Cooper&Hunter CH24LCOU Specifications

Duct Light Commercial Series
Duct Air Conditioners
Submittal Data Sheet
Job Name:_________________________________________________________________________ Location:______________________________________________________ __________________ Engineer:____________________________________________________ _ _________________ Submitted to:_____________________________________________________________________ Submitted by:_____________________________________________________________________ Reference:_________________________________________________________________________
This warranty should be registered on our web-site www.cooperandhunter.us within 60 days of installation. The warranty is only valid when installed by a Licensed HVAC Technician. A warranty period of Seven (7) years on compres­sor to the original registered end-user. A warranty period of Five (5) years on all parts to the original registered end user. Warranty applies only to products remaining in their original installation location.
GENERAL FEA TURES
• Flexible Installation
• Fresh Air Function
• Wired Control & Wi-Fi Connection
• Multi-Channel Air Distribution
INDOOR SPECIFICA TIO N
Sound Preassure level (Hi/Mi/Lo)
Design pressure
Dimension (W*D*H)
Net/Gross weight
OUTDOOR SPECIFICAT ION
Air flow
Noise level
Dimension (W*D*H)
Net/Gross weight
CFM
dB(A)
in
Lbs
CH-24LCDTU/I (INDOOR UNIT) CH-24LCU/O (OUTDOOR UNIT)
PERFORMANCE AND EFFICIENCY
OPERATION TEMPERATURE RA NGE
Indoor Outdoor
cooling
• Built-In Water Pump
• Golden fin for outdoor and indoor
• Lower Noise
• Higher Pipe Limits
• Slim Design
44/41/34 dB(A)
550/340 PSIG
43x30x10 in
87/103 Lbs
2354
61.0
37.24x16.14x31.89
135.58/148.81
6290 3286
Power supply V/Hz/Ph 208-230V/ 60Hz/ 1Ph
MCA: Minimum Circuit Ampacity; MFA: Max.fuse amps; RLA: Rated load amps
MCA A 20 MFA A 30
Input RLA
Input RLA
Capacity Input RLA A 14.0
Cooling
Capacity SEER EER
Input 1920
Capacity COP HSPF4 HSPF5
heating
EL ECTRICA L
Indoor fan motor
W 90
A 1.5
Outdoor fan motor
W 150
A 0.5
Compressor
Btu/h 24345
W 1970
PI PIN G
Btu/h
Btu
W
Heating at 47F
Btu/h
W/W
cooling heating
-22122 -2286
24000
20.5
12.5
24000
3.81
12.5
10.6
Refrigerant Type
Refrigerant precharge
Additional charge for each ft
ft
oz
R410/91.7
25
0.32
Refrigerant piping/Gas side in (3/8"5/8")
Max. pipe length ft 164
Max. difference in level ft 82
CH-24LCDTU/I (INDOOR UNIT)
Duct Light Commercial Series
Duct Air Conditioners
43 10 30 27.6 6.9 36.5 8.9 39.4 44.9 23.5
CH-24LCU/O (OUTDOOR UNIT)
Cooper&Hunter products are subject to continuous improvements. Cooper&Hunter reserves the right to modify product design,
specifications and information in this data sheet without notice and without incurring any obligations.