Do not store or use gasoline o
other flammable vapors o
liquids in the vicinity of this o
any other appliance.
Disconnect power before servicing
WARNING
Improper installation, adjustment, alterations,
service or maintenance can cause property
damage, injury or death. Read the
installation, operating and maintenance
instructions thoroughly before installing or
servicing this equipment.
IMPORTANT
IT IS IMPORTANT TO POST INSTRUCTIONS WHICH ARE TO BE FOLLOWED
IN THE EVENT THE USER SMELLS GAS. THESE INSTRUCTIONS SHOULD
BE LOCATED IN A PROMINENT LOCATION, AND BE FULLY UNDERSTOOD
BY ALL USERS OF THIS EQUIPMENT. THIS INFORMATION SHOULD BE
OBTAINED FROM YOUR LOCAL GAS SUPPLIER.
ALL SERVICE MUST BE PERFORMED BY A QUALIFIED CLEVELAND
RANGE AUTHORIZED TECHNICIAN.
The wiring diagram is located on the back of the lower front panel.
RETAIN THIS MANUAL FOR YOUR REFERENCE
WARNING
Page 3
INSTALLATION AND MAINTENANCE
Gemini Dual Gas Steam Generator and Convection Steamer
Table of Contents
Chapter Page
CHAPTER 1 PRODUCT IDENTIFICATION ________________________________________ 1
A. MODEL NUMBER ________________________________________________________ 1
B. SERIAL NUMBER ________________________________________________________ 1
C. PRODUCT INFORMATION PLATE __________________________________________ 1
D. 24CGA6.2 PRODUCT VIEW _______________________________________________ 2
E. 24CGA10.2 PRODUCT VIEW _______________________________________________ 3
CHAPTER 2 INSTALLATION INSTRUCTIONS _____________________________________ 4
A. GENERAL ______________________________________________________________ 4
B. INSTALLATION OF THE STEAMER _________________________________________ 4
1. Locating the Steamer __________________________________________________ 5
a. Location and Clearance Requirements of the Steamer _____________________ 5
b. Exhaust Hood Requirements _________________________________________ 8
c. Positioning and Leveling the Steamer __________________________________ 8
3. Install the Free Air Vented Drain Lines _____________________________________ 9
4. Install Gas Supply Lines ________________________________________________ 10
a. Gas Supply Requirements ___________________________________________ 10
b. Install Gas Supply Lines ____________________________________________ 10
c. Testing Gas Supply Lines ___________________________________________ 11
5. Install Electric Power Lines _____________________________________________ 11
6. Water Supply Requirements and Installation ________________________________ 12
a. Water Supply Requirements _________________________________________ 12
b. Setting the Descale Required Light ____________________________________ 13
c. Install Water Supply Lines ___________________________________________ 15
d. Testing Water Supply Lines __________________________________________ 16
C. STARTUP AND CHECKOUT _______________________________________________ 16
2. Burner Ignition Test (Lighting and Shutdown Instructions) ______________________ 18
a. Lighting Instructions ________________________________________________ 18
b. Shutdown Instructions ______________________________________________ 19
3. Start Up Test Procedure Gas Gemini ______________________________________ 19
a. Startup Procedure __________________________________________________ 20
b. Blowdown Inspection _______________________________________________ 20
c. Operating Tests and Final Checkout Procedure __________________________ 21
CHAPTER 3 PREVENTATIVE MAINTENANCE AND TROUBLESHOOTING ____________ 23
A. MAINTENANCE _________________________________________________________ 23
1. Maintenance Records __________________________________________________ 23
B. TROUBLESHOOTING GUIDE ______________________________________________ 24
Page 4
CHAPTER 1 PRODUCT IDENTIFICATION
Cleveland Range, Inc. assigns two product identification numbers to each steamer: a model number and a
serial number. The model number identifies the product characteristics. The serial number identifies the
individual unit.
A. MODEL NUMBER
This manual covers the Gemini Model No. 24CGA6.2 and 24CGA10.2 Dual Steam Generator and
Convection Steamer.
Each character of this model number identifies a characteristic of the steamer. The Gemini Model No.
24CGA10.2 is 24 inches wide, a Convection steamer, Gas powered, and an Atmospheric steam generator
with a capacity for 10 cooking pans, this model has the extra suffix “.2” to differentiate it from our standard
10 pan model that does not have two separate generators. This manual covers all standard features and
options available on Gemini gas steamers.
Other than selection of options, there are presently no significant design, parts, or operating differences
among steamers with this model number. Figures 1-2 and 1-3 illustrate the two Gemini designs of gas fired
steamers and identifies their major components.
B. SERIAL NUMBER
During manufacture, Gemini Steamers are assigned individual serial numbers. Whenever any inquiry is
made with Cleveland Range regarding a steamer the serial number should be referenced.
C. PRODUCT INFORMATION PLATE
The Product Information Plate on the left side of the unit lists the model and serial number of the steamer.
Refer to Figures 1-2 and 1-3 for the location of the plate. Figure 1-1 illustrates a typical Gemini Product
Information Plate. The rating plate also lists power and wiring requirements.
This equipment should only be installed by qualified, professional plumbers, pipe fitters, and electricians.
·
The installation of this steamer must conform with the Basic Plumbing Code of the Building Officials and
Code Administrators International, Inc. (BOCA), the National Fuel Gas Code, ANSI Z223.1-(latest
edition) or the Natural Gas Installation Code CAN/CGA-B149.1 or the Propane Installation Code
CAN/CGA-B149.2 as applicable, The National Electrical Code, ANSI/NFPA No. 70-(latest edition) or the
Canadian Electrical Code, CSA C22.2 as applicable, the Food Service Sanitation Manual of the Food
and Drug Administration (FDA) and all applicable state and local codes and regulations.
·
The installation instructions must be read in their entirety before starting the installation of this steamer.
WARNING
DEATH, INJURY, AND EQUIPMENT DAMAGE could result from the
improper installation, adjustment, alteration, service or maintenance
of a steamer or installation of a unit damaged during shipment or
storage. Any of these conditions could also void the equipment
warranty.
DO NOT INSTALL a Gemini steamer that has been damaged.
Install the Gemini steamer according to the policies and procedures
·
To install this steamer, the following requirements must be considered when selecting a location.
a. A suitable drain must be available within 12 ft. of the steamer.
b. An electrical supply matching the power requirements found on the rating plate must be available.
c. A gas supply matching the fuel requirements found on the rating plate must be available.
d. The location must have sufficient space to meet the clearance requirements of the steamer as
outlined in Chapter 2, Section B, Part 1, “Locating the Steamer”.
e. A water supply meeting the requirements outlined in Chapter 2, Section B, Part 6 “Water Supply
Requirements and Installation” must be available.
