Cooline DWL SERIES, DWL02, DWL03, DWL04, DWL06 Installation, Operation & Mainenance Manual

...
Page 1
INSTALLATION,
OPERATION
&
MAINTENANCE
MANUAL
CONCEALED CHILLED WATER FAN COIL UNITS
'DWL' SERIES
Part Number: 800-213-51 (Rev.-01)
Page 2
INDEX
Contents Page
General information .................................................................................................................................. 2
Warranty terms......................................................................................................................................... 2
Inspection procedure ................................................................................................................................ 2
Model decoding ........................................................................................................................................ 3
Options ..................................................................................................................................................... 3
Installation procedures ............................................................................................................................. 4
Location of indoor units ............................................................................................................................ 4
Site preparation ........................................................................................................................................ 4
Unit installation ......................................................................................................................................... 4
Piping connection ..................................................................................................................................... 5
Condensate drain connection ................................................................................................................... 5
Unit dimensions ........................................................................................................................................ 6
Dimensional data - coil connections ......................................................................................................... 7
Typical wiring diagram ........................................................................................................................... 8-9
Valve packages ...................................................................................................................................... 10
Parts list ................................................................................................................................................. 10
Thermostat operation & specification data ........................................................................................ 11-12
Installation .............................................................................................................................................. 13
Electrical ................................................................................................................................................. 13
Maintenance ........................................................................................................................................... 13
Servicing instructions ............................................................................................................................. 14
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1
Page 3
GENERAL INFORMATION
Thank you for your purchase of this equipment from the COOLINE Air Conditioners. We trust that this unit will provide you with the proper Cooling/Heating requirements for years to come.
However, we would suggest that you read carefully this manual before you proceed with the installation and operation of this equipment and follow the instructions for a safe, trouble free operation.
This unit has been tested to the extremes in terms of working conditions and successfully passed all the requirements of quality, safety and performance.
WARRANTY TERMS
All of the DWL series of indoor fan coil (concealed) units are covered by the standard warranty terms against any manufacturer defect. Should you encounter any problem that falls under the warranty terms please contact your nearest COOLINE representative.
INSPECTION PROCEDURES
The moment you receive this unit, check the packaging carton for any visible damage due to shipment and mishandling. If you suspect any damage to the unit please call your nearest COOLINE representative.
After you open the carton, make sure that there is no visible damage to the body. Check the condition of the protective Styrofoam. Manually rotate the blower wheels to make sure that it is running freely.
Inside every DWL packaging you will find:
- DWL Concealed FCU 1 No
- Service Manual 1 No
WARNING: Electric shock hazard and / or serious injury from rotating parts can result from improper handling and servicing. Only skilled and trained technicians should attempt at installing and servicing these units.
CAUTION: Improper handling and operating procedures might adversely affect the proper functioning of the unit. Please read carefully this manual before operating the unit.
2
Page 4
MODEL DECODING
1, 2 & 3
BASIC (SERIES)
DWL : COOLINE
CHILLED WATER FAN COIL UNIT
4 & 5
SIZE
(x 100 CFM)
02 03 04 06 08 10 12 14 16 18 20
6
ELECTRICAL
SUPPLY (V-Ph-Hz)
B : 220/240-1-50
7
COIL
A :
3 ROW CHILLED WATER
J :
3 ROW CHILLED WATER + 1 ROW
HEAT
B :
4 ROW CHILLED WATER
K :
4 ROW CHILLED WATER + 1 ROW
HEAT
8
HEATER
NO HEATER
N : D :2 kW E :3 kW G:5 kW
N :
NO HEATER
E :3 kW G:5 kW J :7 kW M: 10 kW
9
ACCESSORIES
N : STANDARD
A :
3C VALVE PACKAGE (COOL ONLY)
B :
3D VALVE PACKAGE (COOL ONLY)
J :
4C VALVE PACKAGE (HEAT & COOL)
K :
4D VALVE PACKAGE
(HEAT & COOL)
10
FIN
A : ALUMINUM
FIN
B : COATED
ALUMINUM FIN
C : COPPER FIN
11
COIL
CONNECTION
R : RH SIDE,
STANDARD (FACING AIR DIS­CHARGE)
L : LH SIDE,
OPTIONAL (FACING AIR DIS­CHARGE)
12
FILTER
N : NONE
A :
ALUMINUM
(1/2" THICK)
13
OPTION
N :
STANDARD
UNIT
OPTIONS
ELECTRIC HEATERS
The heater element is of the resistance open coil type. Thermal overheat cut-outs and fusible links are provided to shut­off power to heaters in case of airflow failure. The heaters are available as an option and can be installed at the blower outlet.
