Cla-Val 131-01-631-01 User Manual

Page 1
131-01/631-01
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Description
The CIa-VaI Model 100-01 Hytrol Valve is a main valve for CIa-VaI Automatic Control Valves. It is a hydraulically operated, diaphragm-actuated, globe or angle pattern valve.
This valve consists of three major components; body, diaphragm assembly, and cover. The diaphragm assembly is the only moving part. The diaphragm assembly uses a diaphragm of nylon fabric bonded with synthetic rubber. A synthetic rubber disc, contained on three and one half sides by a disc retainer and disc guide, forms a seal with the valve seat when pressure is applied above the diaphragm. The diaphragm assembly forms a sealed chamber in the upper portion of the valve, separating operating pressure from line pressure.
Installation
1. Before valve is installed, pipe lines should be flushed of all chips, scale and foreign matter.
2. It is recommended that either gate or block valves be installed on both ends of the 100-01 Hytrol Valve to facilitate isoIating the valve for preventive maintenance and repairs.
3. Place the valve in the line with flow through the valve in the direction indicated on the inlet nameplate. (See “Flow Direction” Section)
4. Allow sufficient room around valve to make adjustments and for disassembly.
5. CIa-VaI 100-01 Hytrol Valves operate with maximum effic iency when mounted in horizontal piping with the cover UP, however, other positions are acceptable. Due to size and weight of the cover and internal components of 8 inch and larger valves,
installation with the cover UP is advisable. This makes internal parts readily accessible for periodic inspection.
6. Caution must be taken in the installation of this valve to insure that galvanic and/or electrolytic action does not take place. The proper use of dielectric fittings and gaskets are required in all systems using dissimilar metals.
7. If a pilot control system is installed on the 100-01 Hytrol Valve, use care to prevent damage. If it is necessary to remove fittings or components, be sure they are kept clean and replaced exactly as they were.
8. After the valve is installed and the system is first pressurized, vent air from the cover chamber and pilot system tubing by loosening fittings at all high points.
Tight Closing Operation
When pressure from the valve inlet (or an equivalent independent operating pressure) is applied to the diaphragm chamber the valve closes drip-tight.
Full Open Operation
When pressure in diaphragm chamber is relieved to a zone of lower pressure (usually atmosphere) the line pressure (5 psi Min.) at the valve inlet opens the valve.
Modulating Action
Valve modulates when diaphragm pres­sure is held at an intermediate point between inlet and discharge pressure. With the use of a Cla-Val. "modulating control," which reacts to line pressure changes, the pressure above the diaphragm is varied, allowing the valve to throttle and compensate for the change.
Principles of Operation
Three Way
Pilot Control
Three Way
Pilot Control
Restriction
Modulating
Control
100-01
Hytrol Valve
MODEL
INSTALLATION / OPERATION / MAINTENANCE
Page 8
2
Flow Direction
The flow through the 100-01 Hytrol Valve can be in one of two directions. When flow is “up-and-over the seat,” it is in “normal” flow and the valve will fail in the open position. When flow is “over­the seat-and down,” it is in “reverse” flow and the valve will fail in the closed position. There are no permanent flow arrow markings.
The valve must be installed according to nameplate data.
BRIDGEWALL INDlCATOR
Normal Flow Reverse Flow
Troubleshooting
The following troubleshooting information deals strictly with the Model 100-01 Hytrol Valve. This assumes that all other compo­nents of the pilot control system have been checked out and are in proper working condition. (See appropriate sections in Technical Manual for complete valve).
Three Checks
The 100-01 Hytrol Valve has only one moving part (the diaphragm and disc assembly). So, there are only three major types of prob­lems to be considered.
First: Valve is stuck - that is, the diaphragm assembly is not free to move through a full stroke either from open to close or vice versa.
Second: Valve is free to move and can’t close because of a worn out diaphragm.
Third: Valve leaks even though it is free to move and the diaphragm isn’t leaking.
Closed isolation valves in control system, or in main line.
Lack of cover chamber pressure.
Diaphragm damaged. (See Diaphragm Check.)
Diaphragm assembly inoperative. Corrosion or excessive scale build up on valve stem. (See Freedom of Movement Check)
Mechanical obstruction. Object lodged in valve. (See Freedom of Movement Check)
Worn disc. (See Tight Sealing Check)
Badly scored seat. (See Tight Sealing Check)
Closed upstream and/or downstream isolation valves in main line.
Insufficient line pressure.
Diaphragm assembly inoperative. Corrosion or excessive buildup on valve stem. (See Freedom of Movement Check)
Diaphragm damaged. (For valves in "reverse flow" only)
After checking out probable causes and remedies, the following three checks can be used to diagnose the nature of the problem before maintenance is started. They must be done in the order shown.
Open Isolation valves.
Check upstream pressure, pilot system, strainer, tubing, valves, or needle valves for obstruction.
Replace diaphragm.
Clean and polish stem. Inspect and replace any damaged or badly eroded part.
Remove obstruction.
Replace disc.
Replace seat.
Open isolation valves.
Check upstream pressure. (Minimum 5 psi flowing line pressure differential.)
Clean and polish stem. Inspect and replace any damaged or badly eroded part.
Replace diaphragm.
Fails to Close
Fails to Open
CAUTION: Care should be taken when doing the troubleshooting checks on the 100-01 Hytrol Valve. These checks do require the valve to open fully. This will either allow a high flow rate through the valve, or the downstream pressure will quickly increase to the inlet pressure. In some cases, this can be very harmful. Where this is the case, and there are no block valves in the system to protect the downstream piping, it should be realized that the valve cannot be serviced under pressure. Steps should be taken to remedy this situation before proceeding any further.
(cast into side of valve body)
SYMPTOM PROBABLE CAUSE REMEDY
Recommended Tools
1. Three pressure gauges with ranges suitable to the instal­lation to be put at Hytrol inlet, outlet and cover connections.
2. Cla-Val Model X101 Valve Position Indicator. This pro­vides visual indication of valve position without disassembly of valve.
3. Other items are: suitable hand tools such as screw­drivers, wrenches, etc. soft jawed (brass or aluminum) vise, 400 grit wet or dry sandpaper and water for cleaning.
All trouble shooting is possible without removing the valve from the line or removing the cover. It is highly recommended to permanently install a Model X101 Valve Position Indicator and three gauges in unused Hytrol inlet, outlet and cover connections.
Page 9
Diaphragm Check (#1 )
1. Shut off pressure to the Hytrol Valve by slowly closing upstream and downstream isolation valves. SEE CAUTION.
2. Disconnect or close all pilot control lines to the valve cover and
leave only one fitting in highest point of cover open to atmosphere.
3.With the cover vented to atmosphere, slowly open upstream isolation valve to allow some pressure into the Hytrol Valve body. Observe the open cover tapping for signs of continuous flow. It is not necessary to fully open isolating valve. Volume in cover cham­ber capacity chart will be displaced as valve moves to open posi­tion. Allow sufficient time for diaphragm assembly to shift posi­tions. If there is no continuous flow, you can be quite certain the diaphragm is sound and the diaphragm assembly is tight. If the fluid appears to flow continuously this is a good reason to believe the diaphragm is either damaged or it is loose on the stem. In either case, this is sufficient cause to remove the valve cover and investigate the leakage. (See “Maintenance” Section for procedure.)
Freedom of Movement Check (#2)
4. Determining the Hytrol Valve’s freedom of movement can be
done by one of two methods.
5. For most valves it can be done after completing Diaphragm Check (Steps 1, 2, and 3). SEE CAUTION. At the end of step 3 the valve should be fully open.
6. If the valve has a Cla-Val X101 Position Indicator, observe the indicator to see that the valve opens wide. Mark the point of max­imum opening.
7. Re-connect enough of the control system to permit the appli­cation of inlet pressure to the cover. Open pilot system cock so pressure flows from the inlet into the cover.
8. While pressure is building up in the cover, the valve should close smoothly. There is a hesitation in every Hytrol Valve closure, which can be mistaken for a mechanical bind. The stem will appear to stop moving very briefly before going to the closed posi­tion. This slight pause is caused by the diaphragm flexing at a particular point in the valve’s travel and is not caused by a mechanical bind.
9. When closed, a mark should be made on the X101 Valve posi­tion indicator corresponding to the “closed” position. The distance between the two marks should be approximately the stem travel shown in chart.
10. If the stroke is different than that shown in stem travel chart this is a good reason to believe something is mechanically restrict­ing the stroke of the valve at one end of its travel. If the flow does not stop through the valve when in the indicated “closed” position, the obstruction probably is between the disc and the seat. If the flow does stop, then the obstruction is more likely in the cover. In either case, the cover must be removed, and the obstruction locat­ed and removed. The stem should also be checked for scale build­up. (See “Maintenance, section for procedure.)
11. For valves 6” and smaller, the Hytrol Valve’s freedom of move­ment check can also be done after all pressure is removed from the valve. SEE CAUTION. After closing inlet and outlet isolation valves and bleeding pressure from the valve, check that the cover chamber and the body are temporarily vented to atmosphere. Insert fabricated tool into threaded hole in top of valve stem, and lift the diaphragm assembly manually. Note any roughness. The diaphragm assembly should move smoothly throughout entire valve stroke. The tool is fabricated from rod that is threaded on one end to fit valve stem and has a “T” bar handle of some kind on the other end for easy gripping. (See chart in Step 4 of “Disassembly” Section.)
12. Place marks on this diaphragm assembly lifting tool when the valve is closed and when manually positioned open. The distance between the two marks should be approximately the stem travel shown in stem travel chart. If the stroke is different than that shown, there is a good reason to believe something is mechani­cally restricting the stroke of the valve. The cover must be removed, and the obstruction located and removed. The stem should also be checked for scale build-up. (See “Maintenance” Section for procedure.)
Tight Sealing Check (#3)
13. Test for seat leakage after completing checks #1 & #2 (Steps
1 to 12). SEE CAUTION. Close the isolation valve downstream of the Hytrol Valve. Apply inlet pressure to the cover of the valve, wait until it closes. Install a pressure gauge between the two closed valves using one of the two ports in the outlet side of the Hytrol. Watch the pressure gauge. If the pressure begins to climb, then either the downstream isolation valve is permitting pressure to creep back, or the Hytrol is allowing pressure to go through it. Usually the pressure at the Hytrol inlet will be higher than on the isolation valve discharge, so if the pressure goes up to the inlet pressure, you can be sure the Hytrol is leaking. Install another gauge downstream of isolating valve. If the pressure between the valves only goes up to the pressure on the isolation valve discharge, the Hytrol Valve is holding tight, and it was just the iso­lation valve leaking.
STEM TRAVEL
(Fully Open to Fully Closed)
Valve Size (inches) Travel (inches)
Inches MM Inches MM
1 1/4 32 0.4 10 1 1/2 40 0.4 10 250 0.615 2 1/2 65 0.7 18 380 0.820 4 100 1.1 28 6 150 1.7 43 8 200 2.3 58 10 250 2.8 71 12 300 3.4 86 14 350 4.0 100 16 400 4.5 114 20 500 5.6 143 24 600 6.7 165 30 800 7.5 190 36 900 8.5 216
COVER CHAMBER CAPACITY
(Liquid Volume displaced when valve opens)
Valve size (inches) Displacement
Gallons Liters
1 1/4 .020 .07 1 1/2 .020 .07 2 .032 .12 2 1/2 .043 .16 3 .080 .30 4 .169 .64 6 .531 2.0 8 1.26 4.8 10 2.51 9.5 12 4.00 15.1 14 6.50 24.6 16 9.57 36.2 20 12.00 45.4 24 29.00 109.8 30 42.00 197.0 36 90.00 340.0
3
Page 10
Maintenance
Preventative Maintenance
The Cla-Val Co. Model 100-01 Hytrol Valve requires no lubrication or packing and a minimum of maintenance. However, a periodic inspec­tion schedule should be established to determine how the operating conditions of the system are affecting the valve. The effect of these actions must be determined by inspection.
Disassembly
Inspection or maintenance can be accomplished without removing the valve from the line. Repair kits with new diaphragm and disc are recommended to be on hand before work begins.
WARNING: Maintenance personnel can be injured and equipment damaged if disassembly is attempted with pressure in the valve. SEE
CAUTION.
1. Close upstream and downstream isolation valves and independ- ent operating pressure when used to shut off all pressure to the
valve.
2. Loosen tube fittings in the pilot system to remove pressure from valve body and cover chamber. After pressure has been released from the valve, use care to remove the controls and tubing. Note and sketch position of tubing and controls for re-assembly. The schemat­ic in front of the Technical Manual can be used as a guide when reassembling pilot system.
