Digital displays come in both seven (7) segment bright LED displays for alphanumeric
information and bargraph displays f or percentage information.
Currently available displa ys:
102046Flowmeter
102190Pump Pressure (Intake and Discharge)
102245T ank Le vel Gauge (Water and F oam)
102245Pressurized Tank Level (0 to 100 %)
102007Speedometer
102342Aerial Loading
102263Breathing Air Lev el (0 to 100 %)
102264Oxygen System Level (0 to 100 %)
103282Dual Current Amplifier for dual displa ys
(air, O2 and Aerial Loading)
0 25 50 75 100
LOW LEVEL LOADING
0 25 50 75 100
% AIR REMAINING
TEST
ALARM SILENCE
0 25 50 75 100
WATER LEVEL
0 25 50 75 100
% OXYGEN REMAINING
TEST
ALARM SILENCE
SPEEDOMETER
PUMP INTAKE
FLOWMETER
TOTALIZER
PUMP DISCHARGE
2
Mounting
The
Class1
Overall area necessary for installation is 2.5” by 3.2”.
Two 0.20 diameter holes are pro vided for mounting screws .
1.510
.277
digital display mounts in a 2.85” by 1.55” cutout.
2.840"
Ø 0.201"
(2) HOLES
.4701.900
3.125"
DIGITAL DISPLAY
2.462"
0.285"3.832"
3
Harness
The digital displays are connected to the OEM harness with a Deutsch 8 pin miniconnector .
Mating Connector:DTM 06-08S
Locking WedgeWM-8S
Mating T erminal:0462-201-2014120 gauge socket
General T erminal Assignments:
1)Alarm Output (Ground)
8
7
6
5
Wire Insertion View
1
2
3
4
2)Primary Pressure Signal
3)Sensor Supply (+ 5 or +10 VDC)
4)System P ower (+ 12 VDC)
5)System Ground
6)Sensor Ground
7)Signal (frequency or secondary PSI in)
8)Test, Total or Alarm Switch (Ground)
Not all of the digital displays use all of the terminals.
See individual display pages for application specific inf ormation.
Harnesses are available for the digital displa ys in v arious lengths.
These include transmitter/transducer and power connections.
Breathing Air Display102670102671102672
Oxygen System Display “ “ “
Tank Level Display102193102194102195102729
Dual T ransducer102439Y102455
Speedometer102242102243102244
DC Voltmeter“ ““
Dual Display “Y”102294102295
Dual Current Amplifier103318
Display Pigtail102272Extension 15’103367
4
Cal. Overview
Location of Magnetic Switches
Digital Display Calibration should be performed to assure accuracy.
The calibration mode is entered by the use of a “password”.
There are two magnetic switches, one located at each side of the display.
These switches are activated with the use of a magnet.
Switch activation is visually confirmed by the lighting of the closest decimal point on
the display to the switch.
Display Calibration sequence for Gauges with 7 segment LED’s
A password will look like the following example.
L L L R R R
Enter the switch sequence with a magnet to enter the basic calibration mode.
Left Switch Left Switch Left Switch Right Switch Right Switch Right Switch
If the password is correctly entered,
ber that is dependent on the display being calibrated (usually 0 ). If necessary, the calibration
number can be changed using the switch on the right side.
CAL
will be displayed for 1/2 second followed by a num-
Establish accurate and stable conditions f or calibration.
When the calibration conditions are stable, activ ate the left switch.
The display will read
and then return to normal operation.
donE
5
Cal. Overview
Location of magnetic switches
0 25 50 75 100
BAR GRAPH DISPLAY
Display Calibration for Gauges with bargraph displays
The calibration mode is entered by the use of a “password”.
There are two magnetic switches, one located at each side of the display.
These switches are activated with the use of a magnet.
Switch activation is visually confirmed by the toggling of the four closest bars on the
display to the switch. If they are on they will turn off, if they are off they will turn on.
A password will look like the following example.
L L L R R R
Enter the switch sequence with a magnet to enter the basic calibration mode.
Left SwitchLeft SwitchLeft SwitchRight SwitchRight SwitchRight Switch
If the password is correctly entered, the left-most bar will turn on and flash. This indicates that
the display is ready to be calibrated for the low set point.
With the system adjusted to the minimum calibration point (the system should be empty or at
the lowest pressure condition) activate the left switch and then the right switch.