VALVE PACKAGES
A variety of valve packages, as a set are available as an option (3C & 3D for two pipe system and 4C & 4D for four pipe systems). These valves are supplied loose for field installations.
THERMOSTAT
An attractive wall mount three speed thermostat with all required functions and features for safe and smooth operation which can be used for cooling & heating. This thermostat can be supplied loose through separate Kit number.
TYPICAL THERMOSTAT
3
Page 5
INSTALLATION PROCEDURES
A. Location of Indoor units
The Indoor FCU should be ideally located in a plenum or false ceiling clearance/cavity near the conditioned area where the access to the chilled water piping connection is easy.
Position the FCU in a way to avoid obstruction to return airflow, supply air, electrical cable connections, condensate drain pipe and chilled water piping.
The required clearances are shown in figure-1. (All dimensions are in cm).
B. Site Preparation
The site for the FCU installation should be free from any obstacle that can be hazardous to the installation personnel and/or damaging to the unit.
Properly identify all existing building utilities (such as electrical cables, plumbing pipes, sanitary hardware, etc.).
Make sure that live electrical cables are not hanging or running near the FCU proposed location or obstructing in any way the movement of the installation personnel.
Clear the floor from all objects with sharp edges. Remove liquid or slippery material from the installation
site before proceeding.
C. Indoor unit installation
Cut the top carton panel and mark it with a sketch simulating the FCU. Use it as a template for positioning the unit and the corresponding mounting brackets hole/slot.
- Put the template against the ceiling and mark the corners. Make sure that you leave at least 30 cm. clearance from the rear and anther 50 cm. from the right hand side of the unit (when looking at the unit from the supply side) as shown in figure-1.
- Mark the 4 holes.
- Drill those 4 holes. Insert the threaded rods using anchor bolts (8 mm).
- Fit and tighten the nuts at the loose end of each threaded rod as per the arrangement show in figure- 2.
- Lift the FCU unit and insert the threaded rods into the mounting bracket slots. Let it rest on the lower nut/washer.
- After you complete the electrical connections (see corresponding sections (Electrical Wiring and Thermostat Installation and Connection)), level the FCU and press it against the ceiling (ensuring to separate it from the ceiling by inserting rubber cork pieces) by further tightening action of the lower nut(s). For added security counter tighten the upper nut as shown in figure-3. Cut the extra length of the threaded rod and round the edges.
FIGURE - 1
REQUIRED INDOOR UNIT CLEARANCES
FIGURE - 2
Note: Always leave 7 to 8 cm extra length in the
threaded rod below the lower nut/washer.
FIGURE - 3
4
Page 6
D. Piping connection
MODEL NUMBER
DWL 02 DWL 03 DWL 04 DWL 06 DWL 08 DWL 10 DWL 12 DWL 14 DWL 16 DWL 18 DWL 20
SWEAT CONNECTION
WATER INLET WATER OUTLET
1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Note: The water lines must be installed level in both the horizontal & vertical plane.
Insulation of pipes
The pipe insulation should cover both inlet & outlet pipes as shown below.
WATER IN
WATER OUT
WATER OUT
WATER OUT
INSULATION
INSULATION
NO NOYES
WATER INWATER IN
E. Condensate Drain connection
- Use PVC Class 3 material for the condensate drain piping (3/4") as per figure-4.
- Provide a "P" trap immediately at the condensate drain connection.
- Run your piping avoiding bends and elbows.
- Pitch the piping away from the unit with 2/100 slope.
- If the pipe is routed though a room (or an unconditioned space) insulate to avoid condensation on its outer walls.
FIGURE - 4
5
Page 7
DIMENSIONS
MODELS: DWL02 - DWL20
D
4
I
5
A
H
2
3/4" NPT(14TPI) DRAIN TUBE.