3. Remove cover nuts and remove cover. If the valve has been in service for any length of time, chances are the cover will have to be loosened by driving upward along the edge of the cover with a dull cold chisel.
On 6” and smaller valves block and tackle or a power hoist can be used to lift valve cover by inserting proper size eye bolt in place of the center cover plug. on 8” and larger valves there are 4 holes (5/8” — 11 size) where jacking screws and/or eye bolts may be inserted for lifting purposes. Pull cover straight up to keep from damaging the integral seat bearing and stem.
4. Remove the diaphragm and disc assembly from the valve body. With smaller valves this can be accomplished by hand by pulling
straight up on the stem so as not to damage the seat bearing.
On large valves, an eye bolt of proper size can be installed in the stem and the diaphragm assembly can be then lifted with a block and tackle or power hoist. Take care not to damage the stem or bearings. The valve won't work if these are damaged.
5. The next item to remove is the stem nut. Examine the stem threads above the nut for signs of mineral deposits or corrosion. If the threads are not clean, use a wire brush to remove as much of the residue as possible. Attach a good fitting wrench to the nut and give it a sharp “rap” rather than a steady pull. Usually several blows are sufficient to loosen the nut for further removal. On the smaller valves, the entire diaphragm assembly can be held by the stem in a vise equipped with soft brass jaws before removing the stem nut.
The use of a pipe wrench or a vise without soft brass jaws scars the fine finish on the stem. No amount of careful dressing can restore the stem to its original condition. Damage to the finish of the stem can cause the stem to bind in the bearings and the valve will not open or close.
6. After the stem nut has been removed, the diaphragm assembly breaks down into its component parts. Removal of the disc from the disc retainer can be a problem if the valve has been in serv­ice for a long time. Using two screwdrivers inserted along the out­side edge of the disc usually will accomplish its removal. Care should be taken to preserve the spacer washers in water, partic­ularly if no new ones are available for re-assembly.
7. The only part left in the valve body is the seat which ordinarily does not require removal. Careful cleaning and polishing of inside and outside surfaces with 400 wet/dry sandpaper will usually restore the seat’s sharp edge. If, however, it is badly worn and replacement is necessary, it can be easily removed.
Seats in valve sizes 1 1/4” through 6” are threaded into the valve body. They can be removed with accessory X109 Seat Removing Tool available from the factory. On 8” and larger valves, the seat is held in place by flat head machine screws. Use a tight-fitting, long shank screwdriver to prevent damage to seat screws. If upon removal of the screws the seat cannot be lifted out, it will be nec­essary to use a piece of angle or channel iron with a hole drilled in the center. Place it across the body so a long stud can be insert­ed through the center hole in the seat and the hole in the angle iron. By tightening the nut a uniform upward force is exerted on the seat for removal.
NOTE: Do not lift up on the end of the angle iron as this may force the integral bearing out of alignment, causing the stem to bind.
VALVE STEM THREAD SIZE
Valve Size Thread Size (UNF Internal)
1 1/4"
—2 1/2" 10—32 3"—4" 1/4—28 6"—14" 3/8—24
16" 1/2—20
20 3/4-16 24" 3/4-16 30” 3/4-16 36” 3/4-16
COVER CENTER PLUG SIZE
Valve Size Thread Size (NPT)
1 1/4"
—1 1/2" 1/4" 2"—3" 1/2" 4"—6" 3/4" 8"—10" 1"
12" 1 1/4" 14" 1 1/2"
16" 2" 20” & 24" 2" 30” & 36” 2”
NUT
ANGLE OR CHANNEL IRON
LONG STUD OR BOLT
NUT OR BOLT HEAD
DO NOT
LIFT
VALVE SEAT
VALVE BODY
4
Page 11
Lime Deposits
One of the easiest ways to remove lime deposits from the valve stem or other metal parts is to dip them in a 5-percent muriatic acid solution just long enough for the deposit to dissolve. This will remove most of the common types of deposits. CAUTlON: USE EXTREME CARE WHEN HANDLING ACID. Rinse parts in water before handling. If the deposit is not removed by acid, then a fine grit (400) wet or dry sandpaper can be used with water.
Reassembly
1. Reassembly is the reverse of the disassembly procedure. If a
new disc has been installed, it may require a different number of spacer washers to obtain the right amount of “grip” on the disc. When the diaphragm assembly has been tightened to a point where the diaphragm cannot be twisted, the disc should be com­pressed very slightly by the disc guide. Excessive compression should be avoided. Use just enough spacer washers to hold the disc firmly without noticeable compression.
2. MAKE SURE THE STEM NUT IS VERY TIGHT. Attach a good fitting wrench to the nut and give it a sharp “rap” rather than a steady pull. Usually several blows are sufficient to tighten the stem nut for final tightening. Failure to do so could allow the diaphragm to pull loose and tear when subjected to pressure.
Test Procedure After Valve Assembly
There are a few simple tests which can be made in the field to make sure the Hytrol Valve has been assembled properly. Do these before installing pilot system and returning valve to service. These are similar to the three troubleshooting tests.
1. Check the diaphragm assembly for freedom of movement after all pressure is removed from the valve. SEE CAUTlON. Insert fabricated tool into threaded hole in top of valve stem, and lift the diaphragm assembly manually. Note any roughness, sticking or grabbing. The diaphragm assembly should move smoothly throughout entire valve stroke. The tool is fabricated from rod that is threaded on one end to fit valve stem (See chart in Step 4 of “Disassembly” section.) and has a “T” Bar handle of some kind on the other end for easy gripping.
Place marks on this diaphragm assembly lifting tool when the valve is closed and when manually positioned open. The dis­tance between the two marks should be approximately the stem travel shown in stem travel chart. (See “Freedom of Movement Check” section.) If the stroke is different than that shown, there is a good reason to believe something is mechanically restricting the stroke of the valve. The cover must be removed, the obstruc­tion located and removed. (See “Maintenance” Section for procedure.)
Inspection of Parts
After the valve has been disassembled, each part should be examined carefully for signs of wear, corrosion, or any other abnormal condition. Usually, it is a good idea to replace the rub­ber parts (diaphragm and disc) unless they are free of signs of wear. These are available in a repair kit. Any other parts which appear doubtful should be replaced. WHEN ORDERlNG PARTS, BE SURE TO GIVE COMPLETE NAMEPLATE DATA, ITEM NUMBER AND DESCRlPTlON.
NOTE: If a new disc isn’t available, the existing disc can be turned over, exposing the unused surface for contact with the seat. The disc should be replaced as soon as practical.
3. Carefully install the diaphragm assembly by lowering the stem through the seat bearing. Take care not to damage the stem or bearing. Line up the diaphragm holes with the stud or bolt holes on the body. on larger valves with studs, it may be necessary to hold the diaphragm assembly up part way while putting the diaphragm over the studs.
4. Put spring in place and replace cover. Make sure diaphragm is Iying smooth under the cover.
5. Tighten cover nuts firmly using a cross-over pattern until all nuts are tight.
6. Test Hytrol Valve before re-installing pilot valve system.
Due to the weight of the diaphragm assembly this procedure is not possible on valves 8” and larger. on these valves, the same determination can be made by carefully introducing a low pressure-less than five psi) into the valve body with the cover vented. SEE CAUTION. Looking in cover center hole see the diaphragm assembly lift easily without hesitation, and then settle back easily when the pressure is removed.
2. To check the valve for drip-tight closure, a line should be connected from the inlet to the cover, and pressure applied at the inlet of the valve. If properly assembled, the valve should hold tight with as low as ten PSI at the inlet. See “Tight Sealing Check” section.)
3. With the line connected from the inlet to the cover, apply full working pressure to the inlet. Check all around the cover for any leaks. Re-tighten cover nuts if necessary to stop leaks past the diaphragm.
4. Remove pressure, then re-install the pilot system and tubing exactly as it was prior to removal. Bleed air from all high
points.
5. Follow steps under “Start-Up and Adjustment” Section in
Technical Manual for returning complete valve back to service
.
5
Page 12
1
5
8
10
14
16
6
17
7
9
OUTLE
T
INLET
GLOBE PATTERN
9
26
27
12
15
14
16
INLET
OUTLET
ANGLE PATTERN
22
23
13
12
14
10
11
15
23
TOP VIEW
8" - 24" SEAT DETAIL
1 1/4" - 6" SEAT DETAIL
16" COVER DETAIL
4
24
2
25
13
31
28
30
29
5
14
3
Item Description
1. Pipe Plug
2. Drive Screws (for nameplate)
3. Hex Nut (8” and larger)
4. Stud (8” and larger)
5. Cover Bearing
6. Cover
7. Stem Nut
8. Diaphragm Washer
9. Diaphragm
10. Spacer Washers
11. Disc Guide
12. Disc Retainer
13. Disc
14. Stem
15. Seat
16. Body
17. Spring
22. Flat Head Screws (8” and larger)
23. Seat O-Ring
24. Hex head Bolt (1 1/4” thru 4”)
25. Nameplate
26. Upper Spring Washer (Epoxy coated valves only)
27. Lower Spring Washer (Epoxy coated valves only)
28. Cover Bearing Housing (16” only)
29. Cover O-Ring (16’” only)
30. Hex Bolt (16” only)
31. Pipe Cap (16” only)
PARTS LIST
6
Page 13
100-01
Hytrol Valve Service Data
MODEL
INSTALLATION / OPERATION / MAINTENANCE
Description 100-01 Hytrol Valve
The CIa-VaI Model 100-01 Hytrol Valve is a main valve for
CIa-VaI Automatic Control Valves. It is a hydraulically operated,
diaphragm-actuated, globe or angle pattern valve.
This valve consists of three major components; body, diaphragm
assembly, and cover. The diaphragm assembly is the only
moving part. The diaphragm assembly uses a diaphragm of nylon
fabric bonded with synthetic rubber. A synthetic rubber disc,
contained on three and one half sides by a disc retainer and disc
guide, forms a seal with the valve seat when pressure is applied
above the diaphragm. The diaphragm assembly forms a sealed
chamber in the upper portion of the valve, separating operating
pressure from line pressure.
Description 100-20 600 Series Hytrol Valve
The CIa-VaI Model 100-20 Hytrol Valve (600 Series main valve)
have only one part -the body- that is different from standard 100
Series Cla-Val main valve parts. The remaining parts of the 600
series main valve are standard Cla-Val main valve parts. All serv-
ice and maintenance information for the standard 100 Series
main valves also apply to the 600 series main valves.
The most important thing to remember when ordering main
valve repair kits and replacement parts, except for the body, all
other parts are going to be for a smaller size main valve. Cla-
Val identifies main valve parts with the flange size of the stan-
dard 100 Series main valve. Refer to the "Main Valve Sizes”
chart below.
HYTROL Service Data
HYTROL SIZE
Stem
Travel
Cover Capacity
Displacement
Valve Stem
Thread
UNF-Internal
Cover
Center
Plug
NPT
Cover Nut or Bolt
Cover
Lifting
Holes
UNC
Cover Plug Cover Torque
Stem Nut**
Stem Nut Torque
(ft. Lbs.)
100-01
100-20
Thread
(Bolt)
Socket
Qty Thread
Socket ft. Lbs. in. Lbs.
