ComAp IG-NT, IG-NTC, IG-NT-BB, IG-NTC-BB, IS-NT-BB Operator Guide

...
Page 1
ComAp, a.s
E-mail: info@comap.cz, www.comap.cz
InteliGen
NT
, InteliSys
NT
Operator Guide
IG-NT, IG-NTC, IG-NT-BB, IG-NTC-BB, IS-NT-BB, IS-NTC-BB, IM-NT, IM-NT-BB, IM-NTC-BB
Copyright © 2006 ComAp a.s,. Written by Pavel Mareš Prague, Czech Republic
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Page 2

Table of Contents

Table of Contents .................................................................................................................................... 2
General guidelines ................................................................................................................................... 3
Description of the controller system .................................................................................................... 3
Conformity declaration ........................................................................................................................ 3
!! Warnings !! ....................................................................................................................................... 3
Dangerous voltage .............................................................................................................................. 4
Adjust set points .................................................................................................................................. 4
Adjust set points .................................................................................................................................. 4
Available related documentation ............................................................................................................. 5
InteliVision 5 ............................................................................................................................................ 6
Page Structure .................................................................................................................................... 8
Connection .......................................................................................................................................... 9
Alarms ................................................................................................................................................. 9
Setpoint Change................................................................................................................................ 11
Entering the Password ...................................................................................................................... 12
History ............................................................................................................................................... 17
Display Contrast Adjustment ............................................................................................................. 17
Controller Information Screen ........................................................................................................... 18
InteliVision 8 .......................................................................................................................................... 19
Page Structure .................................................................................................................................. 24
Connection ........................................................................................................................................ 25
Alarms ............................................................................................................................................... 26
Setpoint Change................................................................................................................................ 28
Entering the password ...................................................................................................................... 31
History ............................................................................................................................................... 32
Display Contrast Adjustment ............................................................................................................. 33
Controller Information Screen ........................................................................................................... 35
InteliGen
Mode and function description............................................................................................................... 54
List of abbreviations ............................................................................................................................... 57
NT
GC and InteliSysNT .............................................................................................................. 36
InteliGenNTGC pushbuttons and LEDs ............................................................................................ 36
InteliSysNT Basebox pushbuttons and LEDs ................................................................................... 38
Description of InteliGenNT MEASUREMENT screens ....................................................................... 44
Description of InteliSysNT MEASUREMENT screens ........................................................................ 47
Users and Passwords ....................................................................................................................... 53
OFF mode ......................................................................................................................................... 54
MAN mode ........................................................................................................................................ 54
AUT mode ......................................................................................................................................... 54
TEST mode (SPtM only) ................................................................................................................... 55
SEM mode ......................................................................................................................................... 55
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
2
Page 3

General guidelines

Be aware that the binary outputs can change state during and after software
This manual provides general information on how to operate the IG/IS-NT controller via InteliVision 5, InteliVision 8, IS-Display or from the front panel of InteliGen
intended for everybody who is concerned with operation and maintenance of the gen-set.
NT
GC or InteliMainsNT GC. This manual is

Description of the contr oller system

NT family controllers are comprehensive AMF-controllers for single and multiple generating sets operating in stand-by or parallel modes. Synchronizer, isochronous load sharer, Mains and Generator protections allow for a total integrated solution for gen-sets in stand-by and parallel modes with multiple engine support. NT family controllers (IG-NT, IG-NTC, IG-NT-BB, IG-NTC-BB, IS-NT-BB, IS-NTC-BB, IM-NT, IM-NT­BB and IM-NTC-BB) could be equipped with a powerful colour display showing icons, symbols and bar-graphs for intuitive operatio n, w hich sets , tog ether with high functionality, new standar ds in gen-set controls. The controller automatically starts the gen-set, closes the gen-set C.B. when all conditions are met, then stops the engine on external signal or by pressing push buttons. Parallel to Mains operation can be achieved without additional HW. Forward and reverse synchronizing, Mains protection including vector shift, load and power factor control, earth fault protection are the major functions provided. Interfacing to foreign synchronizers and load sharers is supported. The key feature of NT family controllers is their easy-to-use installat ion and operation. Predefined configurations for typical applications are available as well as user-defined configurations for special applications.

Conformity declaration

Following described machine complies with the appropriate basic safety and health requirement of the EC Low Voltage Directive 2006/95/EC and EC Electromagnetic Compatibility Directive 2004/108/EEC based on its design and type, as brought into circulation by us.
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.

!! Warnings !!

reprogramming (before the controller is used again ensure that the proper
configuration and setpoint settings are set in the controller)!!!
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
3
Page 4
Be aware that gen-set can automatically or remotely start when following
controller terminals are disconnected !!!
!!! CAUTION !!!
Mains voltage measuring and / or
Binary outputs for MCB control and / or
MCB feedback
Switch InteliGenNT to OFF mode and disconnect the Binary outputs Starter and Fuel
to avoid unexpected automatic start of gen-set and GCB closing.

Dangerous voltage

In no case touch the terminals for voltage and current measurement! Always properly connect grounding terminals!
Take care when disconnecting In/Im3 terminals when the gen-set is stopped. For safety connect parallel to controller In/Im3 terminals two anti parallel diodes 10A/100V.
In any case do not disconnect generator CT terminals when the gen-set is loaded.

Adjust set points

All setpoints are preadjusted to their typical values. But the setpoints in the “Basic settings” settings group !!must!! be adjusted before the first startup of the gen-
set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
4
Page 5

Available related documentation

PDF files
Description
General description of SPtM applications for
Inputs and Logical Binary Output.
General description of SPI applications for
Inputs and Logical Binary Output.
General description of MINT applications for
Logical Binary Inputs and Logical Binary Output.
General description of Combi applications for
Logical Binary Inputs and Logical Binary Output.
General description of COX applications for
Logical Binary Inputs and Logical Binary Output.
Applications of InteliGen NT, InteliSys NT and
peripheries.
Operator Guide for all hardware variation of InteliVision 8.
Thorough description of installation and
accessories.
Thorough description of connectivity and and InteliMains NT and related accessories.
How to solve most common troubles with Including the list of alarm massages.
Thorough description of accessory modules for
to controller and set them properly.
InteliGen NT and InteliSys NT. Contains
IGS-NT-SPTM-3.0 Reference Guide.pdf
IGS-NT-SPI-3.0 Reference Guide.pdf
IGS-NT-MINT-3.0 Reference Guide.pdf
IGS-NT-Combi-3.0 Reference Guide.pdf
description of engine and generat or contr o l, control of power in parallel to mains operation, list of all Setpoints, Values, Logical Binary
InteliGen NT and InteliSys NT. Contains description of engine and generat or contr o l, control of power in parallel to mains operation, list of all Setpoints, Values, Logical Binary
InteliGen NT and InteliSys NT. Contains description of engine and generat or contr o l, powermanagement, list of all Setpoints, Values,
InteliGen NT and InteliSys NT. Contains description of engine, and gener ator contr ol in SPTM, SPI and MINT mode, powermanagement, list of all Setpoints, Values,
IGS-NT-COX-3.0 Reference Guide.pdf
IGS-NT Application Guide 05-2013.pdf
IGS-NT Operator Guide 05-2013.pdf
IGS-NT Installation Guide 05-2013.pdf
IGS-NT Communication Guide 05-2013.pdf
IGS-NT Troubleshooting Guide 05-2013.pdf
IGS-NT & ID-DCU Accessory Modules 05-2013.pdf
InteliGen NT and InteliSys NT. Contains description of engine and generat or contr o l, powermanagement, list of all Setpoints, Values,
InteliMains NT, examples of connection, description of PLC functions, Virtual and Shared
InteliGen NT and InteliSys NT, InteliVision 5 and
technical information about InteliGen NT, InteliSys NT and InteliMains NT and related
communication for InteliGen NT, InteliSys NT
InteliGen NT and InteliSys NT controllers.
IGS-NT family, technical data, information about installation of the modules, how to connect them
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
5
Page 6