0.5"
B
E
7
END VIEW TOP VIEW
G
C
FRONT VIEW
1
6
1.0"
END VIEW
F
3.5"
3
7.0"
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
MODEL
DWL02 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) DWL03 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) DWL04 805 (31.7) 520 (20.5) 246 (9.7) 863 (34) 444 (17.5) 696 (27.4) 183 (7.2) 736 (29) 208 (8.2) DWL06 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) DWL08 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) DWL10 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DWL12 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DWL14 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DWL16 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) DWL18 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) DWL20 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5)
ABCDEFGH I
DIMENSIONS
1. Blower & motor assembly
2. Cooling coil
3. Control box
4. Filter rack
5. Unit mounting brackets
6. Drip lip
7. Duct connector
6
Page 8
INLET OUTLET
DIMENSIONAL DATA - COIL CONNECTIONS
MODELS: DWL02, 03 & 04 (VERTICAL COIL)
LH SIDERH SIDE
MODELS: DWL06 - DWL20 (INCLINED COIL)
INLET OUTLET
MODEL
AB CD
DWL02 225 (8.9) 237 (9.3) 32 (1.3) 176 (6.9) 3 264 (10.4) 275 (10.8) 1 DWL03 225 (8.9) 237 (9.3) 32 (1.3) 176 (6.9) 3 264 (10.4) 275 (10.8) 1 DWL04 225 (8.9) 237 (9.3) 32 (1.3) 176 (6.9) 3 264 (10.4) 275 (10.8) 1 DWL06 313 (12.3) 324 (12.8) 32 (1.3) 178 (7) 3 351 (13.8) 362 (14.3) 1 DWL08 313 (12.3) 324 (12.8) 32 (1.3) 178 (7) 3 351 (13.8) 362 (14.3) 1 DWL10 313 (12.3) 324 (12.8) 83 (3.3) 227 (8.9) 3 351 (13.8) 362 (14.3) 1 DWL12 313 (12.3) 324 (12.8) 83 (3.3) 227 (8.9) 3 351 (13.8) 362 (14.3) 1 DWL14 319 (12.6) 330 (13) 83 (3.3) 227 (8.9) 4 357 (14) 368 (14.5) 1 DWL16 376 (14.8) 389 (15.3) 129 (5) 273 (10.8) 4 414 (16.3) 427 (16.8) 1 DWL18 376 (14.8) 389 (15.3) 129 (5) 273 (10.8) 4 414 (16.3) 427 (16.8) 1 DWL20 376 (14.8) 389 (15.3) 129 (5) 273 (10.8) 4 414 (16.3) 427 (16.8) 1
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
CHILLED WATER COIL
LH SIDERH SIDE
HOT WATER COIL
No. OF ROWS
7
EF
No. OF ROWS
Page 9
TYPICAL SCHEMATIC WIRING DIAGRAM
HEAT/COOL MODELS - ELECTRIC HEATER
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
CR CONTROL RELAY
EV ELECTRIC VALVE (COOLING)
FM FAN MOTOR
GND LUG GROUND
HC HEATER CONTACTOR
HTR HEATER
HVTB HIGH VOLTAGE TERMINAL BLOCK
L/L1 LINE OR LINE 1
L2/N LINE 2 OR NEUTRAL
OHT OVER HEAT THERMOSTAT _ _ _
1. POWER SUPPLY, 220/240V-1PH-50Hz.
2. MOTORS THERMALLY PROTECTED.
3. HVTB IS NOT REQUIRED FOR HEATER MODELS.
4. USE HEATER AS PER OPTION REQUIRED. IF EV & HEATERS ARE FACTORY IN­STALLED, PLEASE READ DASHED LINE AS CONTINUOUS LINE.
5. USE COPPER CONDUCTORS ONLY.
LEGEND
FIELD WIRING
FACTORY WIRING
NOTES
8
Page 10
TYPICAL SCHEMATIC WIRING DIAGRAM
HEAT/COOL MODELS - HOT WATER
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
CR CONTROL RELAY
EV ELECTRIC VALVE (COOLING)
EV1 ELECTRIC VALVE (HEATING)
FM FAN MOTOR
GND LUG GROUND
HVTB HIGH VOLTAGE TERMINAL BLOCK
L/L1 LINE OR LINE 1
L2/N LINE 2 OR NEUTRAL _ _ _
1. POWER SUPPLY, 220/240V-1PH-50Hz.
2. MOTORS THERMALLY PROTECTED.
3. USE COPPER CONDUCTORS ONLY.
4.IF EV & EV1 ARE FACTORY INSTALLED, PLEASE READ DASHED LINE AS CONTINUOUS LINE.