The right-most bar will begin to flash, indicating the display is ready for the high set point
calibration.
Adjust the system to it’s maximum operating condition. Activate the right switch followed by
the left switch.
The display will return to normal operation and indicate current system status as a percentage
of maximum calibrated capacity.
6
Flowmeter
The
Class1
comes with the digital display, a paddlewheel transmitter and a connecting harness (specify length). Mounting the transmitter to the discharge can be done with a
saddle clamp, a welded boss or a valve
adapter. Call f or options and specify pipe
diameter.
digital flowmeter system
Paddlewheel Installation
The flow display includes a totaliz er function. A momentary switch (optional) is required to operate this feature . The display
will continuously monitor flow when the
unit has power and display the latest total
volume when the totalizer switch is
pressed. The total flow is cleared when
power is removed from the unit.
FLOW METER
6-32x7/16
Lockwasher
O-ring
6-32x7/16internal hex
Spacer
Indexing Pin
White (Signal)
Black (System Ground)
8
7
6
5
1
2
3
4
Red (System Power)
DTM06-08S
Wire Insertion View
7
FlowmeterFlowmeter
Flowmeter
FlowmeterFlowmeter
Installation
The
Class1
the flow rate. The location of the paddlewheel transmitter is important for proper
operation and accurate readings. Mount the transmitter in a location that is accessible for future maintenance and in an area where laminar (non-turb ulent) flow is
most likely to be maintained. Most problems with flowmeter accuracy and perf ormance can be traced to the location of the transmitter .
The hole size for the paddlewheel transmitter (PN102714) mount is 1-1/2”.
The hole size for the paddle wheel transmitter (PN101199) mount is 1-7/8”.
T ransmitter Location
Elbows/BendsA straight run of pipe to the transmitter of at least six (6) times
the pipe diameter after an elbow or other turbulence producing item is desirable
for a successful installation. T ry to locate the transmitter using the longest straight
section of pipe available. Minimal turbulence at the transmitter provides the most
accurate reading.
Valves/GatesIf the transmitter is downstream of a valve, the minimum distance is fifteen (15) times the pipe diameter. Whenev er possible, mount the
transmitter before a v alve .
Digital Flowmeter measures water velocity in the pipe to calculate
Horizontal PipesThe transmitter will work in any position, howe ver when mounted
on a horizontal run, it should be mounted in the top half of the pipe to allow debris
to be flushed out of the paddlewheel.
Increase/Decrease in pipe size The transmitter can be placed after an increase
in pipe diameter, ne ver after a decrease.
Class1
turbulence between the pump and discharge pipe.
Wiring
The Flowmeter system comes with a wiring harness that connects the transmitter to the display.
The OEM must supply power and ground to the digital displa y . Consideration
should be given to the conditions under which the displa y will have pow er.
The display is internally protected against short circuits, overvoltage and reverse
polarity , but standard installation procedures should provide f or circuit protection.
Maximum current used by the flowmeter is 1.5 Amps.
flexible hose can greatly assist in reducing the number of elbo ws and amount of
A momentary grounding switch can be added when the totalizer function is desired. This is connected to the display through the 8 pin mini-connector at pin 8.
8
Operation
The flowmeter displays the current flo w rate whenever the displa y has power and
the discharge is open. Range is 0 to 9995 GPM, LPM or IGPM as calibrated.
Totalizer
The display includes a totalizer function that displa ys the total amount of water
that has been flowed since the unit was turned on. This feature is enabled b y
grounding terminal number eight (8) of the display connector .
When in the totalizer mode, all decimal points will flash to indicate this mode.
While terminal number 8 is grounded, activating the left switch resets the totalizer
to zero (0).
The totalizer resets to zero whene ver pow er is removed from the displa y.
Multiply the reading on the display b y 100 (add two zeroes) for total flow.
FlowmeterFlowmeter
Flowmeter
FlowmeterFlowmeter
9
Calibration
Calibration matches the display to the paddlewheel tr ansmitter installation and
signal for a given flo w rate.
A method of accurately determining flow should be used to calibrate the unit.
A smoothbore nozzle and a Pitot gauge is suitable.
Flowmeter calibration must be perf ormed with the discharge flow stabilized at the
desired calibration flow rate.
Establish and maintain the calibration flow rate f or a minimum of 10 seconds to
assure an accurate and stable reading. When the flow is stab le, enter the
flowmeter calibration mode.
