Comfort Stat CP2801 User Manual

No outputDigital Thermostat Owners Manual
Mode:CP2801
LCD Display:Shows Time,Day,Temperature, and other feature information as required.
Measures and displays heating and cooling system operating time for Today, Yesterday,This Week,Last Week,or Total.
Up and Down Key:Key for changing the Temperature setting. Also used for increasing and decreasing selections in the
functions.
Time,and Span
Backlight key
F
Battery Compartment: Front access allows easy insertion of two AA 1.5V batteries.
Front Door: Battery cover Open with one finger from top.
For entering Time
EMER Mode
Returns display to current time and temperature.
TIME ENER
EMER
RUN
/return
system
cool
heat off
Front Door: Cover keys Open with
Fan Switch: Fan
fan
switch for Automatic or Continuous fan
auto
on
operation.
System Switch: Selector switch for Heat,Cool,and Off.
one finger from left or right.
FEATURES
Structure of thermostat and explanation for the keypads
We are pleased you have selected one of our broad line of wall thermostat.
Our products are manufactured to high quality standards and are designed
for years of service.
For entering Time
EMER Mode
Measures and displays heating and cooling system operating time for Today, Yesterday,This Week,Last
ENER
TIME
EMER
Week,or Total.By monitoring your energy usage,you can
RUN
program the thermostat to optimize energy savings.
Returns display to current
time and temperature.
OPERATION
YOUR THERMOSTAT REPLACES
Description CP2801
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Standard Heat & Cooling Systems Yes
Two Stage Heat & One Stage Cool Yes
Standard Heat Only Systems Yes
Millivolt Heat Only Systems– Floor or Wall
Furnaces
Standard Central Air Conditioning Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat-2 Wires Yes
Hydronic (Hot Water) Zone Heat–3 Wires No
This Thermostat will NOT control 110/220Volt systems.
IMPORTANT
2, Read the entire installation section of this Owner’s Manual thoroughly
before you begin to install or operate your Thermostat.
REMOVE THE MYLAR LABEL FORM THE LCD DISPLAY WINDOW.
INSTALLATION 3, All installation is normally performed at your thermostat. COMPRESSOR PROTECTION
4The thermostat provides a 4 minutes delay after shutting of the heating or
cooling system before it can be restarted. This feature will prevent damage
to your compressor caused by rapid cycling. Note that this delay also applies
to the heating system control. It does not provide a delay when there are
power outages.you can select the function on or off at the configuration.
TEMPERATURE RANGE
5,This thermostat can be programmed between 45˚F and 95˚F (7˚C and
35˚C). However, it will display room temperatures from 30˚F to 99˚F (0˚C and
37˚C). “HI” will be displayed if the temperature is higher than 99˚F (37˚C),
and “LO” will be displayed if the temperature is lower than 30˚F (0˚C).This
thermostat will automatically cutoff in Heat mode if the temperature rises
above 95˚F (35˚C), and automatically cutoff in Cool mode if the temperature
drops below 45˚F (7˚C).
NOTE: The thermostat will automatically change to the Cool mode if the
thermostat measure a temperature over 99˚F(37), ”HI” will be displayed on
the LCD, and the Cooling system will turn On. Similarly, the thermostat will
automatically change to the Heat mode if the temperature is below 32˚F(0℃).
and ”LO” will be displayed on the LCD, and the Heating system will turn On.
POWER FAILURE
6 Whenever the main power is interrupted or fails, the battery power
retains and current time. This thermostat has permanent memory, although
you will have to reset your clock when there are power outages.
POWER SUPPLY
7,The thermostat shall be powered by 24 VAC and with batteries as backup.
BATTERY WARNING
8Fresh alkaline batteries should provide about one year of service.
