Duct Light Commercial Series
Duct Air Conditioners
Submittal Data Sheet
Job Name:_________________________________________________________________________
Location:______________________________________________________ __________________
Engineer:____________________________________________________ _ _________________
Submitted to:_____________________________________________________________________
Submitted by:_____________________________________________________________________
Reference:_________________________________________________________________________
This warranty should be registered on our web-site www.cooperandhunter.us
within 60 days of installation. The warranty is only valid when installed by
a Licensed HVAC Technician. A warranty period of Seven (7) years on compressor to the original registered end-user. A warranty period of Five (5) years on all
parts to the original registered end user. Warranty applies only to products
remaining in their original installation location.
GENERAL FEA TURES
• Flexible Installation
• Fresh Air Function
• Wired Control & Wi-Fi Connection
• Multi-Channel Air Distribution
INDOOR SPECIFICA TIO N
Sound Preassure level (Hi/Mi/Lo)
Design pressure
Dimension (W*D*H)
Net/Gross weight
OUTDOOR SPECIFICAT ION
Air flow
Noise level
Dimension (W*D*H)
Net/Gross weight
CFM
dB(A)
in
Lbs
CH-36LCDTU/I (INDOOR UNIT) CH-36LCU/O (OUTDOOR UNIT)
Date:______________________________________________________________________________
Approval:__________________________________________________________________________
Сonstruction:______________________________________________________________________
Unit #:_____________________________________________________________________________
Drawing #:_________________________________________________________________________
PERFORMANCE
AND
EFFICIENCY
OPERATION TEMPERATURE RA NGE
Indoor Outdoor
cooling
• Built-In Water Pump
• Golden fin for outdoor and indoor
• Lower Noise
• Higher Pipe Limits
• Slim Design
45.5/42/38.5 dB(A)
550/340 PSIG
54x30x10 in
106/122 Lbs
2530
66.0
37.24x16.14x31.89
148.59/160.94
62〜90 ℉ 32〜86 ℉
Power supply V/Hz/Ph 208-230V/ 60Hz/ 1Ph
MCA: Minimum Circuit Ampacity; MFA: Max.fuse amps; RLA: Rated load amps
MCA A 30
MFA A 50
Input
RLA
Input
RLA
Capacity
Input
RLA A 22.0
Cooling
Capacity
SEER
EER
Input 4000
Capacity
COP
HSPF4
HSPF5
heating
EL ECTRICA L
Indoor fan motor
W 250
A 1.6
Outdoor fan motor
W 150
A 1.0
Compressor
Btu/h 32380
W 2600
PI PIN G
Btu/h
Btu
W
Heating at 47F
Btu/h
W/W
cooling heating
5〜122 ℉ 5〜86 ℉
36000
16.5
9.0
40000
3.37
11.5
10.0
Refrigerant Type
Refrigerant precharge
Additional charge for each ft
ft
oz
R410/108
25
0.32
Refrigerant piping/Gas side in (3/8"5/8")
Max. pipe length ft 213
Max. difference in level ft 98
CH-36LCDTU/I (INDOOR UNIT)
Duct Light Commercial Series
Duct Air Conditioners
4736K 10 30 27.6 6.9 46.7 8.9 49.6 55.1 23.5
CH-36LCU/O (OUTDOOR UNIT)
Cooper&Hunter products are subject to continuous improvements. Cooper&Hunter reserves the right to modify product design,
specifications and information in this data sheet without notice and without incurring any obligations.