Cla-Val CPC User Manual

Page 1
INSTALLATION / OPERATION / MAINTENANCE
CPC
Maintenance cable
Adapter socket
Input/Output cable moulded
10 meter standard execution
Maintenance port
PC Connection
Adaptable side
CPC Connection
Power supply cable
moulded 10 meter
standard execution
Security Low Sensor
Security High Sensor
Led indicator
MODEL
CPC
4-20 mA Actuated Position Control
Thank you for purchasing a CLA-VAL CPC. With appropriate care, this CPC will provide accurate and reliable control of your valve for many years. The CPC is built with the latest technology using only very high quality components. The CPC is a 4-20 mA standalone actuated control which is PC calibrated and able to remotely control any CLA-VAL valve. The pilot setting can be adjusted with a standard 4-20 mA signal. It also incorporates a 4-20 mA position feedback signal to cross check if the requested position is reached.
General Disclaimer
In accordance with our policy of continuous development and improvement, CLA-VAL reserves the right to modify or im­prove these products at any time without prior notice. CLA-VAL assumes no liability or responsibility for any errors or omissions in the content of this document.
Please review this manual thoroughly before starting
1. Visit our internet address and, if necessary, update the CPC with the latest Software and Firmware versions.
2. Troubleshooting at start up (after wiring actuator and applying 24 VDC power).
a. View LED diagnostics
located on top of actuator.
b. At start-up, the LED
should remain red for 5 seconds than turn to
3. Blinking red/green
solid Green
c. Green - OK normal
status.
d. No light - Check power
supply.
e. Red - High torque limit
probably exceeded Power down and up again. Excess voltage (above 32 volts).
a. Calibration was not
completed correctly recalibrate.
Page 2
Terminal strip not supplied for Illustration purpose only
*DO NOT WIRE 24 VDC POWER
*
IMPORTANT! Before applying power, connect cable 3 and 4 to terminal strip as shown. Also connect: turquoise, pink, and purple wires. Note jumper between terminals 4, 11 and 13.
Wiring Connections
INSTALLATION / OPERATION / MAINTENANCE
CPC Series Actuator
Wiring Diagram
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
CLA-VAL
Page 2
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
©
N-CPC Series Actuator Wiring Diagram
Page 3
Download Wiring Diagram from website:
(www.cla-val.com)
Other Specifications
Electrical Specifications
Electrical Power:
• 24 VDC, 6 / 10 / 15 rpm / sizes 300 mA max. load draw 85 mA stand-by (no load draw)
Power Protection:
• Max. 32 VDC over voltage Max. 1000 mA torque load Reverse polarity & short circuit 80°C stop @ high temperature
Led Display:
• Green LED
Electrical Connection:
• 2 x Moulded 10 m cables
Power Supply:
• 24 VDC +/- 10%, min. 20 mA, normal 60 mA, max. 1 A
Input Command:
• 4-20 mA (2 wires)
• 2 x dry contact (manual positioning)
Operating Pressure:
PN 16 bar standard
Operation Type: Continuous Control
Operating Temperature Range: -10°C to +80°C
Protection: IP68 standard allowing full immersion
(solenoid, junction box, sensor, not
included in IP68)
Interface: Plug & Play / NT / 2000 / XP / Vista
Default Mode
Troubleshooting:
Refer to user manual for Led diagnostics (red-green-blinking)
Remote Command Failure:
Options available: maintain current position, go to 4 mA position, go to 20 mA position
Input 4-20 mA Protection:
• Max. 32 VDC over voltage Optocoupler isolation @ CMR 100 V
(CMR: common mode rejection) Insulated (2 wires)
Output feedback:
• 4-20 mA (Output charge ≤ 500 Ω
• 2 x programmable position alarms
Output 4-20 mA Protection:
• Max. 32 VDC over voltage (The input dry contact and 4-20 mA output have the
same common or earth but are not individually Isolated
Page 3
Page 4
Installation Instructions
3. The CPC should be mounted in the vertical position.
4. All installation, adjustment and maintenance should be carried out by a competent electrician.
5. Do not exceed the maximum ratings given in the specifications and printed on the label.
6. The electrical connections should be made as described in the user’s manual.
7. Before any maintenance operation the main power should be turned off.
Do not attempt to open the product as this will invalidate the warranty!