However, when the batteries become drained, “BATT” will alternate on the
display with the current time. When this message occurs, install 2 new AA
batteries, You have approximately 1 minute to change the batteries and keep
thermostat’s clock. Once the batteries have become too low to ensure
proper operation, your system will be turned off, and the display will be
cleared except for “BATT” flashing on the LCD display. CAUTION: Once only the “BATT” only display occurs, the thermostat is shut
down, and your system will no longer operate. In this condition, there is no temperature control of your dwelling. NOTE: The
backlight will not function when the thermostat is in low battery condition.
NOTE: If you plan to be away from the premises over 30 days, we recommend that you replace the old batteries with new alkaline batteries prior to leaving.
INSTALLATION
What You Need
This thermostat includes two #8 slotted screws and two wall anchors for
mounting. To install your thermostat, you should have the following tools and
materials.
Slotted Screwdriver(s) Small Philips screwdriver Hammer
Ye s
Electric drill and 3/16” bit Two1.5V (AA) size alkaline batteries
(included)
CAUTION: To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
Before removing wires from old thermostat's switching subbase, label each
wire with the terminal designation it was removed from.
1. Shut off electricity at the main fuse box until installation is complete.
Ensure that electrical power is disconnected.
2. Remove Old Thermostat: A standard heat/cool thermostat consists of
three basic parts:
a. The cover, which may be either a snap-on or hinge type.
b. The base, which is removed by loosening all captive screws.
c. The switching subbase, which is removed by unscrewing the mounting
screws that hold it on the wall or adaptor plate.
3. Remove the front cover of the old thermostat. With wires still attached,
remove wall plate from the wall. If the old thermostat has a wall mounting
plate, remove the thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a time. DO NOT LET
WIRES FALL BACK INTO THE WALL.
6. Install new thermostat using the following procedures.
WARNING Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard. Do not shor t out terminals on gas valve or primary control to test. Short or incorre ct wiring will damage thermostat and could cause personal injury and/or property damage.
Selector Switches
Electric/Gas Switch (Fan Option)
Elec-Gas Switch
Figure 1. Electric/Gas Switch (Fan Option)
This thermostat is configured from the factory to operate a heat/ cool, fossil
fuel (gas, oil, etc.), forced air system. It is configured correctly for any system
that DOES NOT require the thermostat to energize the fan on a call for heat.
If you system is an electric heat or heat-pump system that requires the
thermostat to turn on the fan on a call for heat, locate the ELEC/GAS switch
on the back of the thermostat (see fig. 1) and switch it to the ELEC position.
This will allow the thermostat to energize the fan immediately on a call for
heat. If you are unsure if the heating/ cooling system requires the thermostat
to control the fan, contact a qualified heating and air conditioning service
person. When the thermostat is configured for Heat Pump, the thermostat
will always power the circulator fan on a call for heat in the HEAT mode. The
ELEC/GAS switch must be set to match the type of Auxiliary heat your
system uses for proper operation in the EMERgency mode.
All wiring diagrams are for typical systems only. Refer to equipment
manufacturers’ instructions for specific system wiring information.
Attach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover
straight off the base. Forcing or prying on the thermostat will cause damage
to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring
schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole locations on wall
using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws.
Place a level against bottom of base, adjust until level, and then tighten
screws. (Leveling is for appearance only and will not affect thermostat
operation.) If you are using existing mounting holes, or if holes drilled are too
large and do not allow you to tighten base snugly, use plastic screw anchors
to secure subbase.
6. Push excess wire into wall and plug hole with a fireresistant material (such
as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Mounting Hole
Figure 2. Thermostat base
Re v e r s i n g Val ve Energi zed i n Co o l Mode
O
Re v e r s i n g Valve Ener gi zed i n Heat, Off, Emer gency Mode
Y1
B
Co mpr essor Cont act or
Figure 3 Typical wiring diagram for single transformer heat pump
K2
G
Fan Rel ay
systems
GAS
ELEC
Mounting Hole
Aux Heat Re l ay
W2
E/ W1
Emer gency Heat Re l ay
C
SYSTEM MONITOR SWITCH
THERMOSTAT
LR
SYSTEM
TRANSFORMER
( Cl ass Cur r ent
Li mited)
24 VAC
Ho t 120 VAC
Neut r al
CUT A ND TA PE OFF!
