ComAp InteliPro Comprehensive Manual

InteliPro
Protection Relay for Parallel Applications
Comprehensive Guide - rev. 1
SW version 1.0, May 2011
Installation and Operation Guide
Communication Brochure
Application Guide
Reference Guide
Copyright © 2011 ComAp s.r.o. Written by Tomas Jelen Prague, Czech Republic
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 246 316 647 E-mail: info@comap.cz, www.comap.cz

Purpose of the InteliPro manuals

Installation and Operation Guide

The Installation and Operation Guide serves for the personnel, providing installation of the InteliPro unit. It contains wiring and setting instructions, needed for service and commissioning of the unit. It also contains introduction of the user interface and necessary procedures to perform setting and operating of the unit. Though InteliPro is very simple and intuitive for the operating personnel, we recommend to keep one copy of this manual available permanently at the installation site, where InteliPro unit is installed, to facilitate the necessary service and operation tasks.

Application Guide

The Application Guide serves for the designers and engineers, who process the necessary documentation and implementation procedures on the installation site, where InteliPro is installed. It contains detailed description of InteliPro functionalities and their practical application.

Communication Brochure

The Communication Brochure gives specific tips for wiring and set-up of communication interface of InteliPro and preparing it for local or remote communication. For more detail about communication of ComAp products, see the IL-NT, IA-NT, IC-NT Communication Guide as published on ComAp
download centre.

Reference Guide

The Reference Guide contains library of setpoints, inputs and outputs functionalities and technical data for the purpose of detailed technical information. This information is referenced in the Installation and Operation Guide and Application Guide.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Comprehensive Guide – r2
2
InteliPro
Protection Relay for Parallel Applications
Installation and Operation Guide
SW version 1.0, May 2011
Installation and Operation Guide
Copyright © 2011 ComAp s.r.o. Written by Tomas Jelen Prague, Czech Republic
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 246 316 647 E-mail: info@comap.cz, www.comap.cz

Table of contents

Introduction.............................................................................................................................................. 3
Conformity declaration ........................................................................................................................ 3
Warnings ............................................................................................................................................. 3
Installation data ....................................................................................................................................... 4
Unpacking the unit - what is in the package ....................................................................................... 4
Mechanical mounting .......................................................................................................................... 4
Terminal diagram ................................................................................................................................5
Voltage and current inputs .................................................................................................................. 5
Binary inputs........................................................................................................................................ 7
Binary outputs ..................................................................................................................................... 7
Analog inputs....................................................................................................................................... 8
Tristate inputs ................................................................................................................................. 9
Recommended wiring ................................................................................................................... 10
Configurability.................................................................................................................................... 11
Options system ................................................................................................................................. 13
User Interface ........................................................................................................................................ 15
Control and navigation Pushbuttons - basic operation ..................................................................... 15
Sinalization LEDs .............................................................................................................................. 15
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-2

Introduction

Thank you for buying ComAp InteliPro protection relay unit. InteliPro is a microprocessor-based door­mounted protective device, providing a comprehensive set of protective and supplementary functionalities. ComAp unique modular concept of HW extension modules, SW options and full configurability allow perfect solution for most of the generator-to-mains parallel applications. For the complete list of protective functions please refer to the chapter "Protective functions in detail" in the Application guide. The full configurability feature allows to cover advanced requirements for mains-decoupling (inter-tie, „G59/2“), as well as other advanced protection applications.

Conformity declaration

Following described machine complies with the appropriate basic safety and health requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type, as brought into circulation by us.

Warnings

Be aware that the relay outputs can change state during and after the unit
setting (before the unit is used again ensure that the proper setting is done)!!!
Be aware that the devices connected to binary outputs of the unit may operate
upon disconnection of power supply, measurement inputs and/or binary
inputs!!!
!!! CAUTION !!!
Dangerous voltage
In no case touch the terminals of voltage measurement!
Adjust set points
All setpoints are pre-adjusted to their typical values. Before putting into operation, the setpoints must
be checked and/or adjusted to the required values.
Installation may be done by qualified personnel only.
To avoid personal injury do not perform any action not specified in this guide!!!
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-3

Inst allation data

Unpacking the unit - what is in the package

The package contains:
InteliPro unit
Relay Card CT2-REL2 plug-in module (plugged in the unit)
Mounting holders
Terminal blocks
NOTE:
The package does not contain any communication module nor any extension module. The required module should be ordered separately.