B. INSTALLATION OF THE STEAMER
After selecting the steamer’s operating location the steamer can be positioned, and installed. After Final
Setup and Checkout, the Gemini steamer should provide years of reliable operation.
outlined in this manual.
4
Page 8
1. Locating the Steamer
a. Location and Clearance Requirements of the Steamer
For safe and efficient operation, observe the following criteria when selecting an operating location
for the Gemini steamer.
1) The unit should be installed in an area that is free and clear of combustible materials.
2) Do not locate the steamer directly over a floor drain.
3) A proper air supply for combustion and ventilation is critical to safe, efficient operation of Gemini
gas steamers.
4) Do not install any heat producing equipment near the air vents of the equipment. Do not block
the air vents of the unit. Do not store articles on top of the unit.
.
5) Figure 2-1 and 2-2 illustrate the dimensions and clearances required for these steamers.
Maintain the following minimum dimensions around the unit for safe and efficient operation,
maintenance and service.
·
·
·
6) The steamer must be level both front to back and side to side. Select an operating surface
that is level enough to allow leveling the unit without extreme adjustment of the legs.
7) The location selected must be capable of supporting 650 lbs. for a Gemini steamer. This
includes the weight of the water and the food.
Malfunctions and equipment damage may result from improper
mounting. Malfunctions and/or damage resulting from improper
mounting are not covered by the equipment warranty.
The steamer MUST BE LEVEL BOTH FRONT TO BACK AND
SIDE TO SIDE in all mounting arrangements.
Catastrophic damage will result from shifting the steamer more than
o
10
out of level with power supplied to the unit.
All clearance requirements above, below, and
around the unit are the same for non-combustible
locations as for combustible locations.
Maintain a 3-inch operating clearance at the sides of the unit, and at least a 3-inch
clearance at the back.
A 12 in clearance is recommended on the right side for servicing the steamer.
Approximately 24 inches of clearance is recommended in front of the unit for opening the
door and standard pan clearance.
CAUTION
WARNING
5
Page 9
OPERATING
CLEARANCE
SECONDARY
CLEARANCE
GAS ELECTRIC COLD WATER CLEARANCE DRAINAGE
1-1/4" IPS line size, 3/4" connection
NATURAL PROPANE BTU 2 Fans & controls 60 psi maximum SIDES = 3.00” Do not connect other
Piping 3/4" N.P.T Piping 3/4" N.P.T. 50,000
Supply pressure Supply pressure Generator (1) 3/8" dia. IPS for FRONT = 24.00”
4.50" W.C. Min.
14.00” W.C. Max.
Manufacturer must be notified if unit will
be used above 2,000 feet
11.00" W.C. Min.
14.00” W.C. Max.
Do not use PVC pipe
each
100,000 total
120V-1Phase, 60 Hz. 35 PSI minimum RIGHT = 12.00" for service 1-1/2" dia.
150 watts each (1) 3/8" dia. IPS for
Generator
Condenser
REAR = 3.00” units to this drain
Drain must be vented
Figure 2-1 Gemini 24CGA6.2 Dimensions and Clearances
6
Page 10
OPERATING
CLEARANCE
SECONDARY
CLEARANCE
GAS ELECTRIC COLD WATER CLEARANCE DRAINAGE
1-1/4" IPS line size, 3/4" connection
NATURAL PROPANE BTU 2 Fans & controls 60 psi maximum SIDES = 3.00” Do not connect other
Piping 3/4" N.P.T Piping 3/4" N.P.T. 72,000
Supply pressure Supply pressure Generator (1) 1/4" dia. IPS for FRONT = 24.00”
4.50" W.C. Min.
14.00” W.C. Max.
Manufacturer must be notified if unit will
be used above 2,000 feet
11.00" W.C. Min.
14.00” W.C. Max.
Do not use PVC pipe
each
144,000 total
120V-1Phase, 60 Hz. 35 PSI minimum RIGHT = 12.00" for service 1-1/2" dia.
150 watts each (1) 1/4" dia. IPS for
Generator
Condenser
REAR = 3.00” units to this drain
Drain must be vented
Figure 2-2 Gemini 24CGA10.2 Dimensions and Clearances
7
Page 11
b. Exhaust Hood Requirements
The Gemini gas steamer MUST be installed under an exhaust hood. The exhaust hood must
extend over the gas flue opening on top of the steamer and meet the following requirements:
1). The Gemini gas steamer must be vented in accordance with all local, state and national
codes for venting gas fired appliances.
2). The exhaust hood must be sized for the cumulative ventilation requirements of all the gasfired appliances in the area including the Gemini. Figures 2-1 and 2-2 contains the
dimensions, gas flow, and BTU per hour data required to calculate the minimum required
hood dimensions and minimum ventilation capacity (c.f.m.) for the Gemini 6 and 10 pan
steamers.
3). Do not connect the exhaust hood directly to the flue outlet of the steamer.
4). If an existing hood cannot be used, a new one should be constructed over the steamer.
c. Positioning and Leveling the Steamer
NOTE: If there is not enough room to work on the drain, electrical, gas and water lines with the
unit in place, postpone positioning and leveling the unit until all site preparation is
completed. After the lines are prepared, position and level the steamer, then connect the
utility lines.
Move the steamer into position. Using a level, adjust the adjustable legs until the unit is level.
2. Install Slide Racks
a. Refer to Figure 2-3. Each rack has four
loops: two at the top and two at the
bottom. Hold the slide rack so the ends
of the hanger loops are towards the
cavity wall, as shown in the figure.
b. Slide one rack into the compartment with
loops toward one side.
c. Hook the loops over the top and bottom
pins.
d. Repeat steps a. through c. for the other
racks.
INJURY AND EQUIPMENT DAMAGE could result from improper
lifting. A Gemini Steamer weighs approximately 545 pounds. Use
enough workers with experience lifting heavy equipment to place
the steamer on the supporting surface.
WARNING
Figure 2- 3 Slide
Rack Installation
8
Page 12
3. Install the Free Air Vented Drain Lines
Furnishing and installing the drain line is the responsibility of the owner and/or installer. Figure 2-4 illustrates
a drain layout recommended by Cleveland Range.
WARNING
DEATH, INJURY, AND EQUIPMENT DAMAGE could result from improper installation of the
drain outlet lines.
Improper installation of these lines could void the Gemini Steamers warranty. The following
restrictions are critical to the safety of personnel and equipment, and must not be violated under
any circumstances.
