Mechanical Installation Instructions
Figure 1: Dimensions are for a standard ComNet™one slot module.
FDX54
.156 [3.96 mm]
Installation Considerations
This fiber-optic link is supplied as
tandalone/Rack module.
a S
Units should be installed in dry
locations protected from extremes
of temperature and humidity.
Standalone Module:
The unit is provided with a mounting
e with holes for two No.6 pan
plat
head screws (3-mm or 3.55-mm).
Attach the module to a solid piece
od using two No. 6 pan head
of wo
wood screws with a minimum
penetration into the wood of
3/4 inch. (Screws not supplied)
.313 [7.95 mm]
See figure 1.
1. Determine where the module will be
installed
, and ensure that there is
adequate space at both ends for
making the various cable
connections and for reading the
diagnostic LEDs.
2. Attach the module to a flat surface
using two mounting screws.
(Not Supplied)
Rack Module:
The unit is designed to be installed in the ComN
et 19-inch (483-mm) EIA standard card-cage rack, the C1-US,
C1-EU, or the C1-CH. Follow these guidelines to install rack cards after performing module setup procedures.
C1-US,
C1-EU, or the C1-CH Card Cage Racks
CAUTION: Although the units are hot-swappable and may be installed without turning power off to the rack,
ComNet recommends that the power supply be turned off and that the rack power supply is disconnected
from any power source.Note: Remove electrical connector before installing in card cage rack.
1. Make sur
e that the card is oriented right side up, and slide it into the card guides in the rack until the
edge connector at the back of the card seats in the corresponding slot in the rack’s connector panel.
Seating may require thumb pressure on the top and bottom of the card’s front panel.
CAUTION:Take care not to press on any of the LEDs.
2. Tighten the two thumb scr
ews on the card until the front panel of the card is seated against
the front of the rack.
INS_FDX54_REVA
03/06/09
Page 1
![](/html/85/85b4/85b41bc8188134abb260f10b8bdacccf11cf2332be26a5a31d0e6eb35f3e3df8/bg2.png)
FDX54
INSTALLATION INSTRUCTIONS
1 FIBER IN/1 FIBER OUT RS485 2/4 WIRE
DATA REPEATER
MULTIMODE OR SINGLE MODE OPTICAL FIBER
LEDS: RED = “No Activity”
GRN = “Activity”
NOTE: RED DOES NOT MEAN “Error”
WARNING: Unit is to be used with a Listed Class 2 or LPS power supply rated 9-12 VDC @ 1A.
WARNING: This unit should be installed in a restrict
means of security. Access should be limited to service personnel who have been instructed about the reasons for the restrictions
to the location. Any and all precautions should be taken and controlled by the authority responsible for the location.
IMPORTANT SAFEGUARDS:
A) Eleva
the op
Therefore,consideration should be given to installing the equipment in an environment compatible with
the maximum ambient temperature (Tma) specified by the manufacturer.
B) Reduced Air Flow - Installation of the equipment in a rack should be such tha
required for safe operation of the equipment is not compromised.
ted Operating Ambient - If installed in a closed or multi-unit rack assembly,
erating ambient temperature of the rack environment may be greater than room ambient.
BLACK WITH WHITE STRIPE
BLACK
NOTE: Remove Electrical Connector
for Rack Mount Units
ed access location; available through the use of a lock and key or other
t the amount of air flow
INS_FDX54_REVA
03/06/09
Page 2