InteliVision 5

1
2
3
4
5
14
13
12
11
678
5
910
15
POSITION
DESCRIPTION
1
Status LED indication. The InteliVision 5 is running.
POSITION
BUTTON
DESCRIPTION
Up button. Use this button to move up, scrol l up the
screens or increase a value.
Menu button. Use this button to switch to menu for more details.
Enter button. Use this button to enter item from the list, menu, or confirm a value.
Down button. Use this button to move down, scroll down the screens or decrease a value.
INTELIVISION 5 INDICATION
DISPLAY AND CONTROL BUTTONS
2
3
subpages. See Pages Structure chapter below this table
4
5
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
6
Page 7
POSITION
INDICATOR DESCRIPTION
6
Mode button. Use this button to call mode change.*
7
History button. Use this button to call controller history screen.*
8
Alarm list button. Use this button to enter Alarm list.*
GCB button. Works in MAN mode only. Press this button to open or
otherwise GCB closing is blocked.*
MCB button. Works in MAN mode only. Press this button to open or
Be sure you know well what you are about to do!
POSITION
BUTTON
DESCRIPTION
Stop button. Works in MAN and SEM mode only. Press this
down or cooling) and next phase will continue.
Fault reset button. Use this butt on t o ack nowledge alarms and deactivate the horn output. Inactive alarms will disappear
dismiss.
Horn rest button. Use this button to deactivate the horn output without acknowledging the alarms.
Start button. Works in MAN and SEM mode only. Press this button to initiate the start sequence of the engine.
15 Colour display, 320x240 pixels.
CONTEXT SENSITIVE BUTTONS
9
close the GCB manually. Note that certain conditions must be valid
close the MCB manually.*
10
CAUTION!
You can disconnect the load from the mains supply with this button!
* - It is valid in default configuration only. Screens description and buttons 6 to 10 could have different meaning in customized versions or SW branches .
GEN-SET CONTROL BUTTONS AND DISPLAY
button to initiate the stop sequence of the gen-set. Repeated
11
pressing or holding the button for more than 2s will cancel current phase of stop sequence (like ramping the power
12
immediately and status of active alarms will be changed to “confirmed” so they will disappear as soon as their reasons
13
14
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
7
Page 8

Page Structure

+
+
+
+
Metering
Setpoints
Menu
AlarmList
History
Help/Othhers
Display Screens and Pages Structure The displayed information is structured into "pages" and "screens".
1. The pages Metering consists of screens which displays measured values like voltages, current, oil pressure etc., computed values like i.e. gen-set power, statistic data and etc.. Use arrows Up and Down buttons to switch over the pages.
2. The Setpoints screen contains all setpoints organized to groups and also a special group for entering password.
3. The History screen shows the history log in the order that the last record is displayed first.
4. Help/Others screen allows set-up languages, user access, InteliVision 5 setting and etc..
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
8
Page 9

Connection

Alarm indication
Second level alarm
First level alarm
Direct button to AlarmList
Configuration reading
InteliVision 5 information SW, HW version and release date

Alarms

Alarms are structured into two levels and inteliVision 5 allows easy interpreted their meaning based on the colour schem e. First level alarm (yellow lamp, warnings) is
interpreted with yellow colour . Red colour is used for all second level alarms (Red lamp, ShutDown,…). When an error occurs, a new alarm appears in the AlarmList screen, exclamation mark starts blinking on the metering screens.
Hint:
When a new alarm appears AlarmList screen is displayed automatically when the main/first Metering screen is dis pl ay ed. From different screen, Alarm button has to be used to display AlarmLis t scr een.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
9
Page 10

AlarmList Screen

Number of active alarms
Sum of unacknowledged active and inactive al arms
Sum of all alarms
Second level alarm
First level alarm
Second level alarm
First level alarm
Active ECU alarm
Inactive unacknowledged first level alarm
Active unacknowledged first level alarm
Inactive unacknowledged second level alarm
Active unacknowledged second level alarm

Alarm activated with analogue value

Alarm activated with binary inputs

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
10
Page 11

Setpoint Change

+
Hint:
Setpoints marked wit h a padlock icon are password protected. Enter password as described in the chapter Entering the Password below.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
11
Page 12

Entering the Password

+
Locked setpoint
Display is locked, no user is logged in

Locked Display and Setpoints

Hint:
Log in? Password dialog has to be open and then use → or ← for position and f or the field use ↑ or ↓.
Password is a five-digit number (0 - 65535). Only setpoints associated with the entered password level can be modified. Display is locked automatically when no action is done within 15 minutes.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
12
Page 13
Hint:
Display is unlocked, an user is logged in
Unlocked setpoint
Min ... Max value
Actual cursor position
Actual setpoint value
Cursor position - Arrow right Cursor position - Arrow left
Break through password prottection
- Break through password function can be ENABLED/DISABLED from the password management window in InteliMonitor (initial status is DISABLED).
- Warning “PassInsertBlck” appears in alarm list when controller is blocked
- It is not allowed to insert the password in case that controller is blocked. There is information that controller is blocked for next password attempt and time remaining till the end of blocation instead of password input window at the terminal screen.
- The controller is locked for 5 minutes when the password is 6 times wrong entered (in case of next 6 wrong attempts (correct password was not inserted at all) for 30, 60, 120, 240 minutes). Incorrect password message appears in the history of the controller when the invalid password is used.

Unlocked Display and Setpoints

For setpoints change use arrows ↑ or ↓ to go to a certain setpoint (e.g. Base load) and press Enter button, see pictures below:

Numeric Setpoint Change

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
13
Page 14
Use → or ← buttons to go to a certain position of the field and use ↑ or ↓ buttons to change the value. Then use Enter button to confirm new val ue.
Hint: If you set the value out of limit, the field will get red colour and the new value is invalid. Invalid value cannot be confirmed.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
14
Page 15
Actual setpoint value
Sum of the setpoints group
Actual position in characters list
Actual setpoints group
Cursor position - Arrow right Cursor position - Arrow left
Numbers / lower case / upper case
Insert space / character
Remove space / character
Direct button to the last Metering screen

String Selection

Use ↑ or ↓ buttons to select the string from the list and press the Enter button.