Do not connect the drain line into PVC or any drain material that cannot sustain 180
o
F.
Do not connect drains from any other equipment to the drain line of the Gemini Steamer.
Do not connect the drain outlet extension line directly to a floor drain or sewer line.
The drain line must be free air vented, have gravity flow from the steamer, and terminate
outside the perimeter of the unit.
a. The drain lines must be installed in compliance with the Basic Plumbing Code of the Building
Officials and Code Administrators International, Inc. (BOCA), and the Food Service Sanitation
Manual of the Food and Drug Administration (FDA) and any state, provincial or local codes.
b. Do not install the steamer directly over a drain. Steam rising up out of the drain will adversely
affect operation, cooling air ventilation and may damage electrical components.
c. The total length of pipe and number of bend fittings required to reach the open drain determines
the pipe size used to extend the drain line to an open drain.
·
If the drain outlet extension requires 6 feet or less of pipe, and no more than two elbows are
required, 1- ½ inch pipe and fittings are acceptable.
·
If the drain outlet extension requires 6 to 12 feet of pipe, or requires three or more elbows,
2-inch pipe and fittings are required.
d. The drain line must have a gravity flow from the steamer
drain outlet to the floor drain. Do not install a trap in the
drain line.
e. Free air venting requires a minimum of 1 inch of
clearance between the end of the drain line and the top of
the floor drain.
f. Do not connect the steamer drain directly to drains or
plumbing of any other equipment.
g. Refer to Figure 1-2 or 1-3 depending on Model. Connect
the drain to the steamer as described below:
·
The steamer is supplied with a 1-½ -inch pipe
connection at the bottom of the unit (Figure 2-4).
·
When assembling the pipes and fittings of the drain
outlet extension, apply a hardening type pipe sealant
to the threads, and thread them together FINGER
TIGHT ONLY. DO NOT USE A WRENCH.
DRAIN
1” CLEARANCE
MINIMUM
REAR DRAIN
Figure 2-4 Typical Drain
Connection for Both Models
(Gemini 6-pan shown)
DRAIN LINE
9
Page 13
A
4. Install Gas Supply Lines
a. Gas Supply Requirements
1) Make sure the gas supply type matches the type of gas shown on the rating plate.
2) Make sure that the gas supply pressure does not exceed 14” water column, and falls within
the acceptable gas pressure range shown below:
·
Natural gas pressure must be between 4½” – 14” water column.
·
Propane gas pressure must be between 11” – 14” water column.
b. Install Gas Supply lines
The installer/owner is responsible for furnishing and installing the gas supply lines, valves,
regulators, and accessories. When installing the gas supply lines and accessories, observe the
following:
1). The installation must conform with local codes, or in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1 (latest edition) or the Natural Gas Installation Code,
CAN/CGA-B149.1 or the Propane Installation Code, CAN/CGA-B149.2 as applicable.
2). THE GAS SUPPLY PRESSURE TO THE
STEAMER MUST NEVER EXCEED 14”
WATER COLUMN (½ psi). If the gas supply
pressure exceeds 14” water column; a
pressure regulator must be installed in the
gas supply plumbing to reduce the pressure
to the steamer.
3). Refer to Figure 2-5 for the recommended
layout of the gas supply lines. Refer to
Figure 2-1 or 2-2 depending on which model
you have, Detail A for the location of the ¾
inch gas inlet of the steamer.
4). Install a manual shut off valve between the
gas supply and the steamer. See Figure 2-5.
From now on this valve will be referred to as
the Main Manual gas valve.
5). It is recommended that a sediment trap (drip
leg) be installed in the gas supply line. See
Figure 2-5.
6). Use a pipe sealant compound, which is
resistant to LP gas.
10
MAIN GAS
SUPPLY
PRESSURE REGULATING
VALVE (IF
Gemini
GAS MANIFOLD
CONNECTION
Figure 2-5, Recommended
Gas Supply Line Layout
CONNECTION
DIMENSION DIAGRAM
REQUIRED)
MAIN
MANUAL GAS
SHUTOFF VALVE
DRIP LEG
GAS SUPPLY
ON
Page 14
c. Testing Gas Supply Lines
1). Leak Testing the appliance
LEAKING GAS CAN CAUSE FIRE OR EXPLOSION WITH PROPERTY
DAMAGE, INJURY OR LOSS OF LIFE. If the installer smells gas, or
suspects there is a gas leak, immediately refer to the posted gas leak
instructions. The posted instructions are provided by the local gas
supplier, and supersede any other instructions. Until the leak is stopped
observe the following precautions in addition to the posted instructions:
Do not light or start any appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Immediately call the gas supplier from a phone away from the building.
Follow the gas supplier’s instructions.
If the gas supplier cannot be reached call the fire department.
Before permanently turning on gas to the steamer or after any service to the gas supply, test
all pipe joints for leaks with a soap and water solution. All leaks must be corrected before
attempting to operate the steamer.
WARNING
FIRE OR EXPLOSION HAZARD
2). Pressure Testing the Gas Supply Lines
The steamer must be isolated from the gas supply system during any pressure testing as
follows:
· The appliance and its main manual shut-off valve must be disconnected
supply piping system during any pressure testing of the system at test pressures in
excess of 14” water column (½ psi or 3.45 kPa). Be sure to leak test all fittings with a
soap and water solution after reconnecting the gas supply.
· The appliance must be isolated from the gas supply piping system by closing its main
manual shut-off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 14” water column (½ psi or 3.45 kPa).
5. Install Electric Power Lines
The electrical supply must match the power requirements specified on the steamers rating plate and be
made in accordance with the following requirements.
a. The steamer must be grounded and have the electrical power lines installed in accordance with
local codes and/or the National Electric Code, ANSI/NFPA No. 70-LATEST EDITION (USA) or the
Canadian Electrical Code, CSA C22.2, as applicable. The wiring diagram is located on the back of
the lower front panel.
b. Optional Factory Supplied Plug
·
If a cord and plug are supplied with the unit, plug the unit into a grounded outlet dedicated to
the steamer.
·
A cord-equipped appliance will be equipped with a three-prong (grounding) plug for your
protection against shock hazard, it should be plugged directly into a properly grounded threeprong receptacle. Do not cut off or remove the grounding prong from the plug.
11
from the gas
Page 15
i
c. A main disconnect switch and a separate fuse or breaker should be installed near the unit as shown
in Figure 2-6. See Figure 2-1 or 2-2 for the steamers power requirements. Throughout the
remainder of this manual the fused disconnect switch is referred to as the main external power
switch.
d. Refer to the connection diagrams in Figure 2-7, and connect the wires to the terminal block and
ground connector accordingly.
