Codume X-Vent II 300 Operating Manual

CODUME sa.
X
-
V
II 300
Installations and Operations Guide
Version 2011-06-24
CODUME Page 2
DANGER SYMBOLS
Non-observance of instructions indicated with a danger symbol entails a risk of injury or material damage.
Read and save these instructions
By following these instructions, we guarantee you correct installation and safe use of this product.
Airmaster A/S disclaims any liability for damage or injury resulting from use, non-compliant with this manual.
This guide applies to the ventilation unit X-Vent II 300.
WARNINGS
Prior to installation and commissioning, read and observe the instructions provided in this manual.
Do not operate the unit until the service cover and grates on duct connections have been mounted.
Do not open the service cover until the power has been cut off.
CODUME Page 3
Contents
1. GENERAL INFORMATION ....................................................................................................................................................... 4
1.1 P
REFACE
................................................................................................................................................................................... 4
1.2 Z
ONE OF USE
............................................................................................................................................................................. 4
2. DESCRIPTION ............................................................................................................................................................................. 4
2.1 M
AIN CONTROLLER FUNCTIONALITIES
....................................................................................................................................... 4
2.2 R
EGULATED EQUIPMENT
........................................................................................................................................................... 4
2.3 T
ECHNICAL SPECIFICATIONS AM II
300 .................................................................................................................................... 4
2.4 B
ASIC CIRCUIT DIAGRAM
........................................................................................................................................................... 5
2.5 C
OMPONENT NAME
................................................................................................................................................................... 5
2.6 S
TRUCTURE
.............................................................................................................................................................................. 6
3. MECHANICAL INSTALLATION ............................................................................................................................................. 7
3.2 M
OUNTING UNIT IN WALL FRAME
.............................................................................................................................................. 8
3.3 M
OUNTING PIPES AND GRATES
................................................................................................................................................ 12
3.4 C
ONNECTING THE WATER HEATING SURFACE
........................................................................................................................... 12
3.5 C
ONNECTING THE ELECTRIC HEATING SURFACE
....................................................................................................................... 15
4. ELECTRICAL INSTALLATION ............................................................................................................................................. 15
4.1 C
ONNECTING THE POWER
........................................................................................................................................................ 15
4.2 C
ONNECTING THE DISPLAY PANEL
........................................................................................................................................... 16
4.3 C
ONNECTING A
CO
2
SENSOR (OPTION
) .................................................................................................................................... 16
4.4 C
ONNECTING A
PIR
SENSOR (OPTIONAL
) ................................................................................................................................. 16
4.5 E
XTERNAL CONNECTIONS
....................................................................................................................................................... 17
4.6 S
CREEN TERMINATION
............................................................................................................................................................ 17
5. APPENDIX .................................................................................................................................................................................. 19
5.1 M
AIN DIMENSIONS
X-V
ENT II
300 WALL MODEL .............................................................................................................. 19
5.2 M
AIN DIMENSIONS
X-V
ENT II
300 WALL MODEL
PARTIALLY INTEGRATED
......................................................................... 20
5.3 M
AIN DIMENSIONS
X-V
ENT II
300 WALL MODEL
COMBI
3 .................................................................................................. 21
5.4 M
AIN DIMENSIONS
X-V
ENT II
300 ROOF MODEL
PARTIALLY INTEGRATED
......................................................................... 22
5.5 E
LECTRICAL DIAGRAM
............................................................................................................................................................ 23
5.6 C
APACITY DATA
..................................................................................................................................................................... 24
5.7 ON-
SITE TESTING OF AIR VOLUMES
.......................................................................................................................................... 26
5.9 EU
DECLARATION OF CONFORMITY
......................................................................................................................................... 27
CODUME Page 4
1. General information
1.1 Preface
This installations and operations guide contains technical information as well as information regarding installation and maintenance of the unit.
1.2 Zone of use
The tolerated zone of use for the air extraction temperature is -12 ... 35 °C.
2. Description
The X-Vent II 300 is a ventilation unit with air diffusion and extraction ventilators, filters in diffusion and exhaust, countercurrent heat exchangers and compact electronic control.
