CAPACITOR
5
VALVE
YL
1
See note 2
35 mfd 370 VAC
2
WH
COMPRESSOR
START
CAPACITOR
RD
145-174 mfd
250 VAC
OR
RD
RD
UNIT
SWITCH
BL
RH Evap.
Switch
N S
LH Evap.
Switch N S
(White Lead)
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
Unit
(if required)
D-13
YL
RH Evap.
D-10 YL
LH Evap.
Condenser Plug
Suction Plug
Test
Plug
Options
Plug
Micro
Processor
Stacking Cable Plug
BR
D-15
GR
D-14
GR
GR
D-12
Error
Adjustable Ice Thickness Pot.
RD
Water
Dump
Valve
Relay
Water Pump
D-11
GR
D-6
GR
D-5
Manual Harvest Switch
Hot Gas
Valve
Condenser
Fan
Transformer
YL
3
7 5
3 1
230V
Voltage
Selector
Switch
115V
WATER DUMP
1
SWITCH
2
8 6
4 2
RD
BK
RD
BL
BL
CONDENSOR FAN MOTOR
(A/C ONLY)
BL
HOT GAS
SOLENOID
M
BK
WH
PUMP
CORD
WATER PUMP
IAC 830, IWC 830 & IRC 830
IAC 630, IWC 630 & IRC 630
WH
WH
M
12/1/94 Rev 3/4/96
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTER USED ONLY ON W/C & R/C UNITS.
NOTE 2: CAPACITORS USED ON 630 BRISTOL COMPRESSOR:
RUN CAP, 25mfd 440 VAC START CAP. 161-193mfd 250 VAC
59
RD
BK
RD
GR
CONTACTOR
BK
BK
LIQUID LINE SOLENOID
(R/C ONLY)
RD
BR
BK
M
RD
BK
RD
COMPRESSOR
R
C
S
EXTERNAL
COMPRESSOR
OVERLOAD
RD
YL
RD
COMPRESSOR
RUN
CAPACITOR
SEE NOTE 2
40 mfd
370 VAC
YL
COMPRESSOR
START
CAPACITOR
RD
189-227 mfd 330 VAC
RD
OR
CRANKCASE HEATER
(RC ONLY)
BK
BL
BK
BK
CONDENSATION FAN (W/C & R/C)
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C & R\C)
CO
RD
SWITCH
BL
RH Evap.
N S
LH Evap.
N S
(White Lead)
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
(if required)
Switch
Switch
Unit
UNIT
BR
D-13
YL
RH Evap.
D-10 YL
LH Evap.
Condenser Plug
Suction Plug
Test Plug
Options
Plug
Micro
Processor
Stacking Cable Plug
450 PSIG
D-15
GR
D-14
GR
GR
D-12
Error
Adjustable Ice Thickness Pot.
D-11
RD
Water Dump
Relay
Pump
D-6
Valve
Water
GR
GR
D-5
Manual Harvest Switch
BR
Hot Gas
Condenser
BL
Valve
Fan
Transformer
YL
BK
3
7 5
3
230V
Voltage
Selector
Switch
115V
1
2
8
6
4
21
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C & R/C UNITS.
BR
WATER DUMP SWITCH
BK
RD
RD
BL
BL
POTENTIAL START RELAY
WATER DUMP
M
M
BL
HOT GAS
SOLENOID
2
5
1
RD
VALVE
WH
CONDENSER FAN MOTORS (A/C ONLY)
BK
BK
WH
WH
WH
PUMP
CORD
M
WATER PUMP
IAC 1230, IWC 1230 & IRC 1230 IAC 1030, IWC 1030 & IRC 1030
12/1/94 Rev 3/4/96
2: CAPACITORS USED ON 1030 COMPRESSOR
RUN CAP. 37MFD 370V START CAP. 145 - 174 MFD 250V
60
RD
UNIT
SWITCH
RD
RD
GR
CONTACTOR
BK
BK
BR
LIQUID LINE
SOLENOID
(R/C ONLY)
RD
BL
BK
RD
BR
M
CONDENSATION
FAN (W/C & R/C)
BK
BK
CRANKCASE HEATER
(A/C & R/C ONLY)
BK
BK
BK
RD
COMPRESSOR
BR
RD
R
C
S
EXTERNAL
COMPRESSOR
OVERLOAD
POTENTIAL START RELAY
WATER DUMP
VALVE
COMPRESSOR
RUN
CAPACITOR
RD
YL
YL
2
5
1
WH
RD
40 mfd 440 VAC
COMPRESSOR
START
CAPACITOR
189-227 mfd 330 VAC
RD
OR
RD
BL
BR
RH Evap.