Software / Firmware Updates
For Software updates please visit our web site at www.cla-val.com:
1. Select "Actuators and Controls" to find the latest Software (PC) & Firmware (actuator internal software) updates.
2. Follow instructions to download automatically.
3. All the software is multi-language. Only the installation Software is in French or English.
Firmware Update (Actuator internal Software)
1. Before updating the Firmware, save program to laptop.
2. Connect the USB cable to the USB connection on laptop.
3. Connect the CPC to the USB cable.
4. Select "Read Parameters" to read CPC settings and record output parameters.
5. Select "Firmware update" in "Parameters".
6. Open the corresponding ".hex" file.
7. Select "Read Parameters" to check that the Firmware has been updated.
Page 4
Page 5
USB Driver Installation
Donʼt search. I will choose the driver to install
Choose this option to select the device driver from a list. Windows does not guarantee that the driver you choose will be the best match for your hardware
Hardware Update Wizard
Next > Cancel< Back
Search for the best driver in these locations
Use the check boxed below to limit or expand the default search, which includes local paths and removable media. The best driver found will be installed.
Search removable media (floppy, CD-Rom...)
Include this location in the search
Please choose your search and installation options.
C:\Program Files\CLA-VAL\Muliti-USB Driver Setup
Browse
Completing the Hardware Update Wizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Hardware Update Wizard
Continue Anyway STOP Installation
The software you are installing for this hardware
CLA-VAL Muliti-USB Interface
has not passed Windows Logo Testing to verify it compatbility with Windows XP. (Tell me why this testing is important)
Continuing your installation of this software may impair or distabilize the correct operation of your system either immediately or in the future. Microsoft strongly recommends that you stop this installation now and contact the hardware vendor for software that has padded Windows Logo testing.
!
Welcome to the Hardware Update Wizard
This wizard helps you install software for:
USB Device
If your hardware came with an installation CD or floppy disk, insert it now.
What do you want the wizard to do?
Install the software automatically (Recommended)
Install from a list or specific location (Advanced)
Click Next to continue
Hardware Update Wizard
Next > Cancel< Back
Update USB driver or install in another USB port
When the CPC cable is connected the first time, the laptop will detect it and request a driver.
Select "Cancel". Install the "Multi-USB driver setup" software on your PC (you can download this software from the internet
www.cla-val.com).
When you see this message below, select "Continue Anyway".
Hardware Update Wizard
1. Download the Multi-USB Driver Setup software from
our web site www.cla-val.com.
2. Connect USB cable to laptop.
3. Select: "Install from a list or specific location".
4. Browse to file: C\Program Files\CLA-VAL\Multi-USB
Driver
Hardware Update Wizard
Welcome to the Hardware Update Wizard
This wizard helps you install software for:
USB Device
If your hardware came with an installation CD or floppy disk, insert it now.
What do you want the wizard to do?
Install the software automatically (Recommended)
Install from a list or specific location (Advanced)
Click Next to continue
The software you are installing for this hardware
!
CLA-VAL Muliti-USB Interface
has not passed Windows Logo Testing to verify it compatbility with Windows XP. (Tell me why this testing is important)
Continuing your installation of this software may impair or distabilize the correct operation of your system either immediately or in the future. Microsoft strongly recommends that you stop this installation now and contact the hardware vendor for software that has padded Windows Logo testing.
Completing the Hardware Update Wizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Continue Anyway STOP Installation
Hardware Update Wizard
Completing the Hardware Update Wizard
Installation is complete
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Next > Cancel< Back
Microsoft Validation press "Continue Anyway".
Finish Cancel< Back
Page 5
Page 6
Hardware Update Wizard
e-line list
Cancel
View All
X
e-line list
Cancel
View All
X
CPC : (8)..>907060023
Product
Name
Firmware
Version
Serial
Number
Please wait while the wizard installs the software
CLA-VAL Muliti-USB Intervace
Setting a system restore point and backing up old files in case your system needs to be restored in the future.
If you are connected to one or more CPC’s or another e-Line product, click on "View All" then select the CPC you would like to communicate with from the list (see picture below) then click once on left mouse button. The name of product, Firmware version and serial number are displayed.