The unit is designed for installation in the room to be ventilated. Ducts for supply and exhaust air are connected either to the back of the unit and lead out through the wall, or to the top of the unit and out through the roof.
X-Vent Controller is a compact electronic controller designed for full control of the X-Vent ventilation unit, fitted with effective heat recovery and energy-efficient EC ventilators.
2.1 Main controller functionalities
Unlimited control of air volume
Control of air supply temperature
Bypass operation (optional)
Night cooling and background ventilation
Manual operation or automatic operation via
weekly timer
Operation via CTS, movement sensor or CO2 sensor
The defrost functionalities protects the counterflow heat exchanger from freezing over when outdoor temperatures are low.
Monitoring and alarm functionalities
2.2 Regulated equipment
Inlet- and extract ventilators
Closing damper, intake
Bypass damper (optional)
Electric heating surface (optional)
Adjustment valve for water heating surface
(optional)
2.3 Technical specifications AM II 300
Power supply: 1 ~ 230 V, 50 Hz, N+PE Duct connections: Ø200 mm. Condensation drain: Ø16 mm Net weight: 49.8 kg Transportation weight (incl.
packaging):
62.9 kg
Heat exchanger: Counterflow Filters: F5 standard Main dimensions: 1274 x 327x 578 (WxHxD) excl. connecting pieces, incl. wall frame Colour: Cover panels Ral 9010 (white), sub panels Ral 7024 (grey)
Specifications water heating surface
Max. operating temp.:
90 °C Max. operating pressure: 10 bars Capacity: * 400 W Connection dimensions: ” (DN 10) Material pipes/fins: copper/aluminium
Open/shut time motorised valve
< 60 s
* Capacity at: in/out temperature 70/40 °C, water volume 15 L/h
Specifications electric heating surface
Heating stick: 1 x 230 V Output: 1500 W Minimum air velocity: 0.3 m/s
Thermal cutout, aut. reset:
70 °C
Thermal cutout, man. reset:
120 °C
CODUME Page 5
2.4 Basic circuit diagram
UDSUGNING
AFKAST
UDELUFT
F2
OT
FT CT
ET
IT
INDBLÆSNING
+
HE
CH *
BP *
MD
PU
PI
IF
EF
FI
RT
ED
FL
2.5 Component name
Pos. Description Function Spare part :
1 - Connecting spigot for exhaust air (wall model), placed at top (roof
model) 2 - Connecting spigot for intake air (wall model), placed at top (roof model) 3 F1 Inlet fan 4 F2 Exhaust fan 5 EF Exhaust filter 6 IF Intake filter (fresh air) 7 MD Motor for closing damper (motorised) 8 ED Exhaust damper (overpressure) 9 BP Bypass damper (optional)
10 HE Counter-flow heat exchanger 11 CT Condensation tray 12 FT Floater 13 - Connecting piece for condensation drainage
13 a - Lead-in for condensation drainage
14 RT/ FL Room temperature sensor / flow sensor 15 OT Outdoor temperature sensor 16 ET Exhaust temperature sensor 17 PI Pressure tap for air volume measurement, supply 18 PU Pressure tap for air volume measurement, exhaust 19 - Extract opening right side 20 - Inlet opening in front 21 - Power hook-up on right side 22 - Power hook-up on mounting plate for main box 23 - Main box 24 CH Post-heating surface (optional) 25 IT Inlet temperature sensor 26 Condensate Pump (optional)
INTAKE EXHAUST
EXTRACT
INLET
CODUME Page 6
2.6 Structure
The unit seen from below, without service cover.
1
2
3
4
6
5
7
8
9
10
13
11
20
23
22
14
19
15
17
21
12
24
25
13a
18
16
2
6
CODUME Page 7
3. Mechanical installation
The installer is responsible for safely and securely fastening the unit to the wall.
Note: When lifting the unit, it is important to place a protective underlay, to avoid scratching the base plate. The underlay can consist of, e.g. thick cardboard or a similar material.
