Digital controller with off cycle defrost
XR20C – XR20D
1592007211
CONTENTS
1. GENERAL WARNING __________________________________________ 1
3. CONTROLLING LOADS ________________________________________ 1
4. FRONT PANEL COMMANDS ____________________________________ 1
5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___1
6. MAIN FUNCTIONS_____________________________________________ 2
7. PARAMETERS________________________________________________ 2
8. DIGITAL INPUT (IF AVAILABLE)__________________________________ 2
9. INSTALLATION AND MOUNTING_________________________________3
10. ELECTRICAL CONNECTIONS ___________________________________3
11. HOW TO USE THE HOT KEY ____________________________________3
12. ALARM SIGNALS______________________________________________ 3
13. TECHNICAL DATA_____________________________________________ 3
14. CONNECTIONS _______________________________________________ 3
15. DEFAULT SETTING VALUES ____________________________________ 4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the
Warning: disconnect all electrical connections before any kind of
Fit the probe where it is not accessible by the End User. The instrument must
In case of failure or faulty operation send the instrument back to the distributor
Consider the maximum current which can be applied to each relay (see
Ensure that the wires for probes, loads and the power supply are separated
In case of applications in industrial environments, the use of mains filters (our
SAFETY PRECAUTIONS
operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation
maintenance.
not be opened.
or to “Dixell S.p.A.” (see address) with a detailed description of the fault.
Technical Data).
and far enough from each other, without crossing or intertwining.
mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Models XR20C, format 32 x 74 mm, and XR20D, DIN rail format, are thermostats with off cycle defrost designed for refrigeration applications at normal temperature. They have a relay output to drive the compressor and a PTC or NTC probe input. A internal timer manages the off cycle defrost. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “COn” and “COF”.
3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter “IdF” controls the interval between defrost cycles, while its length is controlled by parameter “MdF”.
4. FRONT PANEL COMMANDS
XR20C
XR20D
SET: To display target set point; in programming mode it selects a parameter or
confirm an operation.
(DEF) To start a manual defrost
o (UP): To see the last temperature alarm happened; in programming mode it
browses the parameter codes or increases the displayed value.
n (DOWN) To see the last temperature alarm happened; in programming mode it
browses the parameter codes or decreases the displayed value.
KEY COMBINATIONS:
o + n To lock & unlock the keyboard. SET + n To enter in programming mode.
SET + o To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE FUNCTION
ON Compressor enabled
Flashin
-Programming Phase (flashing with
g
- Anti-short cycle delay enabled
ON Defrost enabled
Flashin
- Programming Phase (flashing with
g ON An temperature alarm happened
)
)
5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP)
XR20C signals and records temperature alarms, together with their duration and max value reached. See drawing:
Ex. High temperature alarm
Temperature
Max
Temperature
Lu
High temp. alarm
Set
ALL
Low temp. alarm
X
Safe food zone
X
larm duration
X
Time
5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min) reached temperature and alarm duration do as follows:
1. Push the Up or Down key.
2. On the display the following message is shown:: “HAL” for high temperature alarm (“LAL” fot the minimum allarm), followed by the Maximum (minimum) temperature. Then the “tiM” (tiMe) message is displayed, followed by the “Duration” in h.mm.
3. Then the instrument displays the temperature once again.
NOTE1: if an alarm is still occurring the “tim” shows the partial duration. NOTE2: the alarm is recorded when the temperature come back to normal values
5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS
STILL OCCURRING
1. Hold the SET key pressed for more than 3s, while the recorded alarm is
displayed. (the rSt message will be displayed)
2. To confirm the operation, the “rSt” message starts blinking and the normal
temperature will be displayed.
1592007211 XR20C-D GB r1.0 22.04.2005.doc XR20C – XR20D 1/4
dIXEL
Installing and Operating Instructions
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
1. Push and immediately release the SET key: the display will show the Set point value;
2. Push and immediately release the SET key or wait for 5 seconds to display the probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
LED starts blinking;
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost will start.
6.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
1. Enter the Programming mode by pressing the Set and DOWN key for 3s (
2. Select the required parameter.
3. Press the “SET” key to display its value (now only the LED is blinking).
4. Use “UP” or “DOWN” to change its value.
and
start blinking).
6.5 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.5.1 HOW TO ENTER THE HIDDEN MENU
3. Select the required parameter.
4. Press the “SET” key to display its value (Now only the
5. Use o or n to change its value.
6. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + o or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the
time-out to expire.
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user level) by pressing “SET + n”. In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
1. Enter the Programming mode by pressing the Set + n
key for 3s (LED 1 and
2. When a parameter is displayed keep pressed the Set+n
for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
start blinking).
LED is blinking).
6.6 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the o and n keys.
2. The “POF” message will be displayed and the keyboard will be locked. At this
point it will be possible only to see the set point or the MAX o Min temperature stored
3. If a key is pressed more than 3s the “POF” message will be displayed.
6.7 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and n keys, till the “Pon” message will be displayed.