MAIN EXTERNAL
POWER SWITCH
Gemin
DRAIN LINE
COLD WATER SUPPLY LINES
ELECTRICAL CONDUIT
INLET
TERMINAL
BLOCK
Figure 2-6, Recommended Electrical Layout
Figure 2-7, Electrical Connections
6. Water Supply Requirements and Installation
a. Water Supply Requirements
Using water not within the limits specified in this
manual could void or reduce Cleveland Range’s
warranty coverage of the steamer.
CAUTION
1). Water Quality
GROUND
LUG
As with any steam generating equipment, poor water quality degrades the performance of the
steamer.
Check the quality of supply water as described below before starting construction of the water
supply lines. If a water treatment system must be installed to achieve acceptable water quality,
install it before connecting the water supply lines to the Gemini Steamer.
If softened or chlorinated water is used in a Gemini steam generator, a carbon type filter must
be used for the water before it enters the steamer to remove Chlorine or other salts. If the water
supply is treated or softened either by the Water Company or on the premises, it may contain
chlorine or various salts. These additives are damaging to the steam generator. Salts and
chlorine used to soften or treat water cause rapid scale buildup, and/or increased corrosion if
allowed to flow into the steamer.
Contact a local water treatment specialist for an on-the-premises water analysis. The
recommended minimum feed water quality requirements for the steamer are listed in Table 2-1.
12
Page 16
Table 2-1. Minimum Water Quality Requirements
Scale Forming Factors
Total Dissolved Solids less than 60 parts per million
Silica less than 13 parts per million
Alkalinity less than 20 parts per million
Corrosion-Causing Factors:
Free Chlorine less than 0.5 parts per million
Chloride less than 30 parts per million
PH factor greater than 7.5
2). Water Supply System
Provide a water supply system that fulfills the requirements of the limits listed in Table 2-1. The
supply must provide a minimum dynamic pressure of 35 psi (2.4 kg/cm
pressure of 60 psi (4.1 kg/cm
2
).
2
) and a maximum static
·
If analysis shows that the supply water is NOT within the required limits, either a water
treatment system and/or carbon filter must be installed in the line feeding the steam
generator or the frequency of maintenance, cleaning, and descaling must be increased
beyond that recommended in the maintenance schedule (Chapter 3). If more frequent
descaling is selected as the means of protecting the steamer from premature failure, the
“DESCALE REQUIRED” light timing should be readjusted to reflect the increased cleaning
schedule.
b. Setting the Descale Required Light
The Descale Required Light feature
tracks the number of hours the unit has
been operating since it was last reset,
and lights when it is time for descaling.
1). General
The Descale Required Light consists of
an indicator light, a solid state timer
module, and a reset/rocker switch. (The
light and reset switch consist of a single
device on the front panel identified by the
“DESCALE REQUIRED” label.) See
Figure 2-8. The timer is a digital clock
module inside the unit that keeps track of
how many hours your steamer has been
in operation since the last reset of the
timer.
DESCALE REQUIRED LIGHT/RESET
SWITCH. NOTE: ORIENTATION OF
SWITCH WILL VARY DEPENDING ON
MODEL
Figure 2-8 Descale Required Light
and Timer Module
13
Page 17
2). Determining the Timer Setting
The recommended setting of the Descale
Required light is determined by the
quality of the water supply. Table 2-2
suggests appropriate timer settings.
3). Switches Determine Timer Setting
The Timer Module contains a bank of
miniature switches that determine the
timer setting. The switches can be placed
in either the ON or OFF positions.
Each switch has a specific value. The
total timer setting is the sum of the values
of all of the switches that are in the ON
position. (See Figure 2-9 for switch
values).
The Descale Required Light timer is
preset at the factory with switches 1 and
2 turned ON. Adding the values of these
switches results in a setting of 384 hours
(128+256=384).
4). Procedure to Change Descale Required Light Timer Switch Settings
Read this procedure completely before starting. The Descale Required Light Timer setting
should be changed only by qualified maintenance technicians familiar with electrical safety
procedures.
a) Make sure all power to the unit is OFF.
Disconnect the electrical power before servicing.
WARNING
Suggested Timer Settings
Based on Water Quality/Hardness
Quality of
Feed Water
Poor 25 128 hours
Average 15 256 hours
Good 7 384 hours
Very Good 3 or less 512 hours
✳17.1 ppm = 1 grain/gal of hardness
1 2 3 4
ON
128
256
512
Hardness
(grains/gal.)
Table 2-2
Timer
Settings
✳
Switch
Values
(in Hours)
1,024
Figure 2-9 Switch Values
b) Determine the time you want to set.
c) Locate the timer modules, which are located horizontally in the front, at the right and left of
the electrical drawer.
d) Set the timer switches. It is a good idea to turn them all OFF first then turn ON the desired
switches.
e) Verify that the switches are in the desired position. Replace the electrical drawer cover.
14
Page 18
c. Install Water Supply Lines
The installer/owner is responsible for the correct water connection of the unit. When connecting the
water supply lines observe the following instructions and all national and local codes and
regulations:
1). Never
connect the unit to HOT WATER. The condenser system of the steamer will not work
properly if it is connected to HOT or WARM water.
2). The water supply should have a minimum flow pressure of 35-psi (2.4 kg/cm²) and a maximum
static pressure of 60-psi (4.1 kg/cm²). If the static pressure is above 60 psi, a pressure regulator
must be used set at approximately 50 psi. Pressure above 60 psi can damage the solenoid
valves.
3). The Gemini Steamers are supplied with two connection points for incoming water, one feeds
the condensers and the second supplies feed water to the generators. If the local water supply
is of poor quality (see Chapter 2, Section 6, Part a.1 for details of water quality), it is
recommended that treated or otherwise filtered or conditioned water be used to supply the feed
water to the generators. In the case of using a separate water supply, use the layout shown in
Figure 2-11.
4). Pay attention to the following requirements and recommendations when connecting the
steamer to the water supply:
a) Cleveland Range recommends the plumbing layout illustrated in either Figure 2-10, for
installations using a single water supply or Figure 2-11 if a separate conditioned water
supply is being used for boiler feed. Note: If using a single water feed to the system the
supply piping to the tee fitting should be of at least the next largest size of pipe to the
connection provided at the steamer.
b) The steamer has two 3/8-inch IPS fittings (Model 24CGA6.2) or two 1/4-inch IPS fittings
(Model 24CGA10.2) for the water connections to the generator and to the condenser.