Hardware Update Wizard
Configuration Mode
Next >
Completing the Hardware Update Wizard
This wizard has finished installing the software for
Cla-Val Multi-USB Interface
Click Finish to close the wizard
Finish Cancel< Back
Cancel< Back
To open e-Drive Software when not connected to the actua­tor, the e-Line list will be empty. Click "Cancel" to launch. The software will open so that the various windows can be viewed to become familiar with the programming.
Page 6
Page 7
p
yp
Programming Windows
Display Window
1. Connect CPC to the laptop using the USB cable.
2. Start the e-Drive/CPC CLA-VAL Software.
3. Select the CPC in the e-Line list.
4. Select language and click "Read parameters".
5. On the right side the configuration information is displayed.
6. On the top general information including the date of the latest calibration, the average & total working time since the first power up, the number of starts, the serial number, the Firmware version and the maximum and minimum recorded temperature are displayed.
7. Click on continuous reading if you would like see the position of CPC, set point (mA) and feedback position (mA and units).
8. If you would like to manually change the setting, write your setting and click on "Override Setpoint".
Improper use of "Override Set Point" may cause damage to your system.
Activated continuous
reading
Activated override
set point
Display Set point and
feedback position
ressure values
General
information
Configuration information
la
Dis
Page 7
Page 8
Static Calibration (0% - 100%)
e-line list
OK
You are going to put the e-Drive / CPC in calibration Mode (Led Blinks Red/Green
X
Cancel
(2)
(1)
(4)
(3)
0-100% Calibration without System Pressure
The “Set range” allows calibration in either dynamic or static mode. When the “Set Range” is clicked, the following mes­sage appears. If you would like to proceed with calibration, click "OK", if not click "Cancel".
Initial preparation:
It is highly recommended that the valve and actuator as­sembly is isolated by closing upstream and downstream iso­lation valves and pressure is removed from valve. If this is not possible, consult the factory. The objective is to remove the site plug and visually determine the position of the “orifice
coupling” with respect to the “stem tube”. They should be flush with no gap between the two assemblies (see Fig.
1). The procedure for
Orifice coupling
this is shown below:
1. Isolate and remove pressure from the valve assembly.
2. Remove plug as shown in figure 1.
3. Open e-Drive / CPC Software then go to "Set Range" tab and click OK on the menu.
4. Select "Static Calibration" Mode and check "CPC
Motor" box is checked and select trim size from the drop down menu (3).
5. Using the "Increase actuator"/ "Decrease actuator" Buttons, adjust the position of the “orifice coupling” until there is no gap (flush) with the stem tube (See Fig. 1)
6. Select the valve size to be calibrated from the drop down menu (3) to determine the number of turns required to achieve full opening of the valve.
7. Select units.
8. Enter 4 mA value and 20 mA value.
9. Turns to low point (1): Enter the number ‘1’.
Plug
Stem tube
Fig. 1
No gap between orifice coupling and stem tube
Orifice coupling
No gap between orifice coupling and stem tube
10.Turns to high point (2): Enter the “Number of turns” value for the valve selected (4) minus ‘1’.
11. Select "Write Set Range" to upload settings to CPC.
Calibration is complete
Page 8
Page 9
Calibration - Variable Range
Calibration Mode to a specific process WITH System pressure.
Initial preparation:
This calibration mode is for field installations where water pressure is available and you want to control flow over a specific range of positions.
Now you are in the calibration, please enter the required settings.
1. Select "Dynamic Calibration" mode and ensure that the "CPC Motor" check box is checked (Enabled).
2. Select units.
3. Enter the required setting Value at 4 mA point and Value at 20 mA point. Look at the position on the display and use
the "Increase actuator / Decrease actuator" button, until it reaches.
4. The low position point. When the low position point is reached click on the button "Low point setting".
5. Look at the position on the display and use the "Increase actuator / Decrease actuator" button, until it reaches the high position.When the high position point is reached click on the button "High point setting".