Switch
N S
LH Evap.
Switch
N S
(White Lead)
Condenser Sensor
See note 1
Suction Line
Sensor
(Brown Lead)
To Stacked
Unit
(if required)
CO
450 PSIG
MANUAL RESET
HIGH PRESSURE
CONTROL(W/C & R/C)
BR
D-15
GR
D-13
D-14
YL
GR
RH Evap.
GR
D-12
YL
D-10
LH Evap.
Condenser
Plug
Suction
Plug
Test Plug
Options
Plug
Micro
Processor
Stacking Cable Plug
RD
Error
Adjustable Ice Thickness Pot.
D-11
D-6
Water Dump
Valve
Relay
Water
Pump
GR
GR
D-5
Manual Harvest Switch
BL
Hot Gas
Valve
Condenser
Fan
Transformer
3
YL
7 5
3
230V
Voltage
Selector
Switch
115V
WATER DUMP
1
SWITCH
2
8 6
4 21
BK
RD
BL
BL
BK
CONDENSER FAN MOTOR (A/C ONLY)
BL
RD
HOT GAS
SOLENOID
M
WH
WH
WH
PUMP
CORD
M
WATER PUMP
IAC 1448, IWC 1448 & IRC 1448
WH
12/1/94 Rev 3/4/96
NOTE 1: CONDENSER SENSOR USED ONLY ON A/C UNITS.
1.8K ohm RESISTOR USED ONLY ON W/C & R/C UNITS.
61
BK
M
CAPACITOR
2 mfd 440 VAC
RED
COLORED
BAND
BK
HEAT SHRINK TAPE
GR
FAN CYCLING SWITCH
CONDENSER
FAN MOTOR
HEAT SHRINK TAPE
BK
HEAT SHRINK TAPE
12/1/94 Rev 3/4/96
RD
CR800, CR1200, & CR1400 REMOTE CONDENSERS
208/230 VOLTS 60 HZ
62
GR
12/1/94
Rev 3/4/96
AIR COOLED CONDENSER
FAN BLADES
WATER DUMP VALVE
63
WATER FLOAT VALV E
WATER PUMP
EVAPORATOR
THERMOSTATIC EXPANSION VALVE
HOT GAS SOLENOID VALV E
S
HIGH SIDE SERVICE VALV E
FAN MOTOR
HEAT EXCHANGER
FILTER/DRIER
LOW SIDE SERVICE VALV E
REFRIGERATION AND WATER SYSTEMS
MODELS IAC227, IAC322, IAC330, IAC522, AND IAC530 MODELS IAC630, AND IAC830 MODEL IWCS227
COMPRESSOR
AIR COOLED CONDENSER
FAN BLADES
WATER DUMP VALVE
WATER PUMP
64
WATER FLOAT VALVE
EVAPORATOR
HOT GAS SOLENOID VALVE
EVAPORATOR
THERMOSTATIC EXPANSION VALV E
THERMOSTATIC EXPANSION VALV E
FAN MOTOR
HEAT EXCHANGER
HIGH SIDE SERVICE VALV E
FILTER/DRIER
LOW SIDE SERVICE VALV E
COMPRESSOR
12/1/94
Rev 3/4/96
Refrigeration and water system
Models IAC1030, IAC1230, and IAC1448
August 3, 1994
12/1/94
Rev 3/4/96
WATER REGULATING VALV E
WATER-COOLED CONDENSER
WATER INLET
WATER DUMP VALVE
65
WATER
S
FLOAT VALV E
WATER PUMP
EVAPORATOR
Refrigeration and Water Systems
Models IWC322, IWC330, IWC522, and IWC530
Models IWC603, and IWC830
Model IWCS227
August 3, 1994
THERMOSTATIC EXPANSION VALVE
HOT GAS SOLENOID VALV E
S
HIGH SIDE SERVICE VALV E
HEAT EXCHANGER
PRESSURE SWITCH
LOW SIDE SERVICE VALV E
COMPRESSOR
FILTER/DRIER
WATER REGULATING VALV E
66
S
WATER DUMP VALVE
WATER PUMP
WATER FLOAT VAVLE
EVAPORATOR
HOT GAS SOLENOID VALV E
S
EVAPORATOR
THERMOSTATIC EXPANSION VALVE
THERMOSTATIC EXPANSION VALVE
WATER INLET
HEAT EXCHANGER
HIGH SIDE SERVICE VALV E
LOW SIDE SERVICE VALV E
W
WATER-COOLED CONDENSER
FILTER/DRIER
PRESSURE SWITCH
COMPRESSOR
12/1/94
Rev 3/4/96
REFRIGERATION AND WATER SYSTEM MODELS IWC1030, IWC1230 AND 1WC1448
AUGUST 3, 1994
12/1/94
Rev 3/4/96
FAN BLADES
PRESSURE SWITCH
HEAD PRESSURE CONTROL
67
S
WATER DUMP VALVE
WATER PUMP
WATER FLOAT VALV E
EVAPORATOR
HOT GAS SOLENOID VALV E
THERMOSTATIC EXPANSION VALVE