6.8 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding the “o” key pressed for about 3 seconds.
The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle can be terminated before the end of the set time using the same activation key “o” for 3 seconds.
7. PARAMETERS
NOTE: the parameters preceded by dots are in the Hidden Menu. REGULATION Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.
Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.
1592007211
LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum
acceptable value for the set point.
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum
acceptable value for set point.
Ot Thermostat probe calibration: (-12.0÷12.0°C;
-120÷120°F) allows to adjust possible offset of the thermostat probe.
OdS Outputs activation delay at start up: (0÷255min) This function is
enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the
compressor stop and the following restart.
CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res.
10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products.
COn Compressor ON time with faulty probe: (0÷255 min) time during which
the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during
which the compressor is OFF in case of faulty thermostat probe. With COF=0
compressor is always active.
CH Type of action: CL = cooling; Ht = heating. DISPLAY
CF Temperature measurement unit:
°C=Celsius; °F=Fahrenheit. WARNING: When the measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. DEFROST IdF Interval between defrost cycles: (0÷120h) Determines the time interval
between the beginning of two defrost cycles.
MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator
probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost.
dFd Temperature displayed during defrost: (rt = real temperature; it =
temperature at defrost start; SEt = set point; dEF = “dEF” label)
dAd MAX display delay after defrost: (0÷255min). Sets the maximum time
between the end of defrost and the restarting of the real room temperature display.
ALARMS
ALC Temperature alarms configuration: (Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU
values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this
temperature is reached the alarm is enabled, after the “ALd” delay time.
ALL Minimum temperature alarm: (-50.0 ÷ SET°C;
-58÷230°F when this temperature is reached the alarm is enabled, after the “ALd” delay time.
ALd Temperature alarm delay: (0÷255 min) time interval between the
detection of an alarm condition and alarm signalling.
dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h)
time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling.
DIGITAL INPUT (IF AVAILABLE) i1P Digital input polarity: oP: the digital input is activated by opening the
contact; CL: the digital input is activated by closing the contact.
i1F Digital input configuration:
EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA”
message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt =not enabled; Htr = kind of action inversion (cooling – heating).
did: (0÷255 min)
with i1F= EAL or i1F = bAL digital input alarm delay: delay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay with i1F = PAL: time for pressure switch function: time interval to
calculate the number of the pressure switch activation.
nPS Pressure switch number: (0
switch, during the “did” interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
odc Compressor status when open door: no, Fan = normal; CPr, F_C =
Compressor OFF
OTHER PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC
= PBC probe, ntC = NTC probe.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
8. DIGITAL INPUT (IF AVAILABLE)
The free contact digital input is programmable in five different configurations by the “i1F” parameter.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter:
no, Fan = normal (any change);
÷15) Number of activation of the pressure
1592007211 XR20C-D GB r1.0 22.04.2005.doc XR20C – XR20D 2/4
dIXEL
CPr, F_C = Compressor OFF; Since the door is opened, after the delay time set through parameter “did”, the door alarm is enabled, the display shows the message “dA” and the regulation restarts. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.
Installing and Operating Instructions
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
8.5 START DEFROST (i1F = dFr)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time is expired.
8.6 INVERSION OF THE KIND OF ACTION: HEATING­COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.7 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” parameter. i1P=CL: the input is activated by closing the contact. i1P=OP: the input is activated by opening the contact
9. INSTALLATION AND MOUNTING
Instrument XR20C shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-C) as shown in figure.
Instrument XR20D shall be mounted on an omega DIN rail The temperature range allowed for correct operation is 0÷60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
10. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 mm supply complies with the instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
2
. Before connecting cables make sure the power
10.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
11. HOW TO USE THE HOT KEY
1592007211
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.
11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “doL” message is blinking followed a by flashing
“End”.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the “Hot
key” to abort the operation.
12. ALARM SIGNALS
Message Cause Outputs
“P1” Room probe failure Compressor output according
“HA” Maximum temperature alarm Outputs unchanged. “LA” Minimum temperature alarm Outputs unchanged. “dA” Door open Regulation restarts “EA” External alarm Output unchanged. “CA” Serious external alarm (i1F=bAL) All outputs OFF. “CA” Pressure switch alarm (i1F=PAL) All outputs OFF
12.1 ALARM RECOVERY
Probe alarm “P1” starts some seconds after the fault in the related probe; it automatically stops some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values and when defrost starts. Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled. Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
13. TECHNICAL DATA
Housing: self extinguishing ABS. Case: XR20C frontal 32x74 mm; depth 60mm;
XR20D 4 DIN modules 70x85 mm; depth 61mm
Mounting: XR20C panel mounting in a 71x29mm panel cut-out
XR20D DIN RAIL mounted in a omega (3) din rail Protection: IP20. Frontal protection: XR20C IP65 with frontal gasket RG-C (optional). Connections: Screw terminal block 2,5 mm Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;
230Vac ±10%, 50/60Hz, 110Vac ±10%, 50/60Hz
Power absorption: 3VA max Display: 3 digits, red LED, 14,2 mm high. Inputs: 1 NTC or PTC probe. Digital input: free contact Relay outputs
compressor: SPDT relay 8(3) A, 250Vac or
SPST relay 20(8)A; 250Vac
Data storing: on the non-volatile memory (EEPROM). Kind of action: 1B; Pollution grade: normal; Software class: A. Operating temperature: 0÷60 °C. Storage temperature: -30÷85 °C. Relative humidity: 20÷85% (no condensing) Measuring and regulation range:
NTC probe: -40÷110°C (-40÷230°F)
PTC probe: -50÷150°C (-58÷302°F) Resolution: 0,1 °C or 1°C or 1 °F (selectable). Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
to par. “Con” and “COF”
2
wiring.