String Edit

Use ↑ or ↓ buttons to select the character and → ← buttons for the next position and press Enter button.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
15
Page 16

Time and Date Edit

Scroll bar shows cursor position on the current screen
Cursor position - Arrow right Cursor position - Arrow left
Cursor position - Arrow right Cursor position - Arrow left
Actual setpoint value
Use ↑ ↓ buttons to select the number, → ← for the next position and press Enter button.

Combined Setpoints

Use or buttons to select the number, or for the next position or go Up or go Down context buttons and press Enter button.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
16
Page 17

History

Hold
Press
Or press
Direct button to the last Metering screen
Direct button to the first position / or column
In the history log
Page scroll (1x, 1x Page, 10x Page)
Scroll history log - Arrow right
Scroll history log - Arrow left

History page

Display Contrast Adjustment

Display brightness could be set from the keyboard with button combination Menu button and ↑ or ↓.
Two modes for backlight could be used day or night mode. Hold Menu button until the day or night pictogram app ear s.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
17
Page 18
Serial number
Password decode
Day mode - active
Night mode - inactive
Hint:
Display backlight could be switched off due to Backlight Time. For recovery any button has to be pressed. (see IV5 Settings).

Controller Information Screen

Hint:
Lost password? Display the information screen containing the serial number and password decode num ber as descr i be d in the picture bellow and send them to your local distributor.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
18
Page 19

InteliVision 8

2
1
3
4
567
891011
1213
14
123
654
DIRECT BUTTONS (GROUP 1)
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
19
Page 20
POSITION
BUTTON
DESCRIPTION
Help/Others - settings and information (users/passwords, Measurement button. Display actual values (power, synchro,
Trends button. Use this button to go to the trends screen
displayed.
1
2
3
4
communication, languages, InteliVision 8 and controller info, InteliVision 8 settings)
History button. Use this button to call controller history.
Alarm list button. Use this button to enter AlarmList.
analog. inputs, binary I/O, cylinders, engines, etc.)
5
6
where chosen values in graphs/real time trends are
Setpoints button. Use to go to the setpoints group screen.
CONTEXT SENSITIVE BUTTONS (GROUP 2)
The context sensitive buttons allow display predefined screens when a suitable button is pressed. Meaning of the buttons depends on the Main menu option that is currently displayed (Metering, Trends and etc.) and on the controller firmware. The Picture above introduces standard SW IGS-NT-2.5.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
20
Page 21
Hint:
1
2
4
3
7
6
5
8 9
POSITION
BUTTON
Description
ESC button. Escape from any dialog window or menu (cancels an action).
Right button. Use this button to move the cursor to the right, scroll to the right history page and etc.
Home button. Jump to Home screen. Main Metering screen Down button. Use this button to move down, scroll down the
screens or decrease a val ue.
PgDn button. Use this button to quickly go down among
active).
Left button. Use this button to move the cursor to the left, scroll to the left history page and etc.
PgUp button. Use this button to quickly go up among
The icon in the bottom right hand corner (see picture above) indicates possibility to use PgDn button to see next items of the context menu.

Navigation Buttons

There are nine navigation buttons:
1
2
3
is used in default configuration.
4
5
Metering screens or Setpoints groups (when menu is active) or among Setpoints or History records (when menu is not
6
Metering screens or Setpoints groups (when menu is active)
7
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
or among Setpoints or History records (when menu is not active).
21
Page 22
8
Up button. Use this button to move up, scroll up the screens or increase a value.
Enter button. Use this button to confirm a value or opens a value adjustment within setting dialogs.
45678910111213
14
POSITION
BUTTON
DESCRIPTION
STOP button. Works in MAN mode only. Press this button to
cooling) and next phase will continue.
START button. Works in MAN mode only. Press this button mode only).
HORN RESET button. Use this button to deactivate the horn output without acknowledging the alarms.
9
Hint:
To leave the context menu, use Esc, Enter or buttons.
GEN-SET CONTROL BUTTONS
initiate the stop sequence of the gen-set. Repeated pressing
4
5
or holding the button for more than 2s will cancel current phase of stop sequence (like ramping the power down or
to initiate the start sequence of the engine (MAN and SEM
6
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
22
Page 23
POSITION
BUTTON
DESCRIPTION
8
Fault reset button . Us e this but t on to ac knowledge alarms and deactivate the horn output. Inactive alarms will disappear
dismiss.*
GCB button. Works in MAN mode only. Press this button to open or close the GCB manually. Note that certain conditions must be valid otherwise GCB closing is blocked.*
MCB button. Works in MAN mode only. Press this button to
button! Be sure you know well what you are about to do!
14 Colour display, 800x600 pixels.
POSITION
DESCRIPTION
POWER indication. LED diode turns on when InteliVision 8 is
powered up.
Alarm indication. Alarm LED indication indicate alarms. Yellow
active.
Engine indication. Engine LED indication lights only when engine is
running.
Mode button. Use this button to call mode change.*
9
immediately and status of active alarms will be changed to “confirmed” so they will disappear as soon as thei r reas ons
12
open or close the MCB manually.*
13
CAUTION!
You can disconnect the load fro m the mai ns s uppl y w i th this
* - It is valid in default SPtM configuration only. Screens description and buttons from 8 to 13 could have different meaning in customized versions or SW branches.
INTELIVISION 8 LED INDICATION
7
colour for the first level alarms and red colour for the second level alarms.
10
Hint:
LED diode blink when at least one acknowledge alarm is present in the Alarm List. LED diode lights when alarms were acknowledged but are still
11
Hint:
When you switch on InteliVision 8 display, Power LED turns on and Engine and Alarm LEDs start to blink for a while.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
23
Page 24

Page Structure

Metering pages structure
Display Screens and Pages Structure The displayed information is structured into "pages" and "screens".
1. The pages Metering consists from pages which displays measured values like
voltages, current, oil pressure etc., computed values like i.e. gen-set power, statistic data and etc.. Use arrows Up and Down buttons to switch over the pages.
2. The Setpoints screen contains all setpoints organized into the groups and also a
special group for entering password.
3. The History screen shows the history log in the order that the last record is
displayed first.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
24
Page 25

Connection

Configuration reading
InteliVision 8 core information
Serial number and re lease dat e
InteliVision 8 SW and HW version
InteliVision 8 is not connected
Not available value
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
25
Page 26
Alarm indication
Reloaded configuration

Alarms

Alarms are structured into two levels and InteliVision 8 allows easy interpreted their meaning based on the colour scheme. When an error occurs, a new alarm appears in the AlarmList screen, exclamation mark starts blinking on the metering screens. When all alarms are acknowledged, the exclamation stops blinking and is on.
Hint:
When a new alarm appears AlarmList screen is displayed automatically when the main/first Metering screen is displayed. From different screen, AlarmList button has to be used to display AlarmList screen.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
26
Page 27