These fittings are detailed as D and E in Figure 2-1 or 2-2.
c) Install a manual water valve between the main cold water supply line(s) and the steamer
supply lines.
d) The National Sanitation Foundation (NSF) requires installation of a check-valve in all supply
lines in accordance with and as required by local plumbing codes.
e) The water supply line(s) should be designed so that the unit can be moved for service.
Gemini
Condenser Solenoids
Steam Generator
Solenoids
Water Connection D on
Dimension Diagram
Strainer
*
Water Connection E on
Dimension Diagram
Check Valve
Pressure Reducer
(if required)
Air/Water Column
(if required)
Main Cold
Water Supply
Main Water
Shut Off Valve
Flow
Figure 2-10 Cleveland Range Single Water Supply Arrangement
(
May be installed internal to the steamer on some models)
*
15
Page 19
r
r
Gemini
Condenser Solenoids
Steam Generator
Solenoids
Water Connection D on
Dimension Diagram
Water Connection E on
Dimension Diagram
Strainer
*
Check Valve
Pressure Reduce
(if required)
Air/Water Column
(if required)
Main Wate
Shut Off Valve
Standard Cold
Water Supply
Conditioned Cold
Water Supply
Flow
Flow
Figure 2-11 Cleveland Range Single Water Supply Arrangement when Using
Separate Conditioned Feed Water Supply
(
May be installed internal to the steamer on some models)
*
f) A 40 or 50-mesh water strainer (dirt filter)
of one of the types and construction
P/N 106684
P/N 19870
illustrated in Figure 2-12, Cleveland
Range part number 106684 or 19870 is
supplied with the unit and should be
installed where indicated in the plumbing
layout. Note: On some Models the
strainer has already been installed as
part of the internal water piping.
·
Make sure the arrow on the strainer
body points in the direction of flow
into the steamer.
·
Install the strainer so the access nut
Figure 2-12 Water Strainer Assembly
points down.
g) Construct all supply lines up to the point of installing the strainer. Flush the water supply
lines before connecting the strainer.
h) Apply pipe dope or Teflon tape to any threaded connection.
d. Testing Water Supply Lines
1). Check all connections for proper tightness. Remove the side panel to inspect water connections
inside the steamer.
2). Open the water supply valves.
3). Check all lines and connections for leakage, both inside and outside the steamer.
4). If Startup and Checkout will be performed next, leave the right side panel off; otherwise, replace
the side panel and secure it to the unit.
C. STARTUP AND CHECKOUT
The Startup and Checkout procedure prepares a recently installed or repaired steamer for operation. The
procedures check proper electrical, gas, water, and drain connections to the steamer, and verify basic
steamer operation.
16
Page 20
1. Installation Checkout
Use the Installation Checklist Table 2-3, to check the overall installation.
Table 2-3. Installation Check List
TASK REFERENCE COMPLETED
Page No.
Preparation
Verify Electric Power Requirements. 6 or 7
Verify Gas Supply Requirements 10
Verify Exhaust Hood Requirements 8
Test supply water quality. 12
Check operating location clearances 6 or 7
Installation
Verify steamer is level. 8
Check drain line connection. 9
Check Exhaust Hood 8
Check electrical line connection. 11
Check water supply connection. 15
Test water supply lines. 16
Check Gas Supply Connection 10
Leak Test Gas Supply Connection 11
Check Burner Ignition Test 18
Perform Startup and checkout. 19
Notes on installation:
17
Page 21
2. Burner Ignition Test (Lighting and Shutdown Instructions)
It is recommended that this test be performed before beginning the Startup Test Procedure. This will
insure that the basic heating system is operating normally before reviewing the overall operation of
the steamer, since much of the operation is dependant on the operation of the burner control system.
a. Lighting Instructions
This is a functional test of the intermittent pilot ignition system. Pilot/burner ignition is completely
automatic.
NOTE: Each compartment has its own steam generator and control system, and must be started
1). If not already done during prior installation or testing:
2). The controls should be set as follows:
3). Turn ON the electrical power to the steamer at the main power switch.
4). Turn ON the electrical power to the steamer at the ON/OFF levers/switches.
DO NOT TRY TO LIGHT THE BURNERS OR PILOT WITH A FLAME.
The Gemini has an electronic ignition system, which automatically lights the
pilot and burners, senses the flame, and controls gas flow. This provides
precise burner control, safety ignition, and shutdown features.
DEATH, INJURY OR EQUIPMENT DAMAGE may result from an improperly
adjusted gas control and ignition system. Do not alter any adjustments on this
electronic control or automatic gas valve.
If adjustment is required, contact an authorized service center. Cleveland
Range is in no way responsible for the operation or safety of this equipment if
the controller, valve or igniter probe is adjusted by anyone other than a
Cleveland Range authorized service representative.
independently.
·
Test the water supply lines.
·
Leak test the gas supply lines.
·
Check that the ON/OFF valve of the automatic gas control valve is in the ON position.
·
Turn the Main Manual gas valve to the open position.
·
The main power switch should be in the OFF position.
·
The steamer’s ON/OFF levers/switches should be set to the OFF position.
·
The MANUAL/TIMED switches should be set to the TIMED position.
NOTE: When initial power is supplied to the steamer with the ON/OFF lever/switch in the
a) The red indicator lights in the control panel light and water begins filling the steam
generator. The pilot/burners do not light until water reaches the safety level in the probe
assembly.
OFF position, a 3-minute blowdown cycle starts. This blowdown cycle stops
when the 3 minutes have elapsed or the ON/OFF lever/switch is changed to the
ON position.
WARNING
18
Page 22
b) After 2 to 3 minutes, water reaches the middle probe (safety level).
c) Turn on a cooking compartment (for non-”Instant ON” units only) and the burners will light
with a distinctive sound. NOTE: Cooking compartment doors must be closed first.
¨
If the burners light within 5 minutes of turning the unit ON, the ignition controls are
functioning normally. End this test procedure here.
¨
If the burners do not light within 7 minutes, there may be air in the gas supply lines
proceed to step 5.
5). Turn off electrical power to the Steamer, at both the ON/OFF levers/switches and the main
power switch.
NOTE: When the burners fail to ignite, a safety circuit in the igniter control de-energizes
the system and closes the automatic gas valve. The safety circuit resets when
the steamer’s power is turned OFF and then back ON.
6). Wait 5 minutes and then repeat steps 2 through 6. If this is a brand new installation, or an
excessive amount of air in the lines is suspected for any other reason, it may be necessary to
bleed the excess air from the lines. This should be done at a union or connection as close as
possible to the inlet of the automatic gas valve.
7). If the burner does not light after the third attempt, call a Cleveland Range authorized service
representative to adjust the burner controls.