Thread
Socket
(Long)
inches mm inches mm inches mm
Gallons
Liters
Lubed DRY
1"
25 0.3 8 1/4"
1/4" - 20 (B)
7/16" 8
4
48 3/8" - 24
4
6
1 1/4"
32
0.4
10
0.020
0.07
10 - 32
1/4" 5/16" - 18 (B) 1/2"
8
8 96 7/16" -20 6 10
1 1/2" 40 0.4 10 0.020 0.07
10 - 32
1/4" 5/16" - 18 (B) 1/2"
8
8 96 7/16" -20 6 10
2" 50 0.6 15 0.032
0.12 10 - 32
1/2" 3/8" - 16 (B) 9/16" 8 3/8" 7/16" 12
1/2" - 20
3/4" 10 15
2 1/2"
65 0.7 18
0.043 0.16
10 - 32
1/2" 7/16" - 14 (B) 5/8" 8 1/2" 9/16" 20
5/8" - 18 15/16" 21
30
3" 80 4" 100 0.8
20
0.080 0.30
1/4 - 28 1/2"
1/2" - 13 (B)
3/4" 8 1/2" 9/16" 30 5/8" - 18
15/16"
21 30
4" 100 6" 150 1.1 23
0.169 0.64
1/4 - 28 3/4"
3/4" - 10 (B)
1 1/8" 8 3/4" 5/8" 110 3/4" - 16
1 1/16"
40
60
6" 150 8" 200 1.7 43 0.531 2.00 3/8 - 24 3/4"
3/4" - 10 (B) 1 1/8"
12 3/4"
5/8" 110
7/8" - 14
1 5/16"
85 125
8"
200 10"
250
2.3 58
1.26 4.80 3/8 - 24
1"
3/4" - 10
1 1/4" 16 5/8" - 11
1" 13/16" 110
1 1/8" -12 1 13/16"
125
185
10" 250 12" 300 2.8 71 2.51 9.50
3/8 - 24
1" 7/8" - 9 1 7/16"
20
3/4" - 10
1"
13/16" 160 1 1/2" -12 1 7/8" 252 375
12" 300 16" 400 3.4 86 4.0 15.10
3/8 - 24
1 1/4" 1 1/8" - 7 1 13/16"
20
3/4" - 10
1" 13/16" 390 1 1/2" -12 2 1/2" 270 400
14" 350 3.9
99
6.5
24.60
3/8 - 24 1 1/2" 1 1/4" - 7
2" 20
1" - 8
1" 13/16" 545 1 1/2" -12
2 1/2"
280 420
16"
400
20", 24"
600
4.5
114
9.6 36.20
1/2 - 20
2" 1 1/4" - 7
2" 20
1" - 8
1" 13/16" 545 2" - 16 3" 500 750
20" 500 5.63
143
12 45.40
3/4 - 16 1 1/2" 1 3/8" - 6
2 1/8" 24
1" - 8
1" 13/16" 670
2 1/4" - 16
3 1/2" 930
N/R
24" 600
30"
800 6.75 165
29.0
108.80 3/4 - 16*
3/4"
1 1/2" - 12 2 3/8" 24
1 1/8"- 7
1" 13/16"
800
3" - 12
Special
1350
N/R
* Adapter
p/n 2594101E
inside 1/4" - 28"
Grade 5 Bolts
"Heavy" Grade Nuts
Tighten cover nuts in a "star" cross-over pattern
** Must Use ONLY
Cla-Val Supplied part
Page 14
COVER
PIPE PLUG
COVER BEARING
SPRING
STEM NUT
DIAPHRAGM WASHER
DISC RETAINER
BODY
*
SPACER WASHERS
DISC GUIDE
SEAT
PIPE PLUG
STEM
SEAT O-RING
STUD
8" and Larger
*
DIAPHRAGM
*
DISC
*
Repair Parts
Seat Screw
8" and Larger
(Globe
or
Angle)
PIPE PLUG
HEX NUT
8" and Larger
Cover Bolt
6" and Smaller
KO
DISC GUIDE
KO
SEAT
KO Anti-Cavitation
Trim Option
N-100-01 (R-3/2011
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
BOLT/NUT TORQUING PROCEDURES ON VALVE COVERS
4
BOLTS
6
BOLTS
8
BOLTS
12
BOLTS
16
BOLTS
20
BOLTS
4
3
2
1
65
4
3
2
1
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
Follow this procedure when reassembling MAIN Valve:
1. Tightens bolts/nuts in a “Star” or “Cross-Over” pattern following the
numbers shown above to insure that cover seats evenly on the diaphragm
material and body.
2. Torque the bolt/nuts in three stages with a "Star" or "Cross-Over" pattern
for each stage:
A. To approximately 10% of final torque.
B. To approximately 75% of final torque.
C. To final required torque.
3. Valves that are to be tested to 375 PSI or higher should be retorqued
after 24 hours.
100-01 Hytrol Main Valve Assembly
Page 15
UNDERSTANDING THE 600 SERIES VALVES
In 1987, Cla-Val introduced the Model 100-20 Hytrol as the basic main valve for the 600 Series of automatic control valves. To identify all new valves using the 100-20 Hytrol, an existing cata­log number is modified. Making a 600 Series catalog number is simply done by using a "6" in front of the two digit catalog num­bers or replacing the "2" with a "6" in three digit catalog num­bers. Current schematics reflect both catalog numbers together separated by a slash ( i.e. - 90-01/690-01, 58-02/658-02, 210­01/610-01, etc). Since these two valves 'share' the same catalog number and schematic, they provide the same function in a sys­tem. The only difference between the two valves is the relative capacity of the two main valve series.
The 100-01 Hytrol is the basic main valve for Cla-Val automatic control valves. This valve is the current version of the Clayton Hytrol valve design originated in 1936. The 100-01 Hytrol is designed as a full flow area valve. This means that the inlet, seat and outlet openings are the same size. Thus, the pressure drop is kept to a minimum for this globe style design.
The 100-20 Hytrol valve has all of the basic features and advan­tages of the original 100-01 Hytrol. Only one part has been changed - the body. It is designed with different size inlet, seat and outlet openings. The 100-20 Hytrol has inlet and outlet flanges one valve size larger than the seat opening size. This results in what is sometimes called a ''reduced port' main valve. For example, a 4" 100-20 valve has a 3" seat. Note: valve size is always determined by the flange size. The following chart compares the 100-01 and the 100-20 main valves.
600 Series Hytrol Valve
100-20
MODEL
INSTALLATION / OPERATION / MAINTENANCE
SERVICE AND MAINTENANCE OF 600 SERIES VALVES
The 600 series main valves have only one part -the body- that is different from standard 100 Series Cla-Val main valve parts. The remaining parts of the 600 series main valve are standard Cla­Val main valve parts. All service and maintenance information for the standard 100 Series main valves in this manual also apply to the 600 series main valves.
The most important thing to remember when ordering main valve repair kits and replacement parts, except for the body, all other parts are going to be for a smaller size main valve. Cla-Val iden­tifies main valve parts with the flange size of the standard 100 Series main valve. Refer to the "Main Valve Sizes Comparison" chart. For example, if you are servicing a 6" 100-20 Hytrol and needed a repair kit, you would order a repair kit for a 4" 100-01 Hytrol. This kit is also suitable for a 6" 100-20 Hytrol. Complete Technical Manuals include a repair kit data sheet N-RK that shows this relationship.
When you order repair parts, it is a good idea to include valve nameplate data (size, catalog number, and part number) and description of the parts desired. Do this to be sure parts will fit the valve you are working on and not be too big for it. Pilot con­trols and repair kits maintenance information remain the same for 100 or 600 Series valves.
Cla-Val Main Valves
Catalog Number
The 100-20 Hytrol is available only in ductile iron, 150 and 300 pressure class, and Bronze trim standard. Available extra cost main valve options include stainless steel trim, epoxy coating, Dura-Kleen stem, Delrin sleeved stem, and high temperature rub­ber parts. All four basic main valves have a 600 Series version available with all of the same benefits and size relationships. The following chart shows the relationship of Cla-Val main valve catalog numbers.
Catalog Name
Hytrol
Powertrol
Powercheck
Hycheck
Circa 1936
100 (Angle =2100)
100P & 100PA
100PC & 100PCA
181
100-Series
100-01
100-02
100-03
100-04
600 Series
100-20
100-21
100-22
100-23
(Reduced Internal Port)
Basic Main Valve Size Comparison
Globe Pattern Valves
Flange Size (inch)
Seat Size
100-01 (100 Series) 100-20 (600 Series) 3 3 2 4 4 3 6 6 4 8 8 6
10 10 8 12 12 10 14 14 ---­16 16 12 18 ---- 16 20 20 16 24 24 16 30 30 24 36 36 30 42 ---- 36 48 ---- 36
Angle Pattern Valves
Flange Size (inch)
Seat Size
100-01 (100 Series) 100-20 (600 Series) 4 4 3 6 6 4 8 8 6
Page 16
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-100-20 (R-3/2011)
100-20
PARTS LIST
NO. DESCRIPTION
1 Pipe Plug
2 Drive Screws (for nameplate)
3 Hex Nut (8" and larger)
4 Stud (8" and larger)
5 Cover Bearing
6 Cover
7 Stem Nut
8 Diaphragm Washer
9 Diaphragm
10 Spacer Washers
11 Disc Guide
12 Disc Retainer
13 Disc
14 Stem
15 Seat
16 Body
17 Spring
22 Flat Head Screws (10" and larger)
23 Seat O-Ring
24 Hex Bolt (3 " Thru 6")
25 Nameplate (Mounted on inlet flange)
26 Upper Spring Washer (Epoxy coated valves only)
27 Lower Spring Washer (Epoxy coated valves only)
28 Cover Bearing Housing (20" & 24" & 30")
29 Cover Bearing Housing O-Ring (20"& 24" & 30")
30 Hex Bolt (20" & 24")
31 Pipe Cap (20" & 24 & 30"")
11
14
12434
5 17
16
26
14
7
8
9
27
14
13
22
12
15
31
28
5
30
29
10" — 24" SEAT DETAIL
20" — 24" COVER DETAIL
TOP VIEW
12
13
15
OUTLET
GLOBE
INLET
ANGLE
INLET
6
8
9
2
25
3" — 6" COVER DETAIL
23
11
WHEN ORDERING PARTS, BE SURE TO GIVE COMPLETE NAMEPLATE DATA, ITEM NUMBER AND DESCRIPTION.
10
Page 17
DESCRIPTION
Bulletin 8210’s are 2-way, normally closed internal pilot operated solenoid valves. Valve bodies and bonnets are of brass construction. Standard valves have a General Purpose, NEMA Type 1 Solenoid Enclosure. Bulletin 8211’s are the same as Bulletin 8210’s except the solenoids are equipped with an enclosure which is designed to meet NEMA Type 4, Watertight, NEMA Type 7 (C or D) Hazardous Locations - Class 1, Group C or D and NEMA Type 9 (E, For G) Hazardous Locations - Class 2, Groups E, F or G. The Explosion-Proof/Watertight Solenoid Enclosures are shown on separate sheets of installation and Maintenance Instructions, Form Numbers V-5380 and V-5391.
OPERATION
Normally Closed: Valve is closed when solenoid is de-energized and opens when solenoid is energized.
MANUAL OPERATOR
(Optional) Valves with Suffix ‘MO’ in the catalog number are provided with a manual operator which allows manual operation when desired or during an interruption of electrical power. To operate valve manually, push in knurled cap and rotate clockwise 180° Disengage manual operator by rotating knurled cap counterclockwise 180° before operating electrically.
MANUAL OPERATOR LOCATION
(Refer to Figures 1 and 3) Manual operator (when shipped from factory) will be located over the valve outlet. Manual operator may be relocated at 90° increments by rotating valve bonnet. Remove bonnet screws (4) and rotate valve bonnet with solenoid to desired position. Replace bonnet screws (4) and torque in a crisscross manner to 110 ± 10 inch pounds. If valve is installed in the system and is operational, proceed in the following manner:
WARNING:
Depressurize valve and turn off electrical
power supply.
1. Remove retaining cap or clip and slip the entire solenoid enclosure off the solenoid base sub-assembly.
CAUTION:
When metal retaining clip
disengages, it will spring upwards.
2. Remove bonnet screws (4) and rotate valve bonnet to desired position.
3. Replace bonnet screws (4) and torque in a crisscross manner to 110 ± 10 inch pounds. Replace solenoid enclosure and retaining clip or cap.
INSTALLATION
Check nameplate for correct catalog number, pressure, voltage and service.
TEMPERATURE LIMITATIONS
For maximum valve ambient and fluid temperatures, refer to chart. The temperature limitations listed are for UL applications. For non-UL applications, higher ambient and fluid temperature limitations are available. Consult factory, Check catalog number on nameplate to determine maximum temperatures.
POSITIONING/MOUNTING
This valve is designed to perform properly when mounted in any position. However, for optimum life and performance, the solenoid should be mounted vertical and upright so as to reduce the possibility of foreign matter accumulating in the core tube area. For mounting bracket (optional feature) dimensions, refer to Figure 2.
PIPING
Connect piping to valve according to markings on valve body. Apply pipe compound sparingly to male pipe threads only; if applied to valve threads, it may enter the valve and cause operational difficulty. Pipe strain should be avoided by proper support and alignment of piping. When tightening the pipe, do not use valve as a lever, Wrenches applied to valve body or piping are to be located as close as possible to connection point.
IMPORTANT:
For the protection of the solenoid valve, install a strainer or filter suitable for the service involved in the inlet side as close to the valve as possible. Periodic cleaning Is required depending on the service conditions. See Bulletins 8600, 8601 and 8602 for strainers.
WIRING
Wiring must comply with Local and National Electrical Codes. Housings for all solenoids are provided with connections for 1/2 inch conduit. The general purpose solenoid enclosure may be rotated to facilitate wiring by removing the retaining cap or clip.
CAUTION:
When metal retaining clip disengages, it will spring upwards. Rotate to desired position. Replace retaining cap or clip before operating.