AlarmList Screen

Second level alarm
First level alarm
Number of active alarms
Sum of all alarms
Inactive unacknowledged alarm
Active unacknowledged alarm
Active acknowledged alarm
Sum of unacknowledged alarms
Hint:
Use Fault reset but ton to confirm alarm in the AlarmList.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
27
Page 28
Second level alarm
First level alarm
Setpoints Group
User Access Level
Locked setpoint
Sum of the setpoints group
Order of the setpoints group

Setpoint Change

On Setpoints screens you can set various setpoints. To go to Setpoints screen press Setpoints button. Setpoints screen appears with the context sensitive buttons for the the setpoints group.
Hint:
Content of the context buttons list depends on the type of the application. To be more familiar with setpoints, see Reference Guide of the specific application (e.g.IGS-NT­SPTM-2.5-Reference Guide.pdf or IGS-NT-MINT-2.5-Reference Guide.pdf).
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
28
Page 29

Change of the Numerical Value

Actual setpoint value
Cursor position
Min. value
Edited setpoint
Actual setpoint value
Max. value
Administrator signed in
Use →, ← buttons to go to a certain position of the field and use ↑ ↓ to change the value. Then confirm your settings with Enter button.
Hint:
If the value is out of limit, the field will color red and the value could not be confirmed.

String Selection

Use ↑ ↓ to go to a certain setpoint and press Enter, see picture below:
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
29
Page 30

String Edit

Cursor position
Setpoint
Written text
Character table
The characters set table appears on the screen when string will be edited (like gen­set name). Use → ← and ↑ ↓ to find the position, then press button to confirm
text.

Time and Date Edit

Date and Time are edited as the numerical value. See Change of the Numerical
Value.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
30
Page 31

Combined Setpoints

Unlocked setpoint
Cursor position
Actual cursor position
Actual setpoint value
Use Left or Right buttons to move between the cells. Use Left or Right arrow to change cursor position.

Entering the password

User has to be logged in before setpoint is changed. Use Help/Others button to open login dialogue, then use ↑ ↓ to go to Users field and Password then press
Enter.
Hint:
Password is a five-digit number (0 - 65535). Only setpoints associated with the entered password level can be modified.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
31
Page 32
Displayed values in columns
1
Actual line (row) with the appropriate values in the history log
2 3 4
5
Administrator signed in
The icons in the top right-hand corner then show you that you are logged on.

History

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
32
Page 33
HISTORY CONTEXT BUTTONS
POSITION
DESCRIPTION
First Row/Col. Use to jump to the first column and first row (the Date and Time)
2
First Row. Use to jump to the first row .
3
First Col. Use to jump to the first column.
4
Last Col. Use to jump to the last column.
PageMode On. Use this button when the PageMode is ON you
indicates that PageMode is On.
Hold
Press
Or press
1
first column is RPM – you cannot move among columns Reason,
can use buttons to jump by page right or left (quicker
5
movement through columns). Icon at the top of the screen

Display Contrast Adjustment

From the mains screen the day or night mode can be choose. The mode is switched when ESC button is pressed for one second. The brightness is adjustable in the full range of 0 % - 100 % in the both modes. The display brightness can be increased/decreased by holding Esc butt on a nd rep eated pressing ↑ ↓. See picture below:
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
33
Page 34
Hold
Press
Or press
Day mode - active
Night mode - inactive
When brightness dialogue is active, use ESC + PgUp buttons or ESC + PgDn to switch between modes, which shall be adjusted.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
34
Page 35

Controller Information Screen

Control unit serial number
InteliVision 8 SW verison
InteliVision 8 SN
Supported languages
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
35
Page 36
NT
Where
Function
Measurement screens, Alarm list
Go to Menu screen Setpoints screen
Go to Menu screen; within setpoint
10
11 9 13
12
16
7
15
20 8 14
17 3 6 5 21
19
18 2 1
4
InteliGen

InteliGenNTGC pushbutt ons a nd LE Ds

GC and InteliSys
NT

Pushbuttons:

1. MODE Cycle forward through gen-set operation modes OFFMAN
AUT TEST.
2. MODE Cycle backward through gen-set operation modes OFFMAN
AUTTEST.
3. HORN RESET Deactivates the HORN (AUDI BLE ALARM).
4. FAULT RESET Acknowledges faults and alarms.
5. START Starts the gen-set in MAN mode.
6. STOP Stops the gen-set in MAN mode.
7. MCB ON/OFF Opens and closes (synchronizes) the Mains circuit breaker
in MAN mode.
8. GCB ON/OFF Opens and closes (synchronizes) the Generator circuit
breaker in MAN mode.
9. ESC
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
36
Page 37
group, go to group list
Setpoint edit
Leave setpoint edit without changes
History screen
Go to Menu screen
FastEdit screen
Fast edit exit (to previous measurement screen) without changes
Language screen
Language screen exit (to menu) without save
Where
Pushbutton combination
Function
Measurement
ENTER + ESC
Contrast increase Info screen
ENTER + ENTER +
Backlight increase
Where
Function
Menu screen
Go to selected display gr oup (Measurement CU, Measurement IO, …)
Measurement
Go to FastEdit screen (hold ENTER for 4
standard SPtM)
Setpoints screen
Go to selected setpoint group
Setpoint edit
Start setpoint edit / save changes
History screen
Go to the first column of the first history record
FastEdit screen
FastEdit exit (to previous measurement screen) with setpoint change
Language screen
Language screen exit (to menu) and save selection
10. ↑ Select the setpoint, select the screen, select history record or increase
setpoint value.
11. ↓ Select the setpoint, select the screen, select history record or decrease
setpoint value.
12. → Moves history record displayed columns to the right, 5% increase of
edited setpoint’s value (step given by the setpoint range), go bac k fr om Alarm list.
13. ← Moves history record displayed columns to the left, 5% decrease of
edited setpoint’s value (step given by the setpoint range), view Alarm list from measurement scr eens.
14. ENTER
screens, Alarm list
sec.) – then it is possible to adjust selected setpoint (typically Base load for

Pushbuttons’combinations

Following table determines controller functions when , , , , ENTER and
PAGE buttons’ combination is pressed:
ENTER +
screens, Alarm list
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
ENTER +
Contrast decrease Info screen
Backlight decrease
37
Page 38

LEDs

1 2 3
4
5 6 7
8 9 24
23
10
22
11
21
20
15
14
16
19
18
12
13
17
15. MAINS VOLTAGE PRESENT: GREEN LED is on, if voltage on the mains
terminals is present (in SPI and SPtM). LED is not active in MINT, COX.
16. MAINS FAILURE: RED LED starts flashing when the mai ns fail ure occurs
and gen-set does not run, goes to steady light when the gen-set starts and goes off when the mains restores.
17. GEN VOLTAGE PRESEN T: GREEN LED is on, if gen. voltage is present
and within limits.
18. GEN-SET FAILURE: RED LED starts flashing when any failure occurs.
After FAULT RESET button is pressed, goes to steady light (if an alarm is still active) or is off (if no alarm is active).
19. GCB ON: GREEN LED is on, if GCB feedback is active. Flashes during
synchronizing.
20. MCB ON: GREEN LED is on, if MCB feedback is active. Flashes during
reverse synchronizing (synchronizing of the loaded gen-set back to the restored mains).
21. Bus – GREEN LED is on if bus voltage is present and within limits.

