Citadel XR1 ENGINEERING INFORMATION

XR1
1 2 3 4 5 6 7 8
/!
Accenta
mini
8EP 394 XR1 G3 panel with built-in keypad
The above intruder system is designed to comply with the installation requirements of BS 4737 1986/87.
This manual provides information on Installation design, panel fixing, wiring, power up and programming of the intruder panel.
Power
Attack
Tamper
Day
0123
5678
Chime Omit
Prog
Reset
4
PA
9
Set
Intruder alarm system
Engineering Information
Features
8
z
MEM
8
8 zones, all programmable for Security, Fire,
ÿ
RKP
REMOTE
SET
24H Fire, PTS or keyswitch applications
PA input
ÿ
Tamper input
ÿ
Outputs for Bell and Strobe
ÿ
4 Access level Codes, User 1, User 2 and
ÿ
Engineer, all programmable
3 fully selectable part set programs
ÿ
ÿ
Chime on any zone
ÿ
8 event memory
ÿ
Programmable timers including bell cut off
ÿ
Walk Test facilities
ÿ
Quick set feature
ÿ
Remote keypad with on board PA and illuminated keys - Optional
ÿ
Option for connection of Lighting controllers
ÿ
Options to connect up to four remote keypads / Lighting controllers
ÿ
NVM for protection of engineer programme
ÿ
Service warning indicator, programmable between 100 and 800 set and unset events
ÿ
Battery capacity of up to 2.1Ah
PART
SET
4
5
0
9
Features
4188-693 issue 1_8/01 1
Downloaded from: http://www.guardianalarms.net
Engineering information Citadel XR1G3 Intruder system

Contents

Features -------------------1 Installation Design --------------2 Fixing --------------------3 Wiring the system --------------4 Tamper network ---------------4 Connect Remote Keypads / Lighting controllers 4 Security zones ----------------5 Push to set zone ---------------5 Remote keyswitch zone -----------6 Fire zone ------------------6 PA circuit ------------------7 Extension speaker --------------7 Bell Output (External sounder) --------8 13V Supply output --------------8
Installation Design
The purchase of this alarm system represents a major step forward in the protection of the property and its occupants. It is important to plan the installation before proceeding and then follow the procedures and advice contained in this manual.
Plan the position of each part of the alarm system and the cable runs. Detectors should be sited with particular regard to the degree of coverage required and the function of each of the zones.
Set ---------------------8 Factory set condition -------------9 First Power up ----------------10 Mains Connection --------------10 Testing the system --------------11 Engineer program mode -----------11
To exit ---------------------11
System indications --------------11 To enter Engineer program mode -------11 To Exit Engineer program mode -------11 To reset panel to Factory set conditions ----11 Access Codes ----------------12 Programs ------------------13
Installation Design
Zone Function per Program----------13 Exit Modes program -------------13
A
ccenta
1 2 3 4 5 6 7 8
/!
mini
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
ZONE7
ZONE8
Tamper
Attack
Day Power
0123
5678
Reset
Chime Omit
A
ccenta
All of the system wiring is
Power
0123
4
PA
Attack
5678
9
Tamper
Prog
Reset
Set
Chime Omit
Day
connected directly to the panel. The panel may be installed near an entry/exit point.
The Remote keypads (RKPs)
4
PA
should be mounted in positions
9
Prog
Set
which allows ease of operation for the system users, typically within the entry/exit route close to the final door and the master bedroom.
Programs 1,2 and 3--------------14 Alarm and Walk tests ------------15 ‘Flag A’ Options ---------------16 ‘Flag B’ options ---------------17 Viewing the event log ------------17 Zone Type ------------------18 Zone Attributes ---------------19 Bell and Service Timers -----------20 Re-arm and Anticode reset code -------21 Lighting controller --------------22 Faults --------------------23 Specification-----------------24
provide good sound distribution throughout the building and so that the exit tone is audible outside the main entry / exit door. This will enable the system operator to check that the system is setting correctly.
Additional internal sound speakers are recommended, these will provide high volume alarm tones and low volume entry/exit tones. Speakers should be positioned to
Index --------------------26 Servicing organisation Details --------27 Parts --------------------27 Quick Reference ---------------28
I
TOTAL
Finally note that the total current output of this
control system (in alarm condition) is 1A when supported by a fully charged
battery. Calculate the total current consumption of every part of the system including the panel, remote keypads, bell/sounders, strobes and detectors to ensure that this rating is not exceeded.
2 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Depending on which area you live, you may be
LA
required, by law to notify the Local Authority and Police of the new security
alarm installation. The local authority requirements may differ from area to area, therefore, it is advisable to contact local environmental officer to obtain full details of your area requirements.
