Thank you for purchasing a CLA-VAL CPC. With appropriate care, this CPC will provide accurate and reliable control of
your valve for many years. The CPC is built with the latest technology using only very high quality components.
The CPC is a 4-20 mA standalone actuated control which is PC calibrated and able to remotely control any CLA-VAL
valve. The pilot setting can be adjusted with a standard 4-20 mA signal. It also incorporates a 4-20 mA position feedback
signal to cross check if the requested position is reached.
General Disclaimer
In accordance with our policy of continuous development and improvement, CLA-VAL reserves the right to modify or improve these products at any time without prior notice. CLA-VAL assumes no liability or responsibility for any errors or
omissions in the content of this document.
Please review this manual thoroughly before starting
1. Visit our internet address and, if necessary, update the CPC with the latest Software and Firmware versions.
2. Troubleshooting at start up (after wiring actuator and applying 24 VDC power).
a. View LED diagnostics
located on top of
actuator.
b. At start-up, the LED
should remain red for 5
seconds than turn to
3. Blinking red/green
solid Green
c. Green - OK normal
status.
d. No light - Check power
supply.
e. Red - High torque limit
probably exceeded
Power down and up
again. Excess voltage
(above 32 volts).
a. Calibration was not
completed correctly
recalibrate.
Page 2
Terminal strip not
supplied for
Illustration
purpose only
*DO NOT WIRE 24 VDC POWER
*
IMPORTANT!
Before applying power, connect cable 3 and 4 to terminal strip as shown.
Also connect: turquoise, pink, and purple wires. Note jumper between
terminals 4, 11 and 13.
Wiring Connections
INSTALLATION / OPERATION / MAINTENANCE
CPC Series Actuator
Wiring Diagram
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
CLA-VAL
Page 2
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
• 24 VDC, 6 / 10 / 15 rpm / sizes
300 mA max. load draw
85 mA stand-by (no load draw)
Power Protection:
• Max. 32 VDC over voltage
Max. 1000 mA torque load
Reverse polarity & short circuit
80°C stop @ high temperature
Led Display:
• Green LED
Electrical Connection:
• 2 x Moulded 10 m cables
Power Supply:
• 24 VDC +/- 10%, min. 20 mA, normal 60 mA, max. 1 A
Input Command:
• 4-20 mA (2 wires)
• 2 x dry contact (manual positioning)
Operating Pressure:
PN 16 bar standard
Operation Type: Continuous Control
Operating Temperature Range: -10°C to +80°C
Protection: IP68 standard allowing full immersion
(solenoid, junction box, sensor, not
included in IP68)
Interface: Plug & Play / NT / 2000 / XP / Vista
Default Mode
Troubleshooting:
Refer to user manual for Led diagnostics
(red-green-blinking)
Remote Command Failure:
Options available: maintain current position, go to
4 mA position, go to 20 mA position
Input 4-20 mA Protection:
• Max. 32 VDC over voltage
Optocoupler isolation @ CMR 100 V
(CMR: common mode rejection)
Insulated (2 wires)
Output feedback:
• 4-20 mA (Output charge ≤ 500 Ω
• 2 x programmable position alarms
Output 4-20 mA Protection:
• Max. 32 VDC over voltage
(The input dry contact and 4-20 mA output have the
same common or earth but are not individually
Isolated
Page 3
Page 4
Installation Instructions
3. The CPC should be mounted in the vertical position.
4. All installation, adjustment and maintenance should be carried out by a competent electrician.
5. Do not exceed the maximum ratings given in the specifications and printed on the label.
6. The electrical connections should be made as described in the user’s manual.
7. Before any maintenance operation the main power should be turned off.
Do not attempt to open the product as this will invalidate the warranty!
Software / Firmware Updates
For Software updates please visit our web site at www.cla-val.com:
1. Select "Actuators and Controls" to find the latest Software (PC) & Firmware (actuator internal software) updates.
2. Follow instructions to download automatically.
3. All the software is multi-language. Only the installation Software is in French or English.
Firmware Update (Actuator internal Software)
1. Before updating the Firmware, save program to laptop.
2. Connect the USB cable to the USB connection on laptop.
3. Connect the CPC to the USB cable.
4. Select "Read Parameters" to read CPC settings and record output parameters.
5. Select "Firmware update" in "Parameters".
6. Open the corresponding ".hex" file.
7. Select "Read Parameters" to check that the Firmware has been updated.
Page 4
Page 5
USB Driver Installation
Donʼt search. I will choose the driver to install
Choose this option to select the device driver from a list. Windows does not guarantee that the
driver you choose will be the best match for your hardware
Hardware Update Wizard
Next >Cancel< Back
Search for the best driver in these locations
Use the check boxed below to limit or expand the default search, which includes local paths and
removable media. The best driver found will be installed.
