Cooper&Hunter CH24KRL230V Installation Manual

Page 1
KAROLINA
HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM
INSTALLATION
Models: CH09KRL230VI/CH09KRL230VO (230V) CH1
KRL230VI/CH12KRL230VO (230V)
CH1
KRL230VI/CH18KRL230VO (230V)
CH
24
KRL230VI/CH24KRL230VO (230V)
MANUAL
Page 2
CH09KRL230VI/CH09KRL230VO System Includes: CH09KRL230VI, CH09KRL230VO
CH12KRL230VI/CH12KRL230VO System Includes: CH12KRL230VI, CH12KRL230VO
CH18KRL230VI/CH18KRL230VO System Includes: CH18KRL230VI, CH18KRL230VO
CH24KRL230VI/CH24KRL230VO System Includes: CH24KRL230VI, CH24KRL230VO
Page 3
Content
Installation Notice
Precautions ...........................................................................................................1
System Requirements Piping Requirements . . .........................................................9
Installation dimension diagram . . .........................................................................10
Tools for installation . ...........................................................................................11
Selection of installation location .. .......................................................................11
Requirements for electric connection . .................................................................12
Installation
Installation of indoor unit. . ...................................................................................13
Installation of outdoor unit . ................................................................................18
Vacuum pumping ...............................................................................................21
Leakage detection ..............................................................................................21
Check after installation .......................................................................................22
Test and operation
Test operation . ..................................................................................................22
Attachment
Configuration of connection pipe . ....................................................................23
Pipe expanding method .....................................................................................25
Start-Up and troubleshooting . ............................................................................26
Page 4
Explanation of Symbols
DANGER
WARNING
CAUTION
N OTIC E
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, may result in minor or moderate injury.
Indicates important but not hazard-related information, used to indicate risk of property damage.
Indicates a hazard that would be assigned a signal word WARNING or CAUTION.
Page 5
Precautions
WARNING
Operation and Maintenance
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision. Do not connect air conditioner to multi-purpose socket.
Otherwise, it may cause fire hazard. Do disconnect power supply when cleaning air
conditioner. Otherwise, it may cause electric shock. If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Do not wash the air conditioner with water to avoid electric shock. Do not spray water on indoor unit. It may cause electric shock or malfunction.
After removing the filter, do not touch fins to avoid injury. Do not use fire or hair dryer to dry the filter to avoid
deformation or fire hazard.
1
Page 6
Precautions
WARNING
Maintenance must be performed by qualified professionals. Otherwise, it may cause personal injury
or damage. Do not repair air conditioner by yourself. It may cause
electric shock or damage. Please contact dealer when you need to repair air conditioner.
Do not extend fingers or objects into air inlet or air outlet. It may cause personal injury or damage.
Do not block air outlet or air inlet. It may cause malfunction.
Do not spill water on the remote controller, otherwise the remote controller may be broken. When below phenomenon occurs, please turn off air conditioner and disconnect power immediately, and then contact the dealer or qualified professionals for service.
Power cord is overheating or damaged.
There’s abnormal sound during operation.
Circuit break trips off frequently.
Air conditioner gives off burning smell.
Indoor unit is leaking.
If the air conditioner operates under abnormal conditions, it may cause malfunction, electric shock or fire hazard.
When turning on or turning off the unit by emergency operation switch, please press this switch with an insulating object other than metal.
Do not step on top panel of outdoor unit, or put heavy objects. It may cause damage or personal injury.
2
Page 7
Precautions
WARNING
Attachment
Installation must be performed by qualified professionals. Otherwise, it may cause personal injury or damage.
Must follow the electric safety regulations when installing the unit.
According to the local safety regulations, use qualified power supply circuit and circuit break.
Do install the circuit break. If not, it may cause malfunction. An all-pole disconnection switch having a contact separation
of at least 3mm in all poles should be connected in fixed wiring.
Including an circuit break with suitable capacity, please note magnet buckle
the circuit-short and
the following table.Air switch should be included
and heating buckle function, it can protect
overload.
Air Conditioner should be properly grounded. Incorrect grounding may cause electric shock.
Don't use unqualified power cord. Make sure the power supply matches with the
requirement of air conditioner. Unstable power supply or incorrect wiring or malfunction. Please install proper power supply cables before using the air conditioner.
Properly connect the live wire, neutral wire and grounding wire of power socket.