8). Go to Shutdown Instructions.
b. Shutdown Instructions
1). Turn off electrical power to the steamer, at both the ON/OFF levers/switches and the main
power switch.
2). Turn off gas supply at the main manual gas valve.
3. Start up Test Procedure Gas Gemini
Cleveland Range steamers have either a manual dial timer control panel, an electronic control panel with a
keypad timer control, an “Instant ON” control system (available only for the Gemini 6 pan model) or an
ON/OFF control panel. There are a few operating differences between steamers with the dial timer controls
and steamers with the keypad controls.
The differences in cooking operation of the two types of timer controls are fully explained in the separate
OPERATORS MANUAL. The “Instant ON” model has no operating controls other than the Power ON/OFF
lever, and begins heating to produce steam as soon as the ON/OFF lever is set to the ON position. The
ON/OFF Control Panel, operates exactly like the manual operation of the timed models except a selector
switch is used to turn the steam to the cooking compartments ON and OFF. After performing the startup
procedure, perform the test procedure as appropriate to the control panel on the steamer being tested.
Ignore any steps, which do not apply to the steamer being tested.
This procedure is appropriate for steamers with keypad control panels, dial timer control panels, “Instant
ON” or manual control panels. Read through all steps of this procedure before starting. Complete the startup
procedure before starting the actual operating tests. This procedure should be performed only by a
service technician or installer.
NOTE: Each compartment has its own steam generator and control system, and must be started
independently.
19
Page 23
a. Startup Procedure
1. Check that the water supply line valves are open.
2. Check that the main manual gas valve is open.
3. Open the steamer door. Check for proper installation of the drain screen, slide racks, and door
gasket assembly. Be sure the drain is not blocked. Shut the steamer door.
4. Refer to electrical layout, Figure 2-6, and Figure 2-1 or 2-2. Be sure the main power switch is in
the OFF position. Verify installation of the proper size fuses or circuit breakers.
5. Set the control panels as follows:
a) Set the ON/OFF levers/switches to the OFF position.
b) Press the TIMED (top) end of the TIMED/MANUAL switch for both compartments.
c) The timer setting is not important while the ON/OFF lever/switch is in the OFF position.
·
The keypad timer display is blank without power.
·
Even if the timer is not zeroed, the timing circuits are not powered.
6. Remove the right side access covers (see Figure 1-2 or 1-3).
b. Blowdown Inspection (continue from Startup Procedure)
1. Turn ON electric power to the steamer at the main power switch. The steamer will
2. Stop the blowdown cycle before it is complete by setting the ON/OFF levers/switches to the
3. Restart the blowdown cycle by setting the ON/OFF switches to the OFF position. During the
NOTE: If the clean light comes ON, and this is a new installation or the steamer is not in need of
Death, severe electrical shock or equipment damage can result from touching
any component inside unit when main power switch is in the ON position. Use
extreme caution during testing with the access cover removed.
immediately start a 3-minute blowdown cycle. During blowdown, the fill and drain valves are
fully open while the steam generator drains are flushed with fresh water.
ON position. This energizes the operating control circuits, the red indicator on the control
panels light, blowdown stops, and the steam generator fills with water.
automatic blowdown cycle, make the following checks.
·
Check for plumbing leaks.
·
Look at the one-inch vent gap between the steamer drainpipe and the floor drain. A steady
stream of water should be draining from the steamer.
·
NOTE: The ON/OFF lever must be turned fully to the OFF position to START the proper
blowdown sequence.
·
After about 3 minutes, the cycle is complete. Check the gap at the steam drain; there
should be no more water flow at this point.
descaling reset the clean timer; otherwise arrangements should be made to descale the
steamer soon.
WARNING
20
Page 24
c. Operating Tests and Final Checkout Procedure (Continue from Blowdown Inspection)
(Sequence of Operation)
1). At the start of this test the controls should be set as follows:
2). Set both the upper and lower compartment timers to zero.
When checking inside the steamer always open the door slowly
and stand to the side and back away from the steamer. Water
leaking from the door gasket can be a sign of a blocked drain. If
the drain is blocked, hot water can accumulate inside the
compartment and spill out when the door is opened.
·
The main power switch is ON.
·
The ON/OFF levers/switches are OFF (The red indicators on the control panels are not lit).
·
The TIMED/MANUAL switch is in the TIMED position. (or for ON/OFF models the ON/OFF
compartment selector switch is in the OFF position)
·
The timer display will be blank while the ON/OFF lever/switch is set to OFF. [key pad
models]
a). KEYPAD MODELS
If the timer is not zeroed (00:00) when power is turned on in step 3, press and hold the
CLEAR key on the key pad control panel to zero the timer.
WARNING
b). DIAL TIMER MODELS
If the Timer is not zeroed, turn the dial counter clockwise until it points to the 0 mark.
3). Set the ON/OFF lever/switch to the ON position. As the steam generator fills with water, check
the following functions.
a). The red ON/OFF indicator light turns ON. The fill valve opens and water begins to fill the
steam generator. The combustion blower turns on to purge the combustion chamber.
b). After a few minutes, water appears in the bottom of the probe cylinder. As the water level in
the steam generator rises;
¨
Check that no water flows from the drain opening.
¨
Check for plumbing leaks.
4). When the water in the steam generator reaches a safe operating level (which is the level of the
middle probe), the combustion blower shuts off and the pilot ignition cycle starts. The steam
generator begins to heat the water to stand-by temperature by lighting the pilot/standby burner.
a) Water continues to fill the generator and the water level in the probe cylinder continues to
rise.
b) The water in the probe cylinder stops rising, when water reaches the upper probe.
¨
If the water level continues to rise above the tip of the higher probe, have a qualified
service representative check the probe circuit.
5). Set the TIMED/MANUAL switches of both compartments to MANUAL (or for ON/OFF Models
set the compartment selector switches to ON), the steaming cycle starts. Check the following
functions.
·
If the water level in the steam generator is above the lower probe, the heating components
turn ON and begin to heat the water to steam. (For mechanical timer models only, the
pause light comes ON)
21
Page 25
·
After a few minutes steam begins to enter the compartment from the nozzles. A small
quantity of water may drip from the nozzles until steam clears the lines.
·
After a few more minutes the compartment will reach cooking. The thermostat will close
temperature (the pause light will go OFF for mechanical timer units) and the condenser
solenoid clicks open and condenser flow starts. After a few seconds, a stream of water
flows from the drainpipe. If no drain water flows, check that the water supply valves are
open, and the lines are connected properly.
·
With the unit in manual cooking mode the unit should steam continuously until turned OFF,
or set to the timed cooking mode. After several minutes of steaming, check for steam leaks
around the door gasket.
