Cooper&Hunter CH48LCOU Specifications

Duct Light Commercial Series
Duct Air Conditioners
Submittal Data Sheet
Job Name:_________________________________________________________________________ Location:______________________________________________________ __________________ Engineer:____________________________________________________ _ _________________ Submitted to:_____________________________________________________________________ Submitted by:_____________________________________________________________________ Reference:_________________________________________________________________________
This warranty should be registered on our web-site www.cooperandhunter.us within 60 days of installation. The warranty is only valid when installed by a Licensed HVAC Technician. A warranty period of Seven (7) years on compres­sor to the original registered end-user. A warranty period of Five (5) years on all parts to the original registered end user. Warranty applies only to products remaining in their original installation location.
GENERAL FEA TURES
• Flexible Installation
• Fresh Air Function
• Wired Control & Wi-Fi Connection
• Multi-Channel Air Distribution
INDOOR SPECIFICA TIO N
Sound Preassure level (Hi/Mi/Lo)
Design pressure
Dimension (W*D*H)
Net/Gross weight
OUTDOOR SPECIFICAT ION
Air flow
Noise level
Dimension (W*D*H)
Net/Gross weight
CFM
dB(A)
in
Lbs
CH-48LCDTU/I (INDOOR UNIT) CH-48LCU/O (OUTDOOR UNIT)
PERFORMANCE AND EFFICIENCY
OPERATION TEMPERATURE RA NGE
Indoor Outdoor
cooling
• Built-In Water Pump
• Golden fin for outdoor and indoor
• Lower Noise
• Higher Pipe Limits
• Slim Design
50.5/49.5/46 dB(A)
550/340 PSIG
47x34x12 in
120/142 Lbs
4470
62.5
37.48x16.34x52.48
217.4/246.0
6290 3286
Power supply V/Hz/Ph 208-230V/ 60Hz/ 1Ph
MCA: Minimum Circuit Ampacity; MFA: Max.fuse amps; RLA: Rated load amps
MCA A 35 MFA A 50
Input RLA
Input RLA
Capacity Input RLA A 23.5
Cooling
Capacity SEER EER
Input 5215
Capacity COP HSPF4 HSPF5
heating
EL ECTRICA L
Indoor fan motor
W 560
A 2.0
Outdoor fan motor
W 126
A 1.2
Compressor
Btu/h 44697
W 3420
PI PIN G
Btu/h
Btu
W
Heating at 47F
Btu/h
W/W
cooling heating
5122 586
48000
17.4
9.2
49500
3.52
10.3
8.8
Refrigerant Type
Refrigerant precharge
Additional charge for each ft
ft
oz
R410/148.2
25
0.32
Refrigerant piping/Gas side in (3/8"5/8")
Max. pipe length ft 213
Max. difference in level ft 98
CH-48LCDTU/I (INDOOR UNIT)
Duct Light Commercial Series
Duct Air Conditioners
47 12 34 31.5 8.9 41.1 11 43.3 48.8 4321748K
CH-48LCU/O (OUTDOOR UNIT)
Cooper&Hunter products are subject to continuous improvements. Cooper&Hunter reserves the right to modify product design,
specifications and information in this data sheet without notice and without incurring any obligations.