Mechanical mounting

The unit is to be mounted onto the switchboard door. Requested cutout size is 175x115mm. Use the screw holders delivered with the unit to fix the controller into the door as described on pictures below.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-4

Terminal diagram

Voltage and current inputs

WARNING!
Risk of personal injury due to electric shock when manipulating with voltage terminals under voltage! Be sure the terminals are not under voltage before touching it.
WARNING!
Do not open secondary circuit of current transformers when primary circuit is closed!!! Open the primary circuit first!
Use 1.5 mm
Adjust nominal voltage, nominal current, CT ratio and PT ratio by appropriate setpoints in the Basic Settings group. Learn about how to view and change setpoints in the User interface chapter.
VOLTAGE MEASUREMENT WIRING
G
2
cables for voltage connection and 2.5 mm
L1
2
for current transformers connection.
L2 L3
N
<Comm Trp> /
<Trip 1> /
<Trip 2>
MAINS
VOLTAGE
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
L3L2L1N
1-5
L1
G
<Comm Trp> /
<Trip 1> /
<Trip 2>
VOLTAGE
CURRENT MEASUREMENT WIRING
G
MAINS
K L k l
L3L2L1N
L2 L3
K L k l
K L k l
L1
L2 L3
<Comm Trp> /
<Trip 1> /
<Trip 2>
NVD
AND SYNC CHECK WIRING
G
NVD 1
NVD 2
SYNC
NVD
CHECK
L1
COM
L2
L3
MAINS
CURRENT
L1
L2 L3
N
L2/NL1
N
L1
MAINS
VOLTAGE
L3L2
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-6

Binary inputs

Use min. 1 mm
NOTE:
The name and function or alarm type for each binary input have to be assigned during the
configuration.
2
cables for wiring of binary inputs.
WIRING OF BINARY INPUTS

Binary outputs

Use min. 1 mm
below for all outputs except those where low-current loads are connected (signalization etc..).
NOTE:
The function of each output has to be assigned during the configuration.
CAUTION!
Use suppression diodes on all relays and other inductive loads!
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
2
cables for wiring of binary outputs. Use external relays as indicated on the schematic
1-7
WIRING OF BINARY OUTPUTS

Analog inputs

The analog inputs are designed for resistive automotive type sensors like VDO or DATCON. The sensors are connected either by one wire (the second pole is sensor body) or by two wires.
In case of grounded sensors connect the AI COM terminal to the engine body as near from the sensors as possible.
In case of isolated sensors connect the AI COM terminal to the negative power supply terminal of the controller as well as the opposite poles of the sensors.
NOTE:
The fail sensor alarm is issued if the measured resistance is smaller than one half of the first (lowest) point of the sensor curve characteristic or is greater than 112,5% of the last (greatest) point of the sensor curve characteristic.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-8
W
IRING OF ANALOG INPUTS - GROUNDED SENSORS
WIRING OF ANALOG INPUTS - ISOLATED SENSORS

Tristate inputs

Analog inputs can be used also as binary or tristate, i.e. for contact sensors without or with circuit check. The threshold level is 750. In case of tristate, values lower than 10 and values over 2400 are evaluated as sensor failure (short or open circuit).
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-9
WIRING OF ANALOG INPUTS - USED AS BINARY OR TRISTATE
NOTE:
The name, sensor characteristic and alarm types for each analog input have to be assigned during the configuration.