LEGEND
FIELD WIRING
FACTORY WIRING
NOTES
9
Page 11
VALVE PACKAGES
VALVE PACKAGE 3-C (for 2-pipe)
Two compression stop valves
1
One balancing valve
2
One 3-way motor valve
3
VALVE PACKAGE 3-D (for 2-pipe)
Two gate shut off valves
1
One balancing valve
2
One 3-way motor valve
3
VALVE PACKAGE 4-C (for 4-pipe)
Four compression stop valves
1
Two balancing valves
2
Two 3-way motor valves
3
VALVE PACKAGE 4-D (for 4-pipe)
Four gate shut off valves
1
Two balancing valves
2
Two 3-way motor valves
3
1
FCU
2
3
CHILLER
Two gate valves
1
One balancing valve
2
One 3-way motor valve
3
1
PARTS LIST
MODEL NUMBER
DESCRIPTION
DWL02/03/04 DWL06/08 DWL10/12/14 DWL16/18 DWL20
FAN DECK ASSEMBLY 800-089-75 800-089-71 800-089-72 800-089-73 800-089-76
BLOWER MOTOR 800-547-55 800-547-51 800-547-52 800-547-53 800-547-56
BLOWER WHEEL 800-711-50 800-711-51 800-711-52 800-711-53 800-711-53
` VALVE PACKAGE (3C) 700-362-51 700-362-51 700-362-51 700-362-51 700-362-51
VALVE PACKAGE (3D) 700-364-81 700-364-81 700-364-81 700-364-81 700-364-81
RETURN AIR FILTERS 800-249-43 800-249-39 800-249-38 800-249-36 800-249-36
THERMOSTAT 800-646-20 800-646-20 800-646-20 800-646-20 800-646-20
NOTE: For 4C & 4D type valve package, order 2 x 3C & 2 x 3D valve packages.
10
Page 12
THERMOSTAT OPERATION & SPECIFICATION DATA
OPERATING INSTRUCTIONS
+
-
+
°C
-
FUNCTIONSYMBOL
OFF mode switch position
COOL mode switch position
FAN mode switch position
HEAT mode switch position
Temperature set button (increasing)
Temperature set button (decreasing)
LOW fan speed switch position
MEDIUM fan speed switch position
HIGH fan speed switch position
OPERATING PROCEDURE
FUNCTIONSWITCH POSITION COOLING MODE
+
-
+
-
Notes:
1. Start-up display: When power is supplied to the thermostat, the LCD indicates a flashing display of the standard set point value. Press the (+) & (-) button at the same time to change the display to ambient temperature.
2. Set point adjustment: When the (+) or (-) button is pressed, the thermostat assumes the temperature set point setting mode and the present set point is displayed. The displayed set point can now be adjusted in 0.5K steps to the required value. After 3 seconds (approx.) the actual temperature will then be displayed.
- Position the switch S1 to COOL mode function.
- Set desired temperature setting by pressing the (+) or (-) button to increase or decrease the set value displayed on the LCD of the thermostat .
- Fan speeds can be selected by positioning the switch S2 to: LOW speed MEDIUM speed HIGH speed
HEATING MODE
- Position the switch S1 to HEAT mode function.
- Set desired temperature setting by pressing the (+) or (-) button to increase or decrease the set value displayed on the LCD of the thermostat .
- Fan speeds can be selected by positioning the switch S2 to: LOW speed MEDIUM speed HIGH speed
FAN MODE
- Position the switch S1 to FAN mode function.
- Fan speeds can be selected by positioning the switch S2 to: LOW speed MEDIUM speed HIGH speed
UNIT OFF
- Position the switch S1 to OFF position to turn off the unit.