InteliSysNT Basebox pushbuttons and LE Ds

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
38
Page 39

Pushbuttons:

Where
Function
Setpoints screen
Change setpoint value
Menu screen
Go to selected display group directly
Measurement screens
Go to another screen directly Language screen
Select language directly
History screen
If pressed ± button a  symbol
page of records using arrow buttons
Where
Function
Measurement screens, Alarm list
Go to Menu screen
Setpoints screen
Go to Menu screen; within setpoint group, go to group list
Where
Function
Menu screen
Go to selected display group (Measurement CU, Measurement IO, …)
Measurement
Go to FastEdit screen (hold ENTER for 4
standard SPtM)
Setpoints screen
Go to selected setpoint group
Setpoint edit
Start setpoint edit / save changes
History screen
Go to the first column of the first history record
FastEdit screen
FastEdit exit (to previous measurement screen) with setpoint change
Language screen
Language screen exit (to menu) and save selection
1. Numeric keypad
appears on the display (bottom right corner) and it is possible to move by one
2. Clear Clears character on the left side of the cursor, exits from menu
3. Enter
4. Mode Cycle forward through gen-set operation modes OFFMAN SEM AUT TEST.
5. Mode Cycle backward through gen-set oper a ti on m odes OFFMANSEMAUT TEST.
6. START Starts the gen-set in MAN or SEM mode.
7. STOP St ops the gen-set in MAN or SEM mode.
8. FAULT RESET Acknowledges faults and alarms.
9. HORN RESET Deactivates the horn (audible alarm).
10. MCB ON/OFF Opens and closes (synchronizes) the Mains circuit breaker in MAN mode (SPtM application only).
11. GCB ON/OFF Opens and closes (synchronizes) the Generator circuit breaker in MAN mode.
12. ESC
screens, Alarm list
sec.) – then it is possible to adjust selected setpoint (typically Base load for
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
39
Page 40
Setpoint edit
Leave setpoint edit without changes
History screen
Go to Menu screen
FastEdit screen
Fast edit exit (to previous measurement screen) without changes
Language screen
Language screen exit (to menu) without save
Table of characters
Jump among table of characters, menu and text line
Where
Pushbutton combination
Function
Measurement
ENTER +
ENTER + ESC
Contrast increase Info screen
ENTER + ENTER + ↓
Backlight increase
History screen
number + ENTER
Go to record with this number
13. Select the setpoint, setpoint group, select the screen, select history record, increase setpoint value, edit stringlist value, select language
14. Select the setpoint, setpoint group, select the screen, select history record, decrease setpoint value, edit stringlist value, select language
15. In AlarmList screen, shift the Alarm list page down (if more than 7 items), moves history record displayed columns to the right
16. In AlarmList screen, shift the Alarm list page up (if more than 7 items), moves history record displayed columns to the left, go to Info screen
17. Enter Same as 3.
18. Alarm list Shortcut to Alarm list screen from any other screen
19. History Shortcut to History screen from any other screen

Pushbuttons’ combinations

Following table determines controller functions when , , , , ENTER and
PAGE buttons’ combination is pressed:
screens, Alarm list

LEDs:

20. Mains status LED
21. MCB status LED
22. Load status LED
23. GCB status LED
24. Gen-set status LED
ENTER +
Contrast decrease Info screen
Backlight decrease
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
40
Page 41

How to select gen-set mode?

Use MODEor MODE to select requested gen-set operation mode OFF – MAN – SEM – AUT – TEST. It is not possible to go directly from OFF to AUT or TEST.

Display menus

There are several display menus (functions) available: ALARMLIST, MEASUREMENT CU, MEASUREMENT IO, SETPOINTS, HISTORY, PASSWORD and LANGUAGE. Each menu consists of several screens. Pressing the ESC (repeatedly when necessary) button the menu screen will be displayed.
Hint:
IS-NT – When pressing ESC on the screen with characters, focus jumps from menu to bottom line and table of characters. See picture on the right.

How to view Alarm list?

1. Select the A LARM LIST menu item and press ENTER or press ← in measurements’ screens to go directly to the Alarm list.

How to view measured data?

1. Select the MEASUREMENT CU menu item and press ENTER.
2. Use and to select the screen with requested data.

How to view IO values?

1. Select the MEASUREMENT IO menu item and press ENTER.
2. Use and to select the screen with requested data.

How to view and edit setpoints?

1. Select SETPOINTS menu item and press ENTER.
2. Use o r to select requested set points group.
3. Press ENTER to confirm.
4. Use or to select requested set point.
5. Set points m ar k ed are password protected.
6. Press ENTER to edit.
7. Use or to modify the set point. When ↑ or ↓ is pressed for 2 sec, auto
repeat function and speedup is activated. Use ← or → to change the setpoint value by 5% of it’s range.
8. Press ENTER to confirm or ESC to leave without change.
9. Press ESC to leave selected set points group.

How to view the HISTORY menu?

1. Select HISTORY menu item and press ENTER
2. Use or to select a requested record.
3. Use or to cycle forward/backward through columns of the record.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
41
Page 42
4. Press ± to cycle through the whole screens of columns/rows.
Language
0 1 2 3 4 5 6
7
Lang sel xxx
A
Lang sel xxx
B
Lang sel xxx
C
InteliGen
NT
InteliSysNT
Controller INFO screen contains:
3. Password decoding string
Controller INFO screen contains:
which contains:

How to change password?

1. Select USERS/PASSWORD menu item and press ENTER.
2. Use or to select User.
3. Press ENTER to confirm.
4. Select ChangePassword and press ENTER
5. Use or or or to set new password
6. Press ENTER to confirm password

How to set Language?

1. Select LANGUAGE menu item (if not already selected) and press ENTER
2. Use or to select a requested Language.
3. Press ENTER to confirm.
Hint:
If binary inputs Lang sel int A,B,C (for IG-NT/EE internal display and IS-Display with address 1) or Lang sel #2 A,B,C (for IG-Display and IS-Display with address 2) or Lang sel #3 A,B,C (for IS-Display with address 3) are used, it is not possibl e to change languages from Language screen.

How to change the display contrast?

Press and hold ENTER and use ↑ or ↓ to adjust the best display contrast.
Hint:
Available from the MEASUREMENT screens only.

How to check the serial number and software revision?