Recommended wiring

In the diagram below, see the typical wiring of the InteliPro unit inputs and outputs. The wiring is to be considered as an example for the default configuration and operation mode with 1 common trip output The relay contacts of Relay Card CT2-REL2 module can be reconfigured to Trip 1 and Trip 2 outputs in case of operation with 2 trip outputs particular needs of the application.
, as well as any inputs and outputs can be reconfigured to the
.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-10
LOAD
dry contact to
CB1 backup
L1
L2 L3
N
dry contact to CB1 OFF coil
K L k l
!Comm Trp
K L k l
K L k l
K L k l
CB1
(MCB)
CB2
(GCB)
G
Block 2
Block 1
CB1 Feedback
CB2 Feedback
Alar m 8
F.R. But ton
Alar m 9
Access Lock
DC Tri p Cir cuit
!Bak Comm Trp
CAN bus to
extension
analog
inputs
open collector bin.
outputs (signalling)
modules
CAN bus to
ComAp
controllers
+ -

Configurability

One of the key features of InteliPro unit is high level of flexibility and adaptability of the system to the
particular application. The way how to achieve this is the configuration. Use LiteEdit PC software to
read the configuration from the controller or disk, view it, modify it and write the configuration to controller or disk. To work with InteliPro, LiteEdit version 4.5.2 or higher is necessary. Visit
www.comap.cz
The firmware contains large number of binary inputs and outputs. However, not all functions are required the application, also the controller hardware does not as many input and output terminals. One of main tasks of the configuration is mapping of "logical" firmware input and output signals to the "physical" hardware inputs and outputs.
Configuration parts:
1. Mapping of logical binary inputs (functions) or assigning alarms to physical binary input terminals
2. Mapping of logical binary outputs (functions) to physical binary output terminals
3. Assigning sensor characteristics and alarms to analog inputs
4. Assigning control values and output characteristics to analog outputs
for download or update of this PC application.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-11
5. Selecting of peripherial modules which are connected to the controller and doing the same as above for them
6. Changing language of the unit texts
PRINCIPLE OF BINARY INPUTS AND OUTPUTS CONFIGURATION
The unit is delivered with a default configuration, which should fit to most standard applications.
This default configuration can be changed only using PC and LiteEdit software. See LiteEdit documentation for details.
NOTE:
You need one of communication modules to connect the controller to a PC with LiteEdit. There is a special easy removable service module for cases, where there is no communication module permanently attached.
Once the configuration is modified, it can be stored in a file for later usage with another controller or
for backup purposes. The file is called archive and has file extension "aic". An archive contains full
image of the controller at the moment of saving (if the controller is online to the PC) except firmware, i.e. besides configuration there are also current adjustment of all setpoints, all measured values, copy of history log and copy of alarm list.
The archive can be simply used for cloning of InteliPro units, which means preparing units with
identical configuration and settings.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-12
CONFIGURATION WINDOW IN LITEEDIT

Options system

The unit offers wide range of protective functionalities. To allow flexibility of the protective functions at the particular application, some of the features are provided as SW options. These functions are unlocked by a software dongle, delivered by ComAp or its approved distributors. The SW dongle is a unique number generated according to the serial number of the unit and the selected protective functions. The functions are referred by their ANSI numbers, according to the following table:
IPro-25 Synch Check IPro-51V Time over current with voltage control IPro-59N Neutral voltage displacement IPro-67 Directional overcurrent IPro-78 Vector shift IPro-79 AC reclosing relay IPro-81R Rate of change of frequency + rocof filter
The appropriate selection of InteliPro optional functions is to be marked on the rear side of the unit:
For unlocking the desired functions or changing those functions that are already unlocked, contact your sales person for the appropriate SW dongle. The following information will be needed:
- Serial number of the unit
- List of requested functions to unlock
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-13
Entering the SW dongle: once received the appropriate SW dongle relative to the unit serial number, go to the setpoint Basic Settings: Dongle and enter the numerical string, which you have obtained. Though it is more
convenient to enter the SW dongle via LiteEdit PC software, it is also possible to enter it through the controller screen and pushbuttons.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-14

User Interface

128 x 64 pixels graphical display
Control and navigation pushbuttons
Fault Reset button
TRIP LED
Signalization LEDs

Control and navigation Pushbuttons - basic operation

General operation using buttons:
In the measurement screens, use the measured values as displayed on the graphical display. See the chapter Measurement screens to get the basic orientation.
Use the view the history table. For setpoints change, see the following chapter.
To enter the init screen, change language or read the list of unlocked InteliPro options, push
the performs lamp test by simultaneous blinking of all LEDs.
For confirmation of change any setpoint, use the
Entering the password
The password must be entered prior adjusting setpoints, that are password-protected. Password is located in the first group of setpoints and the way how to enter or change password is similar to change of setpoints.
button to cycle through display of measurement screens, adjust setpoints and
and buttons at the same time. Together with the init screen display, the unit
and , arrow buttons to browse through the
button.
NOTE:
It is possible to change only passwords of the same or lower level than actually entered password!