11
Page 13
PRODUCT DATA
Part Number : 800-646-20 Switches : Fan speed high/med/low
Heat/Fan/Cool/Off
Outputs : Heat
Cool Fan speed high/med/low
Inputs : Remote sensor (optional)
TECHNICAL DATA
Operating voltage : 230V + 10%; AC 50/60 Hz Operating ambient : 00C to 400C Temperature range : 50C to 300C Selectivity of set value : 0.5K Display range (actual value) : 0... + 400C Selectivity of actual value : 0.1K Hysteresis : ~0.5K Switching current at 250 VAC : 3 (2)A Maximum fan current : 6 (3)A Sensor system : NTC (in housing)
Optional Remote Sensor 193720
Switches : Heat/Off/Cool/Fan
3 Fan Speed
Indicator lamps : Cool/Heat
PHYSICAL DATA
Color : Polar white Material : ABS plastic Protection class : IP30 Plastic Weight : 130 grams Accessories : Base plate and screws Option : Transparent wall mounted housing, lockable with ventilation slit.
DIMENSIONS
83
75
UP OPEN
135.5
127
194
160
92
HOUSING PROTECTION (OPTIONAL)BASE PLATE
28.6
6
0
85
120
105
THERMOSTAT
NOTE: All dimensions are in mm.
12
Page 14
INSTALLATION
The complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immedi­ately to the delivery man or driver and noted on the shipping invoice.
Place unit in position and make sure that unit is level. This is important to assure proper drainage and operation. Slots provided in the mounting brackets should be used for installing the units.
ELECTRICAL
Please ensure power supply (V-Ph-Hz) to the unit is as per unit nameplate requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
Warning: Before installation or servicing, always TURN OFF all power to the unit. There may be more than
one disconnect switch. Ensure all of them are turned off.
GROUND & POWER WIRES
Connect power wires as per wiring diagram. Connect ground wire to the ground lug inside the control box.
MAINTENANCE
COIL
Coil may be cleaned by removing and brushing between fins with a stiff wire brush. Brushing should be followed by cleaning with vacuum cleaner. The coil may also be cleaned by using a high pressure air, if compressed air source is available. It should be pointed out that if air filters are used and periodically cleaned, the coils will not be clogged up prematurely.
DRAIN PIPE
Drain pipe should be checked before summer operation of unit. If it is clogged, steps should be taken to clear the debris so that condensate will flow out easily. A standard pipe cleaner for 1/2" ID pipe may be used. Periodic checks of the drain pipe should be taken during summer operation, as there is a possibility of it becoming clogged with dirt.
FILTER CLEANING
Remove access panel, slide filter out of filter rack, and clean as follows: Tap filter on solid surface to dislodge heavy particles. Wash under stream of hot water. If filter has been put to excep­tional service, a mild solution of Sal-Soda, Tri-Sodium Phosphate or any other commercial solvent can be used. Set filter on end with slots in frame down, which allows it to drain. Filters should dry thoroughly before reuse.
REPLACEMENT PARTS
When writing for replacement parts, refer to model number and serial number on the nameplate of the unit.
ROUTINE/PREVENTIVE MAINTENANCE
- Clean the thermostat box with a dry soft cloth.
- Remove the filter by either: a) Swinging away the knuckles on top of the filter rack then lifting the filter from the lower rack. b) Swinging away the knuckles on top of the filter rack then sliding the filter sideways. c) Clean the filter by a jet of air in the reverse return air direction. d) Inspect the condensate pipe for clogging.
SAFETY INSTRUCTIONS
Warning: Before you attend to any routine maintenance, make sure that the electrical power is disconnected.
- Avoid spilling any liquid on the thermostat
- Always allow for 1 to 2 minutes before activating different commands.
13
Page 15
&
rs
e
w
o
l
b
r
o
f
s
s
e
c
c
A
M
C
95
Blower deck holding bolt
SERVICING INSTRUCTIONS
r
o
t
o
m
M
C
30
50
C
M
M
C
0
5
Blower deck
Bottom panel
Note:
1) Required indoor unit access clearances are shown as hatched area.
2) Free sevice access should be available from the bottom of the unit for removing & servicing the blower/motor deck.
3) Servicing instructions:
a) Remove the bottom panel. b) Support the blower deck while unscrewing the 4 blower deck holding bolts and bring down the blower deck.
14