Be sure to cut off the power supply before proceeding any work related to electricity and safety.
3
Page 8
Precautions
WARNING
Do not put through the power before finishing installation. If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
The appliance shall be installed in accordance with national wiring regulations.
Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.
The air conditioner is the first class electric appliance. It must be properly grounding with specialized grounding device by a professional. Please make sure it is always grounded effectively, otherwise it may cause electric shock.
The yellow-green wire in air conditioner is grounding wire, which can't be used for other purposes.
The grounding resistance should comply with national electric safety regulations.
The appliance must be positioned so that the plug is accessible.
All wires of indoor unit and outdoor unit should be connected by a professional.
If the length of power connection wire is insufficient, please contact the supplier for a new one. Avoid extending the wire by yourself.
4
Page 9
Precautions
WARNING
For the air conditioner with plug, the plug should be reachable after finishing installation.
For the air conditioner without plug, an circuit break must be installed in the line.
If you need to relocate the air conditioner to another place, only the qualified person can perform the work. Otherwise, it may cause personal injury or damage.
Select a location which is out of reach for children and far away from animals or plants. If it is unavoidable, please add the fence for safety purpose.
The indoor unit should be installed close to the wall.
Instructions for installation and use of this product are provided by the manufacturer.
FCC WARNING
WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
FCC STATEMENT
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions :
5
Page 10
Precautions
FCC STATEMENT
(1) this device may not cause harmful interference, and (2) this device must accept any interference received,including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.
6
Page 11
Precautions
IC STATEMENT
This device complies with Industry Canada licence­exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
This equipment complies with FCC’s and IC’s RF radiation exposure limits set forth for an uncontrolled environment. The antenna(s) used for this transmitter must be installed and operated to provide a separation distance of at least 7.9in from all persons and must
not be collocated or operating in conjunction with any other antenna or transmitter. Installers must ensure that 20cm separation distance will be maintained between the device (excluding its handset) and users.
Cet appareil est conforme aux limites d’exposition au rayonnement RF stipulées par la FCC et l’IC pour une utilisation dans un environnement non contrôlé. Les
7
Page 12
Precautions
IC STATEMENT
antennes utilisées pour cet émetteur doivent être installées et doivent fonctionner à au moins 7.9in
de
distance des utilisateurs et ne doivent pas être placées près d’autres antennes ou émetteurs ou fonctionner
avec ceux-ci. Les installateurs doivent s’assurer qu’une
distance de 20 cm sépare l’appareil (à l’exception du combiné) des utilisateurs.
Working temperature range
Indoor side DB/WB Maximum cooling 80/66.9(26.7/19.4) 115/75(46.1/23.9) Maximum heating 80/-(26.7/-) 75/64.9(23.9/18.3)
NOTICE:
The operating temperature range (outdoor temperature) for cooling only unit is
-0.4°F(-18°C)~115°F(46.1°C)for heat pump unit is -4°F(-20°C)~115°F(46.1°C)
* Cooper&Hunter is constantly working to improve their products, so the information in this manual is subject to change without prior notice.
(°F/°C)
Outdoor side DB/WB
(°F/°C)
8
Page 13
System Requirements
Piping Requirements
PIPE SIZE in (mm)
Unit Size
(BtuH)
9,000 208/230v - 1ph 60hz 1/4 (6) 3/8 (9.5) 12,000 208/230v - 1ph 60hz 1/4 (6) 3/8 (9.5) 18,000 208/230v - 1ph 60hz 1/4 (6) 1/2 (12) 24,000 208/230v - 1ph 60hz 1/4 (6) 1/2 (12)
REFRIGERANT LINE LENGTHS ft (m)
Unit Size
(BtuH) Length Length (ID over OD)
9,000 208/230v - 1ph 60hz 10 (3) 50 (15) 33 (10) 12,000 208/230v - 1ph 60hz 10 (3) 50 (15) 33 (10)
18,000 208/230v - 1ph 60hz 10 (3) 82 (25) 33 (10)
24,000 208/230v - 1ph 60hz 10 (3) 82 (25) 33 (10)
Notes: Insulate both refrigerant lines, separately.