Sinalization LEDs

There are 5 LEDs for indication of InteliPro status with the meaning indicated in the table below:
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
1-15
LED state Meaning
-
(red)
-
(green)
ON
(green)
OFF
Status of the InteliPro unit - used in combination with green LED, see the table below
Status of the InteliPro unit - used in combination with red LED, see the table below
CB1 feedback - activated - state "I"
CB1 feedback - deactivated - state "0"
ON
CB2 feedback - activated - state "I"
(green)
OFF
ON
CB2 feedback - deactivated - state "0"
Indicates TRIP state, measured values are in fault conditions (out of limits)
(red)
blinking
Indicates TRIP state, measured values are in fault-free conditions (within limits)
(red)
OFF
The unit is not in TRIP state
Status LED signalization:
red green state Display reading Meaning OFF OFF
blink OFF
ON OFF
ON ON
"Program Corrupted" or "System Error" or "System Error + Wrong config format" Normal reading Wrong checksum of parameters Check the complete settings
Normal reading Wrong checksum of "R" parameters Contact technical support
No power supply or PowerFail occured
Transient SW failure Contact technical support with information abut the display message
of your unit and change any one of the parameters. If the state persists, contact technical support
blink ON
OFF ON
blink blink
Normal reading Watchdog reset was performed Save the archive, contact
Normal reading Normal operation of the unit
Not initialized Unit HW failure → Request repair of the unit
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Installation and Operation Guide
technical support and attach the archive
1-16
InteliPro
Protection Relay for Parallel Applications
Application Guide
SW version 1.0, May 2011
Application Guide
Copyright © 2011 ComAp s.r.o. Written by Tomas Jelen Prague, Czech Republic
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 246 316 647 E-mail: info@comap.cz, www.comap.cz

Table of contents

Introduction.............................................................................................................................................. 2
Operation mode with 1 common trip output........................................................................................ 3
Operation mode with 2 trip outputs ..................................................................................................... 4
Priority switching ................................................................................................................................. 4
TRIP and Fault Reset description ....................................................................................................... 5
TRIP................................................................................................................................................ 5
Fault reset ....................................................................................................................................... 5
Shared peripheries.............................................................................................................................. 5
Protective functions ................................................................................................................................. 7
The concept......................................................................................................................................... 7
Protective functions in detail ............................................................................................................... 8
Overvoltage, Undervoltage (ANSI 59, 27) ...................................................................................... 8
Overfrequency, Underfrequency (ANSI 81 H, L)............................................................................ 8
Voltage unbalance (ANSI 47) ......................................................................................................... 8
"Loss of mains" protections ............................................................................................................ 8
Vector shift (ANSI 78) ..................................................................................................................... 8
Rate Of Change Of Frequency (df/dt, ROCOF, ANSI 81R) ........................................................... 9
Overcurrent: definite-time, IDMT and with voltage control ........................................................... 10
Neutral overcurrent (ANSI 50N, ANSI 51N) ................................................................................. 11
Current unbalance (ANSI 46) ....................................................................................................... 11
Directional overcurrent (DOC, ANSI 67)....................................................................................... 11
Neutral Voltage Displacement (NVD, ANSI 59N)......................................................................... 12
Directional power (ANSI 32) ......................................................................................................... 12
Synchro check (ANSI 25) ............................................................................................................. 13
AC reclosing (ANSI 79)................................................................................................................. 13
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Application Guide
2-2