11.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push o key; the "uPL"
message appears followed a by flashing “End”
1592007211 XR20C-D GB r1.0 22.04.2005.doc XR20C – XR20D 3/4
dIXEL
Installing and Operating Instructions
1592007211
14. CONNECTIONS
14.1 XR20C: 8A COMPRESSOR
8(3)A250V
12 3 6 7
N.C.
Comp
Line
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
8
14.2 XR20C: 20A COMPRESSOR
20(8)A250V
456 7
8
Comp
Line
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
14.3 XR20D: 8A COMPRESSOR
9101112
Hot Key
9101112
Hot Key
Room
Room
15. DEFAULT SETTING VALUES
Label Name Range °C/°F
Set point LS÷US 3.0/37
Set
Differential
Hy
Minimum set point
LS
Maximum set point
US
Thermostat probe calibration
Ot
Outputs delay at start up 0÷255 min 0
OdS
Anti-short cycle delay
AC
Continuos cycle duration 0.0÷24.0h
CCt
Compressor ON time with faulty
COn
probe Compressor OFF time with faulty
COF
probe Kind of action CL=cooling; Ht= heating CL
CH
Temperature measurement unit
CF
Resolution
rES
Interval between defrost cycles
IdF
(Maximum) length for defrost
MdF
Displaying during defrost
dFd
MAX display delay after defrost 0 ÷ 255 min 30
dAd
Temperat. alarms configuration
ALc
MAXIMUM temperature alarm
ALU
Minimum temperature alarm
ALL
Temperature alarm delay
ALd
Delay of temperature alarm at
dAO
start up Digital input polarity oP=opening;CL=closing cL
i1P
Digital input configuration
i1F
Digital input alarm delay 0÷255min 5
did
Number of activation of pressure
Nps
switch Compressor status with open
odc
door: Kind of probe
PbC
Software release -- 4.0
rEL
Map code -- -
Ptb
0,1÷25.5°C/ 1÷ 255°F
-50°C÷SET/-58°F÷SET
SET÷110°C/ SET ÷ 230°F
-12÷12°C /-120÷120°F
0 ÷ 50 min
0 ÷ 255 min
0 ÷ 255 min
°C ÷ °F
in=integer; dE= dec.point
1 ÷ 120 ore
0 ÷ 255 min
rt, it, SEt, DEF
rE= related to set;
Ab = absolute
Set÷110.0°C; Set÷230°F
-50.0°C÷Set/ -58°F÷Set
0 ÷ 255 min
0 ÷ 23h e 50’
EAL=extern. alarm; bAL=lock regulation; PAL=press. switch; dor=door switch; dEF=defrost;
LHt=disabled; Htr= cooling -
heating
0 ÷15
no, Fan = normal;
CPr; F_C = Compr. OFF;
Ptc; ntc
2.0/4
-40,0/-40 110/230
0.0
1
0.0
15
30
°C/°F
dE/-
8
20
it
Ab
110/230
-50/-58 15
1.3
EAL
15
no
ntc/Ptc
3 4 5 6
8(3)A/250Vac
HOT KEY
13 14 15 16 17 18 19
n.c.
Comp
Line
24Vac/dc supply: connect to the terminals 11 and 12. 120Vac supply: connect to the terminals 11 and 12. 230Vac supply: connect to the terminals 11 and 12.
14.4 XR20D: 20A COMPRESSOR
Power Supply
3 4 5 6
20(8 )A/ 250Vac
HOT KEY
15 16
Comp
Line
11 12
Power
Supply
11 12
Hidden parameters
24Vac/dc supply: connect to the terminals 11 and 12. 120Vac supply: connect to the terminals 11 and 12. 230Vac supply: connect to the terminals 11 and 12.
1592007211 XR20C-D GB r1.0 22.04.2005.doc XR20C – XR20D 4/4
Dixell S.p.A. Z.I. Via dell’Industria, 27 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: dixell@dixell.com - http://www.dixell.com