Voltage
REFRIGERANT CHARGE
Unit Size
(BtuH) Type Charge oz (kg)* Charge oz/ft (g/m)
Voltage
Vol tage
Min Line Max Line Max Elevation
Refrigerant Factory System Additional
Liquid Line Suction/Gas Line
9,000 208/230v - 1ph 60hz R410A 26.1 (0.74) 0.2 (20) 12,000 208/230v - 1ph 60hz R410A 35.3 (1.0) 0.2 (20) 18,000 208/230v - 1ph 60hz R410A 45.9 (1.3) 0.2 (20) 24,000 208/230v - 1ph 60hz R410A 54.7 (1.6) 0.2 (20)
*Precharge amount for up to 25-ft of refrigerant pipe.
ELECTRICAL REQUIREMENTS
Unit Size
(BtuH) Amps (MCA) Protection (MOP) Wire Size (AWG)**
9,000 208/230v - 1ph 60hz 10 12,000 208/230v - 1ph 60hz 10 18,000 208/230v - 1ph 60hz 15 25 24,000 208/230v - 1ph 60hz
**Main power wire from electrical panel to outdoor unit.
Notes: 1) System must be on a single dedicated circuit.
2) Main power is supplied to the outdoor unit.
3) Use table above to size over current protection.
4) Follow all local building codes and NEC (National Electrical Code) regulations.
Recommended cable - 16/4 AWG stranded bare copper conductorsTHHN 600V unshielded wire
Note: Use shield cable if installation is in close proximity of RF and EMI transmitting devices. Condensate Drain Size: 5/8-in OD 7/16-in ID
prevent sweating and possible water damage.
Voltage
Min Circuit Max Overcurrent Main Power
1
6
1
6
1
7
Note: Insulate condensate drain hose to
2
5
Interconnecting Cable:
9
1
6
1
6
1
4
1
2
Page 14
Installation dimension diagram
in (0,15m) 6
Space to the ceiling
6in (0,15m)
Space to the wall
Space to the wall
6in (0,15m)
12in (0,3m)
Space to the wall
(3m)
115in
Space to the obstruction
Space to the
obstruction
Space to the obstruction
20in (0,5m)
12in
(0,3m)
m)
5
ft (2,
.2
8
78.7in (2m)
Space to the obstruction
10
Drainage pipe
19.7in (0,5m)
Space to the
obstruction
Page 15
Tools for installation
1 Level meter 2 Screw driver 3 Impact drill
4 Drill head 5 Pipe expander 6 Torque wrench
7 Open-end wrench 8 Pipe cutter 9 Leakage detector
10 Vacuum pump 11 Pressure meter 12 Universal meter
13 Inner hexagon spanner 14 Measuring tape
Note:
● Please contact the local agent for installation.
Selection of installation location
Basic requirement
Installing the unit in the following pla­ces maycause malfunction. If it is un­avoidable, please consult the local dealer:
1.The place with strong heat sources,
or volatile objects spread in the air.
2.The place with high-frequency devices (such as welding machine, medical equipment).
3.The place near coast area.
4.
The place with oil or fumes in the air.
5.The place with sulfureted gas.
6.Other places with special circums­ tances.
7.The appliance shall not be install­ ed in the laundry.
,
Indoor unit
1. There should be no obstruction near air inlet and air outlet.
2. Select a location where the condensat­ ion water can be dispersed easily and won't affect other people.
3. Select a location which is convenient to connect the outdoor unit and near the power socket.
4. Select a location which is out of reach for children.
5.
The location should be able to withstand the weight of indoor unit and won't incr­ ease noise and vibration.
6.
The appliance must be installed 98,4in (2.5m) above floor.
7. Don't install the indoor unit right above the electric appliance.
8. Please try your best to keep way from fluorescent lamp.
11
Page 16
Requirements for electric connection
Safety precaution
1. Must follow the electric safety regulations when installing the unit.
air switch.
3. Make sure the power supply matches with the requirement of air conditioner. Unstable power supply or incorrect wiring or malfunction. Please install proper power supply cables before using the air conditioner.
4. Properly connect the live wire, neutral wire and grounding wire of power socket.
5. Be sure to cut off the power supply before proceeding any work related to electricity and safety.
7. If the supply cord is damaged, it must be replaced by the manufacturer, its
8. The temperature of refrigerant circuit will be high, please keep the interconnec­ tion cable away from the copper tube.
9. The appliance shall be installed in accordance with national wiring regulations.
Grounding requirement
grounding with specialized grounding device by a professional. Please make sure it is always grounded effectively, otherwise it may cause electric shock.