The mechanical installation involves
Marking, drilling of holes for connecting ducts and mounting of wall frame
Mounting of unit in wall frame
Installation of pipes and grates through walls or over roof, depending on model
Mounting of panels
Important: Before drilling holes in wall or roof, check that there is at least 0.5 m between the wall and the unit’s exhaust end. If the exhaust end is facing out towards glass panes, that distance must be greater. If these minimum distances are not observed, there is a risk of increased noise from the unit.
Simplified picture illustrating mounting of unit on wall frame.
CODUME Page 8
3.2 Mounting unit in wall frame
1
Start by finding the centre of the wall frame using a ruler.
The centre measurement for the wall frame is 62 cm. Mark the measurement.
2
Next mark the middle of the wall or the location you wish to place the centre of the unit.
3
Now line up the two marks. If you like, you can place the
wall frame all the way up to the ceiling. If you do this, there will be a 6 mm gap between the top of the unit and the wall.
4
Now that the wall frame is provisionally hung, you can mark holes for screws and the centre of supply and exhaust. The duct size is Ø200mm. The recommended hole diameter is Ø210-215 mm, so the pipes can be insulated subsequently.
5
Horizontally measure and mark distance down to centre of supply/exhaust, and mark centre in vertical direction.
CODUME Page 9
6
This clearly indicates the marking of the centre of the intake hole.
Note: The length of the two pipes depend of the wall­thickness.
7
All necessary markings show.
Note: The holes for the pipes should have a downward start of 1-2%, to prevent hard rain from penetrating the unit.
8
Here, both holes have been drilled, and the wall frame is now securely fastened to the wall.
Note: The screw type used depends on the wall material.
9
Place the unit on a thick underlay, such as cardboard or the like, to prevent scratches in the base plate. It is important that the unit is stable on the lift.
Note: Remember to remove tape holding the discharge damper in the transport position.
10
The unit is on the underlay and is safely and securely placed on the lift.
In the picture on the right, the unit is raised and can now be adjusted to the two guide hooks placed on the wall frame.
CODUME Page 10
11
Make final adjustments to the unit to unable it to be pushed far enough over the hooks that it cannot fall back out again.
In the picture on the right, the unit is hanging from the two guide hooks.
At the bottom of the picture one of the adjustment screws shows.
12
Now, fasten the unit to the wall frame, using the two factory-supplied M8 bolts, one on each side.
To get the unit to hang properly relative to the wall, adjust it by screwing the two adjustment screws situated just over the base plate.
Use a no. 13 screw wrench.
13
The unit must hang horizontally; therefore, it is important to check and readjust.
CODUME Page 11
14
Attach the display panel.
The photo shows the protected earth terminal.
L = Phase brown 0 = Blue AC = Connection of cooling
module (optional)
Terminal block X3
Display panel attached.
15
The unit is now hung, and the factory-supplied panels can be clicked onto the mounted clips.
CODUME Page 12
3.3 Mounting pipes and grates
Mount two Ø200 mm pipes through the wall with a 1-2% outward slant. The length of the pipes is calculated based on the thickness of the wall.
Remember to remove tape holding the damper in the exhaust in transport position. Finally, mount Ø200 mm grates with slats pointing down. Remember to joint between grate and outer wall. It is important
that the penetrations not are twisted or forced onto the unit’s connecting pieces, to avoid an elevated noise level.
3.4 Connecting the water heating surface
The unit can be purchased complete with water heating surface (optional), motorised valve, automatic heat­retaining thermostat and air escape valve internally mounted and threaded. The heating unit has been tested for leaks and undergone final inspection in accordance with DS 469.
Dimensioning of pipes, valves and connections to the unit must always be carried out by authorised personnel.
36.0
102.0
40.0
Connection
Lead the hot water connection through the cabinet on the right side or at the top to the connecting pieces placed inside the unit, behind the service cover. Connect the forward hot water connection to the connecting piece market FORWARD and the return to the connecting piece marked RETURN. See the below dimensioned sketch for further instructions regarding lead-through of the water connection.
Note: The regulating valve (3) requires clean unit water in order to function optimally, without disruptions from blockage in the valve. Airmaster A/S recommends that a dirt trap and continuous regulating valve be fitted in the hot water connection according to the below-mentioned simplified diagram.