Fixing
Caution: When positioning the control panel ensure that it is located in a dry place away from damp areas.
a. Remove the front cover(s) from the
panel.
Note: When replacing the PCB align it on the round support pillars to the bottom and allow it to click down past the clips at the top of the case. Refit the transformer wires into the terminal.
b. Fit the panel to the wall with suitable
fixings. Ensure the wall surface is flat to prevent base distortion. There are cable entry holes provided in the rear of the base and around the outside edges through the thinned out plastic sections which may be cut away as required.
c. The hole provided adjacent to the
mains transformer is a dedicated mains cable entry point.
Mounting holes
4
PA
9
0123
8
6 7
5
3 4
1 2
Attack
Tamper
Day
Prog
5678
Reset
Omit
Chime
Set
Disconnect the transformer wires from the transformer marked AC terminals on the board. Carefully remove the PCB by gently pushing down the holding clips on the bottom edge of the PCB and withdraw it from the base.
Cable entry
holes
Mounting holes
Board
There are four fuses mounted on the circuit board, all are 20mm quick blow.
F1 1.6A - to protect the +ve line of 12V battery F2 1A - to protect the RKP 13V supply F3 1A - to protect the Speaker 13V supply F5 1A - to protect the Bell and Strobe supply
As supplied, wire links are fitted across the PA and Tamper terminals to represent a closed circuit.
Fixing
4188-693 issue 1_8/01 3
Engineering information Citadel XR1G3 Intruder system
p
RKP FUSE
1A
SOUND
COMMS
+13V
TAMP
J2
F2
J5
0V
2
1
D1 D2 D3 D4 D5 D6 D7 D8
TAMP
7
8
PA
-
+
Factory fitted links
6
4
5
3
Wiring the system
Caution: Always power-down the panel when wiring external circuits, to prevent damage to the panel electronics.
Systematically wire and test each circuit:
ÿ Zone, Tamper circuit and PA circuits
Wiring the system
ÿ
Finish by wiring any additional extension speaker sounders, external bell/sounder, strobe and the 13V supply.
Tamper network
The Tamper circuit is used to protect all cables and detectors in the system from unauthorised access including the panel and RKP covers.
+13V 0V
0 1 2 3
D18
D9
D10
VOLUME
VR1
TAMP
D22
J6
-
+
TA
STROBE
The zone and PA tampers should be series wired and connected to the TAMP terminals. TerminalsT&Aarefortheexternal bell / sounder tamper. The TAMP terminals at the bottom left of the PCB are for the RKP tampers.
Tamper alarms that occur in the Day mode operate internal sounders only. Tamper alarms in Set cause a full alarm condition. Tamper is indicated on the control panel and RKPs by the Tamper indicator.
5 6 7 8
CHIME OMIT RESET
DB
SET
BELL
SCB
-
+
BELL/STROBE
13V / SPEAKER
1A 1A 1.6A
F1F3F5
BATTERY
+­BATT
Connect Remote Keypads / Lighting controllers
A combination of up to four remote keypads and lighting controller can be connected to the panel.
4
9
SETPROG
J4
AC
Keypad
Board
0V
13V
SOUND
TAMP
COMMS
If only one Remote keypad
is being used then connect TAMP
back to the
anel
Panel
Board
1A
RKP FUSE
J5
F2
SOUND
COMMS
+13V
0V
TAMP
GND
Keypad
Board
0V
13V
OPTI-CAM Lighting Controller
Board
COMMS
12V
SOUND
LD R
Maximum of up to 4 Remote Keypad / OPTI-CAM Lighting Controller combination allowed
(See also the instructions supplied with the OPTI CAM lighting controller)
SOUND
COMMS
TAMP
4 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Security zones
Panel
Board
J2
TAMP
4
PIR
+-
PIR
6
5
Terminal block is not supplied
Tamp
Door Contact
Door Contact
2
1
3
Alarm
Note: The panel is not supplied with wire links for unused zones. All unused
zones must be programmed out by setting them to disabled using the Zone Type function see page 18.
PA
8
7
Unused zones must be programmed as Unused.
-
+
+13V 0V
Push to set zone
Any zone can be wired and configured as a Push to Set input. This can be a standard door bell push located outside the premises. After starting the exit timer the building is vacated. As the switch is then momentaraily closed, a chime tone is produced and the system Sets. Sometimes referred to as ‘Terminate Set’ this facility is mandatory for communicating systems installed to NACOSS guidelines
Panel
Board
J2
TAMP
PA
2
1
3
Note: The push to set switch can be connected to any zone. The zone must be programmed for PTS application.
