Cooper&Hunter CH12LCDTUI, CH18LCDTUI, CH09LCDTUI Installation Manual

Page 1
CH-09LCDTU/I CH-12LCDTU/I CH-18LCDTU/I CH-24LCDTU/I
Page 2
Page 3
Table of Contents
Installation Manual
1
Accessories ....................................... 05
2
Safety Precautions . .......................... 06
3
Installation Overview ....................... 07
4
Indoor Unit Installation .................... 08
5
Outdoor Unit Installation . 13
a. Outdoor Unit Installation Instructions . 13
c. Notes on Drilling Hole in Wall . 15
a. Indoor Unit Parts .............................. 08
b. Indoor Unit Installation Instructions ..... 09
6
Drainpipe Installation ....................... 16
Page 4
Refrigerant Piping Connection ....................... 18
7
A. Notes on Pipe Length and Elevation .............. 18
B. Refrigerant Piping Connection Instructions ...20
L N
8
Wiring ................................................. 23
a. Outdoor Unit Wiring .................. 23
b. Indoor Unit Wiring ..................... 24
c. Power Specifications ................... 26
9
Air Evacuation .................................................. 28
a. Evacuation Instructions ................................ 28
b. Note on Adding Refrigerant ....................... 29
MC MC
10
Test Run ............................................. 30
Page 3
Page 5
Accessories
1
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and re, or equipment failure.
Tubing & Fittings
Drainpipe Fittings (for cooling & heating)
EMC Magnetic Ring (some models)
Soundproof / insulation sheath
Seal sponge (some models)
Orice (some models)
Drain joint (some models)
Seal ring (some models)
Magnetic ring (wrap the electric wires S1 & S2 ( P & Q & E ) around the magnetic ring twice)
Magnetic ring (Hitch on the connective cable between the indoor unit and outdoor unit after installation.)
Owner‘s manual
Installation manual
SHAPENAME
S1&S2(P&Q&E)
QUANTITY
2
1
1
1
1
1
1
1
1
Others
Wireless remote control manual
Wired remote control manual
Connecting wire for display (2m)
Display panel *Just for testing purposes only
1(on some models)
1(on some models­KJR-120G,KJR-120H)
Optional accessories
There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller.
1
1
Page 5
Page 6
Safety Precautions
Failure to observe a caution may result in injury or equipment damage.
2
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury.
The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
Failure to observe a warning may result in death. The product must be installed by
WARNING
CAUTION
WARNING
installers or contractors who are licensed HVAC professionals and in compliance with all local, state and provincial laws.
• Carefully read the Safety Precautions before installation.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially
designed air-conditioning units is highly recommended.
• Only trained and certified technicians should install, repair and service this air conditioning unit.
Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment and personal property.
• Strictly follow the installation instructions set forth in this manual.
Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment.
Before you install the unit, consider strong winds, typhoons and earthquakes that might aect your unit and locate it accordingly. Failure to do so could cause the equipment to fail.
After installation, ensure there are no refrigerant leaks and that the unit is operating properly. Refrigerant is both toxic and flammable and poses a serious health and safety risk.
Note about Fluorinated Gases
This air-conditioning unit contains fluorinated gases. For specific information on the type of gas
1. and the amount, please refer to the relevant label on the unit itself.
2.
Installation, service, maintenance and repair of this unit must be performed by a certified technician. Product uninstallation and recycling must be performed by a certified technician.
3.
4.
If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
Page 6
Page 7
Installation Overview
L N
INSTALLATION ORDER
Unit Installation
Overview
3
1
Install the indoor unit
(Page 8)
6
MC MC
2
Install the outdoor unit
(Page 13)
5
3
Install the drainpipe
(Page 15)
4
Evacuate the refrigeration system
(Page 28)
7
Perform a test run
(Page 30)
Connect the wires
(Page 23)
Connect the refrigerant pipes
(Page 18)
Page 7
Page 8
Indoor Unit
Installation
Indoor Unit Parts
Indoor Unit Installation
4
Air inlet
Electric control cabinet
Air filter(on selected models)
Air outlet
Fig. 4.1
Safety Precautions
WARNING
Securely install the indoor unit on a structure
that can sustain its weight. If the structure is too weak, the unit may fall causing personal injury, unit and property damage, or even death
DO NOT install the indoor unit in a bathroom
or laundry room as excessive moisture can short the unit and corrode the wiring.
Indoor Unit Installation Instructions
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following requirements:
Enough room for installation and maintenance.
Enough room for the connecting pipe and
drainpipe.
The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
The air inlet and outlet are not impeded.
The airflow can fill the entire room.
There is no direct radiation from heaters.
It is embeded installation.
Drain hose
Refrigerant connecting pipe
CAUTION
Install the indoor and outdoor units, cables and wires at least 1m (3.2’) from televisions or radios to prevent static or image distortion. Depending on the appliances, a 1m (3.2’) distance may not be sufficient.
If the indoor unit is installed on a metal part of the building, it must be grounded.
CAUTION
DO NOT install the unit in the following
locations:
Where oil drilling or fracking is taking place.