S
FAN MOTOR
LIQUID SOLENOID VALV E
HEAT EXCHANGER
HIGH SIDE SERVICE VALV E
REMOTE CONDENSER
FILTER/DRIER
S
PRESSURE SWITCH
LOW SIDE SERVICE VALV E
COMPRESSOR
COUPLINGS VALVES
RECEIVER
SERVICE VALVE
CHECK VALV E
REFRIGERATION AND WATER SYSTEMS
MODELS IRC630 AND IRC830
AUGUST 3, 1994
FAN BLADES
PRESSURE SWITCH
HEAD PRESSURE CONTROL
68
WATER DUMP VALV E
WATER PUMP
WATER FLOAT VALV E
EVAPORATOR
HOT GAS SOLENOID VALV E
EVAPORATOR
THERMOSTATIC EXPANSION VALVE
THERMOSTATIC EXPANSION VALVE
FAN MOTOR
LIQUID SOLENOID VALV E
HEAT EXCHANGER
HIGH SIDE SERVICE VALV E
REMOTE CONDENSER
PRESSURE SWITCH
LOW SIDE SERVICE VALV E
COMPRESSOR
FILTER/DRIER
CHECK VALV E
COUPLINGS VALVES
RECEIVER
SERVICE VALVE
12/1/94
Rev 3/4/96
REFRIGERATION AND WATER SYSTEM
MODELS IRC1030, IRC1230 AND IRD1448
AUGUST 3, 1994
12/1/94
Rev 3/4/96
FAN BLADES
PRESSURE SWITCH
HEAD PRESSURE CONTROL
FAN MOTOR
COUPLINGS VALVES
69
REMOTE CONDENSER
MODELS CR800, CR1200, AND CR1400
AUGUST 5, 1994
“I” Series “Remote”
Ice Machine
70
12/1/94 Rev 3/4/96
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS
UNIT
LEG
1/4-20 SCREW
LEG
BRACE
1. Follow the standard installation instructions supplied with cuber. Do not hook cuber into the power source until the remote condenser and line set installation is complete.
2. Assembly of remote condenser (see drawing): A. Assemble legs to base panel. Install leg supports on legs. B. Locate the remote condenser in a well–ventilated area on the roof away from other refrigeration equip-
ments condenser discharge air flow.
C. Use the mounting holes provided to secure the remote condenser to the roof. Seal over heads of bolts
or fasteners with tar or pitch to prevent entrance of moisture.
REMOTE CONDENSER
LEG
LEG SUPPORT
3. Remote condenser electrical hook-up: A. Connect remote condenser to a power source (208/230VAC, 60 HZ) separate from the cuber. An ex-
ternal disconnect switch must be used.
B. Make sure the electrical connections follow all local and
national codes. C. DO NOT turn condenser on until cuber install and refrigerant line connections are complete! D. Never wire condenser into cuber section. The condenser is an independent electrical connection. E. Fan motor will not start until pressure rises to 205 PSIG [14.07 Bars] closing fan cycling switch.
12/1/94 Rev 3/4/96
71
F. The condenser fan may cycle off during the harvest cycle – this would be normal.
NOTE: Installing an IMI Cornelius remote cuber with other than an IMI Cornelius remote condenser
and line set may be reason to void the cuber warranty.
LIQUID REFRIGERANT LINE
DISCHARGE LINE
CORRECT
4. Each condenser and cuber is connected with two (2) *pre-charged lines. A. The pre-charged lines are ordered separately from the condenser to suit each individual application. B. The pre-charged line lengths are 20 feet [6.096 meters], 35 feet [10.66 meters] and 55 feet [16.76 me-
ters].