NOTE:
Alternating Current (A-C) and Direct Current (D-C) solenoids are built differently. To convert from one to the other, It Is necessary to change the complete solenoid including the solenoid base sub-assembly and core assembly.
SOLENOID TEMPERATURE
Standard catalog valves are supplied with coils designed for continuous duty service. When the solenoid is energized for a long period, the solenoid enclosure becomes hot and can be touched with the hand only for an instant. This is a safe operating temperature. Any excessive heating will be indicated by the smoke and odor of burning coil insulation.
MAINTENANCE
WARNING:
Turn off electrical power supply and depressurize valve before making repairs. It Is not necessary to remove the valve from the pipe line for repairs.
CLEANING
A periodic cleaning of all solenoid valves is desirable. The time between cleanings will vary, depending on media and service conditions. In general, if the voltage to the coil is correct, sluggish valve operation, excessive leakage or noise will indicate that cleaning is required.
PREVENTIVE MAINTENANCE
1. Keep the medium flowing through the valve as free from dirt and foreign material as possible.
2. While in service, operate the valve at least once a month to insure proper opening and closing.
3. Periodic inspection (depending on media and service conditions) of internal valve parts for damage or excessive wear is recommended. Thoroughly clean all parts, Replace any parts that are worn or damaged.
Construction
A-C Construction
(Alternating Current)
D-C Construction
(Direct Current)
Coil
Class
A
F
H
A, F
or H
Catalog
Number
Prefix
None or
DA
DF or
FT
HT
None, FT
or HT
Max. Ambient Temp.
°F
77
122
140
77
Max. Fluid
Temp.
°F
180
180
180
150
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
2-WAY INTERNAL PILOT OPERATED SOLENOID VALVES
DIAPHRAGM TYPE - 3/8, 1/2 AND 3/4 N.P.T.
NORMALLY CLOSED OPERATION
BULLETINS
8210
8211
ASCO
FORM NO. V-5848
Page 18
IMPROPER OPERATION
1. Faulty Control Circuit: Check the electrical system by energizing the solenoid. A metallic click signifies that the solenoid is operating. Absence of the click indicates loss of power supply. Check for loose or blown-out fuses. open circuited or grounded coil. broken lead wires or splice connections.
2. Burned-Out Coil: Check for open circuited coil. Replace coil if necessary.
3. Low Voltage: Check voltage across coil leads. Voltage must be at least 85% of nameplate rating.
4. Incorrect Pressure: Check valve pressure. Pressure to valve must be within range specified on nameplate.
5. Excessive Leakage: Disassemble valve and clean all parts. Replace worn or damaged parts with a complete Spare Parts Kit for best results.
COIL REPLACEMENT
(Refer to Figures 1, 2 and 3)
Turn off electrical power supply and disconnect coil lead wires. Proceed In the following manner:
1. Remove retaining cap or clip, nameplate and cover.
CAUTION:
When
metal retaining clip disengages. it will spring upwards.
2. Slip yoke containing coil, sleeves and insulating washers off the solenoid base sub-assembly. For D-C Construction. slip spring washer. coil and insulating washers off the solenoid base sub-assembly. Insulating washers are omitted when a molded coil is used.
3. Reassemble in reverse order of disassembly paying careful attention to exploded views provided for identification and placement of parts.
CAUTION:
Solenoid must be fully reassembled as the housing and internal parts are part of and complete the magnetic circuit. Place insulating washers at each end of con, If required.
VALVE DISASSEMBLY Depressurize valve and turn off electrical power supply. For A-C Construction, refer to Figures 1 and 2. For D-C Construction, refer to Figure 3. Proceed In the following manner:
1. Disassemble valve in an orderly fashion. Pay careful attention to exploded views provided for identification of parts.
2. Remove retaining cap or clip and slip the entire solenoid enclosure off the solenoid base sub-assembly.
CAUTION:
When metal retaining clip
disengages, it will spring upwards.
3. Unscrew solenoid base sub-assembly and remove bonnet gasket. Core assembly and core spring.
4. For A-C Construction without manual operator. remove valve bonnet screws (4). Remove solenoid base sub-assembly. core assembly and core spring.
5. Remove diaphragm spring (A-C Construction only). diaphragm assembly and body gasket.
6. For normal maintenance, it is not necessary to disassemble the manual operator unless external leakage is evident To disassemble, remove stem pin. manual operator stem. stem spring and stem gasket.
7. All parts are now accessible for cleaning or replacement. Replace worn or damaged parts with a complete Spare Parts Kit for best results.
VALVE REASSEMBLY
1. Reassemble in reverse order of disassembly paying careful attention to exploded views provided for identification and placement of parts.
2. Replace body gasket and diaphragm assembly. Locate bleed hole in diaphragm assembly approximately 45° from valve outlet.
3. Replace valve bonnet and bonnet screws. Torque bonnet screws (4) in a crisscross manner to 110 ± 10 inch pounds.
4. For A-C Construction, the diaphragm spring. core assembly and core spring must be installed prior to assembly of bonnet as this is the solenoid base sub-assembly. Be sure diaphragm spring is installed properly. Closed turns of spring to seat on diaphragm assembly. For valves with a manual operator (see Figure 1), the small end of diaphragm spring seats on diaphragm assembly.
5. Install core spring in core assembly. Be sure core spring is inserted into core assembly with wide end in first. Closed end protrudes from top of core assembly.
6. Replace bonnet gasket, core assembly, core spring and solenoid base sub-assembly. Torque solenoid base sub-assembly to 175 ± 25 inch pounds
7. If removed, replace manual operator stem gasket. stem spring, stem and stem pin.
8. Replace solenoid enclosure and retaining cap or clip.
9. After maintenance, operate the valve a few times to be sure of proper opening and closing.
ORDERING INFORMATION
FOR SPARE PARTS KITS
When Ordering Spare Parts Kits or Coils
Specify Valve Catalog Number,
Serial Number and Voltage
Spare Parts Kits
Spare Parts Kits and Coils are available for ASCO valves.
Parts marked with an (*) are supplied in Spare Parts Kits
Bulletin 8210 -- A-C Construction
Manual Operator
(Catalog Number Suffixed “MO”)
Figure 1.
Page 19
Bulletin 8210 -- A-C Construction
General Purpose Solenoid Enclosure Shown
For Explosion-Proof/Watertight Solenoid Enclosure used on Bulletin 8211, see Form No. V-5391.
Figure 2.
Page 20
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-V5848 (R-3/2011)
Bulletin 8210 -- D-C Construction
General Purpose Solenoid Enclosure Shown
For Explosion-Proof/Watertight Solenoid Enclosure used on Bulletin 8211, see Form No. V-5390.
Figure 3.
Page 21
DESCRIPTION
Bulletin 8262’s are 2-way normally closed, direct acting solenoid valves having bodies of brass construction. Standard valves have a General Purpose NEMA Type 1 Solenoid Enclosure. Valves may also be equipped with a solenoid enclosure which is designed to meet NEMA Type 4 Watertight, NEMA Type 7 (C or D) Hazardous Locations-Class 1, Groups C or D and NEMA Type 9 (E, For G) Hazardous Locations Class 2, Groups E, F or G. Installation and Maintenance Instructions for Explosion-Proof/Watertight Solenoid Enclosures are shown on Form Nos. V-5391 or V-5380.
OPERATION
Normally Closed: Valve is closed when solenoid is de-energized. Valve opens when solenoid is energized.
NOTE:
Inlet port will either be marked “1” or “1N.” Outlet port will be marked “2.”
IMPORTANT:
No minimum operating pressure required.
INSTALLATION
Check nameplate for correct catalog number, pressure, voltage and service.
TEMPERATURE LIMITATIONS
For maximum valve ambient and fluid temperature, refer to chart below. For higher ambient and fluid temperatures, consult factory. Check catalog number and watt rating on nameplate to determine the maximum temperatures.
POSITIONING
Valve is designed to perform properly when mounted in any position. However, for optimum life and performance, the solenoid should be mounted vertical and upright so as to reduce the possibility of foreign matter accumulating in the core tube area.
MOUNTING
For valve body and mounting bracket mounting dimensions, refer to Figures 1 and 2.
PIPING
Connect piping according to markings on valve body. Apply pipe compound sparingly to male pipe threads only; if applied to valve threads, it may enter valve and cause operational difficulty. Pipe strain should be avoided by proper support and alignment of piping. When tightening the pipe, do not use valve as a lever. Wrenches applied to valve body or piping are to be located as close as possible to connection point.
IMPORTANT:
For the protection of the solenoid valve. install a strainer or filter suitable for the service involved in the inlet side as close to the valve as possible. Periodic cleaning is required depending upon service conditions. See Bulletins 8600, 8601 and 8602 for strainers.
WIRING
Wiring must comply with Local and National Electrical Codes. Solenoid housings are provided with a 7/8 diameter hole for 1/2 inch conduit. The general purpose solenoid enclosure may be rotated to facilitate wiring by removing the retaining cap or clip.
CAUTION:
When metal retaining clip disengages, it will spring upward. Rotate enclosure to desired position. Replace retaining cap or clip before operating.
NOTE:
Alternating Current (A-C) and Direct Current (D-C) solenoids are built differently. To convert from one to the other, it is necessary to change the complete solenoid including the core assembly and solenoid base sub-assembly.
SOLENOID TEMPERATURE
Standard catalog valves are supplied with coils designed for continuous duty service. When the solenoid is energized for a long period, the solenoid enclosure becomes hot and can be touched with the hand only for an instant. This is a safe operating temperature. Any excessive heating will be indicated by the smoke and odor of burning coil insulation.
MAINTENANCE
WARNING:
Turn off electrical power supply and depressurize valve before making repairs. It is not necessary to remove the valve from the pipe line for repairs.
CLEANING
A periodic cleaning of all solenoid valves is desirable. The time between cleanings will vary depending upon media and service conditions in general, if the voltage to the coil is correct. sluggish valve operatIon, excessive noise or leakage will indicate that cleaning is required. Clean valve strainer or filter when cleaning solenoid valve.
PREVENTIVE MAINTENANCE
1. Keep the medium flowing through the valve as free from dirt and foreign material as possible.
2. While in service, operate the valve at least once a month to insure proper opening and closing.
3. Periodic inspection (depending on media and service conditions) of internal valve parts for damage or excessive wear is recommended Thoroughly clean all parts. Replace any parts that are worn or damaged.
IMPROPER OPERATION
1. Faulty Control Circuit: Check the electrical system by energizing the solenoid. A metallic click signifies the solenoid is operating. Absence of the click indicates loss of power supply. Check for loose or blownout fuses, open-circuited or grounded coil, broken lead wires or splice connections.
2. Burned-Out Coil: Check for open-circuited coil. Replace coil if necessary.
3. Low Voltage: Check voltage across the coil leads. Voltage must be at least 85% of nameplate rating.
4. Incorrect Pressure: Check valve pressure. Pressure to valve must be within range specified on nameplate.
5. Excessive Leakage: Disassemble valve and clean all parts. Replace worn or damaged parts with a complete Spare Parts Kit for best results.
COIL REPLACEMENT
Turn off electrical power supply and disconnect coil lead wires. Refer to watt rating stamped on nameplate for identification of solenoid construction. When you have determined the watt rating of solenoid, select the correct paragraph below.
FIGURE 3 SHOWS A SOLENOID WITH A WATT RATING OF 6 A-C, 9.7 D.C,OR 9 A-C.
1. Remove retaining cap or clip, nameplate and cover.
CAUTION:
When
metal retaining clip disengages, it will spring upward.
2. Slip the yoke containing a coil, sleeves and insulating washers off the solenoid base sub-assembly. Insulating washers are omitted when a molded coil is used.
3. Slip coil, sleeves and insulating washers from yoke. 4. Reassemble in reverse order of disassembly paying careful attention to exploded view provided for identification and placement of parts.
Wattage
Coil
Class
Catalog Number
Prefix
Max.
Ambient
Temp.
°F
Max. Fluid
Temp.
°F
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
2-WAY DIRECT ACTING SOLENOID VALVES
NORMALLY CLOSED OPERATION -- 1/4 N.P.T.
BULLETINS
8262
ASCO
FORM NO. V-5927
*Catalog Nos. 8262C200 and 8262B200 and valves with suffix “W” in the catalog number are limited to 140°F fluid temperature.
16.7*
F
None
77 200
11.2*
A, F or H
None, FT
or HT
77 150
9.7
A, F or H
None, FT
or HT
77 120
9
F
None
77 180
A
None
77 180
6
F
FT
122 200
H
HT
140 200
Page 22
ORDERING INFORMATION
FOR SPARE PARTS KITS
When Ordering Spare Pans Kits or Coils,
Specify Valve Catalog Number,
Serial Number and Voltage.