Hold down the ENTER and then press ESC. On the display you can see controller INFO screen for 10 seconds.
1. Controller name (see Basic settings group)
2. Controller serial number (8 character number), SW version, ID string and release date
3. Application: SPtM, SPI, COX…
Using → you can view the INFO2 screen which contains:
1. Display SW version
2. ID chip and Dongle content
0 1 0 1 0 1 0 1 0 0 1 1 0 0 1 1 0 0 0 0 1 1 1 1
1. Controller name (see Basic settings group)
2. Firmware and release date
3. Controller serial number (8 character number)
4. Application: SPtM, SPI, COX…
5. Password decode number
6. IS-Display version and release date
7. Encoding: available character sets
Using → you can view the INFO2 screen
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
42
Page 43
1. IDch: ID string
2. Dngl: connected dongle
1. IS-Display IDchip: ID string
3. Supported code pages
Using → again you can view the INFO3 screen which contains:
Hint:
Available from the MEASUREMENT screens only.

How to view Connection screen on IG-Display?

Press button when in Info screen to see information about IG-Display hardware version and properties and actual state of communication with the master controller.

How to change the display backlight intensity?

Hold down the ENTER and then press ESC. On the display you can see Controller INFO screen for 10 seconds. Press and hold ENTER when in INFO screen and use ↑ or ↓ to adjust the best display backlight. Backlight intensity is set for one of the two modes, depending on the activity of configurable binary inp ut Alt br i ght nes s (IG-NT/EE and modifications). For IG-Display and IS-Display modules, this binary input is located in the Power connector and it’s function is fixed (not configurable). IS-Display with address 1 reads analog input LCD brightness on IS-NT-BB and changes accordingly display backlight intensity in the range 0-100%.
Hint:
Backlight intensity change available from the MEASUREMENT screens only.

How to find active alarms?

Select Alarmlist menu item and press ENTER or press ← in MEASUREMENT IO or MEASUREMENT CU menu.
Inverted alarms are still active. Non-inverted alarms are not active, but not yet confirmed.
Press FAULT RESET to accept all alarms (an asterix mark disappears when an alarm is accepted by FAULT RESET). Non-active alarms immediately disappear from the list.
Active alarm list appears on the screen automatically when a new alarm comes up and Main MEASUREMENT screen was selected.
Hint:
Alarm list does not activate automatically if the display is switched to any other screen than the first one of MEASUREMENT (typically the screen that shows menu selector on the upper). The automatic jump to the alarm list screen will not occur if you are listing through the measured values, set points or histor y!
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
43
Page 44
If setpoint Engine protect:ResetActAlarms is set to DISABLED, only inactive alarms
1
2
6
3
4
7
5
8
OFF MAN AUT
TEST
Ready
Mains Oper
PF 0.00
RPM 0
Timer 0
R
9
can be reset. If an active alarm is present in the alarm list, controller display blinks every 30 seconds.

When to use GCB ON/OFF button?

The button is disabled in AUT mode. In MAN and TEST modes it is enabled, but before closing of the circuit beaker, generator voltage and frequency must be within limits. The controller has internal protection to avoid the breaker closure without synchronizing.
The controller recognizes automatically:
if there is mains / bus voltage and the gen-set shall be synchronized before closing the GCB
or if there is no voltage on the bus and the GCB can be closed without synchronizing.

When to use MCB ON/OFF button?

The button is disabled in AUT mode. Use this button in MAN or TEST mode to close or open the MCB. Be careful while
doing this, because you can disconnect the load from the mains!!!

Description of InteliGenNT MEASUREMENT screens

Main measure screen

1. Operation mode of the gen-set
2. Indication of active alarm
3. Status of the gen-set
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
44
Page 45
4. Actual electric condition
30kW
0.90C
-20kW
1.00R
PWR I/E
-20
10kW
0.90L
Actual value of PF
bargraph)
Gen I1, I2, I3 (triple bargraph)
Gen I1, I2, I3 (triple bargraph)
bargraph)
bargraph)
Im3/EarthFC (single bargraph)
Im3/EarthFC (single bargraph)
5. RPM of the gen-set
6. Active power
7. Power factor
8. Timer – event’s counting time (e.g. prestart, cooling , … )
9. Signalizes, when any remote connection to controller is active
Following table contains an example of MINT and SPtM MEASUREMENT screens. Other applications can be slightly different.

Measurement CU

MINT SPtM

Total power screen

Generator (frequency, voltage) Gen freq
Gen V1, V2, V3 ph-N (triple bargraph) Gen V12, V23, V31 ph-ph (triple

Generator (current)

Bus (frequency, voltage) Bus freq
Bus V1, V2, V3 ph-N (triple bargraph) Bus V12, V23, V31 ph-ph (triple
Left up corner: Actual power control mode None or Base or Imp/Exp and required power values.
Load: Actual value of active power. Actual value of PF Mains: Actual value of active power. Actual value of PF Gen-set: Actual value of active power.
Generator (frequency, voltage) Gen freq
Gen V1, V2, V3 ph-N (triple bargraph) Gen V12, V23, V31 ph-ph(triple bargraph)

Generator (current)

Mains (frequency, voltage) Mains freq
Mains V1, V2, V3 ph-N (triple bargraph) Mains V12, V23, V31 ph-ph (triple

Bus (current)

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf

Mains (current, power, PF)

45
Page 46
P mains
MaxVectorS
Apparent power (total and per phase)
barograph)
in the range 0 to 100%.
the range 0 to 100%.
Service time 4
Service time 4

Statistic

Statistic

Power management
CAN32
Q mains Mains PF
Gen-set power Active power (total and per
phase) Power factor (total and per phase) Reactive power kVAr (total and per phase)
IG-CU Analog inputs Battery voltage (single
barograph) CPU temp (single barograph) Dplus (single
Synchroscope Slip frequency
Synchroscope V1g Generator first phase voltage V1b Bus first phase voltage SRO Speed regulator output indication in the range 0 to ±10,00V VRO Voltage regulator output indication
Gen-set power Active power (total and per phase)
Power factor (total and per phase) Reactive power kVAr (total and per phase) Apparent power (total and per phase)
IG-CU Analog inputs Battery voltage (single
barograph) CPU temp (s ing le barograph) Dplus (single barograph)
Synchroscope Slip frequency
Synchroscope V1g Generator first phase voltage V1m Mains first phase voltage SRO Speed regulator output indication in the range 0 to ±10,00V VRO Voltage regulator output indication in
Statistic Run hours
Number of starts Number of unsuccessful starts Service time 1 Service time 2 Service time 3
kWhours kVArhours Time

Date

Engine priority Total running actual power Actual reserve (single barograph) CAN16
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
Statistic Run hours
Number of starts Number of unsuccessful starts Service time 1 Service time 2 Service time 3
kWhours kVArhours Time

Date

46
Page 47

Measurement IO

AI1 to A I3
AI1 to A I3
Closed lock
Opened lock
Password is set. Password level is visible in opened lock.
2 1 3 4 5 6 7
8 9 10

IG-CU analog inputs

IG-CU analog inputs

+ inputs/outputs of connected ECU and/or modules, depending on actual configuration.