Simplified diagram for external connection
Simplified diagram for internal structure
1: Water heating surface 2: Valve housing with presetting N 3: Valve housing with presetting 6 4: Air escape valve
IT/FS: Temperature and flow sensor TM: Thermo motor TV: Thermostatic heat-retaining valve Shutoff valve (not Airmaster delivery)
X-Vent II unit
RETURN
FORWARD
RETURN 3/6” (DN 10)
FORWARD 3/6” (DN 10)
AIRFLOW
CODUME Page 13
5: Union connections (if mounted) 6: Remote sensor
Continuous regulating valve (not Airmaster delivery) Dirt trap (not Airmaster delivery)
Ventilation
Open water flow and aerate the system using the air release valve (4). After a short while the water flow should be silent, with no noise from air.
The aeration is carried out with fully open valves, dismounted heat-retaining thermostat (TV) and thermal motor
(TM).
Adjustment of motorised valve
The unit comes with regulating valve (3) type TRV-2S preset to 6 – fully open valve. The regulating valve is preset according to the diagram below, such that the prescribed flow is achieved with differential pressure of H, which is available to the unit in nominal operating conditions.
Remember that the unit must be aerated and rinsed prior to adjustment.
It is important to preset the valve so the maximum water flow is not exceeded.
If the differential pressure over the regulating valve is greater than 30 kPa, you risk a flow noise from the valve.
Diagram for determination of pressure loss in the water circuit and for presetting the regulating valve (3) TRV-2S.
Setting example: Water flow: 15 l/h
Desired drop in pressure: 10 kPa Setting value: 2,5
Presetting key for TRV-2S: Plumbing no. 403399-411
Calculation of heating needs
The heat requirement for heating air from temperature after heat recovery to the desired supply temperature is calculated at 20 °C and 101.3 kPa:
Q = 0.34 ⋅⋅⋅ qv ⋅⋅⋅ (IT – t) [ W ] where
q
v
air volume in m3/h IT desired supply temperature t = 15.9 °C temperature prior to post-heating surface
Conditions: - outdoor temperature –12 °C
- room temperature 22 °C
- temperature rate of efficiency 82%
CODUME Page 14
Calculation of water volume
The flow-through volume of water is calculated at 20 °C and 1 bar:
qw =
( )
RF
tt16,1
Q
[ L / h ]
where Q heating needs
tF water temperature forward tR water temperature return
CODUME Page 15
Setting the heat-retaining valve
The heat-retaining valve (2) type RA-N 10 is factory-set to N, fully open valve. The valve is preset to 3.5. The setting zone of the sensor element (TV) type RA is factory-set to a min. of 1.5 to ensure a minimum heating surface
temperature of approx. 14°C, provided that hot water is available.
Frost-resistance
The heat supply or water flow must never be interrupted/shut off in frosty weather
conditions, e.g. on weekends and during holiday periods.
The flow temperature must never drop below 40 °°°°C in frosty weather conditions.
3.5 Connecting the electric heating surface
The unit comes complete with electric heating surface and safety thermostats internally installed and wired.
Note the greater current collection with electric heating surfaces (see the electrical installation section).
Safety functionalities of electric heating surface
The electric heating surface is protected against overheating in accordance with DS 447 thanks to two safety thermostats that disconnect the heating surface in case of overheating.
One thermostat cuts out the heating surface at 70 °C and has an automatic reset
The other thermostat cuts out the heating surface at 120 °C and has a manual reset
Furthermore, the unit is fitted with air volume monitoring
which at air speeds of less than 0.3 m/s cuts out the heating surface and automatically re-connects it again when the air
speed is greater than 0.3 m/s.
4. Electrical installation
The electrical installation must be performed by an authorised electrician.
Fuse and supply separators must be mounted as regulated in the
permanent installation for the unit. Fuse and supply separator are not delivered by Airmaster.
Electrical installation includes:
Connection of conventional power
Connection of display panel
Connection of any other accessories, such as CO2 sensor, PIR sensor or CTS connection
4.1 Connecting the power
Connect the power according to the electrical diagram 23. Size the power cable according to applicable rules and regulations, taking into account existing conditions at the installation site.