SPARE PARTS KITS
Spare Parts Kits and Coils arc available for ASCO valves.
Parts marked with an asterisk (*) are supplied in Spare Parts Kit.
FIGURE 4 SHOWS A SOLENOID WITH A WATT RATING OF 105 A-C,
11.2 D.C OR 16.7 A.C
1. Remove retaining cap or clip, nameplate and housing.
CAUTION:
When metal retaining clip disengages, it will spring upward.
2. Slip spring washer, insulating washer and coil off the solenoid base sub-assembly. Insulating washers are omitted when a molded coil is used.
3. Reassemble in reverse order of disassembly paying careful attention to exploded views provided for identification and placement of parts.
CAUTION:
Solenoid must be fully reassembled as the housing and internal parts are part of and complete the magnetic circuit. Place an insulating washer at each end of coil, if required.
VALVE DISASSEMBLY AND REASSEMBLY
Depressurize valve and turn off electrical power supply. For valves with a watt rating of 6 A-C, 9.7 D-C or 9 A-C, refer to Figure 3. For valves with a watt rating of 10.5 A-C, 11.2 D-C or 16.7 A-C, refer to Figure 4. Proceed in the following manner:
1. Remove retaining cap or clip and slip the entire solenoid enclosure off the solenoid base sub-assembly.
CAUTION:
When metal retaining clip
disengages, it will spring upward.
2. Unscrew solenoid base sub-assembly and remove core assembly, core spring and body gasket.
3. All parts are now accessible for cleaning or replacement. Replace worn or damaged parts with a complete Spare Pans Kit for best results.
4. Reassemble in reverse order of disassembly paying careful attention to exploded views provided for identification and placement of pans.
5. Replace body gasket, core assembly, core spring and solenoid base sub-assembly. Torque solenoid base sub-assembly to 175 ± 25 inch pounds.
6. After maintenance, operate the valve a few times to be sure of proper operation.
Figure 1
Body Molding
Figure 2
Mounting Bracket
Mounting Dimensions
Page 23
NOTE: A-C (ALTERNATING CURRENT) CONSTRUCTION SHOWN. FOR A-C CONSTRUCTION, EITHER END OF THE SPRING MAY BE INSTALLED INTO TOP OF CORE ASSEMBLY. FOR D-C (DIRECT CURRENT) CONSTRUCTION, INSTALL WIDE END OF CORE SPRING IN CORE ASSEMBLY FIRST, CLOSED END OF CORE SPRING PROTRUDES FROM TOP OF CORE ASSEMBLY.
Figure 3
Bulletin 8262 (6 A-C, 9.7 D-C or 9 Watts A-C)
General Purpose Solenoid Enclosure Shown
For Explosion-Proof/Watertight Solenoid Enclosure, See Form No. V-5391
Page 24
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-V5927 (R-3/2010)
Figure 3
Bulletin 8262 (10.5 A-C, 11.2 D-C or 16.7 Watts A-C)
General Purpose Solenoid Enclosure Shown
For Explosion-Proof/Watertight Solenoid Enclosure, See Form No. V-5380
Page 25
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
PL-CK2 (R-3/2011)
Page 26
The strainer is designed for use in conjunction with a Cla-Val Main Valve, but can be installed in any piping system where there is a moving fluid stream to keep it clean. When it is used with the Cla-Val Valve, it is threaded into the upstream body port provided for it on the side of the valve. It projects through the side of the Main Valve into the flow stream. All liquid shunted to the pilot control system and to the cover chamber of the Main Valve passes through the X46 Flow Clean Strainer.
C
Male
Pipe
SAE
H
D
E
B
I
G
Male
Pipe
B
I
Width Across Flats
Female
Pipe
A
D
E
F
• Self Scrubbing Cleaning Action
• Straight Type or Angle Type
The Cla-Val Model X46 Strainer is designed to prevent passage of foreign particles larger than .015". It is especially effective against such contaminant as algae, mud, scale, wood pulp, moss, and root fibers. There is a model for every Cla-Val. valve.
The X46 Flow Clean strainer operates on a velocity principle utilizing the circular "air foil" section to make it self cleaning. Impingement of particles is on the "leading edge" only. The low pressure area on the downstream side of the screen prevents foreign particles from clog­ging the screen. There is also a scouring action, due to eddy cur­rents, which keeps most of the screen area clean.
Dimensions
(In Inches)
INSTALLATION
X46 Angle Type B (In Inches)
B
(NPT)C(SAE)
DEH I
1/8 1/4 1-3/8 5/8 7/8 1/4
1/4 1/4 1-3/4 3/4 1 3/8
3/8 1/4 2 7/8 1 1/2
3/8 3/8 1-7/8 7/8 1 1/2
1/2 3/8 2-3/8 1 1-1/4 5/8
X46A Straight
X46B Angle
X46A Straight Type A (In Inches)
A B D E F G I
1/8 1/8 1-3/4 3/4 1/2 1/2 1/4
1/4 1/4 2-1/4 1 3/4 3/4 3/8
3/8 3/8 2-1/2 1 7/8 7/8 1/2
3/8 1/2 2-1/2 1-1/4 1/2 7/8 3/4
1/2 1/2 3 1-1/4 1 1-1/8 3/4
3/8 3/4 3-3/8 2 1/2 1 7/8
3/4 3/4 4 2 1 1-1/2 7/8
3/8 1 4-1/4 2-3/4 1/2 1-3/8 7/8
1 1 4-1/2 2-3/4 1-1/4 1-3/4 7/8
1/2 1 4-1/4 2-3/4 1/2 1-3/8 7/8
Flow Clean Strainer
X46
INSPECTION
Inspect internal and external threads for damage or evidence of cross-threading. Check inner and outer screens for clogging, embedded foreign particles, breaks, cracks, corrosion, fatigue, and other signs of damage.
CLEANING
After inspection, cleaning of the X46 can begin. Water service usually will produce mineral or lime deposits on metal parts in contact with water. These deposits can be cleaned by dipping X46 in a 5-percent muriatic acid solution just long enough for deposit to dissolve. This will remove most of the common types of deposits. Caution: use extreme care when handling acid. If the deposit is not removed by acid, then a fine grit (400) wet or dry sandpaper can be used with water. Rinse parts in water before handling. An appropriate solvent can clean parts used in fueling service. Dry with compressed air or a clean, lint-free cloth. Protect from damage and dust until reassembled.
REPLACEMENT
If there is any sign of damage, or if there is the slightest doubt that the Model X46 Flow Clean Strainer may not afford completely satisfactory operation, replace it. Use Inspection steps as a guide. Neither inner screen, outer screen, nor housing is fur­nished as a replacement part. Replace Model X46 Flow Clean Strainer as a com­plete unit.
When ordering replacement Flow-Clean Strainers, it is important to determine pipe size of the tapped hole into which the strainer will be inserted (refer to column A or F), and the size of the external connection (refer to column B or G).
When Ordering, Please Specify:
• Catalog Number X46
• Straight Type or Angle Type
• Size Inserted Into and Size Connection
• Materials
DISASSEMBLY
Do not attempt to remove the screens from the strainer housing.
MODEL
INSTALLATION / OPERATION / MAINTENANCE
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-X46 (R-3/2011)
(NPT) (NPT)
X46B
X46A
Page 27
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
INSTALLATION / OPERATION / MAINTENANCE
Flow Control
CV
MODEL
N-CV (R-3/2011)
DESCRIPTION
The Cla-Val Model CV Flow Control is a simply-designed, spring-loaded check valve. Rate of flow is full flow in one direc­tion and restricted in other direction. Flow is adjustable in the restricted direction. It is intended for use in conjunction with a pilot control system on a Cla-Val Automatic Control Valve.
OPERATION
The CV Flow Control permits full flow from port A to B, and restricted flow in the reverse direction. Flow from port A to B lifts the disc from seat, permitting full flow. Flow in the reverse direction seats the disc, causing fluid to pass through the clear­ance between the stem and the disc. This clearance can be increased, thereby increasing the restricted flow, by screwing the stem out, or counter-clockwise. Turning the stem in, or clockwise reduces the clearance between the stem and the disc, thereby reducing the restricted flow.’
INSTALLATION
Install the CV Flow Control as shown in the valve schematic All connections must be tight to prevent leakage.
DISASSEMBLY
Follow the sequence of the item numbers assigned to the parts in the cross sectional illustration for recommended order of disassembly.
Use a scriber, or similar sharp-pointed tool to remove O-ring from the stem.
INSPECTION
Inspect all threads for damage or evidence of cross- thread­ing. Check mating surface of seat and valve disc for exces­sive scoring or embedded foreign particles. Check spring for visible distortion, cracks and breaks. Inspect all parts for damage, corrosion and cleanliness.
CLEANING
After disassembly and inspection, cleaning of the parts can begin. Water service usually will produce mineral or lime deposits on metal parts in contact with water. These deposits can be cleaned by dipping the parts in a 5-percent muriatic acid solution just long enough for deposits to dis­solve. This will remove most of the common types of deposits. Caution: use extreme care when handling acid. If the deposit is not removed by acid, then a fine grit (400) wet or dry sandpaper can be used with water. Rinse parts in water before handling. An appropriate solvent can clean parts used in fueling service. Dry with compressed air or a clean, lint-free cloth. Protect from damage and dust until reassembled.
REPAIR AND REPLACEMENT
Minor nicks and scratches may be polished out using a fine grade of emery or crocus cloth; replace parts if scratches cannot be removed.
Replace O-ring packing and gasket each time CV Flow Control is overhauled.
Replace all parts which are defective. Replace any parts which create the slightest doubt that they will not afford com­pletely satisfactory operation. Use Inspection steps as a guide.
REASSEMBLY
Reassembly is the reverse of disassembly; no special tools are required.
TEST PROCEDURE
No testing of the flow Control is required prior to reassembly to the pilot control system on Cla-Val Main Valve.
Page 28
3/8" Flow Control
CV
2.12
MAX
STAMP PART NO. ON SMOOTH SURFACE
RESTRICTED
FLOW
3/8 - 18 NPT
1.84
ADJUSTING STEM (TURN CLOCKWISE TO INCREASE RESTRICTION)
1
7
2
10
9
8
6
5
4
3
.85
FREE FLOW
BAR STOCK
CONFIGURATION
When ordering parts,
please specify:
• Number Stamped on Side
• Description (CV Flow Control)
• Part Description
• Material
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
PL-CV (R-3/2011)
PARTS LIST
ITEM DESCRIPTION QTY
1
Cap (SS only)
1
2
Nut, Jam
1
3
Seat
1
4
Gasket
1
5
Disc
1
6
Spring
1
7
Ring, Retaining
1
8
Stem
1
9
O-Ring
1
10
Housing
1
Page 29
WIRING
Loosen jam nut holding transmitter and bracket to adapter when connecting transmitter to field wiring. Tighten jam nut after connections and adjustments are made.
Use good field wiring practices for low voltage DC analog instru­mentation wiring (suggest minimum of 18-gauge multistrand wire). Avoid potential ground loops. Calibration of transmitter should be done with a temporary hookup of test equipment before final wiring connections are made.
Units with NEMA 6, IP-68 enclosures have permanently attached 8' shielded cable leads. Use Red wire for positive and Black wire for negative.
Units before Feb. 2000 have NEMA 6 enclosure with MS3102E­14S-6PAmphenol plug and socket for attaching leads. Use "A" contact for positive and "B" contact for negative.
For best noise immunity, use twisted pair shielded cable to connect field wiring to the transmitter. The shield of the cable should be open at the transducer and grounded at the other end. Units with permanently attached cable are supplied with shield open inside transmitter.
CALIBRATION
1. When properly adjusted, the transmitter will have the valve closed position within 0% to 30% of total transmitter range and the valve open position within 80% to 100% of total transmitter range. At valve closed position the transmitter will have a 4 mA output and at fully open position the transmitter will have a 20 mA output.
IMPORTANT CAUTION
: The transmitter wire rope mechanism is
spring loaded to retract and can be damaged by a sudden release
of the wire rope. Use care to insure that it is returned to the trans­mitter very slowly during start up and operation. This damage may not be covered by warranty.
2. You will need the following tools to calibrate and align the X117D: A.) A small flat blade screwdriver (.105 Max. width x .023” max. thickness) with non-metallic handle to fit the span and null potentiometer B.) A 4-20 mA calibration/tester or multiamp-tester/meter or some means of measuring the 4-20 mA transmitter output C.) Hand tools to adjust and tighten X117D assembly during calibration
3. Preliminary mechanical settings. (Refer to Drawing No. 200000)
Be sure that the valve is in the fully closed position. See Technical Manual for the main valve for information on this. Check that line isolation or block valves are closed.