6
4
5
8
7
Press to Set Switch
+13V 0V
-
+
Security zones
It is recommended that no more than 10 magnetic contacts are connected to the same zone.
4188-693 issue 1_8/01 5
Engineering information Citadel XR1G3 Intruder system
Remote keyswitch zone
Any zone can be wired and programmed as a keyswitch input and used with a remote keyswitch or lock switch. For security reasons it is recommended that a tamper proof switch is used and that the switch wiring is not accessible from outside the premises.
Panel
Board
J2
TAMP
PA
6
2
4
1
Note: A keyswitch can be connected to any zone. The zone must be programmed for keyswitch application.
5
3
7
8
Keyswitch
The keyswitch may be used to Set (open contacts) or Unset (closed contacts) independently of RKPs. However in this situation the keyswitch may have to ‘catch up’ with the system. For example if the system is Set via an RKP and Unset with the keyswitch, it would have to be momentarily turned to its Set
Remote keyswitch zone
position then returned to its Unset position.
The keyswitch will always Set program 1. It will also Unset the system or switch off an alarm activation. To Reset after an alarm and return to Day mode, the Reset key on the RKP will have to be pressed.
+13V 0V
-
+
Fire zone
Any zone may be programmed as a fire zone. This will automatically exclude the availability of the zone from programs and normal security applications.
Panel
Board
J2
TAMP
PA
6
2
1
4
3
Note: Fire detector with relay base for output to intruder system.
5
7
8
Fire detector
There are two types of fire zone, Standard and 24 hour type. The Standard fire zone detects
fires only when the system is Set, where as the 24 hour fire zone detects fires all the time and will operate whether the system is Set or Unset. A fire will cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all RKP indicators will flash the affected zone.
+13V 0V
-
+
6 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
PA circuit
Any quantity of normally closed type personal attack button may be wired in series and then connected to the PA circuit.
Operational in Day and Set, the PA circuit will cause a full alarm condition when activated. PA is indicated on the control panel or RKP as Attack.
Panel
J2
6
2
4
1
5
3
Panic Button
Panic Button
8
7
PA buttons may be fitted near the front door, or in a bedroom.
Board
TAMP
PA
+13V 0V
-
+
Extension speaker
Extension speaker may be connected to the loudspeaker terminals to produce high volume alarm tones and low volume entry / exit fault tones.
Panel
VOLUME
VR1
-
+
STROBE
16 Extension Speaker
16 Extension Speaker
TA
SCB
DB
BELL
-
+
Up to two 16 ohm extension speakers may also be wired across the speaker terminals. Mounted in convenient positions within the installation the extension speakers will reproduce all of the alarm tones generated by the control panel.
A control marked VOLUME in the centre of the PCB may be used to adjust the low volume entry/exit tones to suit environmental conditions.
J6
SET
Board
F5
F3
13VSPEAKER
BELL/STROBE
1A
1A
PA circuit
4188-693 issue 1_8/01 7
Engineering information Citadel XR1G3 Intruder system
Bell Output (External sounder)
The bell is usually installed in a high position from where the bell could be seen and heard.
Terminal TADBareforconnection to the external bell or sounder. These terminals provide a power/hold-off supply, sounder trigger and tamper circuit to protect the external sounder housing.
Panel
Bell Output (External sounder)
Board
J6
-
+
TA
STROBE
+- TEADB
STROBE
DB
BELL
SCB
+
F5
SET
BELL/STROBE
1A
-
Panel
Board
J6
-
+
STROBE
+- TEADB
STROBE
Sonade
TA
SCB
DB
BELL
+
F5
SET
BELL/STROBE
1A
-
#
# Terminal block is not supplied
+- TEADB
STROBE
Sonade
Where self contained / powered sounders are used, carefully follow the manufacturers instructions, match each of the terminals to those above.
Panel
Board
J6
-
+
TA
STROBE
SCB
DB
BELL
+
F5
SET
BELL/STROBE
1A
-
Sonade
The terminals are summarised as follows: T - -Ve tamper return A - -Ve supply (0V) D - +Ve supply (12V)
B- -Ve Sounder trigger
For ease of installation, Sonade sounders and modules use the same markings.
Where a discrete bell sounder is used, it should be connected to terminalsD&B.Terminals T & A are then used for tamper protection for the sounder housing.
13V Supply output
The 13V output is to power detectors which require a voltage supply (PIR detectors etc). The supply is present at all times and may be used to supply a total load of 350mA.
Set
-Ve COM
Citadel Defender
Rtn Signal
Siren Trigger -
Strobe Trigger -
Supply Hold Off -
Supply Hold Off +
The output, marked SET is used with latching detectors. The output becomes positive on correct Set of the system and is removed at the commencement of entry time or entry of the valid user code.