2. The yellow-green wire in air conditioner is grounding wire, which can't be used for other purposes.
3. The grounding resistance should comply with national electric safety regulations.
4. The appliance must be positioned so that the plug is accessible.
5. An all-pole disconnection switch having a contact separation of at least 3mm in
6. Including an air switch with suitable capacity, please note the following table. Air switch should be included magnet buckle and heating buckle function, it can protect the circuit-short and overload. (Caution: please do not use the fuse only for protect the circuit)
12
Page 17
Installation of indoor unit
Step one: choosing installation location
rm it with the client.
Step two: install wall-mounting frame
1. Hang the wall-mounting frame on the wall; adjust it in horizontal position with the
expansion particles in the holes.
3. Fix the wall-mounting frame on the wall with tapping screws (ST4.2X25TA) and
Step three: open piping hole
1. Choose the position of piping hole according to the direction of outlet pipe. The position of piping hole should be a little lower than the wall-mounted frame, shown as below.
0912K:
Wall
Mark in the middle of it
Space to the wall 5,9in (0,15m) above
Left
1
Φ2 (55mm)
4
Rear piping hole
Level meter
Wall
Space to the wall 5,9in (0,15m) above
Right
1
Φ2 (55mm)
4
Rear piping hole
18K
Wall
Space
to the wall 5,9in (0,15m) above
Left
Φ
2.6󰿔(
70mm
Rear piping hole
Mark in the middle of it
)
Level meter
Space to the wall 5,9in (0,15m) above
Right
Φ
2.6󰿔(
Rear piping hole
Wall
70mm
)
24K:
Wall
Space to the wall 5,9in (0,15m) above
Left
Φ
2.6󰿔(
70mm
)
Rear piping hole
Mark in the middle of it
Level meter
Space to the wall 5,9in (0,15m) above
Right
Φ
2.6󰿔(
Rear piping hole
Wall
70mm
)
2. Open a piping hole with the diameter of Φ55/Φ70 on the selected outlet pipe position. In order to drain smoothly, slant the piping hole on the wall slightly downward to the outdoor side with the gradient of 5-10°.
13
Page 18
Installation of indoor unit
Note:
● Pay attention to dust prevention and take relevant safety measures when
opening the hole.
The plastic expansion particles are not provided and should be bought
locally.
Step four: outlet pipe
1. The pipe can be led out in the direction of right, rear right, left or rear left.
left
rear right
right
rear left
Indoor
5-10
outdoor
1
4
Φ2 (55)/
Φ
2.6󰿔(
70mm
2. When select leading out the pipe from left or right, please cut off the corresponding hole on the bottom case.
left
right
cut off the hole
)
1. Aim the pipe joint at the corresponding bellmouth.
union nutpipe joint
pipe
2. Pretightening the union nut with hand.
3. Adjust the torque force by referring to the following sheet. Place the open-end wrench on the pipe joint and place the torque wrench on the union nut. Tighten the union nut with torque wrench.
14
Page 19
Installation of indoor unit
Tightening torque (N.m)
15~20 30~40
45~55 60~65 70~75
torque wrench
indoor pipe
open-end wrench
union nut
pipe
Hex nut diameter
1
Φ
4
3
Φ
8
1
Φ
2
5
Φ
8
3
Φ
4
4. Wrap the indoor pipe and joint of con­ nection pipe with insulating pipe, and then wrap it with tape.
insulating pipe
Note:
If a 18k indoor unit is to be connected with Free Match outdoor unit, a transitional pipe joint (provided) should be added at the pipe joint of indoor unit evaporator
assy as the pipe joint of evaporator assy adopts pipe diameter of Φ16. Please
refer to step 1-4 during installation.
Step six: install drain hose
1. Connect the drain hose to the outlet pipe of
indoor unit.
2. Bind the joint with tape.
outlet pipe
drain hose
tape
Note:
Add insulating pipe in the indoor
drain hose in order to prevent condensation.
The plastic expansion particles are
not provided.
Step seven: connect wire of indoor unit
1. Open the panel, remove the screw on the wiring cover and then take down the cover.
15
panel
outlet
pipe
drain hose
insulating pipe
screw
wiring cover
drain hose
Page 20
Installation of indoor unit
2. Make the power connection wire go through the cable-cross hole at the back of indoor unit and then pull it out from the front side.