HOT
120 VAC
NEUTRAL
E/ W1
Emergency Heat Relay
C
SYSTEM MONITOR SWITCH
O
Reversing
Reversing
Valve
Valve
Energized in
Energized in
Cool Mode
24 VAC
Heat, Off, Emergency Mode
Y1
BG
Compressor Contactor
Fan Relay
W2
Aux Heat Relay
TWO COMM ONS MUST BE J UM PERED TOG ETHER!
L
Limit or Safety Switches
24 VAC
THERMOSTAT
R
SYSTEM
TRANSFORMER
Current Limited)
(Class
Hot 120 VAC Neutral
Figure 4. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
O
Reversing Valve Energized in Cool Mode
Y1
BG
Reversing Valve Energized in Heat, Off, Emergency Mode
Compressor Contactor
Fan Relay
E/W 1
W2
Emergency Heat
Aux
Relay Heat Relay
TWO COMMONS MUST BE JUM PERED T OGETHER!
LR
C
SYSTEM MONITOR SWITCH
COMMON
Limit or Safety Switches
24VAC ACCESSORY RELAY N.O. CONTA CY
Limit or Safety Switches
THERMOSTAT
SYSTEM
24VAC
Auxiliary Heating Transformer
COMMON
(Class Current Limited)
24 VAC
Heat Pump Transformer (Class Current Limited)
Limit or Safety Switches
120VAC
NOT E
The accessory relay scheme is required when safety circuits ez ist in both syste ms
Limit or Safety Switches
120 VAC
HOT
NEUTRAL
HOT
NEUTRAL
Figure 5. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems Heat Pump Terminal Outputs
Refer to equipment manufacturers' instructions for specific system wiring
information. You can configure the thermostat for use with the following heat
pump system types: HEAT PUMP TYPE 1 1. Single stage compressor
system; gas or electric backup. This thermostat is designed to operate a
single-transformer system. If you have a two-transformer system, cut and
tape off one transformer. If transformer safety circuits are in only one of the
systems, remove the transformer of the system with NO safety circuits. If
required, replace remaining transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two commons must be jumpered
together.
Use the terminal output information below to help you wire the thermostat
properly for your heat pump system. After wiring, see CONFIGURATION
section for proper thermostat configuration.
THERMOSTAT TERMINALS (HEAT PUMP)
SYSTEM Heat Pump 1
L Malfunction
C* 24 Volt(Common)
R 24 Volt Emergency (hot)
E/W1 Emergency Mode 1st stage
W2 HP 1 and Emergency 2nd stage
Y1 Heat and Cool mode 1st stage
(compressor)
G
Blower/Fan Energized on call for Heat and
Cool
Set GAS/ELEC switch for Emergency
mode
O Energized in Cool Mode
B Energized in Heat Emergency mode
Reversing Valve Energized in Cool Mode
Reversing Valve Energized in Heat, Off, Emergency Mode
Compressor Contactor Stage 1
Fan Relay
Heat Relay Stage 1
Heat Relay Stage 2
Figure 5. Typical wiring diagram for single transformer multi-stage
systems CHECK THERMOSTAT OPERATION Note: To prevent static discharge problems, touch side of thermostat to release static build-up before touching any keys. If at any time during testing your system does not opera te properly, contact a qualified serviceperson. Fan Operation
If your system does not have a G terminal connection, skip to Heating
System System.
1. Turn on power to system.
2. Move FAN switch to ON position. The blower should begin to operate.
3. Move FAN switch to AUTO position. The blower should stop immediately Heating System
1. Move system switch to heat mode. If the auxiliary heating system has a
standing pilot, be sure to light it.