The calibration mode passw ord for the flowmeter isL L L R R R.
Switches are located at each side of the display.
These switches are activ ated with the use of a magnet.
Switch activation is visually confirmed by the lighting of the closest decimal point
on the display.
Enter the switch sequence below to enter calibr ation mode.
Calibration
L
eft Left Left Right Right Right
LEFT SWITCHLEFT SWITCHLEFT SWITCHRIGHT SWITCHRIGHT SWITCHRIGHT SWITCH
If the password is correctly entered,
follow ed b y
Using the right switch on the display, enter the flow rate you intend to calibrate. If
the department will use a standard flow for the discharge, use that figure for
calibration.
The speed that the display increments/decrements increases the longer that the
switch is held. If y ou pass the flow calibration n umber , “release” the s witch and
reactivate it. The display will “reverse direction” each time the switch is activ ated
and the speed will start out at the slowest rate.
When the number on the display matches the discharge flo w rate, check the Pitot
for the desired pressure and then activate the left s witch to complete calibration.
The display will read
0
.
donE
and then return to normal operation.
CAL
will be displayed for 1/2 second
10
Calibration is now complete.
Example CAL
Example Calibration (4”)
Install a Pitot gauge and a two inch (2”) smoothbore nozzle on the deck gun.
Determine the flow rate that you want to use.(70 PSI=994 GPM).
Start pumping water through the deck gun until the Pitot gauge reads 70 PSI.
Enter the calibration mode by bringing a magnet close to the left side of the display and
removing it three (3) times, the left decimal point should light with each s witch closure.
Bring a magnet close to the right side of the display and remove it three (3) times, the
right decimal point should light with each switch closure.
The display should read
Bring the magnet close to the right side of the display and hold it, the display number
should increase. When the displa y reads
If you stop short of
bring it close again for the display to increase. If you pass
close to the right side and hold it until the number decreases to
994
CAL
for 1/2 second and then
994
, move the magnet aw ay from the displa y .
, you must bring the magnet close to the right side, remove it and
0
994
, just bring the magnet
994
When the flow has been stable at 70 PSI for at least 10 seconds , move the magnet close
to the left side of the display and remov e it.
The display should read
Adjust the flow so that the Pitot reads 50, the display should read
Adjust the flow so that the Pitot reads 110, the display should show
All readings should be within +- 3 % of the 120 PSI value. (+-40 GPM f or a 2” nozzle)
Use a Pitot nozzle flow chart to select a calibration setting. Ideally it should be a v alue
close to the average r ate expected from the discharge.
Check your calibration with flow values that are lower and higher than the calibration
flow but within normal flow rates f or the discharge.
donE
for se veral seconds and then displa y
994
840
1245
Note:
There is a default calibration setting f or 2”, 2.5”, 3”, 4” and 5” schedule 80 pipes.
Pass word to enter default calibration:
L R R R L L L
Scroll through the pipe sizes with the right switch and select with the left switch.
The defaults will only work with schedule 80 pipe.
11
Value Flow
4.380
.683
2.750
.037
5.000"
3.750"
3.564"
R 1.325"
should be given to cutting out the panel and mounting this system if you plan to use the bezel.
The panel cutout is a little more difficult than just mounting a gauge and a display and some planning
The Value Series flowmeter uses the digital displa y and a 2-1/2” or 3-1/2” pressure gauge to giv
A stainless steel bezel is available that can have insets color coded to identify the associated discharge.
operator information on both flow and pressure f or the discharge.
e the pump
12
Super Flow
The flowmeter Super System is designed using the digital flowmeter and the digital
pressure gauge. Each piece uses the standard digital display cutout. The only additional
consideration from the standard flowmeter is f or mounting the pressure transducer. This
should generally be mounted after the valve and is a 1/4 NPT fitting. Use only the 1-1/4”
hex to tighten the transducer, not the body of the sensor. Follo w the calibration procedure for pressure and flow as appropriate after installation.
FLOW METER
PUMP DISCHARGE
13
Vehicle Speed
SPEEDOMETER
The Speedometer Display is connected to the OEM harness with a Deutsch 8 pin
mini-connector.
Mating Connector:DTM06-08S
Locking WedgeWM-8S
Mating T erminal:0462-201-2014120 gauge socket
A usable Pulses In signal is available on the World Transmission wire #157 at the
Vehicle Interface Module connection H-2.