3. Remove the wire clip; connect the powe connection wire to the wiring terminal according to the color; tighten the screw
with wire clip.
cable-cross hole
power connection wire
18K (230V):
r
For some models with power
18K BTU wall-mounted type
L
1 S
N(1) 2
Outdoor unit connection
G
L
2
L1 L2 G
3
GND
Wiring cover
09K,12K: (230V)
N(1) 2
N(1)
L1
3
3
2
L
2
Outdoor unit connection
G
GND
GND
G
18K, 24K: (230V)
N(1) 2
N(1) 2
Outdoor unit connection
3
G
3
GND
GND
4. Put wiring cover back and then tighten the screw.
5. Close the panel.
Notice before installation
1. How to install the over line pipe (According to the direction as show.)
Screw
wire pipe
Fixed nut
Note:
All wires of indoor unit and outdoor unit should be connected by a professional.
2. Finish (According to the direction as show in right figure.)
for a new one. Avoid extending the wire by yourself.
installation.
For the air conditioner without plug, an air switch must be installed in the line. The air switch should be all-pole parting and the contact parting distance should be more than 0.12in (3mm).
16
Page 21
Installation of indoor unit
drain hose
Step eight: bind up pipe
1. Bind up the connection pipe, power cord and drain hose with the band.
indoor unit
indoor and
outdoor power cord gas pipe
band
liquid pipe
drain hose
2. Reserve a certain length of drain hose and power cord for installation when binding them. When binding to a certain degree, separate the indoor power and then separate the drain hose.
Step nine: hang the indoor unit
1. Put the bound pipes in the wall pipe and then make them pass through the wall hole.
2. Hang the indoor unit on the wall-mounting frame.
3. Stuff the gap between pipes and wall hole with sealing gum.
4. Fix the wall pipe.
5. Check if the indoor unit is installed firmly and closed to the wall.
indoor
outdoor
connection pipe
indoor power cord
band
3. Bind them evenly.
4. The liquid pipe and gas pipe should be bound separately at the end.
Note:
The power cord and control wire can't be crossed or winding.
The drain hose should be bound at the bottom.
upper hook
wall pipe
sealing gum
lower hook of wall-mounting frame
Note:
● Do not bend the drain hose too excessively in order to prevent blocking.
17
Page 22
Installation of outdoor unit
foot holes
(select it according to the actual installation situation)
1. Select installation location according to the house structure.
2. Fix the support of outdoor unit on the selected location with expansion screws.
Note:
installing the outdoor unit.
Make sure the support can withstand at least
four times of the unit weight.
The outdoor unit should be installed at least
1.2in(3cm) above the floor in order to install drain joint.
● For the unit with cooling capacity of 2300W ~5000W, 6 expansion screws are needed; for the unit with cooling capacity of 6000W ~8000W, 8 expansion screws are needed; for the unit with cooling capacity of 10000W ~16000W, 10 expansion screws are needed.
Step two: install drain joint
gnitaehdnagniloocrof ylnO(
unit)
1. Connect the outdoor drain joint into the hole on the chassis, as shown in the picture below.
2. Connect the drain hose into the drain vent.
at least 1.18in (3cm) above
floor
the
1. Place the outdoor unit on the support.
2. Fix the foot holes of outdoor unit with bolts.
drain vent
Drain hose
chassis
outdoor drain joint
foot holes
18
Page 23
Installation of outdoor unit
Step four: connect indoor and outdoor pipes
1. Remove the screw on the right han­ dle of outdoor unit and then remove the handle.
screw
handle
2. Remove the screw cap of valve and aim the pipe joint at the bellmouth of pipe.
liquid pipe
liquid valve
gas pipe
gas valve
3. Pretightening the union nut with hand.
pipe joint
yellogreen
union nut
4. Tighten the union nut with torque wrench by referring to the sheet below.
Hex nut diameter
1
Φ
4
3
Φ
8
1
Φ
2
5
Φ
8
3
Φ
4
Tight enin g
torque (N.m)
15~20
30~40
45~55 60~65 70~75
1. Remove the wire clip; connect the po-
wer connection wire and signal control
wire (only for cooling and heating unit) to the wiring terminal according to the
GND
L2
L1
Indoor unit connection
For some models with power
18K BTU wall-mounted type
2 3 L1
S L2L1
L2N(1)
G
handle
for 9k12k models
N(1)
L1 L2
N(1)
Indoor unit connection
for 18K24K models
Indoor unit connection
2 3
2 3
2 3 L1
2 3N(1)
GND
GND
GND
L2 GN(1)
GND
GND
POWER
GND
L2 L1
19
G
GND
L2
POWER
L1
SUPPLY
GND
Page 24
Installation of outdoor unit
2. Fix the power connection wire and signal control wire with wire clip (only for cooling and heating unit).
Note:
● Never cut the power connection wire to prolong or shorten the distance.