2. Press to adjust thermostat setting to 1 above room temperature. The
heating system should begin to operate. The display should show “STG1”.
However, if the setpoint temperature display is flashing, the compressor
lockout feature is operating (see Configuration menu, item 5).
3. Adjust temperature setting to 3° above room temperature.If your system
configuration is set at MS2, HP2 or HP1, the auxiliary heat system should
begin to operate and the
display should show “STG1+2”.
4. Press to adjust the thermostat below room temperature. The heating
system should stop operating. Emergency System
EMER bypasses the Heat Pump to use the heat source wired to terminal E
on the thermostat. EMER is typically used when compressor operation is not
desired, or you prefer back-up heat only.
1. Press SYSTEM switch to select Heat mode. then press EMER key..
“EMER” will show on the display.
2. Press to adjust thermostat setting above room temperature. The Aux.
heating system will begin to operate. The display will show “STG1” “EMER”
to indicate that the Aux. system is operating.
3. Adjust temperature setting to 2°C above room temperature.The auxiliary
heat system should begin to operate and the display should show “STG1+2”.
4. Press to adjust the thermostat below room temperature. The Aux. heating
system should stop operating. Cooling System
1. Move SYSTEM switch to select the Cool mode.
2. Press to adjust thermostat setting below room temperature. The blower
should come on immediately on high speed, followed by cold air circulation.
The display should show “STG1”.
Reviewing the Current Temperature Setting
Current time and temperature.
3. Press to adjust the temperature setting above room temperature. The
cooling system should stop operating.
CONFIGURATION MENU
INSTALLER/CONFIGURATION MENU
Step Press
Button
1 F MS 2 SS1, HP2,
Displayed
(Factory
Default)
Press up or
down key
to select
HP1
Comments
Selects Single stage,
Multi-stage, or Heat Pump
(Single stage or 2-stage)
System Configuration
2 F (RECO)off on No use
3 F (SPAN)2 1,3 Span(one stage) set to 1 to
be more accuracy
4 F (BLIT)on off BackLight
5 F (SP2)2 1,3 Span(Two Stage)
6 F (TEMP)F C Selects temperature display
F° or C°
7 F HOUR(12) 24 Selects time format display
12hours or 24hours
8 F COMP(OFF) ON Selects Compressor
Lockout OFF or ON
OPERATION System Selector Switch
The System Selector Switch on the front of the thermostat
determines the Operating mode of the thermostat. You may
select COOL , OFF , HEAT, In order to take full advantage of
this thermostat’s feature. NOTE: Anytime you install or remove the thermostat form the wallplate, slide
the System Selector to the OFF position to prevent the possibility of a rapid
system On-Off.
Fan Switch
The Fan switch should normally be located in the AUTO
position. The Fan will be turned on along with normal
operation of your system. In a normal gas or oil furnace, the
Fan will be turned on by your furnace after its warm-up
delay. For electric heat, air conditioning, and heat pump operation, the Fan
will turn on with the system. To run the Fan on continuously, slide the Fan
switch to the ON position.
Energy Monitor
9 F COOL(1) 2 This model must select 1
10 F FACT(0) 1,2 This model must select 1 to
back factory Default
The configuration menu allows you to set certain thermostat operating
characteristics to your system or personal requirements. Set SYSTEM
switch to OFF, then simultaneously press up and down keys to enter
configuration menu. The display will show the first item in the configuration
menu.The configuration menu table summarizes the configuration options.
An explanation of each option follows.Press F key to change to the next
menu item. To exit the menu and return to the normal operation, press Run
Key. If no keys are pressed within fifteen Seconds, the thermostat will revert
to normal operation.
1)Single Stage, Multi-stage or Heat Pump System Configuration
This control can be configured for Heat Pump or two stage heat/one stage
cool multi-stage operation.The display indicates “MS 2” (default for
multi-stage mode) in the display. The Multi-stage configuration can be
toggled to “SS1”, or “HP1” by pressing the up or down key. In Multi-stage
configuration, EMER mode is useless.in this model.the “HP2” is no use.