Vehicle Speed
Calibration
Digital Speedometer calibration is performed with the vehicle speed stabilized at 40 M.P.H.
or (40 K.P.H. )
The calibration mode is entered by the use of a “password”.
There are two magnetic switches, one located at each side of the display.
These switches are activated with the use of a magnet. Switch activation is visually
confirmed by the lighting of the closest decimal point on the display.
Enter the switch sequence below to enter calibration mode.
L L L R R R
Left SwitchLeft SwitchLeft SwitchRight SwitchRight SwitchRight Switch
If the password is correctly entered, “
Maintain a constant speed of 40 for a minimum of 10 seconds to assure an accurate and
stable calibration before activating the left switch.
Activate the left switch.
The display will read “
donE
”
and return to normal operation showing the current speed.
The pressure transducer (PN 102161) mounts to the pump with a 1/4” NPT fitting. Mount
the pressure transducer on the pump discharge manifold and tighten using the 1-1/4 he x.
Mount the digital display on the pump panel using the dimensions provided.
Connect the wiring harness PN 102035, 102060, or 102061 to the transducer, the display
and to the vehicle power and ground circuits.
8
7
6
5
Wire Insertion View
1
2
3
4
PUMP DISCHARGE
Operation is straightforward.
When the unit is turned on, the display indicates pump pressure at the transducer location. Normally no calibration is required, however if the gauge
does not read zero when the pump is not running, a ZERO calibration can be
performed. Password L R R L L.
This feature works only on displays that read rP1.7 and above at power on.
Harness PN 102060 5’
102035 10’
102061 20’
PINCOLOR FUNCTION
ABLACK SENSOR GROUND
BRED SENSOR SUPPLY
CWHITE SENSOR SIGNAL
PIN COLOR FUNCTION
1 PLUG
2 WHITESIGNAL
3 REDSENSOR SUPPLY
4 REDPOWER IN
5 BLACKGROUND IN
6 BLACKSENSOR GROUND
7 PLUG
8 PLUG
Red +12 VDC
Black Ground
16
Aerial Loading
0 25 50 75 100
LOW LEVEL LOADING
The
Class1
dangerous loading conditions when an aerial device is operated at low angles
of elevation. Live loads (factors that increase this load such as ice, occupants on the ladder, water load, extra equipment, etc.) are instantly taken into
account by the system and displayed to the operator.
The display presents load information in an easy to interpret LED bargraph
display as a percentage of maximum calibrated load and includes visual and
aural warnings.
When the aerial load approaches the maximum load (approx. 80%), 18-20
bars will be illuminated on the display. When the load is increased to 90%100%, the display will begin to flash, when the maximum load is exceeded by
50-100 pounds, an audible alarm output is activated in addition to the visual
warning to notify the operator of a potentially hazardous condition.
Aerial Loading Display is designed to warn aerial operators of
NOTE: THEDISPLAYPROVIDESAWARNINGONLYANDCANNO T
PREVENT
ATIP-OVER. THEAERIALDEVICEMUSTBEOPERA TED
STRICT ACCORDANCEWITHTHEMANUFACTURER’SINSTRUC-
IN
TIONSANDOPERATORSMUSTBETHOROUGHLYTRAINED.
17
Single transducer installation:
The transducer (PN 102606) must be installed in the pressure feed line to the
actuating cylinder(s) or where it can sense the hydraulic pressure necessary to
lift the aerial device.
Supply 12 VDC and ground to the displa y .
Route the transducer wiring from the display to the transducer and plug in the
connector .
If an audible alarm is desired, connect the alarm output (ground) from terminal #1
of the 8 pin display connector to the ground side of the alarm. An alarm test
switch may be connected from ground to terminal #8 of the display connector .
Dual transducer installation:
Identical to a single transducer installation with the addition of a second transducer that should be installed on the rod side of the hydraulic actuator . This
transducer signal is read at terminal #7 of the display connector .
12 VDC
P.N.1800060
Display Power
Alarm Output (Ground)
Aerial Loading
PIN COLOR FUNCTION
1 OEMAlarm OUT (ground)
2 WHITEPRIMARY SIGNAL
3 REDSENSOR SUPPLY
4 REDPOWER IN
5 BLACKGROUND IN
6 BLACKNC
7 WHITESEC. SIGNAL (opt.)
8 OEMAlarm Test (ground)
Primary (barrel) Transducer Cable
Secondary (rod) Transducer Cable (OPTIONAL)
Display Ground
Alarm Test
WIRECOLOR FUNCTION
1RED SENSOR SUPPLY
2WHITE SENSOR SIGNAL
The Aerial Loading Display is connected to the OEM harness with a Deutsch 8 pin miniconnector.