Description of InteliS y sNT MEASUREMENT screens

Main menu screen

1. Selection of alarm list, measurement, history, setpoints, languages or user screen.
2. Cursor shows actual selection.
3. Controller mode indication. Black background indicates active mode (MAN mode in the above example).
4. Timer – events counting time (e.g. prestart, cooling).
5. Engine machine state indication.
6. Electric machine state indication.
7. Actual gen-set power (requested gen-set power).
8. Actual RPM.
9. Indication of access level from the controller panel:
10. Controller date and time. Can be set in Date/Time gr oup o f setpoints.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
No password set
47
Page 48

Alarm list

accepted / all alarms
SPtM Screens
Description
1. Remote communication
5. Actual power factor.
1. Power control mode
power and PF values

Measurement CU

1. Details of the alarm from ECU indicated by the cursor are displayed at the bottom line (SPN, FMI, OC numbers)
2. Asterisk indicates not accepted alarms (Fault reset has not been performed)
3. Alarms displayed inverted are active
4. Number of active / not
indication and access lock indication (symbol is visible when Access lock BI is active).
2. Actual gen-set power.
3. Measur e screen address. For jump to this screen set this number from the numeric keypad.
4. Actual eng i ne RPM.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
(Island / BaseLd / BldEmLm / PwrI/E / TbyPwr)
2. PF control mode (Island / BasePF / PF I/E)
3. Required power value
4. Required PF value
5. Actual Mains active power and PF values
6. Actual load active power and PF values
7. Actual gen-set active
48
Page 49

1. Generator frequency

2. Generator voltage phase-
1. Mains frequency
1. Active power (total and per
phase
3. Generator voltage phase­neutral + triple bargraph
4. Generator current + triple bargraph
2. Mains voltage phase­phase
3. Mains voltage phase­neutral + triple bargraph
4. Mains current (3rd phase)/ Earth fault current
5. Maximal vector shift
phase)
2. Power factor (total and per phase)
3. Reactive power (total and per phase)
4. Apparent power (total and per phase)
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
49
Page 50
1. Battery voltage
2. CPU temperature
1. Synchroscope
range 0 – 100%
Statistics
User 0 is entered.
3. D+ voltage
2. Slip frequency
3. Actual angle between generator and mains voltage
4. Generator first phase voltage
5. Mains first phase voltage
6. Voltage match of all three phases (0 – doesn’t match; 1 – OK)
7. SRO – Speed Regulator Output indication in the range SpeedGovLowLim – SpeedGovHiLim
8. VRO – Voltage Regulator Output indication in the
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
1. Total engine running hours
2. Total number of starts
3. Total number of unsuccessful starts
4. Service times (set in Engine protect group of setpoints)
5. Total gen-set kW hours
6. Total gen-s et kVAr hours
Note:
Statistics can be set in
InteliMonitor → Set
statistics… after password of
50
Page 51

Measurement IO

SPtM Screens
Description
IS-NT analog inputs
IS-NT binary inputs indication
IS-NT binary outputs
1. Analog input 1 (e.g. Oil pressure)
2. Analog input 2 (e.g. Primary water temperature)
3. Analog input 3 (e.g. Fuel level)
4. analog input 4 (e.g. Secondary water temperature)
indication
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
51
Page 52
If the temperatures of
cylinders are
Another screen shows the
Further screens are automatically added if I/O extension modules or ECU are
connected to the controller.
1. Bottom lines show record
configured/measured it is possible to see bargraphs of these temperatures on the separate screen.
differences of cylinder temperatures from the average temperature.

History

InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
number, reason, date and time even if other columns are actually displayed
52
Page 53

Users/Password

This screen shows list of
users. To enter or change password of selected user press Enter.

Users and Passwords

Up to 8 users can be defined in the system. Every user has it’s own defined level of access rights. There are seven levels of password protection. User O – Administrator has alw ays level 7.
Hint:
The lock mark  appears before a set point name (on controller screen) if the setpoint is password protected. The lock mark is removed only when the password is set from controller’s front panel. The lock mark is still visible on controller screen even if the password is set from different terminal. Even though one level may have been set from the front panel, the affected set points are not accessible from InteliMonitor (direct or Modem) until this level is set in InteliMonitor (direct or Modem). Set point screen ope ne d fro m fro nt pan el is automatically closed 15 minutes after the last key has been pressed.
It is possible to protect remote Start, Stop, GCB and MCB commands from InteliMonitor. This seven level command protection can be c on fig ured in GenConfig.

EnterPassword

Password is a five-digit number (0 - 65535). Only setpoints associated with the entered password level can be modified.
Use ↑ or ↓ to select the desired password and then press ENTER. Use ← or → to move the value by 5% of the range.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
53
Page 54

Mode and function description

There are four gen-set operation modes: OFF - MAN – AUT – TEST in SPtM application. There are t hr ee gen-set operation modes: OFF - MAN – AUT in SPI, COX and MINT application.
To select the mode use MODE→ or MODE.

OFF mode

No start of the gen-set is possi bl e. Outputs STARTER, GCB CLOSE/O PEN and FUEL SOLENOID are not energ i z ed.
No reaction if buttons START,STOP,GCB ON/OFF are pressed.
MCB behavior depends on AMF settings: MCB opens on setpoint:
MAINSFAIL: When power-cut comes, MCB opens. After Mains returns, MCB closes with MCB close del. GEN RUNNING:When power-cut comes, MCB stays closed until the gen-set starts and produces voltage within limits.

MAN mode

1) To start the gen-set press START.
2) When the generator voltage is within limits (adjusted in the setpoints group
Generator protections) GCB green LED on the front panel lights.
3) Press GCB ON/OFF to close the GCB. If the generator voltage is out of the limits,
controller does not respond to the GCB ON/OFF .
a) If controller detects dead bus, immediately closes GCB OPEN/CLOSE output. b) If controller detects voltage on the bus, starts synchronizing.
4) To stop the engine press STOP a) controller unloads the gen-set, opens GCB CLOSE/OPEN. Unloading is active only when binary input MCB feedback is closed or other gen-set is connected to bus. In other case GCB CLOSE/OPEN opens immediately. b) Gen-set is cooled down and stopped.

Hint:

Controller does not respond to external signals and/or conditions. The gen-set is fully in manual control; there is no automatic way to stop it (except protections). The gen­set stays running until STOP button is pressed. Controller does not take place in Power management in MINT application

AUT mode

Gen-set is controlled based on external signals (Rem start/stop, Sys start/stop) or conditions (AMF, Peak shaving, Power management system, …).

Hint:

Engine does not stop, if other condition for automatic starts is active.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
54
Page 55
Example: If peak stop condition occurs, but REMOTE START/STOP is active, engine stays running.
Controller does not respond to GCB ON/OFF , MCB ON/OFF, STOP, START buttons and corresponding remote InteliMonitor or Modbus commands.
Set Basic setting: FltRes GoToMAN = ENABLED to avoid automatic engine start
when pressing FAULT RESET after Shut down or Slow stop alarm. Engine can start automatically without warning when pressing FAULT RESET after shut down alarm.

