Cla-Val 136-03-636-03 Quick Manual

Page 1
INSTALLATION / OPERATION / MAINTENANCE
INTRODUCTION
The Cla-Val Model 136-03/636-03 Solenoid Control Valve is an automatic valve designed to either close drip tight or open fully by means of a Three-Way Solenoid Control. It is a hydraulically oper­ated, solenoid controlled, diaphragm type globe or angle valve.
INSTALLATION
1. Allow sufficient room around the valve assembly to make adjustments and for disassembly.
Note: Before the valve is installed, the pipeline should be flushed to remove all chips, scale and foreign matter.
2. It is recommended that gate or line block valves be installed upstream and downstream of the Model136-03/636-03 to facilitate isolating the valve for preventive maintenance.
3. Place the valve in the line with flow in the direction of flow arrows or by the inlet nameplate. Check all fittings and hardware for proper makeup and that no apparent damage is evident. Be sure main valve cover nuts/bolts are tight. Pressure in some appli­cations can be very high so be thorough in checking and inspect­ing for proper installation and makeup.
4. Cla-Val Valves operate with maximum efficiency when mounted in horizontal piping with the cover UP; however, other positions are acceptable. Due to size and weight of cover and internal compo­nents of six inch valves and larger, installation with the cover up is advisable. This makes periodic inspection of internal parts readily accessible.
5. Caution must be taken in the installation of this valve to insure that galvanic and/or electrolytic action does not take place. The proper use of dielectric fittings and gaskets are required in all sys­tems using dissimilar metals.
6. Comply with local and national electrical codes when wiring the Solenoid Control.
OPERATION AND START-UP
1. Prior to pressurizing the valve assembly make sure the neces­sary gauges to measure pressure in the system are installed as required by the system engineer. A Cla-Val Model X101 Valve Position Indicator can be installed in the center cover port to pro­vide visual indication of the valve diaphragm assembly position during start-up.
CAUTION: During start-up and test procedures a large volume of water may be discharged downstream. Check that the downstream venting is adequate to prevent damage to personnel and equip­ment. If the main valve closes too fast it may cause surging in upstream piping.
2. If isolation valves (B) are installed in pilot system open these valves. (see schematic).
3. The three-way Solenoid Control applies or relieves pressure in the 102C-3H three-way valve cover chamber. This, in turn, applies or relieves pressure in the main valve cover chamber. The follow­ing action takes place:
SOLENOID CONTROL(2)
POSITION
ENERGIZED
DE-ENERGIZED
FLOW
1
TO2
3TO1
Note: Solenoids are not
ENERGIZED TO OPEN
136-03 SERIES
THREE-WAY VALVE FLOW(3) COM.
TO N.O.
TO COM.
N.C.
MAIN
VALVE (1)
OPEN
CLOSED
reversible because of different internal construction between Energize to open and De-energize to open solenoids.
DE-ENERGIZED TO OPEN
136-03 SERIES
THREE-WAY
VALVE FLOW(3)
TO COM.
N.C. COM. TO N.O.
M VALVE 1 CLOSED
OPEN
MODEL
136-03/636-03
Solenoid Control Valve
4. Check that solenoid (2) is set to close main valve. Slowly open the gate or block valve upstream of the valve.
5. Carefully loosen tube fittings at highest points and bleed air from system. Carefully loosen the plug at top of main valve cover. If X101 Valve Position Indicator is installed, carefully open the bleed valve at top of Indicator. Bleed air from cover and tighten plug or bleed screw. Tighten tube fittings.
6. Slowly open downstream gate or block valve. Check the oper­ation of the valve by energizing and de-energizing the solenoid. The valve should open fully and close drip tight. Need minimum 5 psi differential under flowing coditions.
MAINTENANCE
1. Cla-Val Valves and Controls require no lubrication or packing and a minimum of maintenance. However, a periodic inspection schedule should be established to determine how the fluid han­dled is affecting the efficiency of the valve assembly. Minimum of once per year.