Mount the power cable in the terminal block on the right side of the unit (pos. 21) and connect terminals L, N and rack (see item 14 in mounting unit on wall frame).
Note that the control panel and any other signalling devices must be installed before the power is switched on.
AM II 300
Without heating surface /
with heating surface
Electric heating surface
Elec. power supply: 1 ~ 230 V + N + PE / 50 Hz 1 ~ 230 V + N + PE / 50 Hz Output: 78 W 1500 W Full-load power: 0.6 A 6.5 A * Connecting terminals: 0.75 mm2 0.75 mm2 Max. fuse: 20 A 20 A
CODUME Page 16
Leakage power: <= 3.O mA
Operation of spring terminal with screwdriver:
1. Open terminal by pressing on the spring.
2. Insert conductor
3. Remove the pressure on the spring.
4.2 Connecting the display panel
The delivery includes a separate display panel, with 3 m cable internally wired to the control box (pos. 23, see page 5 and 6). Connect the display panel according to the electrical diagram, page 23. Mount the connecting cable via the cable lead-through on the right side of the unit (pos. 21, see page 5 and 6).
Mount the display panel at a suitable height on the wall in the same room as the ventilation unit, and so that it can also be pulled out to adjoining rooms. The maximum cable length is 30 m.
The connecting cable for the display panel is a 2x2 conductor, twisted-pair screened cable which must be connected properly according to the following instructions:
1. Sheath and screen foil are stripped as close to the connecting terminals as possible for the sake of EMC noise (see photo on left).
2. Be careful removing the conductors’ insulation, so as not to damage or break them.
3. Maintain the paired twisting of the conductors to the terminals.
4. Terminate the screen at the main box, as shown in section 4.6
4.3 Connecting a CO2 sensor (optional)
Connection of CO2 sensor and transformer is done in accordance with the electrical diagram section, 5.5. The CO2 sensor comes pre-programmed for use with the X-Vent II series. If you prefer a different configuration, please
contact Airmaster A/S. For configuration of the control, see the manual X-Vent Controller – function and menu overview.
Terminate the screen at the main box, as shown in section 4.6
Recommended location of the X-Vent CO2 sensor:
Approx. 1 m from the unit’s exhaust opening
Approx. 2 m above floor level
REMEMBER to keep a distance to
open windows and doors.
4.4 Connecting a PIR sensor (optional)
Connect (PIR) type ”Scantronic 420” movement sensors to the control box as instructed in the electrical diagram, page
23. On installation, refer to the instructions accompanying the PIR sensor (Sensor of movement). For configuration of the control, see the guide X-Vent Controller – functionalities and menu overview.
Extract
CODUME Page 17
Terminate the screen at the main box, as shown in section 4.6
4.5 External connections
Make external connections as shown in the following diagram.
Terminate the screen as shown in section 4.6
4.6 Screen termination
Manual start
CODUME Page 18
Terminal block
X3
Display connection
Bend screen and place under clamps, then tighten screws.
Note: The screen is not terminated at the display and external sensors.
