Class1 Digital Flow Meter User Manual

Engineering Standards
Name Identifier
Digital Flowmeter Information
Display Installation
The flowmeter display mounts in a 2.84” by 1.51” cutout. Overall area necessary for installation is 2.5” by 3.2”. Two 0.201 diameter holes are provided for mounting scre ws.
0.496"
0.612"
3.125"
0.142"
0.142"
Engineering Standard Number
C1-102046-A
0.285" 3.832"
0.182"0.182"
1.510
.277
2.840"
Ø 0.201" (2) HOLES
.470 1.900
page 1 of 9 pages
Engineering Standards
Name Identifier
Digital Flowmeter Information
Saddle Clamp Installation
The Saddle clamp should be mounted on the pump discharge pipe in an area of lami­nar flow. Select a location with as long a straight run as possible. Avoid mounting immediately after an elbow, gate or increase in pipe size (Any thing that would cause turbulence). Allow a straight run of at least 6 pipe diameters after an elbow. Cut a 1.5 diameter hole in the top side of the waterwa y. Position the saddleclamp on the pipe with the indexing hole f acing the pump . Tighten the nuts on the “U” bolt evenly to 30 ft/lbs.
Paddlewheel
Install the paddlewheel adapter (spacer) to the mount using four 7/16 screws. Lubricate the O-rings on the paddlewheel and insert it into the mount . Secure the transmitter with the 4 screws provided.
The Class1 Digital Flowmeter measures water velocity in the pipe to calculate the flow rate. The location of the paddlewheel transmitter is important for proper opera­tion and accurate readings. Mount the transmitter in a location that is accessible for future maintenance and in an area where laminar (non-turbulent) flow is most likely to be maintained. Most problems with flowmeter accuracy and performance can be traced to the location of the transmitter.
The hole size for the paddlewheel transmitter PN102714 mount is 1-1/2”.
Engineering Standard Number
C1-102046-A
Transmitter Location
Elbows/Bends A straight run of pipe to the transmitter of at least six (6) times the pipe diameter after an elbow or other turbulence producing item is desirable for a successful installation. Try to locate the transmitter using the longest straight section of pipe available. Minimal turbulence at the transmitter provides the most accurate reading.
Valves/Gates If the transmitter is downstream of a valve, the minimum dis tance is fifteen (15) times the pipe diameter. Whenever possible, mount the transmitter before a valve.
Horizontal Pipes The transmitter will work in any position, however when mounted on a horizontal run, it should be mounted in the top half of the pipe to allow debris to be flushed out of the paddlewheel.
page 2 of 9 pages
Engineering Standards
Name Identifier
Digital Flowmeter Information
Engineering Standard Number
C1-102046-A
Increase/Decrease in pipe size The transmitter can be placed after an increase in pipe diameter, never after a decrease.
Class1
flexible hose can greatly assist in reducing the number of elbows and amount of
turbulence between the pump and discharge pipe.
Wiring
The Flowminder system comes with a wiring harness that connects the transmitter to the display. The OEM must supply power and ground to the digital display. Consideration should be given to the conditions under which the display will have power. The display is internally protected against short circuits, overvoltage and reverse polarity, but standard installation procedures should provide for circuit protection. Maximum current used by the flowmeter is 1.5 Amps.
A momentary grounding switch can be added when the totalizer function is desired. This is connected to the display through the 8 pin mini-connector at pin 8.
Electrical
The Flowmeter Display is connected to the OEM harness with a Deutsch 8 pin mini-connector.
Mating Connector: DTM06-08S Locking Wedge WM-8S Mating Terminal: 0462-201-20141 20 gauge socket
Terminal Assignments: 1 N/C (no connection)
Connection to the vehicle is simply a matter of connecting the RED power wire to a good 12 VDC voltage source and connecting the BLACK ground wire to a good system ground.
8 7 6 5
Wire Insertion View
1 2 3 4
2 N/C 3 N/C 4 Display Power (Ignition 12 VDC) 5 System Ground 6 N/C 7 Pulses IN (paddlewheel input) 8 Switch input (Totalizer)
page 3 of 9 pages
Engineering Standards
Name Identifier
Operation
The flowmeter displays the current flo w rate whenever the displa y has power and the discharge is open. Range is 0 to 9995 GPM, LPM or IGPM as calibrated.
Totalizer
The display includes a totalizer function that displa ys the total amount of water that has been flowed since the unit was turned on. This feature is enab led by grounding terminal number eight (8) of the display connector . While terminal number 8 is grounded, activating the left switch resets the totalizer to zero (0). The totalizer resets to zero whenev er power is remo ved from the displa y. Multiply the reading on the display b y 100 (add two zeroes) for total flo w .