Mating Connector:DTM06-08S
Locking WedgeWM-8S
Mating T erminal:0462-201-2014120 gauge socket
Terminal Assignments:1Alarm OUT (ground)
2Pressure Signal IN (4-20 mA)
310 VDC OUT
4Display Power (Ignition 12 VDC)
5System Ground
6Sensor Ground OUT
7Rod pressure IN (Dual Transducer 4-20 mA)
8Alarm Test IN (ground)
Aerial manufacturers must ensure that the lift cylinder(s) do not bottom out
during operations. This would cause an erroneous hydraulic pressure reading and the warning system will not operate as designed.
The
Class1
ever two displays are operated from one current transducer (aerial loading, air pressure and oxygen gauges)
Dual Current Amplifier (PN 103282) should be used when-
MANUFA CTURER.
Dual Displays
.
A harness is available to simplify the installation (PN 103283)
19
Tank Level
Tank Level Gauge
Transducer Installation
FLUID TANK
3/4 NPT Elbow (OEM)
The transducer must be mounted vertically as depicted to insure an accurate and reliable reading.
This will also prevent damage to the transducer from freezing.
Harness
102193 5'
102194 10'
102195 20'
Pressure Transducer
1/4 NPT
Adapter 3/4-1/4 NPT Bushing (OEM)
Foam adapter is supplied when a
foam level system is ordered.
The tank level gauge transducer should be mounted near the bottom of the
tank. (Approximately two (2) inches off the bottom)
The display, the transducer and the har ness are supplied to ease installation.
When ordered for foam, a special baffled adapter is included with the installation kit.
0 25 50 75 100
TANK LEVEL
20
Tank Level
The Tank Level Display is connected to the OEM harness with a Deutsch 8
pin connector.
2Pressure Signal IN
35 VDC OUT
4Display Power (Ignition 12 VDC)
5System Ground
6Sensor Ground OUT
7Secondary pressure IN ( option )
8Alarm Silence IN
Mount a 3/4 NPT elbow just off the bottom of the tank, enough to keep sediment out of the elbow and transducer (PN 102162). Attach a 3/4 to 1/4 NPT
adapter (supplied for foam) to the elbow and mount the transducer to that.
The elbow and adapter need to be installed so that the transducer is mounted
vertically.
Pressurized Tanks
If you have a pressurized tank, two pressure transducers (PN 102162) can
be used to compensate for pressure or vacuum in the tank. One transducer
should be mounted near the bottom of the tank and one near the top.
When calibrating the dual transducer installation, the tank should
be vented to the atmosphere .
21
Tank Level
Basic Calibration:(2 point)
With the fluid tank empty, enter the
calibration password.
L L L R R R
The left (0%) bar will flash to indicate that you are ready to calibrate
for an empty tank.
Activate the left switch followed by
the right switch.
The right (100%) bar will flash to
indicate that the display is ready to
calculate for a full tank.
When the tank is full, actuate the
right and then the left switch.
Advanced Calibration: (5 point)
With the fluid tank empty, enter the
calibration password.
L L R R L L
The left (0%) bar will flash to indicate that you are ready to calibrate
empty.
Activate the left switch followed by
the right switch.
The fifth bar from the left (25%) will
flash to indicate that the display is
ready to calculate for a quarter tank.
Fill the tank to 1/4 full, actuate the
right and then the left switch.
Calibration is complete.
If after checking the accuracy of
your calibration, you are not satisfied, you can perf orm the adv anced
calibration procedure. This is rarely
necessary except in the case of
oddly shaped tanks.
The tenth bar from the left (50%)
will flash to indicate that the display
is ready to calculate for a half tank.
Fill the tank to 1/2 full, actuate the
left and then the right switch.
The fifteenth bar from the left (75%)
will flash to indicate that the display
is ready to calculate for three f ourths
tank.
Fill the tank 3/4 full, actuate the right
and then the left switch.
The right (100%) bar will flash to
indicate that the display is ready to
calculate for a full tank.