2)Fast or Slow Crycle Selection(one stage)
3)Select Backlight function OFF or ON
4) Fast or Slow Crycle Selection(two stage)
5)Select F° or C° Readout.
Changes the display readout to Centigrade or Fahrenheit as required
6) Selects time format display 12hours or 24hours
7)Select Compressor Lockout COMP OFF or ON
Selecting COMP ON will cause the thermostat to wait 4 minutes before
turning on the compressor if the heating and cooling system loses power. It
will also wait 5 minutes minimum between cooling and heating cycles. This is
intended to help protect the compressor from short cycling. Some newer
compressors already have a time delay built in and do not require this
feature. Your compressor manufacturer can tell you if
the lockout feature is already present in their system. When the thermostat
compressor time delay occurs it will flash the setpoint for about four minutes.
8) This model must select 1
9)This model must select 1 to back factory Default
Setting Day and Time
y The LCD will show this information when
TIME
batteries are first installed. The temperature
will update after a few seconds.
y During time and day setting mode, the
temperature displays will go blank.
y Examples: Set the Thermostat to the current time of 2:16 pm on
Saturday.
Refer to the Steps below.
STEP 1:
y Press to enter time and day setting mode.
TIME
The current hour and the AM/PM indicator will
be flashing.
y Press up or down to change the Hour up or
down to the current hour.
Note the AM/PM indicator, as the display will change at 12AM and
12PM.
STEP 2:
TIME
y Press again to change from hour setting to
minute setting. The current minute will be
flashing.
y Press up or down to change the Minute up
or down to the current minute.
STEP 3:
TIME
y Press again to change from minute setting to
day setting. The current days will be flashing.
y Press up or down to change the Day up or
down to the current day.
STEP 4:
TIME
y Press again to change back to the normal
display.
RUN
NOTE: Clearing the Energy Monitor counter will also clear the Filter Monitor
counter , as Filter usage and Total Energy usage are the same. Also,
clearing the filter Monitor counter will clear ALL Energy Monitor counters as
well.
Filter Monitor
Your thermostat also keeps a record of the number of
hours your filter has been in use. To maximize your
system’s performance and energy efficiency,
change or clear your filter regularly.
When the total system run time for heat and cool reaches 500 hours, you
need clean or change your system’s filter, “FILT” will continue to flash until
the counter is set back to zero.
Press to review total filter usage. The display will blink
“FILT”
Then show the filter Monitor counter. After 15seconds, the
display will return to normal mode, or you can hit RUN to
exit immediately.
The Filter Monitor will display up to 999 hours and 59 minutes of usage. In
this example, the counter is at 410 Hours, 26 minutes.
To reset the Filter Monitor counter, depress FILTER for 3 seconds. The
display will blink, and the counter will be reset to zero. NOTE: Clearing the Filter Monitor counter will also clear ALL Energy Monitor
counters, as Filter usage and Total Energy usage are the same. Also,
clearing the Energy Monitor counters will clear the Filter Monitor counter as well.
Keyboard lock
The keyboard can be locked to prevent unauthorized changes to the
thermostat.
To lock or unlock the keyboard, press and hold run Key for 3
seconds.The keyboard is locked.when LOCK appears on
the display.
All keys are locked, Any time a key is pressed, LOCK will appear on the
display for 1 second.
Backlighting
Your thermostat has an electroluminescent lamp that backlights the display
for easy viewing in the dark.
When any key is pressed the display is illuminated.
The display will remain illuminated for 8 seconds after the last key is pressed.
This allows the light to stay on if you need to operate several keys. NOTE: If the thermostat is in Low Battery warning condition, the backlight
will not operate. Replace with 2 new AA alkaline batteries to restore the
Backlight function.