6. When all values have been entered, click on "Write Set Range". Your calibration is done.
Page 9
Page 10
Configuration
1. The configuration tab sets the Rotation speed and the Dead band.
2. The Rotation speed affects the response time of the valve between set-points.
3. The default condition is 0 seconds "On-time" and 0 seconds "Off-time" achieving continuous rotation speed which
will vary corresponding to the size of your valve.
4. Make sure that the values entered are appropriate to your system to minimize potential for surge.
5. Dead band - The default value is 0.1 mA which may need to be increased depending on the stability of the electrical signal.
6. Choose the loss of signal mode.
7. Go to 4 mA: CPC will default to the 4 mA position (low set point).
8. Last position: CPC will maintain the last position.
9. Go to 20 mA: CPC will default to the 20 mA position (high set point).
Note: Loss of signal can occur on the SCADA system which generates the 4-20 mA command but at the same time the CPC
can stay powered, so it is important to select the right option. When you have finished your configuration, click on "Write Configuration".
Your CPC is configured.
Page 10
Page 11
Alarms
The CPC incorporates a LOW and HIGH Alarm with an adjustable hysteresis setting. The low and High alarm levels are activated within the range:
Example: 10% low alarm = 4 + (10% x 16) = 5.6 mA. 90% High alarm = 4 + (90% x 16) = 18.4 mA.
Hysteresis:
1. The calculation is: 4 + (2% x 16) = 0.32 mA.
Low alarm hysteresis in this example = 5.6 mA + 0.32 mA = 5.92 mA. High alarm hysteresis in this example = 18.4 mA - 0.32 mA = 18.08 mA.
2. Enter the requested percentage, for the alarms and hysteresis.
3. Click on "Test" to close or open your contact relay.
4. Click on "Write Alarms" (1) once your alarm settings are correct.
"Low Level" alarm
range
"Low Level" hysteresis alarm
value
"Low Level" alarm
value
"High Level" hysteresis
alarm range
"High Level" alarm
range
(1)
"High Level" alarm
value
Adjustment of alarms high, low
LIN040UE-07
2%
level and hysteresis alarm level
Page 11
Page 12
Your complete source for top quality
automatic control valves
and related products
GLOBAL HEADQUARTERS
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: (949) 722-4800 1-800-942-6326 Fax: (949) 548-5441 E-mail: claval@cla-val.com
CLA-VAL CANADA
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: (905) 563-4963 Fax: (905) 563-4040 E-mail: sales@cla-val.ca
CLA-VAL EUROPE
Chemin dés Mesanges 1 CH-1032 Romanel/Lausanne Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50 E-mail: cla-val@cla-val.ch
CLA-VAL UK
Dainton House, Goods Station Road GB - Tunbridge Wells Kent TN1 2 DH England Phone: 44-1892-514-400 Fax: 44-1892-543-423 E-mail: info@cla-val.co.uk
CLA-VAL FRANCE
Porte du Grand Lyon 1 ZI de Champ du Périer France - 01700 Neyon Phone: 33-4-72-25-92-93 Fax: 33-4-72-25-04-17 E-mail: cla-val@cla-val.fr
WESTERN REGION
11626 Sterling Avenue, Suite F Riverside, CA 92503 Phone: (951) 687-9145 1-800-247-9090 Fax: (951) 687-9954 E-mail: lvanderk@cla-val.com
SOUTHERN REGION
11500 NW Freeway Suite #200Q Houston, TX 77092 Phone: (713) 681-9559 1-800-336-7171 Fax: (713) 681-9779 E-mail: blindsey@cla-val.com
NORTHERN REGION
P.O. Box 863 Elgin, IL 60121 280 Willard Avenue Elgin, IL 60120 Phone: (847) 697-1413 1-800-238-7070 Fax: (847) 697-5549 E-mail: djurs@cla-val.com
EASTERN REGION
6911 Richmond Highway, Suite 444 Alexandria, VA 22306 Phone: (703) 721-1923 1-800-451-3030 Fax: (703) 721-1927 E-mail: bmoore@cla-val.com
CLA-VAL PACIFIC REGION
306 Port Hills Road, (Level Two) Woolston, Christchurch, 8022 New Zealand Phone: (64) 39644860 Fax: (64) 39644876 E-mail: gnuthall@cla-val.com
www.cla-val.com • 800.942.6326
N-CPC (R-3/2011)
Loading...