When the tank is full, actuate the
right and then the left switch.
22
Calibration is complete.
Breathing Air
0 25 50 75 100
BREATHING AIR
The
Class1
visible indication of breathing air remaining and an audible warning when
there is less than 20% air remaining. The alarm will not activate when there is
less than 50 PSI air in the system, this silences the alarm when the air supply
is turned off.
The display represents air volume information in an easy to interpret LED
bargraph display as a percentage of maximum calibrated pressure. The
Breathing Air Display includes a visual warning and an auxiliary warning alar m
output.
When the relative volume of air remaining reaches 25%, the bars will begin to
flash and the alarm output will becomes active when system pressure drops
to 20%. The alarm can be silenced with an alarm silence switch. Once the
alarm is silenced, it will remain silent for five (5) minutes or until the unit is
turned off and then back on, and is reset whenever the volume of air exceeds
20%.
Breathing Air Display is designed to provide firefighters with a
23
DTM06-08SA
0462-201-20141 20 Ga.
1Alarm OUT (ground)
2PSI IN (Pressure)
3Sensor + 10 VDC
4Power + 12 VDC
5Ground
6NC
7NC
8Alarm Silence (ground)
breathing air gauge is easily wired into the apparatus using the supplied
installation kit that includes the necessary wiring harness and connectors.
24
Breathing Air
Calibration for Breathing Air Gauge installations:
Empty Cylinder (Closed Valve)
With the air bottle closed and the system purged, enter
the calibration password.
L L L R R R
The left (0%) bar will flash to indicate that you are ready to calibrate for an
empty system.
Activate the left switch followed by the right switch.
The right (100%) bar will flash to indicate that the display is ready to calibrate
for a full system.
Maximum Air
With a full air bottle and the valve open actuate the right switch
and then the left switch.
Calibration is complete.
Calibration should be accomplished using an air cylinder filled to the locally
established maximum pressure.
Dual Displays
The
Class1
are operated from one current transducer (aerial loading, air pressure and oxygen gauges).
A harness is available to simplify the installation (PN 103283)
Dual Current Amplifier (PN 103282) should be used whenever tw o displays
25
Oxygen Supply
0 25 50 75 100
O2 REMAINING
The
Class1
a visible indication of Oxygen remaining and an audible warning when there
is less than 20% oxygen remaining. The audible warning is inactive whenever the pressure is below 50 PSI so that it will not sound when the supply is
turned off.
The display represents oxygen volume information in an easy to interpret
LED bargraph display as a percentage of maximum calibrated pressure. The
display includes a visual warning and an auxiliary warning alarm output.
When the relative volume of oxygen remaining reaches 25%, the bars will
begin to flash, and when the system pressure drops to 20%, the auxiliary
output will turn on. The alarm can be silenced with an alarm silence switch.
Once the alarm is silenced, it will remain silent until the unit is turned off and
then back on, and will reset whenever the volume of air exceeds 20%. When
the alarm is silenced, there will be an aler t chirp every fifteen (15) minutes to
remind the operator that the oxygen supply is low.
Oxygen Remaining Display is designed to provide operators with
26
Oxygen Supply
DTM06-08SA
0462-201-20141 20 Ga.
1Alarm OUT (ground)
2PSI IN (Pressure)
3Sensor + 10 VDC
4Power + 12 VDC
5Ground
6NC
7NC
8Alarm Silence (ground)
All of the digital displays have a built in lamp test feature. The password to
activate this function is:
L L R L L.
When activated, all segments on the display LED’s will illuminate for a few
seconds and then return to normal operation.
The digital displays that utilize a pressure sensor have a sensor check feature. The password to activate this function is:
L R R L R R.
Special Function Passwords:
Transducer Status Check:
L R R L R R
Pressure Gauge:
Zero Calibration to match transducer to display:
Used if the gauge indicates pressure or vacuum erroneously.
Flowmeter:
Display Raw Pulses:
Checks paddlewheel operation.
Noise cancellation:
Cancels out flow indication from eddy currents on a transmitter when
the discharge valve is closed. Toggles
Reset Totalizer :
rP1.7 or above
L R L R R R R L
L R R L L
L R L R L L
C on
L
or
C off.
This password will only work when the flowmeter is in totalizer mode.
33
0462-201-20141 20 Ga.
(ground) Switch8
Pulses IN7
Sensor Ground6
System Ground5
The display does not illuminate.