Low Battery Warning
Your thermostat has a two-stage lower battery warning system. When the
batteries are first detected to be weak, the first stage low battery warning is
indicated
by “BATT” flashing on the LCD display. At your earliest
convenience, you need to replace the batteries with 2 new
AA alkaline batteries.
When the batteries become too weak for normal operation,
the thermostat enters the second stage low battery warning
which shuts down the thermostat. In this condition, “BATT”
Press less than 1 second .
Set Temperature is shown above current room temperature.
The Energy monitor feature measures and stores
ENER
the amount of time the heating and air conditioning
system operates. Usage can be display for Today
(since 12 am), Yesterday, This Week (since Monday), Last Week (last
Monday through Sunday), and Total (up to 999 Hrs). By monitoring
your energy usage, you see how much the set-back periods are
saving. To review energy usage, press to cycle through Today,
Yesterday, this Week, Last Week, and Total. Press again to return to
normal mode, or wait 15 seconds for the display to return to normal
mode .You can also return to normal mode at any time by pressing
RUN
RUN.
For example: This LCD display shows Today’s usage to be 10 Hours,
26
minutes.
Press and hold for 3 seconds to reset the Energy Monitor’s
counters.
The display will blink, and counters will be cleared to zero.
flashes alone on the display, and the thermostat will turn your system Off.
Your system will remain shut-off until the batteries are replaced. NOTE: The thermostat will still keep the current Set Temperature and Filter
run time in memory until new batteries are installed. After confirming that
new batteries have been inserted, the thermostat will return to normal
operation.
Error Mode
If the thermostat is unable to control your system due to an
unexpected battery problem, the thermostat will enter Error
system
Mode. In this condition, the thermostat flashes
“E1”,“E2”,”E3”or”E4”on the LCD display, and shuts off your
cool
heat
off
system. To correct this problem, replace the batteries with 2
new AA alkaline batteries, even if you have recently
replaced them. Move the battery out, and then hold any key
to release the rest energy. Then place the battery again. You will need
confirm normal operation.
fan
auto
on
If Error Mode returns, please call us for further information.
Warning Mode
If the SYSTEM MONITOR SWITCH is close show the
system have wrong.the thermostat flashs “E5”on the LCD
Mon
AM
1
HEAT
display. Auto Cut Off
Your thermostat will automatically cutoff in Heat mode if the room
temperature rises above 95˚F (35˚C). It will cutoff in Cool mode if the room
temperature drops below 40˚F (4˚C). Note that if your system has
malfunctioned and no longer responds to thermostat controls, the Auto Cut-Off will have no effect.
TROUBLESHOOTING
Problem
SCRAMBLED OR
Solution
1. Remove clear mylar sticker.
DOUBLE
DISPLAY
(numbers over
numbers)
NO DISPLAY 1. Check battery connections and batteries
2. Move the battery out, and then hold any key to
release the rest energy. Then place the battery
again.
ENTIRE DISPLAY
1. Replace Batteries
DIMS
AUTO/FAN DOES
NOT TURN ON
1. Move Elec/Gas selector to opposite position is in
the correct position.
2. There may be as much as 4 minute delay before
the Heat or Cool system turns On-wait and
check. (Compressor protection delay).
3 Check your circuit breaks and switches to
ensure there is power to the system.
4. Replace batteries.
5. Make sure your furnace blower door is closed
properly.
6. If your system only uses 4-wires, be sure the
jumper wire is installed between the RC and RH
terminals.
7. Check the position of the Furnace or Heat Pump
selector switches: Normal/O/B.
ERRATIC
DISPLAY
1. Move the battery out, and then hold any key to
release the rest energy. Then place the battery
again.
IF UNIT
CONTINUES
1. Replace unit
TO OPERATE IN
THE OFF
POSITION
THERMOSTAT
PERMANENTLY
1. Replace unit.
READS
“E1”,”E2”,”E3”,
“E4”.
If you experience any other problems, call us for technical assistance. The service number is 1-866-591-9898
Loading...