NOTE (Pre-charged is defined as a vapor holding charge – not a portion of the system charge.)
5. Installation of line kits (see drawing). Remove the tubing from the carton. Carefully uncoil the lines so the tubing doesnt become kinked, and route lines to cuber and condenser.
6. Keep line-set as short as possible. Place a 3-foot service loop behind cuber to allow for rear service should it ever be required.
72
12/1/94 Rev 3/4/96
REMOTE CONDENSER LOCATION
1. Physical Line-Set Length: 55 Ft. Maximum [16.764 meters]
The ice machine compressor must have the proper oil return. Line-set rises, drop, or horizontal runs great­er than the maximum distance allowed will exceed the compressor start-up and pumping design limits, and will result in poor oil return to the compressor.
Line-Set Rise: 35 Ft. Maximum [10.66 meters] Line-Set Drop: 15 Ft. Maximum [4.57 meters]
2. Calculated Line-Set Distance: 100 Ft. [30.48 meters]
To prevent the combination of rises, drops and horizontal runs exceeding the compressor start-up and pumping design limit, the following calculations should be made:
NOTE: Max. line–set for IMI Cornelius cubers is 55 ft. Do not confuse line length with calculated line
distance
B
A
B
A - (RISE) CONDENSER HIGHER THAN EVAP.
MAX. 35 FT.
B - LINE LENGTH 15 FT.: EXAMPLE
B - LINE LENGTH 35 FT.: EXAMPLE C - (DROP) CONDENSER LOWER THAN EVAP. 15 FT.: MAX.
Maximum Line-Set Distance Formula
A. Measured rise x 1.7= Calculated Rise 35 ft. Max) [10.66 meters]
B. Measured drop x 6.6= Calculated Drop 15 ft. Max) [4.57 meters]
C. Measured Horizontal Distance = actual measurement.
D. Total Calculated Distance (A+B+C)=Total Calculated Distance (100 ft. Max.) [30.48 meters]
Examples:
a. Insert measured rise (R) into the formula and multiply it by 1.7 to get a calculated rise.
example: A condenser located 15 ft. [4.572 meters] above the ice machine has a 25.5 ft. [8.874 meters] calculated total (15 ft. x 1.7 = 25.5).
H
AIR FLOW
R
C
12/1/94 Rev 3/4/96
b. Insert measured drop (D) into formula and multiply by 6.6 to get a calculated drop.
example: A condenser located 8 ft. [2.438 meters] below the ice machine has a 52.8 ft. [16.093 meters] calculated total (8 ft. x 6.6 = 52.8 ft.).
73
COMBINATION OF DROP(S) WITH HORIZONTAL
H
D
AIR FLOW
c. Insert measured horizontal distance into formula. No calculation is necessary. (6 ft.) [1.828 me-
ters].
d. Add the calculated rise, calculated drop, and horizontal distance together to get the total calcu-
lated distance (25.5 + 52.8 + 6) equals 84.3 ft. [25.694 meters]. If 100 ft. [30.48 meters] total cal­culated distance is exceeded, the condenser must be moved to a new location which permits proper equipment operation.
COMBINATION OF RISE AND DROP(S)WITH HORIZONTAL
H
R
D
AIR FLOW
CAUTION: If a line-set rise is followed by a line-set drop, a second line-set rise cannot be made. Or If a line-set drop is followed by a line-set rise, a second line-set drop cannot be made.
3. Lengthening or Reducing the Line-Set Lengths
In most cases, by routing the line-set properly, shortening will not be necessary (refer to illustration). How­ever, when shortening or lengthening is required, do so before connecting the line-set to the ice machine or the remote condenser. This prevents the loss of refrigerant from the ice machine or the condenser.
The quick connect fittings on the line-sets are equipped with Schrader Valves. Use these valves to recover any vapor charge from the line-set. When lengthening or shortening lines, apply good refrigeration practic­es and insulate new tubing. Do not change the tube sizes. Evacuate the lines and place approximately 5 oz. of vapor refrigerant charge in each line.
