Cooper&Hunter CH48LCOU Specifications

4 (1)
Cooper&Hunter CH48LCOU Specifications

Duct Light Commercial Series

 

 

Duct Air Conditioners

 

 

 

Submittal Data Sheet

CH-48LCDTU/I (INDOOR UNIT)

CH-48LCU/O (OUTDOOR UNIT)

Job Name:_________________________________________________________________________

Location:________________________________________________________________________

Engineer:______________________________________________________________________

Submitted to:_____________________________________________________________________

Submitted by:_____________________________________________________________________

Reference:_________________________________________________________________________

This warranty should be registered on our web-site www.cooperandhunter.us within 60 days of installation. The warranty is only valid when installed by a Licensed HVAC Technician. A warranty period of Seven (7) years on compressor to the original registered end-user. A warranty period of Five (5) years on all parts to the original registered end user. Warranty applies only to products remaining in their original installation location.

GENERAL FEATURES

• Flexible Installation

 

 

• Built-In Water Pump

• Fresh Air Function

 

 

• Golden fin for outdoor and indoor

• Wired Control & Wi-Fi Connection

• Lower Noise

• Multi-Channel Air Distribution

 

 

• Higher Pipe Limits

 

 

 

 

• Slim Design

INDOOR SPECIFICATION

 

 

 

 

 

Sound Preassure level (Hi/Mi/Lo)

 

 

50.5/49.5/46 dB(A)

 

 

 

 

 

Design pressure

 

 

550/340 PSIG

 

 

 

 

 

Dimension (W*D*H)

 

 

47x34x12 in

 

 

 

 

 

Net/Gross weight

 

 

120/142 Lbs

 

 

 

 

OUTDOOR SPECIFICATION

 

 

 

 

Air flow

 

CFM

4470

 

 

 

 

Noise level

 

dB(A)

62.5

 

 

 

 

Dimension (W*D*H)

 

in

37.48x16.34x52.48

 

 

 

 

Net/Gross weight

 

Lbs

217.4/246.0

 

 

 

 

 

Refrigerant Type

 

 

 

R410/148.2

 

 

 

 

Refrigerant precharge

 

ft

25

Additional charge for each ft

 

oz

0.32

 

 

 

 

 

Date:______________________________________________________________________________

Approval:__________________________________________________________________________

onstruction:______________________________________________________________________

Unit #:_____________________________________________________________________________

Drawing #:_________________________________________________________________________

 

 

 

 

Cooling

 

 

 

Capacity

 

Btu/h

 

48000

 

 

SEER

 

 

 

17.4

PERFORMANCE

EER

 

Btu

 

9.2

Input

 

W

 

5215

AND

 

Heating at 47F

 

EFFICIENCY

Capacity

 

Btu/h

 

49500

 

 

COP

 

W/W

 

3.52

 

 

HSPF4

 

 

 

10.3

 

 

HSPF5

 

 

 

8.8

OPERATION TEMPERATURE RANGE

 

 

 

 

 

 

 

 

Indoor

 

 

Outdoor

 

 

 

 

 

 

 

 

cooling

 

heating

 

cooling

 

heating

62 90

 

32 86

5 122

 

5 86

ELECTRICAL

Power supply

V/Hz/Ph

 

208-230V/ 60Hz/ 1Ph

 

 

 

 

MCA

A

 

35

MFA

A

 

50

 

Indoor fan motor

 

Input

W

 

560

RLA

A

 

2.0

 

Outdoor fan motor

Input

W

 

126

RLA

A

 

1.2

 

Compressor

 

Capacity

Btu/h

 

44697

Input

W

 

3420

RLA

A

 

23.5

MCA: Minimum Circuit Ampacity; MFA: Max.fuse amps; RLA: Rated load amps

PIPING

Refrigerant piping/Gas side

in

(3/8"5/8")

 

 

 

Max. pipe length

ft

213

 

 

 

Max. difference in level

ft

98

 

 

 