Step six: neaten the pipes
1. The pipes should be placed along the wall, bent reasonably and hidden possibly. Min. semidiameter of bending the pipe is 3.9in (10cm).
2. If the outdoor unit is higher than the wall hole, you must set a U-shaped curve in the pipe before pipe goes into the room, in order to prevent rain from getting into the room.
U-shaped curve
drain hose
wall
20
Page 25
Vacuum pumping
Use vacuum pump
1. Remove the valve caps on the liquid valve and gas valve and the nut of refri­ gerant charging vent.
2. Connect the charging hose of piezometer to the refri­ gerant charging vent of gas valve and then connect the other charging hose to the vacuum pump.
3. Open the piezometer com­ pletely and operate for 10-15min to check if the pressure of piezometer re­ mains in -0.1MPa.
4. Close the vacuum pump and maintain this status for 1-2min to check if the pres­ sure of piezometer remains in -0.1MPa. If the pressure decreases, there may be leakage.
5. Remove the piezometer, open the valve core of liquid valve and gas valve completely with inner hexagon spanner.
6. Tighten the screw caps of valves and refrigerant charging vent.
liquid valve
gas valve
refrigerant charging vent
nut of refrigerant charging vent
piezometer
valve cap
vacuum pump
inner hexagon
spanner
close
open
Lo Hi
Leakage detection
1. With leakage detector: Check if there is leakage with leakage detector.
2. With soap water: If leakage detector is not available, please use soap water for leakage detection. Apply soap water at the suspected position and keep the soap water for more than 3min. If there are air bubbles coming out of this position, there's a leakage.
21
Page 26
Check after installation
Items to be checked Possible malfunction
The unit may drop, shake or emit noise.
Have you done the refrigerant leakage test? (heating) capacity.
It may cause condensation and water dripping.
Is water drained well?
It may cause condensation and water dripping.
Is the voltage of power supply accord­ing to the voltage marked on the nameplate?
Is electric wiring and pipeline installed correctly?
Is the unit grounded securely? It may cause electric leakage.
Does the power cord follow the speci-
Is there any obstruction in the air inlet and outlet? (heating) capacity.
The dust and sundries caused during installation are removed?
The gas valve and liquid valve of connection pipe are open completely?
Is the inlet and outlet of piping hole been covered?
It may cause malfunction or damaging the parts.
It may cause malfunction or damaging the parts.
It may cause malfunction or damaging the parts.
It may cause malfunction or damaging the parts.
(heating) capacit
It may cause insufficient cooling (heating) capacity or waster eletricity.
y.
Test operation
1. Preparation of test operation
The client approves the air conditioner.
● Specify the important notes for air conditioner to the client.
2. Method of test operation
● Put through the power, press ON/OFF button on the remote controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 61°F(16°C), the air conditioner can’t start cooling.
22
Page 27
Configuration of connection pipe
1. Standard length of connection pipe
● 16,5ft (5m), 25ft (7.5m), 26,5ft (8m).
2.Min. length of connection pipe is 9,8ft (3m).
3.Max. length of connection pipe and max. high difference.
Cooling
capacity
5000Btu/h
(1465W)
7000Btu/h
(2051W)
9000Btu/h
(2637W)
12000Btu/h
(3516W)
18000Btu/h
(5274W)
4. The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 32.8ft (10m) at the basis of standard length, you should add 5ml of refrigerant oil for each additional 16,5ft(5m)
of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe × additional refrigerant charging amount per meter
Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See the
following sheet.