Search removable media (floppy, CD-Rom...)
Include this location in the search
Please choose your search and installation options.
C:\Program Files\CLA-VAL\Muliti-USB Driver Setup
Browse
Completing the Hardware UpdateWizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Hardware Update Wizard
Continue AnywaySTOP Installation
The software you are installing for this hardware
CLA-VAL Muliti-USB Interface
has not passed Windows Logo Testing to verify it compatbility with
Windows XP. (Tell me why this testing is important)
Continuing your installation of this software may impair or
distabilize the correct operation of your system either
immediately or in the future. Microsoft strongly recommends
that you stop this installation now and contact the hardware
vendor for software that has padded Windows Logo testing.
!
Welcome to the Hardware Update
Wizard
This wizard helps you install software for:
USB Device
If your hardware came with an installation CD or
floppy disk, insert it now.
What do you want the wizard to do?
Install the software automatically (Recommended)
Install from a list or specific location (Advanced)
Click Next to continue
Hardware Update Wizard
Next >Cancel< Back
Update USB driver or install in another USB port
When the CPC cable is connected the first time, the laptop
will detect it and request a driver.
Select "Cancel".
Install the "Multi-USB driver setup" software on your PC (you
can download this software from the internet
www.cla-val.com).
When you see this message below, select "Continue Anyway".
Hardware Update Wizard
1. Download the Multi-USB Driver Setup software from
our web site www.cla-val.com.
2. Connect USB cable to laptop.
3. Select: "Install from a list or specific location".
4. Browse to file: C\Program Files\CLA-VAL\Multi-USB
Driver
Hardware Update Wizard
Welcome to the Hardware Update
Wizard
This wizard helps you install software for:
USB Device
If your hardware came with an installation CD or
floppy disk, insert it now.
What do you want the wizard to do?
Install the software automatically (Recommended)
Install from a list or specific location (Advanced)
Click Next to continue
The software you are installing for this hardware
!
CLA-VAL Muliti-USB Interface
has not passed Windows Logo Testing to verify it compatbility with
Windows XP. (Tell me why this testing is important)
Continuing your installation of this software may impair or
distabilize the correct operation of your system either
immediately or in the future. Microsoft strongly recommends
that you stop this installation now and contact the hardware
vendor for software that has padded Windows Logo testing.
Completing the Hardware UpdateWizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Continue AnywaySTOP Installation
Hardware Update Wizard
Completing the Hardware Update
Wizard
Installation is complete
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Next >Cancel< Back
Microsoft Validation press "Continue Anyway".
FinishCancel< Back
Page 5
Page 6
Hardware Update Wizard
e-line list
Cancel
View All
X
e-line list
Cancel
View All
X
CPC : (8)..>907060023
Product
Name
Firmware
Version
Serial
Number
Please wait while the wizard installs the software
CLA-VAL Muliti-USB Intervace
Setting a system restore point and backing up old files in case
your system needs to be restored in the future.
If you are connected to one or more CPC’s or another e-Line
product, click on "View All" then select the CPC you would
like to communicate with from the list (see picture below) then
click once on left mouse button.
The name of product, Firmware version and serial number
are displayed.
Hardware Update Wizard
Configuration Mode
Next >
Completing the Hardware Update
Wizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
FinishCancel< Back
Cancel< Back
To open e-Drive Software when not connected to the actuator, the e-Line list will be empty. Click "Cancel" to launch. The
software will open so that the various windows can be viewed
to become familiar with the programming.
Page 6
Page 7
p
yp
Programming Windows
Display Window
1. Connect CPC to the laptop using the USB cable.
2. Start the e-Drive/CPC CLA-VAL Software.
3. Select the CPC in the e-Line list.
4. Select language and click "Read parameters".
5. On the right side the configuration information is displayed.
6. On the top general information including the date of the latest calibration, the average & total working time since the
first power up, the number of starts, the serial number, the Firmware version and the maximum and minimum
recorded temperature are displayed.
7. Click on continuous reading if you would like see the position of CPC, set point (mA) and feedback position (mA and
units).
8. If you would like to manually change the setting, write your setting and click on "Override Setpoint".
Improper use of "Override Set Point" may cause damage to your system.
Activated continuous
reading
Activated override
set point
Display Set point and
feedback position
ressure values
General
information
Configuration information
la
Dis
Page 7
Page 8
Static Calibration (0% - 100%)
e-line list
OK
You are going to put the e-Drive / CPC in calibration Mode (Led Blinks Red/Green
X
Cancel
(2)
(1)
(4)
(3)
0-100% Calibration without System Pressure
The “Set range” allows calibration in either dynamic or static
mode. When the “Set Range” is clicked, the following message appears. If you would like to proceed with calibration,
click "OK", if not click "Cancel".