2. Repair and adjustment procedures of the Cla-Val Hytrol main valve and control components are included in a more detailed IOM manual. It can be downloaded from our web site (www.cla­val.com) or by contacting a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number
and stock number on the valve nameplate.
SYMPTON PROBABLE CAUSE REMEDY
AIN
Main Valve
Fails to Close
Main Valve Fails to Open
Main Valve Vibrates when Closed
No flow condition Inspect downstream piping for
Too low pressure differential across valve Need minimum 5psi differential under flow coditions
Closed isolation valves in pilot system, or in main line
Lack of cover chamber pressure Check upstream
Diaphragm damaged Replac diaphragm
Mechanical obstruction Object lodged in valve Worn disc
Badly scored seat Replace seat
CNA needle valve closed Open this speed control to
Closed isolation valves in pilot system, or in main line Insufficient line pressure Diaphragm assembly inoperative
Air in cover Bleed all air from valve
closed valve or obstruction
Restrict valve opening with Cla-Val X102A limiting assembly (Contact Cla-Val)
Open valves
pressure, tubing needle valves for restriction
Remove obstruction
Replace disc
allow pressure to cover
Open valves
Clean & polish stem Replace and defective or damaged parts
Page 2
4
D1
Y
F
B
1
A
INDEPENDENT
OPERATING
PRESSURE
B
D2
2
3
S
B
H
DRAIN TO
ATMOSPHERE
INLET OUTLET
CS3
3
2
1
N.C.
N.O.
D3
COM.
136-03/636-03 SCHEMATIC
BASIC COMPONENTS
1 100-01 Hytrol (Main Valve)
100-20 600 Series Hytrol (Main Valve) 2 CS3 Solenoid Control 3 102C-3H Three-Way Valve 4 CNA Angle Needle Valve (Closing)
OPTIONAL FEATURES
A X46A Flow Clean Strainer B CK2 (Isolation Valve) D Check Valves with Isolation Valve F Independent Operating Pressure H Atmospheric Drain S CNA Angle Needle Valve (Opening) Y X43Y Strainer
SOLENOID WIRING
Wiring must comply with local and National Electrical Codes. For valves equipped with an explosion-proof, watertight solenoid enclosure, the elec­trical fittings must be approved for use in the approved hazardous locations. Housings for all solenoids have con­nections for 1/2 inch conduit. The enclosure may be rotated to facilitate wiring.
1
HYTROL MAIN VALVE
COVER
Cover Bolt
6" and Smaller
SPRING
*
DIAPHRAGM
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
DISC RETAINER
HEX NUT
8" and Larger
PIPE PLUG
CS3
2
Manual Operator (Optional)
CNA
4
Screw, Machine, Fil. HD
Washer, Diaphragm
Washer, Lock
Body, Powertrol
Seelskrew
Seat, Valve, Upper
Body
Seat, Valve, Lower
3
Cover
Spring
"O" Ring, Seat
102C-3H
X46A
102C-3H
3
A
Screw, Machine RD. HD.
Gasket, Stem
"O" Ring
Washer, Diaphragm, Spring Retaining
Gasket, Stem
Diaphragm
"O" Ring, Body to Body
Stem Assembly
CLA-VAL
*
STEM
SPACER WASHERS
Seat Screw
8" and Larger
SEAT O-RING
8" and Larger
PIPE PLUG
*
Repair Parts
STUD
CDC-1
CK2
B
D
CV
C
X43
Y
*SUGGESTED REPAIR PARTS
N-136-03/636-03 (R-11/08)
*
DISC
DISC GUIDE
SEAT
BODY
(Globe or Angle)
For a more detailed IOM Manual go to www.cla-val.com or contact a Cla-Val Regional Sales Office.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Copyright Cla-Val 2008 Printed in USA Specifications subject to change without notice.
Loading...