Coastal areas with high salt content in the air
Near geothermal activity and corrosive gas
Buildings that may experience power
Enclosed spaces
Areas with strong electromagnetic waves
Areas that store ammable materials or gas
Rooms with high humidity, such as
uctuations
bathrooms or laundry rooms
Page 8
Page 9
Installation place
Strong and durable ceiling
Left side
Indoor unit
Right side
>0.8in(2cm)
B
>0.8in(2cm)
>11.8in(30cm)
Indoor Unit
Installation
>4in(10cm) >11.8in(30cm)
Maintenance space
> (20cm)
7.9
in
Air outlet
Service access Ceiling
Floor
> (30cm)
11.8in
(When no ceiling)
> 8.2in(250cm)
Air inlet
23.6inx23.6in (60cmx60cm) checking orifice
Fig. 4.2
Step 2: Hang indoor unit.
1. Please refer to the following diagrams to locate the four positioning screw bolt holes on the ceiling. Be sure to mark the paces where you will drill ceiling hook holes.
Air outlet dimensions
Page 9
Page 10
Indoor Unit
Installation
Air inlet dimensions
Air lter
Descending ventilation opening and mounted hook
Air lter
Electric control box
Fig. 4.3
Table.4-1 (unit: inch/mm)
MODEL
(Btu/h)
9K/12K
18K
24K
30K~36K
36K~60K
A B C
Outline dimension
7.9/200 19.9/50627.6/700
8.3/210 26.5/67434.6/880 5.4/136 27.8/70623.6/600
9.8/249 30.5/77443.3/1100 6.9/175 36.5/92627.6/700
9.8/249 30.5/77453.5/1360
11.8/300 34.4/87447.2/1200
Wood
Place the wood mounting across the roof beam,
air outlet opening size
D E F
6/152 21.1/53717.7/450 7.3/186 29.2/74123.6/599
6.9/175 46.7/118627.6/700
8.9/227 41.1/104431.5/800
New concrete bricks
Inlay or embed the screw bolts. (See Fig. 4.5)
air return opening size
G
7.5/190
8.9/228
8.9/228
11/280
H
Size of mounted lug
I
36.2/92030.8/782
44.9/114039.4/1001
55.1/140049.6/1261
48.8/124043.3/1101
then install the hanging screw bolts.(See Fig.4.4)
Wood mounting
Roof beam
Ceiling
(Blade shape insertion)
Fig. 4.5
(Slide insertion)
Hanging screw bolts
Fig. 4.4
Original concrete bricks
Use an embedding screw bolt, crock, and stick
Steel Roof beam structure
Install and use the supporting steel angle. (See Fig.4.7)
harness.(See Fig.4.6)
Hanging screw bolt
J
14.2/360
20/508
23.5/598
23.5/598
27.4/697
(Pipe hanging and embedding screw bolt)
Page 10
Steel bar
Embedding screw bolt
Fig. 4.6
Hanging bolts
Supporting steel angle
Fig. 4.7
Page 11
CAUTION
The unit body must be completely aligned with the hole. Ensure that the unit and the hole are the same size before moving on.
Shockproof cushion
Washer
Screw nut
Overhang part
Indoor Unit
Installation
2.
Install and t pipes and wires after you have nished installing the main body.When choosing where to start, determine the direction of the pipes to be drawn out. Especially in cases where there is a ceiling involved, align the refrigerant pipes, drain pipes, and indoor and outdoor lines with their connection points before mounting the unit.
3.
Install hanging screw bolts.
Cut o the roof beam. Strengthen the point at which the cut
was made. Consolidate the roof beam.
4. After you select an installation location,align the refrigerant pipes, drain pipes, as well as indoor and outdoor wires with their connection points before mounting the unit.
5.
Drill 4 holes 10cm (4”) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
6.
Secure the bolt using the washers and nuts provided.
7. Install the four suspension bolts.
8. Mount the indoor unit with at least two people to lift and secure it. Insert suspension bolts into the unit’s hanging holes. Fasten them using the washers and nuts provided. (See Fig. 4.8).
Hanging screw bolt
NOTE:
Conrm the minimum drain tilt is 1/100
Fig. 4.9
or more.
Step 3: Duct and accessories installation
1. Install the lter (optional) according to the size of the air inlet.
2. Install the canvas tie-in between the body and the duct.
3. The air inlet and air outlet duct should be far enough apart enough to a avoid air passage short-circuit.
Connect the duct according to the following
4. diagram:
Air outlet
Isolation booth
Canvas tie-in Canvas tie-in
Isolation booth
Air inlet
checking orice
Air dust lter
Fig. 4.10
5. Refer to the following static pressure guidelines when installing the indoor unit.
Table.4-2
MODEL
(Btu/h)
Static Pressure
(Pa/in.wg)
Fig. 4.8
9. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit at using a level indicator to prevent leaks. (See Fig. 4.9).
9K
12K
18K
24K
30K~36K
42K~60K
0~50/0~0.2
0~50/0~0.2
0~100/0~0.4
0~160/0~0.64
0~160/0~0.64
0~160/0~0.64
Change the fan motor static pressure according to external duct static pressure.
NOTE: 1. Do not place the connecting duct
weight on the indoor unit.