Digital Flowmeter Information
Engineering Standard Number
C1-102046-A
page 4 of 9 pages
Engineering Standards
Name Identifier
Digital Flowmeter Information
5. Calibration
Flowmeter Calibration is performed with the discharge stabilized at the desired calibra­tion flow. (Smoothbore nozzle and Pitot gauge) The calibration mode is entered by the use of a password”. There are two magnetic switches located at the low er corners of the display. These switches are activated with the use of a magnet, switch activation is visually confirmed by the lighting of the closest decimal point on the display. Enter the switch sequence below to enter calibration mode.
Engineering Standard Number
C1-102046-A
3.125"
2.462"
Location of magnetic switches
Left Switch Left Switch Left Switch Right Switch Right Switch Right switch
If the password is correctly entered,
0 0
by
0
”.
0 0
Hold the magnet on the right switch until the display reads the Gallons per Minute (GPM), Liters per Minute (LPM) or Imperial Gallons per Minute (IGPM) that you are flowing. The speed with which the display increments/decrements the calibration flow display increases as the switch is held. If you pass the flow value, release the switch and reactivate. The display will reverse direction each time the switch is activated and the speed will start out at the slowest rate. Maintain the calibration flow f or a mini­mum of 10 seconds to assure an accurate and stable calibration before activating the left switch. When the flow is stable and the calibration flow r ate is entered into the display, activate the left s witch to complete calibration.
The display will read Calibration is now complete.
6. Operation
The Flowminder will display the current flowrate whenever the display is enabled and the discharge is open. Range is 0 to 9990 GPM, LPM or IGPM.
LEFT LEFT LEFT RIGHT RIGHT RIGHT
Cal Cal
Cal
will be displayed for 1/2 second followed
Cal Cal
donE donE
donE
donE donE
followed by the current flow rate in GPM.
page 5 of 9 pages
Engineering Standards
Name Identifier
Class1 Class1
The
Class1 digital flowmeter system comes
Class1 Class1
Digital Flowmeter Information
with the digital display, a paddlewheel trans­mitter and a connecting harness (specify length). A method of mounting the trans­mitter to the discharge is needed, call for options and specify the pipe diameter.
Paddlewheel Installation
Power and Ground
Engineering Standard Number
C1-102046-A
The flow display includes a totalizer func­tion. A momentary switch (optional) is re­quired to operate this feature. The display will continuously monitor flow when the unit has power and display the latest total vol­ume when the totalizer switch is pressed. The total flow is cleared when power is re­moved from the unit.
FLOW METER
6-32x7/16 Lockwasher
O-ring
6-32x7/16internal hex
Spacer
Indexing Pin
White (Signal)
Black (System Ground)
8 7 6 5
C:\MANUALS\DIGITAL\FMINDER\FMINDSER.PM6_071597
1
DTM06-08S
2
Wire Insertion View
3 4
Red (System Power)
page 6 of 9 pages
Engineering
4.380
.683
2.750
.037
R.370
5.000"
3.750"
3.564"
R 1.325"
Standards
Name Identifier
should be given to cutting out the panel and mounting this system before using the bezel.
The panel cutout is a little more difficult than just mounting a gauge and a display and some planning
A stainless steel bezel is available that can have insets color coded to identify the associated discharge.
Digital Flowmeter Information
information on both flow and pressure for the discharge.
The Value Series flowmeter uses the digital display and a 2-1/2” pressure gauge to give the pump operator
Engineering Standard Number
C1-102046-A
page 7 of 9 pages
Engineering Standards
Name Identifier
Digital Flowmeter Information
Engineering Standard Number
C1-102046-A
The flowmeter Super System is designed using the digital flowmeter and the digital pres­sure gauge. Each piece uses the standard digital display cutout. The only additional consideration from the standard flowmeter is for mounting the pressure transducer. This should generally be mounted after the valve and is a 1/4 NPT fitting. Use only the 1-1/4” hex to tighten the transducer, not the body of the sensor. Follow the calibration proce­dure for pressure and flow as appropriate after installation.
FLOW METER
PUMP DISCHARGE
page 8 of 9 pages
Engineering Standards
Name Identifier
Digital Flowmeter Information
Engineering Standard Number
C1-102046-A
Enhance your Flowminder Installation
The Digital Flow Display is also available in a plain black wrapper that will install into an existing conventional Flowminder cutout on the pump panel.
Call
Class1
at 1-800-533-3569 and ask for details.
page 9 of 9 pages
Loading...