SCHRADER
VALV E
PARENT
METAL
SEAL
INTERMEDIATE
SEAL
4. Connection of Line-Set A. Remove the plastic caps from the line-set, the condenser, and the ice machine. B. Apply refrigeration oil to the threads on the quick connect couplers before connecting them to the con-
denser. C. Carefully thread the female fitting onto the condenser or ice machine by hand. D. Using the proper size wrench, tighten the couplings until they bottom out. Turn an additional 1/4 turn
to ensure proper brass-to-brass seating.
74
12/1/94 Rev 3/4/96
E. Check all fittings for leaks.
5. Final Installation: A. Remove grill from the right-hand side panel of cuber. B. Turn service port on receiver tank to open position releasing refrigerant to the balance of the system. C. Leak check line-set connections at cuber and condenser. D. Replace grill. E. Connect cuber to power source. F. Make sure electrical connections follow all local and national codes.
6. Start Up: A. Use standard procedures from cuber installation instructions. B. After the cuber is running, check the remote condenser and verify that the condenser fan is running.
CAUTION: Once the refrigerant lines are connected, the seal is broken in the fittings. If the lines are removed or loosened from the cuber or remote condenser, the refrigerant charge will be discharged to the atmosphere. DISCHARGING TO THE ATMOSPHERE IS IN
VIOLATION OF THE CLEAN AIR ACT OF JULY, 1992.
12/1/94 Rev 3/4/96
75
ICE CUBER SPECIFICATION
MODEL IRC630 IRC830 IRC1230 IRC1448
UNIT
Volts 208/230 + 10%, –5% 208/230 +10%, –5% 208/230 +10%, –5% 208/230 +10%, –5%
Phase 1 1 1 1
Hertz 60 60 60 60
No. Wires 2+ground 2+ground 2+ground 2+ground
MIN. CIRCUIT
Amps 20 20 20 25
MAX FUSE SIZE (HVAC CIRCUIT BREAKER REQUIRED)
Amps 20 20 20 25
REFRIGERANT
Type R404a(HP62) R404a(HP62) R404a(HP62) R404a(HP 62)
Weight (oz) 170 170 210 250
Weight (g) 4820 4820 5954 7088
COMPRESSOR
Volts 230 230 230 230
Phase 1 1 1 1
Hertz 60 60 60 60
LRA 69 61 96 95.6
RLA 8.8 12.5 13.5 23.9
AIR CIRCULATION FAN MOTOR
Volts 230 230 230 230
Phase 1 1 1 1
Hertz 60 60 60 60
Amps Running 0.36 0.36 0.36 0.36
Watts 6 6 6 6
WATER PUMP
Volts 230 230 230 230
Phase 1 1 1 1
Hertz 60 60 60 60
Amps Running 0.5 0.5 0.5 0.5
HP 1/30 1/30 1/30 1/30
REMOTE CONDENSER SPECIFICATION
MODEL CR800 CR1200 CR1400
Volts 230 230 230
Phase 1 1 1
Hertz 60 60 60
Amps 1.0 1.0 1.0
Output, HP 1/6 1/6 1/6
Max. fuse size, Amps (HVAC circuit breaker required)
20 20 20
76
12/1/94 Rev 3/4/96
HEAD PRESSURE CONTROL [HEADMASTER]
discharge
above 70°F
normal
receiver
discharge
condenser
condenser
below 70°F by-pass
receiver
The Cornelius “I” series remote systems use an Alco Head Pressure Control, normally referred to as a head­master. This control is mounted in the remote condenser with a fan cycling control switch. Using both these controls gives the system positive operation under a wide range of condensing temperatures.
The cycling control starts the fan at 270 PSI and stops it at 205 PSI allowing a positive efficient operation at the high temperature operating ranges.
The headmaster controls the operation when the condensing temperature drops below 70°F. The “I” series re­frigerant charge is HP - 62 [R - 404A] and the headmaster dome charge setting is 200 PSI of nitrogen pressure making it stable under the low temperature operating range down to - 20°F.
The normal flow pattern through the headmaster is from the condenser port to the receiver port. When this flow pattern is unable to maintain a receiver outlet pressure equal to or above the dome pressure setting of the valve, the dome pressure will force the valve portage to change closing the condenser port and opening the by­pass port from the compressor discharge line. This allows the high pressure vapor from the discharge port to buck the receiver pressure back up. With the condenser port closed, the refrigerant is backed up in the con­denser, basically reducing the condenser size, assisting in maintaining the discharge portage flow and increas­ing the head pressure.
Remember, sense of touch to the lines of the headmaster will determine the flow path the headmaster is in, condenser to receive, or bypass to receiver.