2. When connecting the duct, use an nonammable canvas tie-in to prevent vibrating.
3. Insulation foam must be wrapped outside the duct to avoid condensate. An internal duct underlayer can be added to reduce noise, if the end-user requires.
Page 11
Page 12
Step 4: Adjust the air inlet direction (from rear side to under-side).
Indoor Unit
Installation
1. Take o the ventilation panel and ange.
Step 5: Fresh air duct installation
Dimension :
Duct joint for fresh air
Air return ange
MODLE
18-60
Ventilation panel
Fig. 4.11
2. Change the mounting positions of the ventilation panel and air return ange.
Ventilation panel
Air return ange
Fig. 4.12
3. When installing the lter mesh, t it into the ange as illustrated in the following gure.
Ø125mm(4.92”)
Ø160mm(6.3”)
Fig. 4.14
Step 6: Motor and drain pump maintenance
(the rear ventilated panel is used as an example)
Motor maintain:
Take o the ventilated panel.
1. Take o the blower housing.
2. Take o the motor.
3.
Fig. 4.13
NOTE: All the gures in this manual are for
demonstration purposes only. The air conditioner you have purchased may be slightly dierent in design, though similar in shape.
Motor
Blower housing
Ventilated panel
Fig. 4.15
Pump maintainance:
Remove four screws from the drain pump.
1. Unplug the pump power supply and water
2. level switch cable. Detach the pump.
3.
Pump
Fig. 4.16
Page 12
Page 13
Outdoor Unit Installation
Strong wind
Outdoor Unit Installation Instructions
Step 1: Select installation location.
The outdoor unit should be installed in the location that meets the following requirements:
Place the outdoor unit as close to the indoor
unit as possible.
Ensure that there is enough room for
installation and maintenance.
The air inlet and outlet must not be
obstructed or exposed to strong wind.
Ensure the location of the unit will not be
subject to snowdrifts, accumulation of leaves or other seasonal debris. If possible, provide an awning for the unit. Ensure the awning does not obstruct airflow.
The installation area must be dry and well
ventilated.
There must be enough room to install the
connecting pipes and cables and to access them for maintenance.
5
The area must be free of combustible gases
and chemicals.
The pipe length between the outdoor and
indoor unit may not exceed the maximum allowable pipe length.
If possible, DO NOT install the unit where it
is exposed to direct sunlight.
If possible, make sure the unit is located far
away from your neighbors’ property so that the noise from the unit will not disturb them.
If the location is exposed to strong winds (for
example: near a seaside), the unit must be placed against the wall to shelter it from the wind. If necessary, use an awning. (See Fig. 5.1 & 5.2)
Install the indoor and outdoor units, cables
and wires at least 1 meter from televisions or radios to prevent static or image distortion. Depending on the radio waves, a 1 meter distance may not be enough to eliminate all interference.
Outdoor Unit
Installation
Strong wind
Fig. 5.1 Fig. 5.2
Step 2: Install outdoor unit.
Fix the outdoor unit with anchor bolts (M10)
> 23.6”/60cm
CAUTION
Be sure to remove any obstacles that
Fix with bolts
may block air circulation.
Make sure you refer to Length
Specifications to ensure there is enough room for installation and maintenance.
Strong wind
Fig. 5.3
Page 13
Page 14
(Wall or obstacle)
W
Split Type Outdoor Unit
Vertical Discharge Type Outdoor Unit
Outdoor Unit
Installation
(Refer to Fig 5.4, 5.5, 5.6, 5.10 and Table 5.1)
H
Fig. 5.4
W
W
Fig. 5.5
(Refer to Fig 5.7, 5.8, 5.9 and Table 5.2)
Air Outlet
> 47”/120cm
Fig. 5.7
H
Fig. 5.8
H
D
A
D
B
Fig. 5.6
Table 5.1: Length Specifications of Split
Type Outdoor Unit (unit: inch/mm)
Outdoor Unit Dimensions
W x H x D
770x555x300 (30.3x21.85x11.81) 19.2 (487) 11.73 (298)
810x558x310 (31.9x22x12.2) 21.6 (549) 12.8 (325)
845x700x320 (33.27x27.5x12.6) 22 (560) 13.2 (335)
900x860x315 (35.4x33.85x12.4) 23.2 (590) 13.1 (333)
945x810x395 (37.2x31.9x15.55) 25.2 (640) 15.95 (405)
990x965x345 (38.98x38x13.58) 24.58 (624) 14.4 (366)
938x1369x392 (36.93x53.9x15.43) 24.96 (634) 15.9 (404)
900x1170x350 (35.4x46x13.8) 23.2 (590) 14.88 (378)
800x554x333 (31.5x21.8x13.1) 20.24 (514) 13.39 (340)
845x702x363 (33.27x27.6x14.3)
946x810x420 (37.24x31.9x16.53) 26.5 (673)
946x810x410 (37.24x31.9x16.14) 26.5 (673)
952x1333x410 (37.5x52.5x16.14) 24.96 (634)
952x1333x415 (37.5x52.5x16.34) 24.96 (634)
Mounting Dimensions
Distance A Distance B
21.26 (540)
13.8 (350)
15.87 (403)
15.87 (403)
15.9 (404)
15.9 (404)
(Wall or obstacle)
>11.8”/30cm
>11.8”/30cm
Air inlet
Air inlet
Air inlet
>11.8”/30cm
Air inlet
>11.8”/30cm
Fig. 5.9
Table 5.2: Length Specifications of Vertical
Discharge Outdoor Unit (unit: inch/mm)
DIMENSIONS
DIMENSIONS
MODEL
18 25/633 21.8/55421.8/554
24 25/633 21.8/55421.8/554
36 29.8/759 21.8/55421.8/554
36 25/633 23.6/60023.6/600
48 29.8/759 28/71028/710
60 33/843 28/71028/710
W H D
Page 14
Page 15
NOTE: The minimum distance between the
outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 5.10)
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
above
60 cm
78”
11.8”
200 cm
/
/
30 cm
on left
M
in front
/
23.6”
N
11.8”
30 cm
/
from back wall
23.6”
/
60 cm
on right
P
Fig. 5.10
Rows of series installation
Table 5.3 The relations between H, A and L are as follows.