Initial preparation:
It is highly recommended that the valve and actuator assembly is isolated by closing upstream and downstream isolation valves and pressure is removed from valve. If this is
not possible, consult the factory. The objective is to remove
the site plug and visually determine the position of the “orifice
coupling” with respect
to the “stem tube”. They
should be flush with no
gap between the two
assemblies (see Fig.
1). The procedure for
Orifice coupling
this is shown below:
1. Isolate and remove pressure from the valve assembly.
2. Remove plug as shown in figure 1.
3. Open e-Drive / CPC Software then go to "Set Range"
tab and click OK on the menu.
4. Select "Static Calibration" Mode and check "CPC
Motor" box is checked and select trim size from the drop
down menu (3).
5. Using the "Increase actuator"/ "Decrease actuator"
Buttons, adjust the position of the “orifice coupling”
until there is no gap (flush) with the stem tube
(See Fig. 1)
6. Select the valve size to be calibrated from the drop
down menu (3) to determine the number of turns
required to achieve full opening of the valve.
7. Select units.
8. Enter 4 mA value and 20 mA value.
9. Turns to low point (1): Enter the number ‘1’.
Plug
Stem tube
Fig. 1
No gap between
orifice coupling
and stem tube
Orifice coupling
No gap between orifice
coupling and stem tube
10.Turns to high point (2): Enter the “Number of turns”
value for the valve selected (4) minus ‘1’.
11. Select "Write Set Range" to upload settings to CPC.
Calibration is complete
Page 8
Page 9
Calibration - Variable Range
Calibration Mode to a specific process WITH System pressure.
Initial preparation:
This calibration mode is for field installations where water pressure is available and you want to control flow over a specific
range of positions.
Now you are in the calibration, please enter the required settings.
1. Select "Dynamic Calibration" mode and ensure that the "CPC Motor" check box is checked (Enabled).
2. Select units.
3. Enter the required setting Value at 4 mA point and Value at 20 mA point. Look at the position on the display and use
the "Increase actuator / Decrease actuator" button, until it reaches.
4. The low position point. When the low position point is reached click on the button "Low point setting".
5. Look at the position on the display and use the "Increase actuator / Decrease actuator" button, until it reaches
the high position.When the high position point is reached click on the button "High point setting".
6. When all values have been entered, click on "Write Set Range". Your calibration is done.
Page 9
Page 10
Configuration
1. The configuration tab sets the Rotation speed and the Dead band.
2. The Rotation speed affects the response time of the valve between set-points.
3. The default condition is 0 seconds "On-time" and 0 seconds "Off-time" achieving continuous rotation speed which
will vary corresponding to the size of your valve.
4. Make sure that the values entered are appropriate to your system to minimize potential for surge.
5. Dead band - The default value is 0.1 mA which may need to be increased depending on the stability of the electrical
signal.
6. Choose the loss of signal mode.
7. Go to 4 mA: CPC will default to the 4 mA position (low set point).
8. Last position: CPC will maintain the last position.
9. Go to 20 mA: CPC will default to the 20 mA position (high set point).
Note: Loss of signal can occur on the SCADA system which generates the 4-20 mA command but at the same time the CPC
can stay powered, so it is important to select the right option. When you have finished your configuration, click on
"Write Configuration".
Your CPC is configured.
Page 10
Page 11
Alarms
The CPC incorporates a LOW and HIGH Alarm with an adjustable hysteresis setting. The low and High alarm levels
are activated within the range:
Example: 10% low alarm = 4 + (10% x 16) = 5.6 mA. 90% High alarm = 4 + (90% x 16) = 18.4 mA.
Hysteresis:
1. The calculation is: 4 + (2% x 16) = 0.32 mA.
Low alarm hysteresis in this example = 5.6 mA + 0.32 mA = 5.92 mA.
High alarm hysteresis in this example = 18.4 mA - 0.32 mA = 18.08 mA.
2. Enter the requested percentage, for the alarms and hysteresis.
3. Click on "Test" to close or open your contact relay.
4. Click on "Write Alarms" (1) once your alarm settings are correct.
"Low Level" alarm
range
"Low Level" hysteresis alarm
value
"Low Level" alarm
value
"High Level" hysteresis
alarm range
"High Level" alarm
range
(1)
"High Level" alarm
value
Adjustment of alarms high, low
LIN040UE-07
2%
level and hysteresis alarm level
Page 11
Page 12
Your complete source for top quality
automatic control valves
and related products
GLOBAL HEADQUARTERS
P.O. Box 1325
Newport Beach, CA 92659-0325
Phone: (949) 722-4800
1-800-942-6326
Fax: (949) 548-5441
E-mail: claval@cla-val.com