High side gauge installed at the receiver outlet valve will determine if the headmaster is functioning to maintain the proper operating pressure.
In the event the control appears to be stuck in bypass, the pressure drop across the headmaster must be measured. With a gauge installed at the receiver outlet valve and the high side service valve, the pressure dif­ference at these two points must be less than the 15 PSI. The three most common causes of an excessive pressure drop are shortage of refrigerant, kinked remote lines, and excessive line length.
Eliminate refrigerant shortage first. Add refrigerant in two-pound increments (not to exceed six pounds) to determine if it corrects the pressure drop. If pressure drop is not corrected, inspect line set for sharp bends or kinks and correct as required. If adding refrigerant does not correct continued (bypass) condition and line set is not damaged, replace headmaster.
12/1/94 Rev 3/4/96
77
REMOTE SYSTEM EVACUATION/RE-CHARGE
All field repairs to the sealed system must start with a total discharge of the system following the requirements of the Clean Air Act of July, 1992.
Proper evacuation of the total remote system will require a three (3) point hook-up of your manifold and hose set, (see drawing):
Point #1 - Cuber receiver outlet valve Point #2 - Cuber high side service valve Point #3 - Cuber low side service valve
Evacuation:
1. With cuber power supply turned “OFF” disconnect and insulate all 3 compressor leads at the compressor. Turn power supply on, place power switch in the “on” position. This will energize (open) the Liquid Line so­lenoid allowing evacuation of the Liquid Line between the solenoid and the expansion valve(s).
2. Evacuate system to 200/250 microns or less. At this point, there should be a holding test of five(5) minutes. You may expect a slight loss of vacuum as normal. A rapid rise to normal atmospheric pressure indicates moisture still present in the system. On a “wet” system, it will prove beneficial to use heat lamps to warm the compressor dome and evaporator surface during evacuation.
3. Turn cuber power switch OFF. Reconnect compressor leads.
4. *After proper evacuation hold test has been performed, the refrigerant charge should be “dumped” into the receiver until the pressure equalizes, stopping the flow. Do not try to throttle the refrigerant flow. Doing so will allow system pressure to balance too soon. The high-side service valve should be closed and the bal­ance of the charge fed slowly through the suction side service valve with the compressor operational. Con­trol the feed rate at no faster than four (4) ounces [113.g] per minute to ensure the compressor oil does not become too saturated with refrigerant resulting in a loss of compressor lubrication.
5. All refrigerant re-charging must be weighed into the system, utilizing an electronic charging scale. DO NOT attempt to recharge the system by sight glass, system pressure, amperage, frost line or sweat patterns.
6. Always leak check entire system after recharge.
OPEN
RECEIVER
OPEN
RECEIVER
OUTLET
VA LV E
CAUTION: Before programming the electronic scales to “dump” the charge, de-energize the liquid line solenoid, close the shut-off valve on vacuum pump and low side of the manifold set.
EVACUATION
MANIFOLD SET
OPEN
OPEN
CHARGING
OPEN
CYLINDER
HIGH SIDE
SERVICE
VA LV E
LOW
SIDE
SERVICE
VA LV E
CLOSED
1ST STAGE CHARGING
OPEN
RECEIVER
OPEN
RECEIVER
OUTLET
VA LV E
CLOSED
MANIFOLD SET
CLOSED
CLOSED
HIGH SIDE
SERVICE
VA LV E
LOW SIDE
SERVICE
VA LV E
OPEN
CHARGING
CYLINDER
CLOSED
2ND STAGE CHARGING
COMPRESSOR OPERATING
CLOSED
RECEIVER
RECEIVER
OUTLET
VA LV E
CLOSED
MANIFOLD SET
OPEN
CLOSED
CHARGING
CYLINDER
HIGH SIDE
SERVICE
SERVICE
VA LV E
OPEN
VA LV E
LOW
SIDE
VACUUM
PUMP
CLOSED
ELECTRONIC
SCALE
VACUUM
PUMP
78
OPEN
ELECTRONIC
SCALE
VACUUM
PUMP
OPEN
ELECTRONIC
SCALE
12/1/94 Rev 3/4/96
THIS PAGE LEFT BLANK INTENTIONALLY
79 166240004
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place Anoka, Minnesota 55303-6234 (763) 421-6120 (800) 238-3600
80
12/1/94 Rev 3/4/96
Loading...