L A
L 1/2H
9.8”
/
25 cm or more
L H
L > H
1/2H < L H
Can not be installed
11.8”/ 30 cm or more
If the drain joint doesn’t come with a rubber seal (see Fig. 5.12 - B ), do the following:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
NOTE: Make sure the water drains to a safe
location where it will not cause water damage or a slipping hazard.
Base pan hole of outdoor unit
Seal
Seal
Outdoor Unit
Installation
9.8”
or more
/
25 cm
9.8”
or more
/
25 cm
23.6” or more
60 cm
/
Fig. 5.11
H
150 cm
/
59”
or more
118”
300 cm
/
or more
Drain Joint Installation
If the drain joint comes with a rubber seal (see Fig. 5.12 - A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
Drain joint
(A)
Fig. 5.12
L
Notes On Drilling Hole In Wall
A
You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.
1. Determine the location of the wall hole based on the location of the outdoor unit.
2. Using a 2.5”(65-mm) core drill, drill a hole in the wall.
NOTE: When drilling the wall hole, make
sure to avoid wires, plumbing, and other sensitive components.
3. Place the protective wall cu in the hole. This protects the edges of the hole and will help seal it when you nish the installation process.
(B)
Page 15
Page 16
Drainpipe Installation
6
The drainpipe is used to drain water away from the unit. Improper installation may cause unit and property damage.
CAUTION
Insulate all piping to prevent condensation, which could lead to water damage.
If the drainpipe is bent or installed
Installation
Drainpipe
incorrectly, water may leak and cause a water-level switch malfunction.
In HEAT mode, the outdoor unit will
discharge water. Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage.
DO NOT pull the drainpipe forcefully. This
could disconnect it.
NOTE ON PURCHASING PIPES
Installation requires a polyethylene tube (exterior diameter = 3.7-3.9cm, interior diameter = 3.2cm), which can be obtained at your local hardware store or dealer.
Indoor Drainpipe Installation
Install the drainpipe as illustrated in Figure 6.2.
Cover the drainpipe with heat insulation to
1. prevent condensation and leakage.
2.
Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the mouth of the hose and clip it rmly with a pipe clasp. (See Fig 6.1)
Drain hose
NOTE ON DRAINPIPE INSTALLATION
When using an extended drainpipe, tighten the indoor connection with an additional protection tube. This prevents it from pulling loose.
The drainpipe should slope downward at a
gradient of at least 1/100 to prevent water from flowing back into the air conditioner.
To prevent the pipe from sagging, space
hanging wires every 1-1.5m (39-59”).
If the outlet of the drainpipe is higher than
the body’s pump joint, provide a lift pipe for the exhaust outlet of the indoor unit. The lift pipe must be installed no higher than 55cm (21.7”) from the ceiling board. the distance between the unit and the lift pipe must be less than 20cm (7.9”). Incorrect installation could cause water to flow back into the unit and flood.
To prevent air bubbles, keep the drain hose
level or slightly tiled up (<75mm / 3”).
Drainpipe installation for units with a pump
Ceiling
<7.9” 20cm
0- 3”
0 - 75mm
39-59”
(39-59
1-1.5m
Lean over 1/50
(21.7”)
<55cm
Fig. 6.3
Drainpipe
connecting port
Page 16
Pipe clasp
Ceiling
Fig. 6.1
Fig. 6.2
39-59” (1-1.5m)
NOTE: When connecting multiple drainpipes,
install the pipes as illustrated in Fig 6.4.
Insulation
0-20.8” (0-53cm)
4”
≥(10cm)
Lean over 1/50
Fig. 6.4
Page 17
3. Using a 65-mm (2.5”) core drill, drill a hole in
C
L
O
S
E
D
O
P
E
N
C
L
O
S
E
D
O
P
E
N
the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig. 6.5). Place the protective wall cu in the hole. This protects the edges of the hole and will help seal it once you nish installation.
Wall
IndoorOutdoor
≈ 0.5 inch /12mm
Fig. 6.5
Units with a pump.
