CONTINUOUS POWER SYSTEM
DIGITAL TECHNOLOGY CMN SERIES
2000VA
CMN2000IPA
CMN2000IPAL
CMN2000IPAD
CLARY CORPORATION
150 E. Huntington Dr.
Monrovia, California 91016
Tel. 626-359-4486 HTTP://WWW.CLARY.COM Fax. 626-305-0254
800-44-CLARY E-MAIL SALES@CLARY.COM
Information contained herein is the property of Clary Corporation, is proprietary, confidential, and
not to be disclosed, disseminated or used except for the purpose provided by
CLARY CORPORATION
P/N 510-13561-C Lockheed\2000VA Steel Rackmount BK-10/09
TABLE OF CONTENTS PART 1
TITLE PAGE NO.
INTRODUCTION ................................................................................................................. 3
THE CMN SERIES RACKMOUNT ..................................................................................... 4
UNPACKING THE UNIT ..................................................................................................... 5
PHYSICAL DESCRIPTION ................................................................................................. 6
PINOUTS FOR CONNECTORS ......................................................................................... 8
SUMMARY OF INDICATORS AND CONTROLS ............................................................ 10
CONTROL PANEL ............................................................................................................ 12
SUMMARY OF INDICATORS AND CONTROLS ............................................................ 13
SPECIFICATIONS ............................................................................................................ 14
INSTALLATION ................................................................................................................ 15
OPERATION ..................................................................................................................... 16
SIGNALS AND INTERFACING ........................................................................................ 19
CARE AND MAINTENANCE ............................................................................................ 20
OPTIONS ........................................................................................................................... 21
SERVICE AND REPAIR ................................................................................................... 22
WARRANTY ...................................................................................................................... 23
LIST OF FIGURES PART 1 TITLE PAGE NO.
CMN SERIES BLOCK DIAGRAM ...................................................................................... 4
UNPACKING THE UNIT ..................................................................................................... 5
RACKMOUNT FRONT VIEW ............................................................................................. 6
RACKMOUNT REAR VIEW ............................................................................................... 7
FRONT VIEW .................................................................................................................... 12
FRONT PANEL ADJUSTMENT ....................................................................................... 15
SIGNALS AND INTERFACING ........................................................................................ 19
INTRODUCTION
The following text is a complete product description, operating guide and basic maintenance summary of
the C
LARY CMN Series Rackmount, digital continuous, uninterruptible power system (UPS). This UPS
provides a fully on-line sinewave, completely regenerated for typical non-linear loads.
The CMN2000IP(A) has an output rating of 2000VA. The unit can deliver up to 1680 watts for a thermal environment less than or equal to 40 degrees Centigrade.
The only difference between the CMN2000IP and the CMN2000IPA is the chassis. The IP is the steel version and the IPA is the aluminum version.
The CMN2000IPAL has an output rating of 2000VA. The unit can deliver up to 1400 watts. The CMN2000IPAL uses a lower velocity fan.
The CMN2000IPAD has an output rating of 2000VA. The unit can deliver up to 1680 watts. The CMN2000IPAD uses a dual speed option. When the unit is running in normal conditions(less than 85% load, ambient under 25˚C, On AC input Power), the fans are running at low speed. When unit is running on batteries, the fans are running at high speed.
This instruction manual is provided with this unit to enhance your understanding of the product and its applications. Read this handbook carefully in the order it is presented prior to operating or servicing to avoid harm or damage to you or the unit. The UPS may be referred to in the text as the CMN Series, Rackmount, etc. Certain references may be made to specific model numbers, however, the basic difference between models is the output power it can supply.
IMPORTANT SAFETY INSTRUCTIONS,
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during installation and maintenance of the UPS and batteries.
Always operate the unit within the guidelines and specifications presented to maximize this system's efficiency and lifetime.
Page 3
THE CMN SERIES RACKMOUNT
A digital on-line, sinewave UPS is the only total solution to virtually any power problem. It effectively provides CONTINUOUS POWER, by regenerating the incoming AC to DC and then back to a highly regulated AC. A battery is provided at the input of the AC Inverter to support the load in case of utility interruption. The CONTINUOUS power concept is a step above the typical UPS, in that, power protection is maintained under any CONTINUOUS power UPS is designed for the critical, must-not-fail
The CMN Series rackmount is engineered with the latest Insulated Gate Bipolar Transistor/Pulse Width Modulation (IGBT/PWM) technology for high efficiency and reliability. The electronics are completely governed by an on-board microprocessor. This allows for not only a digitally processed precision output waveform, but also provides for full interactive access and control for the user through an RS232 computer port.