6). As the unit continues to steam in Manual Cooking Mode, test the no-water/low water safety
circuit.
a) Close the steamers manual water supply valve. Observe the steam generator probe
cylinders while steaming continues.
b) As water steams out of the generator, the water level drops below the low water safety
cutoff point. The steamer should automatically shutoff.
c) Re-open the manual water supply valve. The steamer’s controls automatically refill the
steam generators with water to the safety level and resumes steaming.
7). When the TIMED/MANUAL switch is set to TIMED (and the timer is zeroed), the steam
generating cycle stops. Press the TIMED end of the TIMED/MANUAL switch for both
compartments.
·
The main burners turn OFF, and the condenser flow stops. On DIAL timer models only
the buzzer will sound for 3 seconds.
·
Steam stops entering the cooking compartment.
8). Open the cooking compartment door to vent the steam and allow the compartment to cool
slightly. After 2 or 3 minutes, close the door and continue testing.
9). With the TIMED/MANUAL switches set to TIMED, set the timers of both compartments for 10
minutes.
10). When the START/STOP key is pressed [Keypad Models] or as soon as the dial is set [Dial timer Models], the steam generating cycle starts. This is the same sequence observed in steps
5 and 7, except:
·
The timer controls the cycle.
·
The elapsed time to produce steam is shorter because the water in the steam generator
and the cooking compartment were preheated during step 5.
·
The timer automatically starts the step 7 functions after counting down to zero.
11). After the timed operation has been started, observe the following steam generating functions.
a) KEYPAD CONTROL
The timer display changes to PAUS until the cooking compartment reaches cooking
temperature. When it does, the timer begins counting down to zero.
DIAL TIMER CONTROL
The Pause light comes ON until the cooking compartment reaches cooking temperature.
When it does, the timer begins counting down to zero, and the Pause light turns OFF.
b) When the unit reaches temperature the condenser solenoid clicks open and condenser flow
starts. A small stream of water flows from the drainpipe.
22
Page 26
c) If the probe cylinder water level drops below the upper probe, 15 to 20 seconds later the
water fill valve opens and fills the generator. When the probe cylinder water level is above
the middle probe, the burners turn ON. A dull roaring sound indicates the burners are firing
and the unit is generating steam.
d) As the unit generates steam, the water level fluctuates and a clicking sound is heard as the
solenoid opens and closes the fill valve. The level in the cylinder rises and falls between the
upper and lower fill limit as the fill valve operates.
e) Check for steam leaks around the door.
f) KEYPAD CONTROL
When the timer counts down to zero (00:00), the burners turn OFF, the condenser flow
stops, and the buzzer sounds continuously. Press the START/STOP key to silence the
buzzer.
DIAL TIMER CONTROL
When the timer counts down to zero, the burners turn OFF, the condenser flow stops, and
the buzzer sounds for 3 seconds.
g) After about 30 seconds steam stops entering the cooking compartment.
12). Turn the steamer OFF by turning the ON/OFF lever/switch counterclockwise to the OFF (top)
position. The red indicator light turns OFF immediately, and the automatic blowdown cycle
starts. DO NOT turn OFF the power at the main power switch until blowdown is complete. The
cycle takes about 3 minutes.
13). When blowdown is complete, turn the steamer OFF at the main power switch.
14). Install the side panels and secure them in place with the screws (See Figure 1-2 or 1-3). After
completing the Startup and Blowdown Inspection procedure, and the Operating Test procedure;
the steamer is ready for service. Refer to the separate OPERATORS MANUAL for complete
operating instructions.
CHAPTER 3 PREVENTATIVE MAINTENANCE AND
TROUBLESHOOTING
A. MAINTENANCE
Maintenance on the steamer must be performed on a regular basis to keep the unit running properly. Follow
the maintenance instructions in this chapter and problems will be kept to a minimum. As with any
preventative maintenance schedule, the frequency of steamer maintenance may need to be increased,
depending on equipment usage and water quality. If problems do occur, refer to the Troubleshooting Guide
in this chapter. For more information on product and services, contact your sales representative.
Instructions for the daily cleaning and operational maintenance and the weekly and monthly maintenance
required for this steamer can be found in the separate OPERATORS MANUAL. The maintenance described
in this manual should only be performed by qualified service or maintenance technicians, except as noted.
(1) Maintenance Records
Make a file solely for maintenance records. Keep a written record of daily, weekly, monthly, and yearly
maintenance. These records will protect warranty coverage, help personnel to know when to perform
various maintenance procedures, and assist service personnel.
23
Page 27
y
(2) Yearly Maintenance
Clean Water Line Strainer
Clean the water line strainer at least once a year as follows:
NOTE: When the steamer is first installed, check the strainer more frequently to find out how often it must
be cleaned.
1. Close the valve(s) in the steamer water supply line(s).
2. Unscrew the filter cap from the bottom of the strainer. Refer to Figure 3-1, which shows the various
strainers supplied with the different steamers.
3. On some models the strainers are built into the steamer and are accessible from underneath the
steamer (See Figure 3-2), otherwise the strainers should be installed upstream of the steamer in the
water supply(s).
4. Remove the filter screen and wash it with clean water.
5. Check the O-ring for wear and replace it if necessary.
6. Put screen back into cap and replace the cap in the strainer.
7. Open water supply valve(s) and check for water leaks.
B. TROUBLESHOOTING GUIDE
The Troubleshooting guide includes a list of symptoms that may be encountered during routine operation
and maintenance. The first column on the left (PROBLEM) describes these symptoms. The second column
lists the possible causes for the problem in column one. The third column lists possible remedies for the
problems and causes in columns one and two. The causes and remedies are listed in the order they should
be checked, with the least costly and easiest to repair listed first. The third column also refers to notes that
are grouped at the end of the troubleshooting guide. Refer to these notes when instructed to do so. Do not
try and correct a problem, which requires an authorized service representative as this may adversely affect
warranty coverage.
Figure 3-1 Water Strainer Assembly
Left Front Leg
24
Figure 3-2 Pre-installed Water
Strainer Assembl
Strainers
Page 28
PROBLEM POSSIBLE CAUSE REMEDY/REFERENCE
Power indicator light
does not turn on when
ON/OFF lever/switch is in
the ON position.
Table 3-1 Trouble Shooting Guide
Power turned OFF at main power
switch.
ON/OFF lever/switch not fully turned
to the ON position.
Inoperative controls or failed light. See note #1
Turn ON power at main power switch.
Turn lever/switch to the full ON position.
Power indicator light
does not turn ON when
ON/OFF lever is in the
ON position.