1. Remove the test cover. Fill the water pan with 2 liters of water.
Drainpipe
Installation
NOTE: When drilling the hole, make sure to
avoid wires, plumbing, and other sensitive components.
4. Pass the drain hose through the wall hole. Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.
NOTE: The drainpipe outlet should be at least
1.9” (5cm) above the ground. If it touches the ground, the unit may become blocked and malfunction. If you discharge the water directly into a sewer, make sure that the drain has a U or S pipe to catch odors that might otherwise come back into the house.
Drainage test
Check that the drainpipe is unhindered. This test should be performed on newly built houses before the ceiling is paved.
Units without a pump.
Test cap
Fig.6.7
Stow tube
Fig.6.8
2. Turn on the unit in COOLING mode. You will hear the drain pump.Check whether the water is discharged properly (a 1-minute lag is possible, depending on the length of the drain pipe), Check whether water leaks from the joints.
Stow tube
Fill the water pan with 2 liters of water. Check that the drainpipe is unhindered.
3. Turn o the air conditioner and put the cap back on.
Fig.6.6
Page 17
Page 18
Refrigerant Piping Connection
7
Safety Precautions
All eld piping must be completed by a
When the air conditioner is installed in a
Connection
Refrigerant Piping
When installing the refrigeration system,
WARNING
licensed technician and must comply with the local and national regulations.
small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. If the refrigerant leaks and its concentration exceeds its proper limit, hazards due to lack of oxygen may result.
ensure that air, dust, moisture or foreign substances do not enter the refrigerant circuit. Contamination in the system may cause poor operating capacity, high pressure in the refrigeration cycle, explosion or injury.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in Table 7.1:
Table 7.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of model Capacity
North America, Australia and the eu frequency conversion Split Ty p e
Other Split Type
(Btu/h)
<15K 82/25 32.8/10
15K - <24K 98.4/30 65.6/20
24K - <36K 164/50 82/25
36K - 60K 213/65 98.4/30
12K 49/15 26/8
18K-24K 82/25 49/15
30K-36K 98.4/30 65.6/20
42K-60K 164/50 98.4/30
Length of
piping
Maximum drop
height
Ventilate the area immediately if there is refrigerant leakage during the installation.
Leaked refrigerant gas is both toxic and flammable. Ensure there is no refrigerant leakage after completing the installation work.
Refrigerant Piping with Twin Indoor Units
When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:
Outdoor unit
The drop height between indoor
unit and outdoor unit must be less than
or equal to 20m
(65.6’)
H2
L
The line branch pipe
L1
L2
Indoor unit
H1
Indoor unit
The drop height
between two
indoor units
must be less
than or equal to
19.6”(50cm)
Fig. 7.1
Page 18
Page 19
CAUTION
CAUTION
Oil traps
If the indoor unit is installed higher than the outdoor unit:
-If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas piping can prevent this.
An oil trap should be installed every 32.8ft (10m) of vertical suction line riser. (See Fig.
7.2)
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be upsized. Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below7.62m/s (1500fpm (feet per minute)), oil return will be decreased. An oil trap should be installed every 20ft (6m) of vertical suction line riser. (See Fig. 7.3)
Connection
Refrigerant Piping
Fig. 7.2 Fig. 7.3
The indoor unit is installed higher than the outdoor unit
The outdoor unit is installed higher than the indoor unit
Page 19
Page 20
Point dow
Piping length
Drop height
Table 7.2
Permitted length
Total piping length 18K+18K 98’/30m L+Max
24K+24K
30K+30K
(farthest distance from the line pipe branch)
(farthest distance from the line pipe branch)
Drop height between indoor and outdoor unit
Drop height between two indoor units
164’/50m
49’/15m L1, L2
32.8’/10m L1-L2
65.6’/20m H1
1.6’/0.5m H2
(L1, L2)
Step1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.
2. Using a pipe cutter, cut the pipe a little
longer than the measured distance.
Size of joint pipes for indoor unit
Table 7.3
Capacity of indoor unit (A)
18K
Refrigerant Piping
Connection
24K
30K
Size of joint pipes for outdoor unit
Base on the following tables, select the diameters of the outdoor unit connective pipes. In case of the main accessory pipe larger than the main pipe, take
the larger one for the selection.
Table 7.4
Model
36K 48K 60K
Size of joint pipes for 410A indoor unit
Size of main pipe(mm)
Gas side
Ø0.5(12.7)
Ø0.626(15.9)
Ø0.626(15.9)
Liquid side
Ø0.25(6.35)
Ø0.375(9.5)
Ø0.375(9.5)
Available branching pipe
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
Size of joint pipes for 410A outdoor unit
the size of main pipe(mm)
Gas side Liquid side
Ø0.626(15.9)
Ø0.626(15.9)
Ø0.626(15.9)
Ø0.375(9.5)
Ø0.375(9.5)
Ø0.375(9.5)
The 1st branching pipe CE-FQZHN-01C CE-FQZHN-01C
CE-FQZHN-01C
CAUTION
DO NOT deform pipe while cutting. Be extra
careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
1. Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 7.4 for examples of bad cuts
90°
Step2: Remove burrs.
Burrs can aect the air-tight seal of refrigerant piping connection. They must be completely removed.