The display must hav e power at terminal 4 and ground at terminal 5.
With the connector removed, chec k across pins 4 and 5 for 12 VDC , if 12 volts is
present with the correct polarity , replace the displa y. If v oltage and/or ground is
not present, check the vehicle wiring and display harness terminations.
DTM06-08SA
1Alarm OUT (grund)
8
7
6
5
Wire Insertion View
1
2
2PSI IN
3
3Sensor +5/10 VDC
4
4System Power
T-shoot
The pressure reading on a discharge or intake gauge does not change.
There is a problem with the pressure transducer or wiring. At the transducer
connector, chec k for 5 VDC between pins A (ground) and pin B (+5 VDC). These
are sent from the display and m ust be of the correct polarity for the transducer to
function. Plug the connector into the transducer and check f or v oltage at the
display between pin 6 (sensor g round) and pin 2 (signal). With zero pressure/
suction at the pump, this v oltage should be between 500 mV and 900 mV. As the
pressure in the pump increases, the voltage should increase. If it does not, then
replace the transducer . If the v oltage increases, and the display does not change,
perform a default calibration, call Class1 (1-800-533-3569) f or instructions. If the
default calibration does not correct the problem, replace the displa y .
The pressure display reads
SEnS
.
There is a problem with the pressure transducer or wiring. At the transducer
connector, chec k for 5 VDC between pins A (ground) and pin B (+5 VDC). These
are sent from the display and m ust be of the correct polarity for the transducer to
function. Plug the connector into the transducer and check f or voltage between
Pin A (sensor ground) and pin C (sensor signal) at the transducer . With zero
pressure/suction at the pump, this v oltage should be between 500 mV and 900
mV, if it is not, replace the transducer. Check f or v oltage at the display betw een
pin 6 (sensor ground) and pin 2 (signal). With zero pressure/suction at the pump ,
this voltage should be between 500 mV and 900 mV. If it is not, check the wiring
from the transducer to the displa y. If the correct voltage is present at pin 2,
replace the display.
34
T-shoot
The tank level gauge has a bar traveling back and f orth across the display .
There is a problem with the pressure transducer (PN 102162) or wiring. At the
transducer connector , check for 5 VDC betw een pins A (+5 VDC) and pin B
(ground). These are sent from the display and m ust be of the correct polarity for
the transducer to function. Plug the connector into the transducer and check f or
voltage between Pin B (sensor ground) and pin C (sensor signal) at the trans-
ducer. With an empty tank, this voltage should be between 500 mV and 900 mV, if
it is not, replace the transducer . Check f or v oltage at the display betw een pin 6
(sensor ground) and pin 2 (signal). With an empty tank, this v oltage should be
between 500 mV and 900 mV. If it is not, check the wiring from the transducer to
the display. If the correct voltage is present at pin 2, replace the displa y.
The T ank Level Gauge does not change or calibrate.
There is a problem with the pressure transducer or wiring. At the transducer
connector, chec k for 5 VDC between pins A (+5 VDC) and pin B (ground). These
are sent from the display and must be of the correct polarity for the tr ansducer to
function. Plug the connector into the transducer and check f or voltage at the
display between pin 6 (sensor g round) and pin 2 (signal). With an empty tank, this
voltage should be between 500 mV and 900 mV. As the water le vel in the tank
increases, the voltage should increase. If it does not, then replace the transducer
If the voltage increases, and the displa y does not change, attempt to calibrate the
unit. If the calibration does not correct the problem, replace the display.
The Flow Meter does not read flow or calibrate.
Place the meter in raw mode L R L R L L. Does the meter read pulses, and do
they change with a flow increase or decrease? If they do , re-calibrate . If you do
not read pulses, then it is a wiring or paddlewheel problem. At the paddlewheel,
check for 12 VDC between pins A (ground) and pin B (+12 VDC). These are sent
from the display and must be of the correct polarity for the paddle wheel to func-
tion. Plug the connector into the paddlewheel and check f or pulses at the display
between pin 6 (sensor ground) and pin 7 (signal). If pulses are not present, then
check the paddlewheel orientation and the signal wire from the paddlewheel to pin
7 at the display. If e v erything checks out OK, replace the paddlewheel. If the
signal is present and the display does not read ra w pulses, replace the display.
A-Ground
Pressure T ransducer Pinout
B-Supply
C-Signal
35
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.