Refer to the simplified block diagram, Figure 1, for system description. An AC source is fed through a double pole breaker for both Hot and Neutral protection. This breaker then feeds the power circuits and all internal microelectronics. Input voltage is monitored to allow for continuous operation over a -25% to +35% range of nominal voltage for all load conditions. An input voltage variation outside the preset window will transfer operation to battery energy without a shutdown.
The input AC, when within the specified window, is power factor corrected and then sent to the rectification stage. The DC rectifier stage provides both positive and negative voltages to a DC rail stage, which then feeds the digitally controlled inverter AC. The AC inverter supplies the load and supports the battery charger as long as input utility is available. Normally the output inverter is at 60Hz independent of the input line frequency. The output inverter is synchronized to the utility line frequency.
circumstance for the most complete and reliable service to the critical load. This
applications.
During a utility power-loss, the AC rectification and battery charging capabilities of the UPS become inactive. The fully charged battery system now becomes the source of power feeding the AC Inverter generator. All systems are controlled by the digital microprocessor at all times.
The CMN Series on-line topology is unique to other on-line systems in that it is designed to meet the needs of all non-linear type loads while providing input power factor correction. Computers and telecommunications equipment, with their switching power supplies are considered a non-linear load, which can be very abusive to most power protection equipment and could decrease life expectancy. The CMN Series is specially designed with a power factor corrected input to eliminate harmonics back into the power source as well as accept non-linear loads and protect them efficiently without any output waveform degradation common to other UPS designs.
If the unit is overloaded, it will shutdown completely if the overload is not corrected within 3 seconds.
INPUT
ISOLATION
TRANSFORMER
UTILITY INPUT
MICROPROCESSOR
CONTROLLER
EMERGENCY
RFI
INPUT
FILTER
VOLTAGE
WINDOW
DETECTOR
POWER
FACTOR
CORRECTOR
RECTIFIER
+ DC
RAILS
AC
INVERTER
GENERATOR
COMMON
MODE
CHOKE
STANDBY BATTERY
CHARGER
BYPASS LINE
CUTOFF
SWITCH
COMPUTER
(LOAD)
FIGURE 1: CMN SERIES BLOCK DIAGRAM
Page 4
UNPACKING THE UNIT
Your UPS has been carefully packaged to withstand most abuse sustained during shipment. If there is significant damage to the carton, or if there is any physical damage to this unit, report this to your carrier.
It is recommended to save the shipping container and packaging materials for future transporting, if necessary. Transporting the unit in other than supplied shipping materials can result in unit damage not covered by the manufacturer's warranty.
FIGURE 2: UNPACKING THE UNIT
Page 5
PHYSICAL DESCRIPTION
The following illustrations depict the basic Rackmount CMN Series unit. Reference the SUMMARY OF INDICATORS AND CONTROLS Section for a further description of the call-outs.
FIGURE 3: FRONT VIEW
12
11
10
9
6
8
7
5
4
ON ON
OFF
BYPASS
LOAD ON/OFF REPLACE
BATT TEST
STATUS
AC IN
COLD
OK
START
ON BATT
BATT
FAULT
AC
ALARM
OUTPUT
RESET
OFF
ON
LOAD
BATTERY
FULL
OVER 100% 75%
LOW
50% 25%
OFF
14
13
INPUT POWER
1
2
SYSTEM
AC
BATTLE SHORT
INPUT
15
16
17
3
18
1 INPUT POWER SWITCH 10 COLD START LED
2 SYSTEM ON/OFF SWITCH 11 LOAD ON/OFF SWITCH
3 AC INPUT INDICATOR 12 BYPASS LED
4 LOAD LEDs 13 BATTERY TEST SWITCH
5 BATTERY LEDs 14 REPLACE BATTERY LED
6 AC IN OK LED 15 ALARM RESET SWITCH
7 ON BATTERY LED 16 FAULT LED
8 AC OUTPUT LED 17 BATTLE SHORT SWITCH
9 COLD START SWITCH 18 BATTLE SHORT LED
Page 6
21
29
26
23
19
20
28
27
22
25
24
FIGURE 4: REAR VIEW
19 OUTPUT- CPC Type Connector
Loads 1 through 4
20 OUTPUT- CPC Type Connector
Loads 5 through 8
21 RS232 CONNECTOR 27 TEMPERATURE SENSOR DB-9
22 CONTROL PANEL CONNECTOR 28 EXTERNAL FAN CONNECTOR
23 INPUT - CPC Type Connector 29 COM
24 GROUND STUD
25 DC INPUT
26 LAN
Page 7