Oblique
Fig. 7.4
Rough
Warped
Refrigerant Piping Connection Instructions
CAUTION
The branching pipe must be installed
horizontally. An angle of more than 10° may cause malfunction.
DO NOTinstall the connecting pipe until both
indoor and outdoor units have been installed.
Insulate both the gas and liquid piping to
prevent water leakage.
Page 20
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Pipe
Reamer
n
Fig. 7.5
Page 21
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring. See Fig. 7.6
Flare nut
Copper pipe
Fig. 7.6
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form
Table 7.5: PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge
Ø 6.4
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1
Ø 22
Tightening
torque
18-20 N.m
(183-204 kgf.cm)
25-26 N.m
(255-265 kgf.cm)
35-36 N.m
(357-367 kgf.cm)
45-47 N.m
(459-480 kgf.cm)
65-67 N.m
(663-683 kgf.cm)
75-85N.m
(765-867 kgf.cm)
Flare dimension (A)
(Unit: Inch/mm)
Min. Max.
0.33/8.4 0.34/8.7
0.52/13.2 0.53/13.5
0.64/16.2 0.65/16.5
0.76/19.2 0.78/19.7
0.91/23.2 0.93/23.7
1.04/26.4 1.06/26.9
Flare shape
°
4
±
90
45
A
R0.4~0.8
Fig. 7.8
°
±
2
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high­pressure pipe.
1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you will connect.
Refrigerant Piping
Connection
Pipe
Fig. 7.7
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.5.
Indoor unit tubing
Flare nut
Pipe
Fig. 7.9
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 7.5.
Page 21
Page 22
NOTE: Use both a spanner and a torque wrench
when connecting or disconnecting pipes to/from the unit.
Ensure to wrap insulation around the piping.
Refrigerant Piping
Connection
Direct contact with the bare piping may result in burns or frostbite.
CAUTION
Fig. 7.10
NOTE: DO NOT intertwine signal cable with
other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
7. Thread this pipeline through the wall and connect it to the outdoor unit.
8. Insulate all the piping, including the valves of the outdoor unit.
9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).
Make sure the pipe is properly connected.
Over tightening may damage the bell mouth and under tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
min-radius 3.9” (10cm)
Fig. 7.11
6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.
Page 22
Page 23
Wiring
8
Safety Precautions
WARNING
Disconnect the power supply before working on the unit.
All wiring must be performed according to
local and national regulations.
Wiring must be done by a qualied
technician. Improper connections may cause electrical malfunction, injury, or re.
An independent circuit and single outlet
must be used for this unit.
DO NOT plug another appliance or
charger into the same outlet. If the cannot handle the load or there is a defect in the wiring, it can lead to shock, re, and unit and property damage.
Connect the power cable to the terminals
and fasten it with a clamp. An insecure connection may cause fire.
Make sure that all wiring is done correctly
and the control board cover is properly installed. Failure to do so can cause overheating at the connection points, fire, and electrical shock.
Ensure that main power supply connection is made through a switch that disconnects all poles, with contact gap of at least 3mm (0.118”).
DO NOT modify the length of the power
cord or use an extension cord.
To prevent distortion when the compressor starts (you can nd the unit’s power information on the rating sticker):
The unit must be connected to the main outlet. Normally, the power supply must have a impedance of 32 ohms.
No other equipment should be connected to the same power circuit.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s printed circuit board (PCB) is designed with a fuse that provides overcurrent protection. The specications of the fuse are printed on the circuit board, examples of such are T5A/250VAC and T10A/250VAC.
Outdoor Unit Wiring
WARNING
Before performing any electrical or wiring work, turn o the main power to the system.
1. Prepare the cable for connection a. You must first choose the right cable size.
Be sure to use H07RN-F cables.
Table 8.1: Minimum Cross-Sectional Area
of Power and Signal Cables in North America
Wiring
CAUTION
Connect the outdoor wires before connecting the indoor wires.
Make sure you ground the unit. The grounding wire should be located away from gas pipes, water pipes, lightning rods, telephone wires or other grounding wires. Improper grounding may cause electrical shock.
DO NOT connect the unit to the power
source until all wiring and piping is completed.
Make sure that you do not cross your
electrical wiring with your signal wiring. This may cause distortion and interference.
Rated Current of
Appliance (A)
7 18
7 - 13 16 13 - 18 14 18 - 25 12 25 - 30 10
AWG
Page 23
Page 24
Table 8.2: Other World Regions
Rated Current of
Appliance (A)
6 0.75
Nominal Cross-Sectional
Area (mm²)
6 - 10 1 10 - 16 1.5
16 - 25 2.5
25- 32 4
32 - 45 6
b. Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal approximately 5.9”(15cm) of wire.
c.
Strip the insulation from the ends.
d. Using a wire crimper, crimp u-lugs on the
ends.
NOTE: When connecting the wires, strictly
follow the wiring diagram found inside the electrical box cover.
2. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, take o the bolts from the maintenance board and remove the protection board. (See Fig. 8.1, 8.2)
Indoor Unit Wiring
1. Prepare the cable for connection a. Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal about 5.9”(15cm) of the wire.
b. Strip the insulation from the ends of the
wires.
c. Using a wire crimper, crimp the u-lugs to
the ends of the wires.
