ComAp NPU Installation And Operation Instructions Manual

Software version 1.8, September 2003 Prague, Czech Republic Copyright © 2003 ComAp s.r.o. Written by Libor Šindelářl and Milan Vandírek
ComAp, spol. s r.o.
Světova 7, 180 00 Praha 8, Czech Republic Tel: +420 2 66316661, Fax: +420 2 66316647 E-mail: info@comap.cz, www.comap.cz
NPU Unit
Mains decoupling relay
Installation and Operation Instructions
User guide
NPU, SW Version 1.8, ©ComAp, September 2003 NPU-1.8r2.PDF 2
1. Contents
1. Contents 2
2. Technical Specification 3 NPU Technical Specification 4 NPU Mechanical Design 5
3. Installation 6 Power Supply 6 Analog Inputs 6 Output Relays 6 The NPU Unit Wiring Diagram 7
Connection NPU Unit to phase-to-neutral voltage 7 Connection NPU Unit to phase-to-phase voltage 8
4. Function 9 Protection types 9
Overvoltage protection 9 Undervoltage protection 9 Overfrequency protection 9 Underfrequency protection 9 Voltage assymetry protection 9
Vector shift supervision 9 Phase sequence supervision 10 Frequency measurement 10 Internal watchdog 10 Output Relays 10 Example: Evaluation of under voltage protection 11 Vector Shift Protection 12
5. Settings 14 Buttons 14 Display and LEDs 14 Parameters settings 14
6. Displayed Quantities and Parameters 15 Set A: 15
Default setting 16
Set B: 17
Default setting 17
7. Order codes 19
NPU, SW Version 1.8, ©ComAp, September 2003 NPU-1.8r2.PDF 3
2. Technical Specification
The NPU unit is designed for 3-phase mains protection. Operator can switch on/off available protections or adjust limits and time delays for each protection. Rated voltages are 100, 230, 400, 480 VAC selected by order - see order codes. Measuring voltage frequency range is from 44 up to 68 Hz. NPU power supply voltage can be in the range 90 ÷ 250 VAC or 16 ÷ 110 VDC selected by order - see order codes.
NPU offers following protections:
Over frequency protection
Under frequency protection
Over voltage protection
Under voltage protection
Phase sequence supervision
Voltage asymmetry protection
Vector shift supervision
NPU, SW Version 1.8, ©ComAp, September 2003 NPU-1.8r2.PDF 4
NPU Technical Specification
Parameter Specification
Dimensions 75 x 100 x 115 mm Power supply NPU XXX/YYY/230VAC NPU XXX/YYY/24VDC
90 ÷ 250 VAC 16 ÷ 110 VDC
Power consumption c. 3 W Insulation 4 kV Elmg. Interference immunity According to IEC 50082-2 Elmg. Interference According to IEC 55022 Temperature range
-20 ÷ +70°C
Protection IP20 Rated voltage 100, 230, 400, 480 VAC (by the order) Maximal voltage range Rated + 30 % Rated frequency 50 / 60 Hz Maximal frequency range 44 – 68 Hz Accuracy of frequency measuring 0,2% from rated value (from 10% of rated voltage value) Accuracy of voltage measuring
1% from rated value at rated frequency ± 10% and 25°C 1,5% over whole temperature range
Signal relay contacts
- max. switched voltage / current
- max. switched power
- rated voltage / current
- minimum load
- lifetime
250 V / 4 A rezistive load: 1000 VA AC, 200 W DC inductive load: 500VA AC, 25W DC rezistive load: 250V / 4A AC 200V/0,1A DC, 24V 4A DC inductive load: 250V / 2A AC 200V/0,1A DC, 24V 3A DC 1W / 1VA at U
min
> 10V
1x105 cycles Overvoltage category Class. III Time delay accuracy
0.2% +0÷30ms
NPU, SW Version 1.8, ©ComAp, September 2003 NPU-1.8r2.PDF 5
NPU Mechanical Design
The NPU is packaged in a plastic box for assembly on a mounting plate TS 35 (DIN rail 35 mm). NPU could be also mounted with two screws M4 (with span 60mm) to a mounting board. For this alternative it is necessary to take out and turn clamp on the rare side of the box. NPU has four operating push-buttons. The SET button (for settings) can be protected with cover (fixed by wire with two seals). The NPU has an LED display (four digits) and 10 LEDs for indication. Dimensions are on the figure.
1
1
5
,
0
75,0
100,0
Set
NPU
PWR
ERR
L1
UU
U
f
L2
L3
NPU, SW Version 1.8, ©ComAp, September 2003 NPU-1.8r2.PDF 6
3. Installation
Power Supply
There are two types of NPU units – see chapter 7 – Order codes: NPU XXX/YYY/230VAC power supply is in range 90 ÷ 250 VAC NPU XX/YYY/24VDC power supply is in range 16 ÷ 110 VDC Power supply polarity is not important in the case of DC power. The terminal PE is only as an anti­interference terminal.
Analog Inputs
The rated voltage (100, 230, 400, 480 VAC) is selected by order. Terminals are designed for connection of either phase-to-phase or phase-to-neutral voltage measurement. For connection see wiring diagram.
Output Relays
See wiring diagram. Relays on figure are without supply voltage (failure situation)