Introduction

InteliPro protection relay provides high range of flexibility to the users and their applications. In the most common cases, one output for tripping is used. In this case, InteliPro allows provides the common trip output, which represents logical "OR" of all activated and pre-set protective functions of the unit. If needed, InteliPro also allows to operate two circuit breakers, where some protective functions are assigned to one of them and other functions to the other. In such case, the circuit breakers can provide backup for each other, so that in "fail to trip" situation the other circuit breaker opens under pre-set conditions to clear the first breaker failure. Furthermore, InteliPro provides two independent blocking inputs, which can be used to activate or deactivate any of the protective functions of the unit. All necessary inputs and outputs can be freely configured to any input or output of the unit. In case of outputs, any of the 2 relay outputs or 8 open­collector outputs can be selected. In case that any of the configured protective functions is activated, InteliPro relay provides a Trip signal. This signal is provided in both positive and negative logic in order to follow the requirements of the application:
Due to increased safety requirements, some protective relays require that negative logic is used, assuring that loss off power supply always causes the relay to trip. I.e. the relay contacts are used, with fault-free position maintained in energized state. In case of power supply fail, the unit goes to “fault” indication position. The outputs using negative logic are marked with exclamation mark "!" as the first character of their name.
In some applications, the negative logic is not a required functionality. The function of opening the circuit breaker in case of loss of power supply is not accepted as a safety point and the safety is assured by different means e.g. in the superior system or within the protection relays intertripping scheme. In such case, the outputs with positive logic (without the exclamation mark) can be used to signal the detected failure state.
In any case, it must be assured that the InteliPro relay has full control at opening the appropriate breaker by the trip command - i.e. in case of Trip state the unit receives the appropriate CB feedback, confirming its open position. The feedback must repond within preset time to the trip command. A special attention should be paid to opening of motorized circuit breakers, as it could take more than 2s on some types. In such cases it is necessary to use undervoltage coil for fast opening.

Operation mode with 1 common trip output

This is the essential mode of operation of the protection relay InteliPro. In this case, CB1 circuit breaker or contactor is considered as the main connection device, protected by InteliPro. In the ComAp controllers, this breaker is called "Mains Circuit Breaker" = MCB.
Second circuit breaker or contactor is not expected in the protection scheme, but there is still possibility to use the "backup trip" signal from InteliPro relay to operate any backup device, if present on the installation. As such device may be considered another circuit breaker in the line of mains-connection, CB1 undervoltage coil, or any device which serves as a backup in case of the CB1 fail.
The Comm Trp (or !Comm Trp) output is used as the main signal to open the CB1 circuit breaker. InteliPro expects that in such case, the CB1 Feedback input deactivates as a result of the protection trip. Adjustable delay can be set by the setpoint General: BackupTrp Del, to provide backup functionality for the CB1 breaker. If the feedback does not deactivate within this delay, the output Bak Comm Trp activates (or !Bak Comm Trp deactivates) immediately.
An function, which is activated and not blocked within the InteliPro unit activated the Comm Trp signal. Use the blocking inputs to control which protective functions will be used under the appropriate circumstances.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Application Guide
2-3

Operation mode with 2 trip outputs

In some cases, the protection relay is requested to operate two circuit breakers. Usually, one of them is considered as the main circuit breaker, with most of the functions configured to operate this cicrcuit breaker. As mentioned above, this breaker often corresponds to the "Mains Circuit Breaker" = MCB as used in ComAp controllers.
The second circuit breaker can be from the point of view of the protection relay considered as a supplementary connection device in the power connection scheme. It can provide back-up functionality in case that the CB1 does not trip on command, or can be operated individually by selected protective functions. It can, but does not necessarily have to correspond to the "Generator Circuit breaker" = GCB as used in the ComAp controllers applications. In such case, e.g. NVD function is the most often case, when GCB (CB2) is tripped instead of MCB (CB1).
In case that 2 circuit breakers are controled by InteliPro unit, it is possible to freely assign, swap or configure the functionalities of both circuit breakers and provide appropriate back-up function of the breakers by the "Priority switching" functionality. It is not practical to use the Comm Trp output in this case. To distinguish between the 2 breakers, outputs Trip 1 and Trip 2 are available.
For each protective function in InteliPro, it is possible to assign either Trip 1 or Trip 2 function, none of them, or both. The setpoint xxx Trp BO in the appropriate group of protection setting is used for this assignment. By this setting, the output Trip 1 or 2 will then contain only those functions which were assigned to it.
Trip 1 output is internally interconnected with CB1 operation, i.e. in case of activation of Trip 1, the CB1 feedback is expected to deactivate. The same applies for Trip 2: in case of activation of Trip 2, the CB2 feedback is expected to deactivate.