2. Remove the cover of the electric control box on your indoor unit.
3. Connect the u-lugs to the terminals. Match the wire colors/labels with the labels
on the terminal block, Firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.
Control box
Wiring
Cover
Screw
Fig. 8.1
Protection Board
Fig. 8.2
3. Connect the u-lugs to the terminals Match the wire colors/labels with the labels on the terminal block, Firmly screw the u-lug of each wire to its corresponding terminal.
4. Clamp down the cable with the cable clamp.
5.
Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.
6. Reinstall the cover of the electric control box.
Wiring diagram
Magnetic ring
Connective wiring diagram
Fig. 8.3
(if supplied and packed with the accessories)
1 2 3
Pass the belt through the hole of the Magnetic
ring to fix it on the cable
Fig. 8.4
Page 24
Page 25
CAUTION
While connecting the wires, please strictly
follow the wiring diagram.
The refrigerant circuit can become very
hot. Keep the interconnection cable away from the copper tube.
- Press “CONFIRM”. The air conditioning unit will then start the fan for airow automatic adjustment.
4. Clamp down the cable with the cable clamp. The cable must not be loose or pull on the u-lugs.
5. Reattach the electric box cover.
Using the wire controller to set external static pressure (some models)
You can use the unit’s automatic airow
adjustment function to set external static pressure.
Automatic airow adjustment is the volume of blow-o air that has been automatically adjusted to the quantity rated.
1. Make sure the test run is done with a dry coil. If the coil is not dry, run the unit for 2 hours in FAN ONLY mode to dry the coil.
2. Check that both power supply wiring and duct installation have been completed Check that any closing dampers are open. Check that the air lter is properly attached to the air suction side passage of the unit.
3. If there is more than one air inlet and outlet, adjust the dampers so that the airow rate of each air inlet and outlet conforms with the designed airow rate. Make sure the unit is in FAN ONLY mode. Press and set the airow adjustment button on the remote control to change the airow rate from H or L.
ON will ash during when the fan is on during automatic airow adjustment.
CAUTION
DO NOT adjust the dampers when
automatic airow adjustment is active.
After 3 to 6 minutes, the air conditioning unit stops operating once automatic airow adjustment has nished.
CAUTION
If there is no change after airow
adjustment in the ventilation paths, be sure to reset automatic airow adjustment.
If there is no change to ventilation paths
after airow adjustment,contact your dealer, especially if this occurs after testing the outdoor unit or if the unit has been moved to a dierent location.
Do not use automatic airow adjustment
with remote control,if you are using booster fans, outdoor air processing unit, or a HRV via duct.
If the ventilation paths have been changed,
reset airow automatic adjustment as described from step 3 onwards.
Wiring
4. Set the parameters for automatic airow adjustment. When the air conditioning unit is o, perform the follwoing steps:
- Press“COPY”.
- Press “+” or “-” to select the AF.
Page 25
Page 26
Power Specifications
NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A.
Indoor Power Supply Specifications
Wiring
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
POWER
CIRCUIT BREAKER/
FREQUENCY
AND VOLT
FUSE(A)
MODEL
(Btu/h)
208-240V 208-240V 208-240V 208-240V 208-240V
25/20 32/25 50/40 70/55 70/60
36K 37K~60K 36K 37K~60K
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
POWER
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
Outdoor Power Supply Specifications
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
POWER
CIRCUIT BREAKER/
FREQUENCY
AND VOLT
FUSE(A)
208-240V 208-240V 208-240V 208-240V 208-240V
25/20 32/25 50/40 70/55 70/60
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
POWER
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
Independent Power Supply Specifications
MODEL
POWER
(indoor)
(Btu/h)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
CIRCUIT BREAKER/
FUSE(A)
POWER
(outdoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
CIRCUIT BREAKER/
FUSE(A)
18K 19K~24K 25K~36K 37K~48K 49K~60K
208-240V 208-240V 208-240V208-240V 208-240V
15/10 15/10 15/10 15/10 15/10
208-240V 208-240V 208-240V
25/20 32/25 50/40 70/55 70/60
208-240V
208-240V
Page 26
Page 27
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
POWER
(indoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
208-240V
208-240V
MODEL
POWER
(indoor)
(Btu/h)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
CIRCUIT BREAKER/
FUSE(A)
POWER
(outdoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
CIRCUIT BREAKER/
FUSE(A)
Inverter Type A/C Power Specifications
18K 19K~24K 25K~36K 37K~48K 49K~60K
220-240V 220-240V 220-240V220-240V 220-240V
15/10 15/10 15/10 15/10 15/10
208-240V 208-240V 208-240V
25/20 25/20 40/30 50/40 50/40
MODEL
POWER (indoor)
(Btu/h)
36K 37K~60K 36K 37K~60K
PHASE 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
220-240V 220-240V 220-240V 220-240V
CIRCUIT BREAKER/FUSE(A) 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 40/30
Wiring
Page 27
Page 28
Air Evacuation
V
Safety Precautions
CAUTION
Use a vacuum pump with a gauge reading
lower than -0.1MPa and an air discharge capacity above 40L/min.