Adjust Nut Coupler (9) up or down on stem until gap between wire rope end and transmitter housing is according to table (below). The Hex Coupler (10) is used to tighten nut coupler to stem. A minimum gap is required, see Reference Table. (Refer to Drawing No. 200000)
Long threaded end of Hex Coupler (10) has two hex nuts (11) for adjusting position of end of wire rope directly over the opening in the top of the transmitter. Use one hex nut on each side of the wire rope end. Wire rope should go vertically up and down without noticeable angle from vertical.
4. Temporarily connect calibration equipment (milliamp meter and
power supply or portable instrumentation tester) to transmitter wiring. Calculate total loop resistance to determine minimum load resistor. See OPERATION
section. Remove two calibration cover
screws found on housing end.
Valve Position Transmitter
X117D
DESCRIPTION
The Cla-Val Model X117D Valve Position Transmitter is designed to provide analog signal (4 - 20 mA, 2 wire) output of valve position for Cla-Val Main Valves. A stem extension is fitted to the main valve stem with the position transmitter mechanically linked to it. The valve stem is mechanically linked to the electronics for an output signal that is in direct proportion to valve position. Provisions are made for bleeding air from valve cover through a small bleed screw and washer located on adapter.
INSTALLATION
Normally, the X117D is supplied mounted on the Cla-Val main valve. If X117D has not been installed at factory, then install stem, adapter, mounting bracket with transmitter (in that order) as shown on drawing No. 200000.
MODEL
INSTALLATION / OPERATION / MAINTENANCE
OPERATION
The signal from the position sensing linkage mechanism is converted to a two-wire 4 to 20 mA current output appearing at the output ter­minals. The excitation voltage ranges from 12 to 35 Volts DC. The minimum supply voltage is a function of total loop resistance. It may be calculated using the formula:
V(min) = (0.02 x Load Resistance) + 12 VDC
Page 30
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-X117D (R-3/2011)
Refer to calibration equipment and adjust transmitter potentiometer marked “NULL” until the meter reads 4 mA. A clockwise turn increases output. Use care in adjusting the potentiometer while turning the screwdriver.
5. For the most accurate calibration it is necessary to open valve fully. CAUTION: This will either allow a high flow rate through the valve, or the downstream pressure will quickly increase to the inlet pressure. In some cases, this can be very harmful. Where this is the case, and there are no block valves in the system to protect the downstream piping, it should be realized that steps should be taken to remedy this situation before proceeding further. Normally, block valves are to be used to protect downstream piping while the valve is in the open position. Close downstream block valve. Vent cover chamber to atmosphere. Slightly open inlet block valve. Allow valve to open while fluid is vented from cover chamber. When flow stops valve is in the fully open position. Note: continuous leakage from cover chamber could mean additional troubleshooting of the main valve or pilot system must be done.
6. With valve in fully open position, inspect position of wire rope and nut coupler. (See Step 3). Adjust if necessary.
Refer to calibration equipment (see Step 4) and adjust potentiometer marked “SPAN” until the meter reads 20 mA. A clockwise turn increases output. Use care in adjusting the potentiometer while turning the screwdriver.
7. There is some interplay between:
1.) the “span” and “null” settings,
2.) the 4 to 20 mA signal and,
3.) the actual valve open and closed positions. Repeat steps 4-6 above. Cycle valve from open to closed posi­tions and check settings as necessary to achieve desired valve position signal accuracy.
8. Remove all calibration equipment and attach permanent wiring. Recheck wiring and output signals at remote location. See Wiring section. Reinstall two cover screws on housing. Recheck and tighten all fasteners. Bleed air from main valve cover through small bleed screw and washer located on one wrench flat of adapter.
MAINTENANCE
The X117D is constructed of durable materials which normally requiring no lubrication or periodic maintenance. The two ‘O’ rings (2) (p/n 00951E) in the adapter (5) that seal against the stainless steel actuating stem (1) will need replacement if signs of leakage at the stem occur.
M
+
Meter
12 to 35 VDC
+
Red
Black
_
GAP
Coupler gap is set with valve in fully closed position. This establishes the minimum mechanical position for 4 mA output.
0
10
15
20 35
30
25
0
200
400
800
600
1000
1200
OPERATING ZONE
1150 OHMS
12V
SUPPLY VOLTAGE, V
MAX. LOAD, R (OHMS)
ADJUSTMENT: Zero and span adjustments allow setting the 4 mA position (valve closed) within 0% to 30% of total transmitter range and setting the 20 mA position (valve fully open) within 80% to 100% of total transmitter range.
X117D
Part Number
Valve Size (inch)
Val ve
Stem Travel
Coupier
Setting
Transmitter
Total Range
100-01 100-20
20000019F 1 1/4 0.400 3/16" 1" 20000019F 1 1/2 0.490 3/16" 1" 20000020A 2 3 0.590 1/8" 1" 20000020A 2 1/2 0.714 1/16" 1" 20000021A 3 0.835 1/16" 1" 20000001A 4 6 1.109 9/16" 2" 20000002A 6 8 1.584 3/16" 2" 20000003A 8 10 2.242 7/16" 3" 20000004A 10 12 2.711 1/8" 3" 20000005A 12 16 3.343 5/16" 4" 20000006A 14 N/A 3.920 9/16" 5" 20000007K 16 20 & 24 4.584 3/16" 5"
20000008J 20 N/A 5.630 2 1/4" 10" 20000008J 24 N/A 6.504 2 1/4" 10" 20000032J 30 N/A 7.500 1 1/2" 10" 20000032J 36 N/A 8.500 1" 10"
“GAP”
Nominal Minimum
Page 31
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Dimensions
Available only in replacement assembly.
PL-CDC-1 (R-6/2011)
NPT
5
3
4
2
1
I
Full Open Operation
NPT
5
3
4
2
1
I
Tight Closing Operation
B
C
A
NSF 61
Approved
Item Description Material
1 Body Brass
2
End
Connection
Brass
3 Disc Polytherimide
4 Seat NBR
5 Spring Stainless Steel
Size
(NPT)
Stock
Number
A B C I CVpsi Wt.
3/8" 9834501A 1.73 0.79 1.06 0.40 4.55 400 0.37
1/2" 9834502J 2.32 0.98 1.35 0.53 6.00 400 0.32
• NSF 61 Approved
• Meets low lead requirements
• Soft Seat for Bubble Tight Shutoff, Spring Loaded for
Fast Seating Action
• Compact Design
• Low Cracking Pressure 1/2 psi
• Flow Profile Designed to Minimize Head Loss
• Perfect Seating both at High and Low Pressure, Wide
Temperature Range: +10
° to 210°F
Polyethermide Disc to ensure the Best Resistance for
Corrosion and Abrasion
Patented Disc Guide to Prevent Any Side Loading
CDC-1
PARTS LIST
Check Valve (Sizes 3/8and 1/2”)
MODEL
Page 32
Electronic Control Systems
Optional Remote Control
Modem
Modem
Computer
131VC
131-01
Control Valve
Signal Transmitter
4-20 mA
Electronic Control of Hydraulic
Cla-Val Valves
Programmable Monitoring and
Control of Flow, Pressure, Delta P, Level or Valve Position
Accurate Control of Valve Speed and
Response
Remote Set-Point Control
Security System - Prevents
Unauthorized Changes
Control Backup Systems in the
Event of an Emergency
The Cla-Val 131VC-1 Electronic Control System is designed to achieve unprecedented valve control accuracy and stability. Ideal for remote valve control, the 131VC-1 Electronic Control System provides the interface between SCADA system computers and hydraulic control valves sites.
Electronic Control of Hydraulic Valves
The 131VC-1 Electronic Control System is designed to work in conjunction with Cla-Val 131 Series hydraulic control valves— a combination that takes advantage of the simplicity of hydraulic valve operation and the control possibilities available with electronics.
The 131VC-1 Electronic Control System receives transmitted signals and activates dual solenoid pilots on the hydraulic con­trol valve. These pilots direct hydraulic pressure within the sys­tem to position and regulate the valve. By continuously com­paring system conditions to the programmed set-point, the sys­tem is automatically maintained at the desired value.
Additional important control features, unique to this type of valve control, are offered as standard. They are designed for user friendly operation and system safety and are addressed in this brochure.
Key Advantages
• Proven reliable hydraulic control valve
• Low electric power requirement
• Solid state electronic components
• No motors, bearings, bushings or packings to wear out or leak
We Not Only Sell Valves—
We Provide Solutions
SERIES
Page 33
How it Works
131-01 Valve
Transmitter
Dead Band
Set-Point Command
131-01 Valve
Transmitter
Transmitter Feedback Signal
Deviation
Transmitter
131-01 Valve
Devitation
Transmitte Feedback Signal
1. Set-Point Command
Set-point command is received from a remote location or entered via the key pad into the Electronic Valve Controller.
2. Feedback and Comparison
The Electronic Valve Controller compares the feedback signal from the transmitter to the set-point. If the deviation exceeds the deadband, the valve control system is activated.
Display
The 131VC-1 has been engineered to be the industry’s most user friendly controller. With three digital displays areas (two offering up to 9 characters of true alphanumeric), the 131VC-1 effectively eliminates cryptic messages, sub-routines and loops that could confuse even the most experienced operator. The bright, crisp display is vacuum fluorescent, and offers much better readability than any other display technology. Additional operator-friendly features include: custom programmable alarm messages, illuminated keys, and an easy-to-use menu system.
Status Indicators - Four status indicators show the controller’s operating status at all times:
Manual Key Light: For manual control.
Set-point Key Light: For indication of remote control.
Output Indicator: “OUT” and indicator lights illuminate
when either output 1 or 2 are on.
Alarm Indicator: “ALM” and indicator lights illuminate when either output 1 or 2 are on.
Keys Pads: All menu entry, configuration, tuning and set-point controls is entered through rugged backlit rubber keys. A simple menu system prompts the operator, step by step, through all procedures. Security system prevents unauthorized changes to all values.
3. Valve Actuation
The Electronic Valve Controller actu­ates the solenoid controls, causing the valve to modulate as needed to regain the set-point condition.
Keypad & Display
Page 34
Features
Alarm - Programmed to signal when system conditions exceed a desired
value or in the event of a system component failure. It can be configured to be latching or non-latching, normally open or normally closed contact with deadbands.
Absolute Alarm -
Activates when the process variable exceeds
alarm set-point. It can be either high and/or low acting.
Deviation Alarm - Shifts as the set-point is changed. It can be symmetrical or asymmetrical.
Fault Alarm - Activates when the process variable is lost.
Set-Point Rate of Change - Prevents accidental or sudden changes in
the programmed set-point. It is also invaluable when used on high differential or surge sensitive applications where valve speed of operation must be tightly controlled.
Process Variable Backup - Can automatically recognize secondary process variable or can be programmed to open or close valve or can default to backup pilot system using alarm function.
DC Power Supply - Provides source of power for signal transmitter.
Retransmission - Transmit process variable or set-point values.
Offsets - Adjusts the process variable and remote set point settings if
respective signals do not match.
Filter - Stabilizes process variable signal when required.
Security System - Prevents unauthorized changes.
Input Linearization - For flow measurement across orifices, venturies, etc.
Serial Communications - RS485 or RS232. (optional)
Digital Inputs - Selects specific set-points. (optional)
NEMA 4X Enclosure (optional)
Input Signals
The 131VC-1 Electronic Control System is designed to accept industry standard 4-20 mA full scale signals for pressure, flow or level control from customer supplied transmitter(s).
Flow Measurement using a differential signal requires activating the square root extractor to obtain direct flow readout.
Modulating Level Control requires the use of an optional X117 Valve Position Transmitter in addition to a level transmitter.
Valve Position Control requires an optional X117 Valve Position Transmitter installed on the valve.
Other configurations are available on a special order basis, consult the factory for details.
Specifications
Control Input:
4-20 mA full scale (others optional)
Control Parameters
Proportional Bands: 1 to 999%, settable in 0.1%
increments independently for opening and closing
Deadbands: achievable up to 15% of input range Cycle Time: 1 to 120 seconds in 1 sec. increments.
Environmental Parameters
Temperature: 0°C to 50°C (32°F to 1 22°F) Humidity: 10 to 90%, non-condensing
Power Consumption
15 watts Max. at 120 VA, 50160 Hz
Voltage and Frequency
Universal power supply: 90 to 250 VAC, 48 to 62 Hz. 24 to 30 volts AC or DC, +/- 5%.
Noise Immunity
Common mode rejection (process input): >120 db. Normal mode rejection (process input): >80 db.
AC line is double filtered and transient protected. Snubbers are provided for each relay output.