Priority switching

Priority switching feature allows using the circuit breakers CB1 and CB2 as a backup to the other one. To clearly understand this, it is necessary first to understand the possibility of assignment of any of the operated two circuit breakers to the appropriate protective function (see the chapter Operation mode with 2 trip outputs). Though both of the breakers are equivalent and fully assignable within the InteliPro relay, the most common application for generator-to-mains connection is as follows:
CB1 is considered as the main connection device of the generator to the mains. In ComAp products, this breaker is called "Mains Circuit Breaker" = MCB.
CB2 is considered as a supplementary connection device on the power connection between generator and mains. There can be specific protection functions assigned the trip CB2 only and it can provide back-up functionality to the CB1. It can, but does not necessarily have to correspond to the "Generator Circuit breaker" = GCB as used in the ComAp products.
As both circuit breakers are equivalent, it is possible to assign CB2 as the main one and CB1 as the backup, or provide a symmetrical backup of both breakers "one to each other".
Depending on setting the setpoint General: Prio Switching, the following backup function is provided:
DISABLED - no CB backup is provided CB1 -> CB2 - CB1 is considered as the primary switch. If the feedback is not deactivated within preset
period after Trp 1, the output Trp 2 is issued immediately to trip CB2 as backup. Bak Trp 1 is issued at the same time.
CB1 <- CB2 - CB2 is considered as the primary switch. If the feedback is not deactivated within preset
period after Trp 2, the output Trp 1 is issued immediately to trip CB2 as backup. Bak Trp 2 is issued at the same time.
CB1 <-> CB2 - both CBs provide a backup switching for each other. If the CB1 feedback doesn't
deactivate in preset period, CB2 is tripped, if the CB2 feedback doesn't come in preset period, CB1 is tripped.
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Application Guide
2-4

TRIP and Fault Reset description

TRIP

TRIP may be considered as event or status of the unit:
TRIP event:
Starts in the moment of terminating the count-down of any protective function with delay, or in the moment of activation of any immediate protective function.
As a result of the trip event, are e.g. the following consequences:
o Immediate deactivation of outputs !Comm Trp o LED TRIP goes to red o History record is created
TRIP status:
Starts at the moment of TRIP event
During this status, the !Comm Trp output keeps in the fault position
During this status, it is not possible to perform Fault reset
TRIP status is active until a successful Fault reset. This may not be done before all measured and
evaluated values are within preset limits.
If during the TRIP status, caused by some value, another value overreached its limits for TRIP evaluation, this second overreach is not considered as TRIP. It does not cause a second TRIP event. However, as a consequence of this, the TRIP duration may be prolonged until the moment when both (all) values are within limits.

Fault reset

Fault reset is an event, caused by either of the following reasons:
Fault reset
Input input F.R. Button is activated
Automatic fault reset is performed according to the setting of General: Auto FR setpoint.
By activation or deactivation of binary input Block 1 or Block 2.
The abovementioned reasons are a trigger to provide Fault reset, however, it is successfully done only in case that the TRIP status is activated and all evaluated values have returned back into limits. If the TRIP status is not activated, or it is activated, but any of the values is still out of limits, Fault reset is not done and any of the mentioned triggers is forgotten. I.e., the unit may not be „provisionally“ fault­reset. By a successful Fault reset, the TRIP status is terminated.
button is pressed

Shared peripheries

The function is compatible with IG/IS-NT controllers. CAN2 interconnection between the gen-set controllers and InteliPro is necessary to allow this feature. Use the LiteEdit configuration window to configure the appropriate binary and analog values to be transmitted from InteliPro via the CAN2
communication. In the Configuration window, click the
button. The following window opens:
InteliPro, SW version 1.0, ©ComAp – May 2011 InteliPro Application Guide
2-5
Loading...
+ 53 hidden pages