The outdoor unit does not need to be
vacuumed. DO NOT open the outdoor
unit’s gas and liquid stop valves.
Ensure that the Compound Meter reads
-0.1MPa or below after 2 hours. If after three hours the gauge reading is still above
-0.1MPa, check if there is a gas leak or water inside the pipe. If there is no leak, perform another evacuation for 1 or 2 hours.
DO NOT use refrigerant gas to evacuate the
system.
9
4.
Turn on the vacuum pump to evacuate the
system.
Run the vacuum for at least 15 minutes, or
5. until the Compound Meter reads -76cmHG (-1x105Pa).
Close the manifold gauge’s Low Pressure
6. valve and turn o the vacuum pump. Wait for 5 minutes, then check that there has
7. been no change in system pressure.
NOTE: If there is no change in system pressure,
unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.
Insert hexagonal wrench into the packed valve
8.
(high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.
Evacuation Instructions
Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.
Air Evacuation
Compound gauge
-76cmHg
Low pressure valve
Charge hose
Manifold Gauge
Pressure gauge
High pressure valve
Charge hose
Vacuum pump
Low pressure valve
Fig. 9.1
1. Connect the manifold gauge’s charge hose to the service port on the outdoor unit’s low pressure valve.
2. Connect the manifold gauge’s charge hose from the to the vacuum pump.
3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.
Flare nut
Cap
alve body
Valve stem
Fig. 9.2
9. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.
10.Remove the charge hose from the service port.
11.Using hexagonal wrench, fully open both the high pressure and low pressure valves.
OPEN VALVE STEMS GENTLY
When opening the valve stems, turn the hexagonal
wrench until it hits against the stopper. DO NOT
try to force the valve to open further.
12. Tighten valve caps by hand, then tighten it using the proper tool.
Page 28
Page 29
Note On Adding Refrigerant
CAUTION
Refrigerant charging must be performed after wiring, vacuuming, and the leak testing.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage the unit or impact it’s functioning.
Charging with unsuitable substances may cause explosions or accidents. Ensure that the appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use protective gear when charging the
system.
DO NOT mix refrigerants types.
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is
7.5m (25’) In other areas, the standard pipe length is 5m (16‘). The additional refrigerant to be charged can be calculated using the following formula:
Liquid Side Diameter
φ6.35(1/4”) φ9.52(3/8”) φ12.7(1/2”)
R22 (orifice tube in the indoor unit):
R22 (orifice tube in the outdoor unit):
R410A: (orifice tube in the indoor unit):
R410A: (orifice tube in the outdoor unit):
(Total pipe length ­standard pipe length)x 30g (0.32oZ)/m(ft)
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length)x 65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length) x30(0.32oZ)/m(ft)
(Total pipe length ­standard pipe length) x65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length ­standard pipe length)x 115g(1.23oZ)/m(ft)
(Total pipe length - standard pipe length) x60g(0.64oZ)/m(ft)
(Total pipe length ­standard pipe length) x115g(1.23oZ)/m(ft)
Air Evacuation
(Total pipe length - standard pipe length) x65g(0.69oZ)/m(ft)
Page 29
Page 30
Test Run
10
Before Test Run
A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:
a) Indoor and outdoor units are properly
installed.
b) Piping and wiring are properly connected. c) No obstacles near the inlet and outlet of
the unit that might cause poor performance or product malfunction.
d) Refrigeration system does not leak. e) Drainage system is unimpeded and
draining to a safe location.
f) Heating insulation is properly installed. g) Grounding wires are properly connected. h) Length of the piping and additional
refrigerant stow capacity have been recorded.
i) Power voltage is the correct voltage for the
air conditioner.
CAUTION
Failure to perform the test run may result in unit damage, property damage or personal injury.
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
Test Run
4. For the Indoor Unit a. Ensure the remote control and its buttons
work properly.
b. Ensure the louvers move properly and can
be changed using the remote control.
c. Double check to see if the room
temperature is registered correctly.
d. Ensure the indicators on the remote
control and the display panel on the indoor unit work properly.
e. Ensure the manual buttons on the indoor
unit works properly.
f. Check to see that the drainage system is
unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal
noise during operation.
5. For the Outdoor Unit a. Check to see if the refrigeration system is
leaking.
b. Make sure there is no vibration or
abnormal noise during operation.
c. Ensure the wind, noise, and water
generated by the unit do not disturb your neighbors or pose a safety hazard.
6. Drainage Test a. Ensure the drainpipe flows smoothly. New
buildings should perform this test before finishing the ceiling.
b. Remove the test cover. Add 2,000ml of
water to the tank through the attached tube.
c. Turn on the main power switch and run
the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to
see if it makes any unusual noises.
e. Check to see that the water is discharged.
It may take up to one minute before the unit begins to drain depending on the drainpipe.
f. Make sure that there are no leaks in any of
the piping.
g. Stop the air conditioner. Turn o the main
power switch and reinstall the test cover.
NOTE: If the unit malfunctions or does not
operate according to your expectations, please refer to the Troubleshooting section of the Owner’s Manual before calling customer service.
Page 30
Loading...