Max length of connec­tion pipe
50ft (15) 83,3ft (25) 16,5ft (5) 33,3ft (10)
50ft (15) 100ft (30)16,5ft (5) 33,3ft (10)
50ft (15) 100ft (30)16,5ft (5) 66,5ft (20)
66,5ft (20) 100ft (30)33,3ft (10) 66,5ft (20)
83,3ft (25) 100ft (30)33,3ft (10) 66,5ft (20)
Max height difference
Cooling
capacity
24000Btu/h
(7032W)
28000Btu/h
(8204W)
36000Btu/h
(10548W)
42000Btu/h
(12306W)
48000Btu/h
(14064W)
Max length of connec­tion pipe
Max height difference
23
Page 28
Additional refrigerant charging amount for R410A
Diameter of connection pipe
Liquid pipe(in) Gas pipe(in)
Φ1/4
Φ1/4 or Φ3/8
Φ1/2
Φ5/8
Φ3/4
Φ7/8
Φ3/8 or Φ1/2
Φ5/8 or Φ3/4
Φ3/4 or Φ7/8
Φ1 or Φ1
1
/
_
_
4
Outdoor unit throttle
Cooling only(g/m) Cooling and heating(g/m)
15
15
30
60
20
50
120
120
250 250
350350
24
Page 29
Pipe expanding method
pipe
pipe
smooth surface
Note:
Improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe according to the following steps:
A: Cut the pipe
the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
pipe cutter
E: Expand the port
● Expand the port with expander.
hard
expander
mold
pipe
leaning uneven burr
B: Remove the burrs
● Remove the burrs with shaper and
prevent the burrs from getting into the pipe.
shaper
downwards
C: Put on suitable insulating pipe D: Put on the union nut
● Remove the union nut on the indoor
connection pipe and outdoor valve; install the union nut on the pipe.
union pipe
Note:
● "A" is different according to the diameter, please refer to the sheet below:
Outer diameter
(mm)
Φ1/4"
Φ3/8"
Φ1/2"
Φ5/8"
A(mm)
Max Min
1.3 0.7
1.6 1.0
1.8 1.0
2.4 2.2
F: Inspection
● Check the quality of expanding port. If there is any blemish, expand the
port again according to the steps above.
improper expanding
pipe
the length is equal
25
leaning damaged
surface
crack uneven
thickness
Page 30
START-UP AND TROUBLESHOOTING
Explain Following Items To Customer With The Aid Of The Owner’s Manual:
1. How to turn system on and off; selecting COOLING,HEATING and other operating modes;setting a desired temperature; setting the timer to automatically start and stop system operation; and all other features of the Remote Control and display panel.
2. How to remove and clean the air filter.
3. How to set air with the swing louv
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to customer.
Troubleshooting
This unit has onboard diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the temperature display. The table below explains the error codes for both units.
DIAGNOSTIC CODES
ers.
Equipment Fault
Indoor Configuration Jumper
Indoor/Outdoor Mismatch
High Current Protection
Communication Error
Indoor Air Temp. Thermistor
Indoor Coil Temp. Thermistor
Outdoor Air Temp. Thermistor
Outdoor Coil Temp. Thermistor
Compressor Discharge Temp. Thermistor
Compressor Overload Protection
IPM Module Protection
Indoor Fan Malfunction
Compressor Synchronism
4-Way Valve Malfunction
High Pressure Protection
Error Codes
C5
LP
E5
E6
F1
F2
F3
F4
F5
H3
H5
H6
H7
U7
E1
Possible Causes
Missing Configuration Jumper on Indoor Control Board
Indoor and Outdoor Units Do Not Match (Model or Capacity)
Power Supply is not Stable and Voltage Range is too Large
Mis-wired or Communication Failure
Bad Connection, or Indoor Air Sensor Failure
Bad Connection, or Indoor Coil Sensor Failure
Bad Connection, or Outdoor Ambient Sensor Failure
Bad Connection, or Outdoor Coil Sensor Failure
Bad Connection, or Discharge Sensor Failure
Low Refrigerant Charge, Blocked Capillary, or Compressor Motor Failure
IPM Module Temperature Too High, High Ambient, Low Voltage, or Bad Connections
Indoor Fan Stopped or Running too Slow
High Pressure, Low Voltage, or Bad Connections
Bad Connection, Solenoid Failure, or Valve Malfunction. (Heat Pumps Only)
Too much refrigerant or High Ambient conditions or low airflow.
2
6
Page 31
www.cooperandhunter.us
PRODUCT & INSTALLATION RECORD
For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information, along with the installation data and dealer contact information, will be helpful should your system require maintenance or service.
UNIT INFORMATION
Model No.
Serial No.
INSTALLATION INFORMATION
Date Installed:
DEALERSHIP/INSTALLER INFORMATION
Company Name:
Address:
Phone Number:
Technician Name:
Cooper and Hunter © 2016
Page 32
www.cooperandhunter.us
66160000459
Loading...