Construction
Case: extruded, non-perforated black anodized
aluminum with ABS plastic sleeve. Bezel:
Black plastic ABS. Chassis assembly: plug-in type. Keys: Silicone rubber with diffusion printed graphics. NEMA rating: front panel conforms to NEMA 4X when instrument is properly installed.
Agency Approvals
Memory Retention
Lithium battery maintains all programming for approximately ten years.
Security
There are two levels of access: restricted and full. A configurable code is used to enter the full access level. Functions not available in the restricted level are configurable.
LISTED
Process Control Equipment
4N66
U
L
®
LR 84603
Page 35
How To Order
Order
Output 1: Control Code
Mechanical Relay (5 amp)
1
A
nalog (milliamp)
2
Solid State Relay (triac) (1 amp)
3
Output 2: Control, Alarm, or Retran
smissi
on
Mechanical Relay (5 amp)
1
A
nalog (milliamp)
2
Solid State Relay (triac) (1 amp)
3
Output 3: Control, Alarm, Retran
smission,
or Loop Power
Mechanical Relay (5 amp)
1
A
nalog (milliamp)
2
Solid State Relay (
tr
iac) (1 amp)
3
Loop Power
5
Output 4: Alarm, Retran
smission,
or Loop Power
Mechanical Relay (0.5 amp, 24 V)
1
A
nalog (milliamp)
2
Solid State Relay (triac) (0.5 amp, 24 V)
3
Loop Power
5
Option
s
Enter Ò0Ó if not desired
24 VAC/24 VDC Operatio
n
F
Remote Setpoint
B
Set of Five Digital Inputs
D
Certification
H
Five Digit
al Inputs and Certification
J
131VC -1
V
C
0
33
Page 36
VALVE RESPONSE TIME
DEVIATION BAND DEVIATION BAND
Faster
Slower
Higher
Lower
Dead Band
VALVE SENSITIVITY
SET-POINT
SOLENOID
CYCLE TIME
Feature in blue are user programmable
PROPORTIONAL
OUTPUT CIRCUIT NO.2
PROPORTIONAL
OUTPUT CIRCUIT NO.1
Valve Solenoid
"On" Time
SOLENOID
CYCLE TIME
100%
75%
50%
25%
0%
Full Programmable Control of Valve Sensitivity and Valve Response
Designed with duplex output circuits (one to control the valve opening solenoid and one to control the valve closing solenoid ). The 131VC-1 Electronic Control System can be programmed to maintain precise control of any process. Each output circuit has an independently programmable proportional band and solenoid cycle time. By adjusting these control algorithms in combina­tion, the response time can be varied over a wide range.
Proportional Band
The proportional band can be programmed from 1 to 999 per­cent of transmitter scale. Programming a narrow deviation band will result in faster valve response, whereas a wider band will result in slower response.
Proportional Response Time
The response time of the valve is proportional to how far the process variable is from the set-point. If there is only a small deviation, the solenoid “on-time” will be short and the valve will move slowly. For large deviations, the “on-time” will be longer and the valve speed will be faster.
Solenoid Cycle Time
The opening and closing solenoid pilots operate in “on-off” cycles. The cycle time is programmable to allow the valve to make a smooth transition to the set-point and avoid overshoot­ing.
Dual Output Circuits
The two output circuits can be programmed independently to respond at different rates. For example: fast response above the set-point; slow response below the set-point.
Set-Point Rate of Change
The controller has a ramping function that will further control valve speed of operation. This feature is especially useful in applications where valve speed is critical and pipeline surges are possible. When turned on, the set-point rate of change feature is operational under the following conditions:
On power up, the set-point will ramp from the process variable value to the set-point value at a specified rate.
On a transfer from manual to automatic control, the set­point will ramp from the process variable to the set-point value at a specified rate.
On any set-point change, the set-point will ramp from the current set-point to the new target set-point.
Programmable Control Features
Page 37
131-01 Valve
Pressure
Transmitter
Position Transmitter
131-01 Valve
131-01 Valve
Level
Transmitter
Position Transmitter
Flow
Transmitter
131-01 Valve
Pressure Control
Downstream pressure control is easily accomplished. The pres­sure transmitter range should be selected to provide the desired accuracy of pressure control. The set-point of the controller can be changed by the remote command signal or by manual adjust­ment at the controller panel. For pressure sustaining control, the transmitter is located upstream of the valve and the solenoid outs are reversed.
Flow Control
Flow control uses a flow transmitter in the configuration shown. The flow transmitter range should be selected to provide the desired accuracy of flow control. If desired, the transmitter may be located downstream of the valve, however, it should be a min­imum of five to nine diameters downstream of the valve.
Position Control
For applications requiring control of valve position, use the optional Cla-Val X117 Valve Position Transmitter. This provides the feedback signal to the controller. A computer or program­mable controller (PLC) may receive inputs from other sensors and output a position command signal for use in complex control applications.
Modulating Level Control
For modulating level control, the controller accepts the signal from the tank level transmitter as the remote set-point. This sig­nal is then compared with the signal generated by an optional X117 Valve Position Transmitter to adjust the valve proportion­ally to the range of the level transmitter.
Applications
Page 38
AC
POWER
131-01 Valve
AC
POWER
AC
Power
AUX
Power
131-01 Valve
AC
POWER
Maintain Valve Position
When there is a power failure, using the standard Model 131-01 Control Valve, the pilot control solenoids lock in the closed position and hold the main valve in the last control position.
Hydraulic Backup
A second hydraulic pilot system is arranged in parallel with the electronic system. On power failure, a third solenoid switches the control from electronic to the backup hydraulic system. The hydraulic system will then modulate the valve to maintain pre­set system conditions. Virtually any hydraulic system can be used.
Direct Voltage Electronic Control
Customer supplied battery power, with a continuous charging system, operates the valve solenoids and controller in the event of power failure.
Open or Close Valve
Adds a third solenoid control to the pilot system which either opens or closes the main valve on power failure.
Transmitter Signal Failure
The 131VC-1 Electronic Control System contains several indis­pensible sub-routines that protect the system if there is a trans­mitter signal failure. The controller has, as standard, terminals for a second transmitter and can be configured to automatically default to that transmitter. The controller can also be configured to cause the valve to remain in last control position, to open or close at an electronically controlled rate, or alarm to an auxiliary hydraulic pilot system.
Remote Communications Failure
The 131VC-1 Electronic Control System is the final link in the communications system at the valve site. In the event of a fail­ure, the controller will continues to function, maintaining the valve at the last set-point command or a pre-programmed set­point. It can also have a new set-point entered on the key pad by the Operator.
Power Failure Options
DC
POWER
POWER SUPPLY
Page 39
The Electronic Control System shall provide the interface between a remote computer system and the control valve. The controlled parame­ter signal shall be accepted through a 4-20 mA feedback signal. Local manual set-point control and full manual control of control valve sole­noids is to be provided on the controller panel for local control.
Upon receiving the set-point command signal from the remote computer system, the controller will signal the valve to move and maintain the valve at the desired set-point. A vacuum fluorescent display of current status and set-point value in scalable engineering units shall be sup­plied.
The controller shall compare set-point and feedback values and adjust the valve accordingly to achieve the set-point. When the feedback sig­nal deviates from the set-point value, the appropriate opening or closing solenoid on the control valve shall activate. As the feedback signal approaches the set-point, the solenoid output will pulse on and off to gradually return the measurement to set-point. One solid-state relay energizes for measurements condition below the set-point, while the other energizes for measurement, greater than set-point. These outputs shall be wired directly to or through intermediate relays to the opening and closing solenoids on the control valve. Solenoid output indicator lights shall illuminate when either the open or closed solenoid is activat­ed.
The total cycle time between each pulse shall be programmable between 1 and 120 seconds. The duration of each pulse shall be direct­ly proportional to the deviation from set-point outside of an adjustable deadband. The time proportioned outputs shall be independently adjustable for conditions above and below the set-point to properly tune valve response. The time proportional output band width shall be inde­pendently programmable between 1 and 999 percent of full scale. When the feedback signal returns within the deadband zone, the valve will maintain position. Provision shall be made to open/close/maintain posi­tion in the event of a loss of the feedback signal.
The operator interface shall consist of two rows of alphanumeric charac­ters to display numeric values and units. Color coded alarm, status and mode indicators shall inform the operator of operating conditions. Security key codes shall protect against undesired changes to the con­troller. All programming shall be menu driven.
The controller shall be all solid-state construction with the internal chas­sis capable of being removed for inspection and adjustment. All program memory, including set-points and tuning parameters, shall be protected by an internal lithium battery rated for 10 year life.
Remote communications shall be accepted through a 4-20 mA DC ana­log set-point signal.When remote operation is selected, the controller shall monitor the remote set-point signal. When local control is selected, the set-point shall be changed at the controller keypad.
When optional remote digital communications are provided, the con­troller shall be capable of direct linkage to a computer or other instru­mentation which has RS-232 or RS-485 communications. The Electronic Control System shall be the Cla-Val Model 131VC-1 as manufactured by Cla-Val, Newport Beach, CA.
Purchase Specifications
The electrical power used to energize the solenoid pilot system on the valve is routed through the 131VC-1 Electronic Control System. Because of practical limitations on wire size and distance, we recom­mend locating the controller near the valve itself.
Transmitter signals of 4-20 mA can travel great distances without difficul­ty, therefore, the controller does not need to be near the signal transmit­ter. For outdoor and high humidity indoor applications, we recommend installation in water-tight NEMA 4 enclosures.
Installation
Retrofitting CLA-VAL Control Valves
Existing hydraulically operated Cla-Val control valves can easily be con­verted to operate with the 131VC-1 Electronic Control System. The valve is modified by simply adding the Series 131 Solenoid Pilot System. The Series 131 Pilot System can be installed in parallel with the existing hydraulic pilot control for backup control in case of electrical power fail­ure. In this case, the hydraulic pilot system must be isolated from the valve by a third solenoid valve (see Power Failure Options above).
When the existing Cla-Val control valve performs a combination of control functions (such as pressure reducing and pressure sustaining), the 131VC-1 Electronic Control System will control the primary function of the valve. The other secondary functions will continue to be controlled by the hydraulic pilot controls. Consult Factory for details.
PO Box 1325 Newport Beach CA 92659-0325
Phone: 949-722-4800 Fax: 949-548-5441
C
LA-VAL
CLA-VAL CANADA CLA-VAL EUROPE
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040
Chemin dés Mesanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50
©COPYRIGHT CLA-VAL 2011 Printed in USA
Specifications subject to change without notice.
www.cla-val.com
E-131VC-1 (R-7/2011)
Represented By:
Page 40
1
2
3
4
5
3/8 NPT
2.06
2.72
Strainer
X43
Standard 60 mesh pilot system strainer for fluid service.
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
PL- X43 (R-3/2011)
PARTS LIST
ITEM DESCRIPTION MATERIAL
1
Pipe Plug Steel
2
Strainer Plug Brass
3
Gasket Copper
4
Screen SST
5
Body Brass
No parts available. Rreplacement assembly only.
Size Stock Number
3/8 x 3/8 33450J
Page 41
Cla-Val Product
Identification
Proper Identification
For ordering repair kits, replacement parts, or for inquiries concerning valve operation, it is important to properly identify Cla-Val products already in service by including all nameplate data with your inquiry. Pertinent product data includes valve function, size, material, pressure rating, end details, type of pilot controls used and control adjustment ranges.
Identification Plates
For product identification, cast-in body markings are supplemented by identification plates as illustrated on this page. The plates, depending on type and size of product, are mounted in the most practical position. It
is extremely important that these identification plates are not painted over, removed, or in any other way rendered illegible.
INLET EINTRITT ENTREE ENTRADA
SIZE & CAT NO.
STOCK NO.
CODE
MFD. BY CLA-VAL NEWPORT BEACH, CALIF, U.S.A.
RESERVOIR
END
I
N
L
E
T
I
N
L
E
T
SIZE & CAT NO.
STOCK NO.
FLOW
MFD. BY CLA-VAL NEWPORT BEACH, CALIF. U.S.A.
CODE
C
®
SIZE & CAT NO.
STOCK NO.
SPRING RANGE
MFD. BY CLA-VAL NEWPORT BEACH, CALIF. U.S.A.
SIZE & CAT NO.
STOCK NO.
CODE
MFD. BY CLA-VAL
NEWPORT BEACH, CALIF.
U.S.A.
C
®
DO NOT REMOVE
THIS VALVE HAS BEEN MODIFIED SINCE ORIGINAL SHIPMENT FROM FACTORY. WHEN ORDERING PARTS AND/ OR SERVICE SUPPLY DATA FROM THIS PLATE & ALL OTHER PLATES ON ORIGINAL VALVE.