Power ON and steam
generator does not fill.
Control panel POW ER
indicator light ON and
steamer does not make
any steam in manual or
timed modes.
Abnormal amount of
steam coming from drain.
Reduced steam flow into
cooking compartment.
timer does not light.
(Electronic Timer Models
only)
Power turned OFF at main power
switch.
ON/OFF lever/switch not fully turned
to the ON position
Inoperative controls or failed light. See note # 1.
Water supply to steamer shut off. Open water supply valves.
Water line strainer and/or external
filter system is clogged
Inoperative Solenoids or controls. See note # 1.
Water supply to steamer shut OFF. Open water supply valves.
Door interlock switch not engaged or
has failed.
Hi-limit switch has tripped. Reset Hi-limit, if condition persists, see
Water line strainer is clogged. Clean water supply strainer.
Gas supply valve is closed. Turn OFF unit and open gas supply
Steamers gas valve is closed. Turn gas valves to open position.
Inoperative controls or solenoid. See note # 1.
Hot water instead of cold water
connected to condenser fitting.
Water supply to condenser turned
OFF.
Condenser water line strainer and/or
nozzle is clogged.
Water supply line to the condenser
blocked, broken, or leaking.
Inoperative controls, thermostat or
solenoids.
Steam generator scale buildup Descale steam generator with Cleveland
Gas inlet pressure is low. The unit requires a minimum inlet
Inoperative or improperly adjusted
controls
Timer transformer has failed See note #1 Power light is ON, but
Inoperative controls See note #1
(Continued on next page)
Turn on power at main power switch.
Turn lever/switch to the full ON position.
Clean water supply strainer and/or filter
system.
Close door completely. If problem
persists see note #1.
note #1.
valve
Make proper connections. See section
on Water Supply
Open water supply valve.
Clean out condenser water supply
strainer and/or nozzle.
Repair or replace water supply line. See
note # 1.
Turn OFF electricity at main external
power switch. See note # 1.
Range approved descaler.
pressure of 4.5 inches W.C. to operate.
See note #2.
See note #1.
25
Page 29
PROBLEM POSSIBLE CAUSE REMEDY/REFERENCE
Steam and/or water
draining around
compartment door.
See Warning under
note #7.
Steam flow does not stop
when TIMER stops.
Compartment bottom
dirty with food drippings.
Water leaking from
bottom of cabinet.
Water leaking from water
pipes or drain lines.
Abnormal amount of
steam coming from drain
during blowdown cycle.
Water coming from drain
even when not cooking.
Descale Required
indicator is lit
Note: Switch does not
descale unit, it is just a
reminder that steamer
must be descaled every
4-6 weeks.
Food takes too long to
cook.
To verify the steamers
proper operation see
note #6.
Table 3-1 Trouble Shooting Guide (Continued)
It is common for a small amount of
water to condense around the door
Compartment drain clogged or
covered.
External drain not properly installed,
should be free-air vented and
pitched down.
Door gasket or door parts worn. See note # 1.
Steamer not level. See note # 2.
Condenser not operative. See note #1.
Operating in manual mode. Switch to timed mode for timer to be
Inoperative controls inside cabinet. Turn OFF power to that compartment at
Juices and/or food leaking from
pans.
Broken or loose plumbing inside
steamer cabinet.
Plumbing needs repair. See note # 3
ON/OFF lever/switch is not turned
fully to the OFF position.
Condenser valve is bad See note #1.
If unit is new, or has just been
descaled
Unit needs descaling Descale unit with Cleveland Range
Bad or improperly set descale timer See note #1.
Pans too close to the bottom of
cabinet.
Not enough steam movement in
compartment. Hot water connected
to condenser line.
Steam generator scale buildup.
Compartment overloaded with too
much food.
Food is frozen Increase cooking times for frozen food
Food is being cooked in covered
solid pans.
Suggested cooking times are usually
listed for cooking at sea level.
Inoperative or improperly adjusted
controls.
This is normal operation of the unit. No
action is necessary.
Clean drain with USDA approved drain
cleaner. If condition persists see note #1
See notes #2 and #3.
effective.
ON/OFF lever/switch. See note # 1.
Put a solid pan under perforated pans to
catch drippings, or put less food in pan.
Turn OFF electricity at main external
power switch and close water supply
valve(s). See note # 1.
Turn ON/OFF lever/switch to the full
OFF position to start the proper
blowdown operation.
Press switch to reset desccale timer
approved descaler. After descaling is
completed, press switch to reset descale
timer.
Put pans in racks near top of cabinet.
Make proper connections. See section
on Water Supply.
See note # 3.
Descale steam generator with Cleveland
Range approved descaler.
Put less food into pan. Use fewer pans.
Remove covering. Steam must have
direct access to the food for cooking to
take place.
Extend cooking times for altitudes above
2500 feet.
See note #1.
26
Page 30
TROUBLESHOOTING NOTES
1. If problem is inside the steamer, call an authorized service representative. Cleveland Range, Inc. will
not pay for warranty repairs by unauthorized repair centers.
2. Proper installation of the steamer is the responsibility of the owner or installer. A qualified installer or
technician should be contacted to correct the installation. Refer to Cleveland Range, Inc. Warranty.
3. Repairs to external plumbing should be done by a Licensed Plumber.
4. Repairs to external wiring should be done by a Licensed Electrician.
5. For more information on products and services, contact your nearest Authorized Sales Representative.
Call factory for a preventative maintenance program, descaling kits, descaling information, and water
treatment systems: USA: (800) 338-2204, Canada: (800) 427-6668.
6. To evaluate whether a convection steamer is producing normal cooking performance, conduct the Egg
Test as follows (Note: This test is not valid for SteamCubs or pressure steamers). A properly operating
steamer will produce cooked eggs as follows.
Turn on the steamer so that steam is being produced. After steam has begun to enter the compartment,
preheat the compartment by turning the timer on for ten minutes.
After the compartment is preheated:
· Place two fresh eggs in a perforated pan.
· Set timer for 10 minutes and turn ON.
· After five minutes, open door and remove one of the eggs.
· Close the door right away and allow second egg to cook.
· Crack open first egg and it should be soft boiled.
· After timer goes OFF, open door, remove egg and crack open. It should be hard-boiled.
7. Whenever opening door, especially when water or steam is leaking around gasket heed the warning
below.
When checking inside the steamer always open the door slowly
and stand to the side and back away from the steamer. Water
leaking from the door gasket can be a sign of a blocked drain. If
the drain is blocked, hot water can accumulate inside the
compartment and spill out when the door is opened.
WARNING
27
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.