CODUME Page 19
5. Appendix
5.1 Main dimensions X-Vent II 300 WALL MODEL
a
g g
b
e
i
k
n
h
p
q
m
l
o
A
B
C
E
D
1
2
3
4
B
E
C
D
5
6
r
A
a b c d e f g h i k l m n o p q r s t u
AM II 300 1274 578 - - 327 - 200 130 157,5 897 324 152 6 20 36 35 45 - - -
A = Bottom B = Inlet side C = Left side D = Right side E = Back side
1 = Exhaust 2 = Intake 3 = Inlet 4 = Extract 5 = Wall frame
6 = Center holes
CODUME Page 20
5.2 Main dimensions X-Vent II 300 WALL MODEL partially integrated
b
A
B
E
d
B
3
C
D
e
C
D
o
i
k
p
q
E
4
5
6
g g
a c
f
m
l
h
n
r
A
a b c d e f g h i k l m n o p q r s t u
AM II 300 1274 578 1244 214 327 564 200 130 157,5 897 324 152 6 20 36 35 45 - - -
1 = Exhaust 2 = Intake 3 = Inlet 4 = Extract 5 = Wall frame 6 = Centre holes
A = Bottom B = Inlet side C = Left side D = Right side E = Back side
CODUME Page 21
5.3 Main dimensions X-Vent II 300 WALL MODEL combi 3
A
B
C
E
D
1
2
3
4
B
E
C
D
5
6
a
g g
b
A
e
h
s
n
m
l
o
r
i
k
p
q
u
t
s
a b c d e f g h i k l m n o p q r s t u
AM II 300 1274 578 - - 327 - 200 130 157,5 897 324 152 6 20 36 35 45 125 210 547
1 = Exhaust 2 = Intake 3 = Inlet 4 = Extract 5 = Wall frame 6 = Centre holes
A = Bottom B = Inlet side C = Left side D = Right side E = Back side
CODUME Page 22
5.4 Main dimensions X-Vent II 300 ROOF MODEL partially integrated
a
b
k
h
d
f
i
n
m
l
g g
c
A
B
C
E
D
1
2
3
4
B
E
C
D
e
5
6
p
q
o
r
A
a b c d e f g h i k l m n o p q r s t u
AM II 300 1274 578 1244 214 327 564 200 217 157,5 897 324 152 6 20 36 35 45 - - -
1 = Exhaust 2 = Intake 3 = Inlet 4 = Extract 5 = Wall frame 6 = Center holes
A = Bottom B = Inlet side C = Left side D = Right side E = Back side
CODUME Page 23
5.5 Electrical diagram
PE
L N
PE
P1
L N
AC
A2 (*1)
X3-14
(*2)
S2
X3-1 X3-4
X3-2 X3-3
GND
12V 0V
B
A
X3-13
A1
B1 (*1)
1 2
7 8
X3-5 X3-11
X3-4 X3-12
GND
B2 (*1)
12V+ 12V-
NC NC
X3-1 X3-4
X3-10 GND
Manuel start (*1)
1 2
X3-1 X3-8
CTS start (*1)
X3-1 X3-9
X3-12 X3-4
CTS flow (*1)
Alarm (*1)
0-10V
GND X3-6 X3-7
< 24V/100mA/2VA
S1
X3-1
12V (DC)
X3-2 -RS485(B) X3-3 +RS485(A) X3-4 GND (DC) X3-5 24 VAC+ (*1) X3-6 Alarm output terminal 1 X3-7 Alarm output terminal 2 X3-8 Manuel start input X3-9 CTS start input X3-10 PIR signal input X3-11 24 VAC- (*1) X3-12 0-10V signal input X3-13 Condensed terminal 1 X3-14 Condensed terminal 2
(*1)
Option
(*2) Jumper has to be removed if A2 is mounted A1 Ventilation unit A2 Cooling unit B1 CO2 sensor (*1) B2 PIR sensor (*1) P1 Display panel or LON module S1 Alarm switch S2 Condensed float switch Manuel start (*1) See section ”4.3.5 External connections” CTS start (*1) See section “4.3.5 External connections” CTS flow (*1) See section ”4.3.5 External connections” Alarm (*1) See section ”4.3.5 External connections”
CODUME Page 24
5.6 Capacity data
Operation/Capacity at 35 dbA
Operation/Capacity at 30 dbA
CODUME Page 25
CODUME Page 26
5.7 On-site testing of air volumes
CODUME Page 27
Test of air volumes are made with help from a differential pressure – manometer and can be read in the following diagrams.
Placement of the pressure connecting piece: Inlet air: Right side at the back. Exhaust air: Left side at the back.
Air volume measured on pressure taps.
WALL MODEL
ROOF MODEL
5.9 EU declaration of conformity
Inlet air Exhaust air
Inlet air
Exhaust air
CODUME Page 28
Product X-Vent II 300
Is compliant with the following directives:
Directives The Machinery Directive 2006/42/EC
The Low Voltage Directive (2006/95/EC) The EMC Directive (2004/108/EU)
CODUME sa.
www.codume.eu info@codume.eu
Tel : +32 2 511 20 10
Fax : +32 2 511 23 59
Loading...