REDUCED PRESSURE BACKFLOW PREVENTION DEVICE
STK. NO.
SER. NO.
CAT.
NO.
RP
-4
CLA-VAL
NEWPORT BEACH, CA.
This brass plate appears on valves sized 21/2" and larger
and is located on the top of the inlet flange.
These two brass plates appear on 3/8", 1/2", and 3/4" size
valves and are located on the valve cover.
These two brass plates appear on threaded valves
1" through 3" size or flanged valves 1" through 2".
It is located on only one side of the valve body.
This brass plate appears on altitude valves only and is
found on top of the outlet flange.
This brass plate is used to identify pilot control valves.
The adjustment range is stamped into the plate.
This tag is affixed to the cover of the pilot control valve.
The adjustment range appears in the spring range section.
This aluminum plate is included in pilot system
modification kits and is to be wired to the new pilot
control system after installation.
This brass plate is used on our backflow prevention
assemblies. It is located on the side of the Number Two
check (2" through 10"). The serial number of the
assembly is also stamped on the top of the inlet flange of
the Number One check.
How to Order
Page 42
HOW TO ORDER
Because of the vast number of possible configurations and combinations available, many valves and controls are not shown in published product and price lists. For ordering information, price and availability on product that are not listed, please contact your local Cla-Val office or our factory office located at:
SPECIFY WHEN ORDERING
• Model Number • Valve Size
• Globe or Angle Pattern • Threaded or Flanged
• Adjustment Range • Body and Trim Materials (As Applicable) • Optional Features
• Pressure Class
UNLESS OTHERWISE SPECIFIED
• Globe or angle pattern are the same price
• Ductile iron body and bronze trim are standard
• X46 Flow Clean Strainer or X43 “Y” Strainer are included
• CK2 Isolation Valves are included in price on 4" and larger valve sizes (6" and larger on 600 Series)
P. O. Box 1325
Newport Beach, California 92659-0325
(949) 722-4800
FAX (949) 548-5441
LIMITED WARRANTY
Automatic valves and controls as manufactured by Cla-Val are warranted for three years from date of shipment against manufacturing defects in material and workmanship that develop in the service for which they are designed, provided the products are installed and used in accordance with all applicable instructions and limitations issued by Cla-Val. Electronic components manufactured by Cla-Val are warranted for one year from the date of shipment.
We will repair or replace defective material, free of charge, that is returned to our factory, transportation charges prepaid, if upon inspection, the material is found to have been defective at time of original shipment. This warranty is expressly conditioned on the purchaser’s providing written notification to Cla-Val immediate upon discovery of the defect.
Components used by Cla-Val but manufactured by others, are warranted only to the extent of that manufacturer’s guarantee.
This warranty shall not apply if the product has been altered or repaired by others, Cla-Val shall make no allowance or credit for such repairs or alterations unless authorized in writing by Cla-Val.
DISCLAIMER OF WARRANTIES AND LIMITATIONS OF LIABILITY
The foregoing warranty is exclusive and in lieu of all other warranties and representations, whether expressed, implied, oral or written, including but not limited to any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.
Cla-Val shall not be liable for any incidental or consequential loss, damage or expense arising directly or indirectly from the use of the product. Cla-Val shall not be liable for any damages or charges for labor or expense in making repairs or adjustments to the product. Cla-Val shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data and services. No representative of Cla-Val may change any of the foregoing or assume any additional liability or responsibility in connection with the product. The liability of Cla-Val is limited to material replacements F.O.B. Newport Beach, California.
TERMS OF SALE
ACCEPTANCE OF ORDERS
All orders are subject to acceptance by our main office at Newport Beach, California.
CREDIT TERMS
Credit terms are net thirty (30) days from date of invoice.
PURCHASE ORDER FORMS
Orders submitted on customer’s own purchase order forms will be accepted only with the express understanding that no statements, clauses, or conditions contained in said order form will be binding on the Seller if they in any way modify the Seller’s own terms and conditions of sales.
PRODUCT CHANGES
The right is reserved to make changes in pattern, design or materials when deemed necessary, without prior notice.
PRICES
All prices are F.O.B. Newport Beach, California unless expressly stated otherwise on our acknowledgement of the order. Prices are subject to change without notice. The prices at which any order is accepted are subject to adjustment to the Seller’s price in effect at the time of shipment. Prices do not include sales, excise, municipal, state or any other Government taxes. Minimum order charge $100.00.
RESPONSIBILITY
We will not be responsible for delays resulting from strikes, accidents, negligence of carriers, or other causes beyond our control. Also, we will not be liable for any unauthorized product alterations or charges accruing there from.
RISK
All goods are shipped at the risk of the purchaser after they have been delivered by us to the carrier. Claims for error, shortages, etc., must be made upon receipt of goods.
EXPORT SHIPMENTS
Export shipments are subject to an additional charge for export packing.
RETURNED GOODS
1. Customers must obtain written approval from Cla-Val prior to returning any material.
2. Cla-Val reserves the right to refuse the return of any products.
3. Products more than six (6) months old cannot be returned for credit.
4. Specially produced, non-standard models cannot be returned for credit.
5. Rubber goods such as diaphragms, discs, o-rings, etc., cannot be returned for credit, unless as part of an unopened vacuum sealed repair kit which is less than six months old.
6. Goods authorized for return are subject to a 35% ($100 minimum) restocking charge and a service charge for inspection, reconditioning, replacement of rubber parts, retesting, repainting and repackaging as required.
7. Authorized returned goods must be packaged and shipped prepaid to Cla-Val, 1701 Placentia Avenue, Costa Mesa, California 92627.
PO Box 1325 Newport Beach CA 92659-0325
Phone: 949-722-4800 Fax: 949-548-5441
C
LA-VAL
CLA-VAL CANADA CLA-VAL EUROPE
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040
Chemin dés Mesanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50
©COPYRIGHT CLA-VAL 2011 Printed in USA
Specifications subject to change without notice.
www.cla-val.com
E-Product I.D. (R-3/2011)
Represented By:
Page 43
Complete Replacement Diaphragm Assemblies for 100-01 and 100-20 Hytrol Main Valves
For:
Hytrol Main Valves with Ductile Iron, Bronze Trim Materials—125/150 Pressure Class Only. FACTORY ASSEMBLED Includes: Stem, Disc Guide, Disc, Disc Retainer, Spacer Washers, Diaphragm, Diaphragm Washer and Stem Nut.
3/8"
1/2" - 3/4"
1"
1 1/4"-1 1/2"
2"
2 1/2"
3" 4"
(Also 81-01 ) (Also 81-01 )
N/A N/A N/A N/A N/A N/A
C2524B
C2525J
6"
8" 10" 12" 14" 16" 20" 24"
40456G 45276D
81752J
85533J 89067D 89068B
N/A N/A
33273E 40456G 45276D
81752J
N/A
85533J 89068B 89068B
Valve
Size
Valve
Size
49097K C2518D C2520K C2522 F C2524B C2523D
C2525J
33273E
100-01 100-20
Diaphragm Assembly
Stock Number
100-01 100-20
Diaphragm Assembly
Stock Number
3/8"
1/2" - 3/4"
1"
1 1/4" - 1 1/2"
2"
2 1/2"
3" 4" 6"
8" 10" 12" 14" 16" 20" 24"
(Also 81-01 ) (Also 81-01 )
N/A N/A N/A N/A N/A N/A
9169805A
9169812G
9169813E 9169815K 9817901D 9817902B
N/A 9817903K 9817905E 9817905E
3/8"
1/2" - 3/4"
1"
1 1/4” - 1 1/2"
2"
2 1/2"
3" 4" 6" 8"
9169806J 9169807G 9169808E 9169809C 9169810A
9169817F 9169818D 9169819B 9169820K 9169834A
N/A N/A N/A N/A N/A
N/A 9169810A 9169818D 9169819B 9169820K
Valve
Size
Valve
Size
9169801K 9169802H 9169803F 9169804D 9169805A 9169811J 9169812G 9169813E 9169815K 9817901D 9817902B 9817903K 9817904H 9817905E
N/A
9817906C
100-01 100-20
Repair Kit
Stock Number
100-01 100-20
Repair Kit
Stock Number
Repair Kits for 100-01/100-20 Hytrol Valves
For:
Hytrol Main Valves—125/150 Pressure Class Only.
Includes: Diaphragm, Disc (or Disc Assembly) and spare Spacer Washers.
(Also 81-01 ) (Also 81-01 )
REPAIR KITS
When ordering, please give complete nameplate data of the valve and/or control being repaired.
MINIMUM ORDER CHARGE APPLIES.
Buna-N®Standard Material
Viton (For KB Valves)
MODEL
INSTALLATION / OPERATION / MAINTENANCE
Page 44
Repair Kits for 100-04/100-23 Hy-Check Main Valves
For:
Hy-Check Main Valves—125/150 Pressure Class Only
Includes: Diaphragm, Disc and O-Rings and full set of spare Spacer Washers.
Larger Sizes: Consult Factory.
Repair Kits for 100-02/100-21 Powertrol and 100-03/100-22 Powercheck Main Valves
For:
Powertrol and Powercheck Main Valves—125/150 Pressure Class Only
Includes: Diaphragm, Disc (or Disc Assembly) and O-rings and full set of spare Spacer Washers.
Repair Kits for Pilot Control Valves (In Standard Materials Only)
Includes: Diaphragm, Disc (or Disc Assembly), O-Rings, Gaskets or spare Screws as appropriate.
Repair Assemblies (In Standard Materials Only)
CLA-VAL
Copyright Cla-Val 2011 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
N-RK (R-3/2011)
Valve
Size
Kit Stock Number
100-02
Valve
Size
Kit Stock Number
100-02 & 100-03 100-21 & 100-22
3
8
9169901H
2
1
2
9169910J N/A
1
2&3⁄4
9169902F
3”
9169911G 9169905J
1” 9169903D
4”
9169912E 9169911G
1
1
4&11⁄2
9169904B
6”
9169913C 9169912E
2” 9169905J
8”
99116G 9169913C
10”
9169939H 99116G
12"
9169937B 9169939H
Valve
Size
Kit Stock Number
Valve
Size
Kit Stock Number
100-04 100-23 100-04 100-23
4” 20210901B N/A 12” 20210905H 20210904J 6” 20210902A 20210901B 14” 20210906G N/A 8” 20210903K 20210902A 16” 20210907F 20210905H
10” 20210904J 20210903K 20” N/A 20210907F
24” N/A 20210907F
BUNA-N
®
(Standard Material)
VITON (For KB Controls)
Pilot
Control
Kit
Stock
Number
Pilot
Control
Kit
Stock
Number
Pilot
Control
Kit
Stock
Number
CDB 9170006C CFM-7 1263901K CDB-KB 9170012A CDB-30 9170023H CFM-7A 1263901K CRA-KB N/A CDB-31 9170024F CFM-9 12223E
CRD-KB (w/bucking spring)
9170008J
CDB-7 9170017K
CRA (w/bucking spring)
9170001D CRL-KB 9170013J
CDH-2 18225D
CRD (w/bucking spring)
9170002B CDHS-2BKB 9170010E
CDHS-2 44607A
CRD (no bucking spring)
9170003K CDHS-2FKB 9170011C CDHS-2B 9170004H CRD-18 20275401K CDHS-18KB (no bucking spring) 9170009G CDHS-2F 9170005E CRD-22 98923G
102C-KB
1726202D CDHS-3C-A2 24657K CRL (55F, 55L) 9170007A CDHS-8A 2666901A CRL-4A 43413E CDHS-18 9170003K CRL-5 (55B) 65755B CDS-4 9170014G CRL-5A (55G) 20666E CDS-5 14200A CRL-18 20309801C CDS-6 20119301A CV 9170019F
Buna-N
®
CDS-6A 20349401C X105L (O-ring) 00951E CFCM-M1 1222301C 102B-1 1502201F CRD Disc Ret. (Solid) C5256H CFM-2 12223E 102C-2 1726201F CRD Disc Ret. (Spring) C5255K
102C-3 1726201F
Control Description Stock Number
CF1-C1 Pilot Assembly Only 89541H CF1-Cl Complete Float Control less Ball and Rod 89016A CFC2-C1 Disc, Distributor and Seals 2674701E CSM 11-A2-2 Mechanical Parts Assembly 97544B CSM 11-A2-2 Pilot Assembly Only 18053K 33A 1" Complete Internal Assembly and Seal 2036030B 33A 2" Complete Internal Assembly and Seal 2040830J
When ordering, please give complete nameplate data of the valve and/or control being repaired. MINIMUM ORDER CHARGE APPLIES
Larger Sizes: Consult Factory.
Loading...