TEST mode (SPtM only)

Use TEST mode for Gen-set start test if the Mains is OK or to transfer the load to the gen-set when Mains fail is announced in advance.

Hint:

The controller does not respond to GCB ON/OFF , STOP, START in Ret from test = AUTO. Engine automatically starts, when TEST mode is selected. Engine can start automatically without warning when pressing FAULT RESET after shut down alarm.

SEM mode

START – starts the gen-set.
The controller closes GCB to dead bus.
If the Mains is within limits and MCB is closed, the controller starts
synchronizing and closes GCB when synchronizing conditions are met. Gen­set remains running in parallel.
If Mains failure is recognized during parallel operation the controller opens
MCB.
After Mains recovers the controller synchronizes MCB and returns to parallel
operation
STOP – unloads the gen-set, opens GCB, cools down the engine and stops.
AMF function – If the Mai ns fails whi l e the gen-set is not running, the controller automatically starts and closes GCB. Other automatic starts/stops (e.g. due to peak shaving, BI Rem start/stop activation) are not performed in SEM mode.

Baseload

Process control: Load ctrl PtM = BASELOAD
Gen-set power is kept at value given by Process control:Base load setpoint.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
55
Page 56

Internal Import export

ProcessControl: Load ctrl PtM = IMP/EXP Process control: IE measurement = IM3 CT INPUT
Gen-set power is controlled to keep the import load at the level given by setpoint Process control: Import load value. Controller measures Import/Export value via current transformers connected to In/Im3 terminal. The value of L3 is then multiplied by 3 to give an estimation of the actual Imp/Exp.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
56
Page 57

List of abbreviations

AI
Analog Input
AMF
Auto Mains Failure (controller starts automatically on mains failure)
AO
Analog Output
AVR
Automatic Voltage Regulator
BI
Binary Input
BO
Binary Output
Breaker Open & Cool-down - protection type (see application manual for details)
BTB
Bus-Tie Breaker
ESF
Engine Specific File
FMI
Failure Mode Identifier
Graphical Characters - option for additional support of one "gr ap hi cal " language
GCB
Generator Circuit Breaker
Combined Heat & Power - cogeneration application, usually with gas engine
IG-AVRi
IG Automatic Voltage Regulator interface
InteliGen EE controller with extended communication possibilities + IG-IB
IG Internet Bridge - for internet/ethernet com munication
IG-NT
InteliGen New Technology gen-set controller
ATS
BOC
CAN1
CAN2
Combi
COX
Automatic Transfer Switch (switches the load to actually supplied bus (by mains or generators))
CAN bus for extension modules connection (e.g. IGS-PTM, IS-BIN8/16, IS­AIN8, I-AOUT8, I-CB, IGL-RA15)
CAN bus for intercontroller communication (in multiple applications) and monitoring (connection of I-LB, IG-IB)
Application where SPTM, SPI or MINT can be used. Application is defined by Binarary inputs combination.
Application for Complex Systems where actions are taken by a PLC and the controller only follows the orders => needs an external driver (cox)
GC
CHP
I-AOUT8 Extension module with 8 AO
I-CB
IG-EE
IG-EEC
IGL-RA15 Indication panel with LEDs signalizing state of 15 BO
Communication Bridg e - interfaces IS, IG/IS-NT, ID controllers and non­standard engine ECU
InteliGen for Electro nic Engi nes (HW optimized for connection to an engi ne equipped with ECU)
switchable sensing ranges of AC voltages and currents
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
57
Page 58
IG-NT-BB InteliGen New Technology Base Box gen-set controller (without display)
InteliGen New Technology Base Box gen-set controller with extended and currents (without display)
Local Bridge – for direct and modem monitoring and control of multiple gen-sets
InteliMains New Technology - Mains supervision controller; the same synchronizer
I-RB
Relay Board
IS-AIN8
Extension module with 8 AI.
IS-NT
InteliSys New technology gen-set controller
IS-NT
InteliSys New technology gen-set controller
LSM
Load Sharing Module
Option for Low Temperature modification (display equipped with heating foil)
MCB
Mains Circuit Breaker
IG-NTC
IG-NTC­BB
IGS-NT­LSM+PMS
InteliGen NT controller with extended communication possibilities + switchable sensing ranges of AC voltages and currents
communication possibilities + switchable sensing ranges of AC voltages
Dongle for IG-XX and IS-NT to enable Load Sharing control loops and PMS
IGS-PTM Extension module with 8 BI/BO, 4 AI and 1 AO
I-LB
IM-NT
IM-NT-BB
IS­BIN8/16
controller in a different SW configuration can work as a bus-tie
InteliMains New Technology – Mains supervision controller; (without display)
Extension module with 8 BO and 16 BI.
IS-NT-BB InteliSys New Technology Base Box (without display)
IS-NT-BB InteliSys New Technology Basic Box (without display) IS-NTC-
BB
InteliSys New Technology Base Box gen-set controller with extended communication possibilities (without display)
KWP2000 Key Word Protocol of Scania S6 unit (for engine diagnostics)
Load Sharing - analog load sharing line to interconnect the gen-sets on the
LS
site (for isolated parallel or mains parallel of multiple gen-sets); IG/IS-NT controllers use digital Load Sharing via CAN2 bus
LT
MGCB
Master Generator Circuit Breaker (sometimes used with multiple gen-sets in island parallel or mains parall el op er ati on)
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
58
Page 59
Multiple application with INTernal control loops - for multiple gen-sets in
MP
Mains protection
NPU
Mains protection relay (voltage, frequency, vector shift protections)
Occurrence Count (number of fault occurrances transmitted in diagnostic frame from ECU)
OfL
Off load - protection type (see application manual for details)
PGN
Parameter Group Number (refer to SAE J1939-71)
SHAIN
Shared (virtual) Analog INput module
SHBIN
SHared (virtual) Binary INput module
Single Parallel Island application - for single gen-sets in parallel with mains SPM
Single Prime Mover application - for single gen-sets without mains
SPN
Suspect Parameter Number (refer to SAE J1939-71)
Single Parallel to Mains application - for single gen-sets in parallel with controlled
transfer gen-set to mains
Virtual periphery I/O module – internal “SW wires” linking binary outputs to inputs
CAN bus (for isolated parallel or mains parallel of multiple gen-sets)
MINT
island parallel or mains parallel operation; Load Sharing and VAr Sharing controlled internally; PMS available
OC
Power Management System - ensures optimization of running gen-sets on
PMS
the site with multiple gen-sets; based on kW/kVA spinning reserve or on relative (%) load; no-master system ensures hi g h rel i abil i ty
SHAOUT Shared (virtual) Analog OUTput module
SHBOUT SHared (virtual) Binary OUTput module
SPI
SPtM
SSB
VPIO
VS
or in island operation; suitable for CHP application; no MCB control
mains or in island operation, with AMF support; both MCB and GCB
Single Stand-By application - for single gen-sets with mains and break
VAr Sharing - ensures VAr sharing between the gen-sets on the site via
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014 IGS-NT Operator Guide 01-2014.pdf
59
Loading...