8 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Factory set condition
User code 1 --------0123 User code 2 --------Notprogrammed Engineer Code -------9999 Bell Duration -------20minutes Bell Delay ---------Nodelay
Program 1
Zone 1 ---------Timed Zone 2 ---------Time Inhibited Zones 3…8 ------Immediate Exit time--------30seconds Entry ---------30seconds Exit mode -------timed
Program 2
Zone1 ---------Timed Zone 2 ---------Time inhibited Zone 3…8 -------Immediate Exit time--------30seconds Entry time -------30seconds Exit mode -------Disabled
Program 3
Zone 1 ---------Timed Zone 2 ---------Time Inhibited Zone3…8 -------Immediate Exit time--------30seconds Entry time -------30seconds Exit mode -------Disabled
Flag A
Silent PA ---------No RKP PA Enable ------Yes Engineer Reset-------No Anti Code Reset ------No Door bell on push to set - - No Single key setting -----No Strobe on setting ------No External bell on Fire ----No
Flag B
User Reset PA --------No User Reset Fire --------No Rearm counter --------3(re-arms) Service counter --------Off Site Code -----------00
Light Controller
Light Threshold ------50% Light Hold Time ------30seconds Light Channel 1 ------Nozones assigned Light Channel 2 ------Nozones assigned Light Channel 3 ------Nozones assigned Light Channel 4 ------Nozones assigned Light Channel 5 ------Nozones assigned Light Channel 6 ------Nozones assigned Light Channel 7 ------Nozones assigned Light Channel 8 ------Nozones assigned
Factory set condition
Security Zones -------Zones 1…8 Standard Fire zones ----None programmed 24 hour Fire zones -----None programmed Push to set zones ------None programmed Keyswitch zones ------None programmed Double Knock zones ----None programmed Omit prevent zones-----None programmed Zone debounce period - - - 300mS ALL zones
4188-693 issue 1_8/01 9
Engineering information Citadel XR1G3 Intruder system
r
r
First Power up
Before power up - fit the top cover on to the base and connect the speaker wires. Leave the cover in position throughout the reset of the installation.
a.
Check that the factory fitted links are connected to terminals PA, TAMP and T-A.
b. Fit the battery wires to the BATT
terminals on the PCB, Red to + and Black to -.
Black -
F1
BATTERY
1.6A
(red)
+
Panel
12V battery
c. On connecting the battery the system
First Power up
will now go into alarm condition and Tamper is indicated
Tampe
indication. .
d. Fit the cover to hold down the tamper
spring at the bottom centre of the PCB.
e.
Enter the user code:
0 1 2 3
0123). The alarm condition will cease and the system will go to Day mode
Day
.
f. Immediately enter the engineer code
Prog
9 9 9 9
The system is now in Engineer program mode and can be
programmed. Note the
Tampe
Tamper indicator is lit.
Board
J4
+-
AC
BATT
N E
L
125mA Fuse
Transformer
and there is an audible
Alarm
(factory set at
.
Note: The panel is not supplied with wire links for unused zones. All unused
zones must be programmed out by setting them to disabled using the Zone Type function see page 18.
Mains Connection
The mains power should be connected using a 3 core cable of not less than 0.75mm sq. from a
fused spur to the mains connector inside the control panel. The 2A fused spur must be located close to the control panel.
Dedicated mains supply
from consumer unit.
2A Fused Spur unit
Panel
12V battery
Note: The mains supply must be connected by a technically competent person and according to current IEE regulations.
CAUTION: To avoid the risk of electrical shock you must always totally isolate the mains supply before opening the control panel cover(s).
ÿ
Mains Input Fuse rating: 125mA, 250V type T (anti surge) and of a type approved to IEC 127 part 2 sheet III.
On connecting the mains supply to the panel the power indicator is lit.
Power
Black -
F1
BATTERY
1.6A
(red)
+
+­BATT
Transformer
Board
J4
AC
N E
L
125mA Fuse
10 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
r
r
ownonemenuleve
Testing the system
Complete the wiring of the system and then:
Fully test the system and ensure it is fault
ÿ
free.
Fully program the system.
ÿ
Fill in the installation log at the back of the
ÿ
manual and retain if for future reference.
Finally explain the operation of the system
ÿ
to the end user. The Operating Instructions are attached to the centre of this manual. Detach them and leave them with the user.
Engineer program mode
The panel may be programmed to suit a wide variety of installations. .
Once the engineer program mode has been accessed, each configuration may be changed in any order. As each configuration is completed the system will automatically return to top level of engineer program mode.
Before entering engineer program mode the system should be in the Day mode, with the Day and Power indicators lit.
Key
LED steady On indication
LED flashing indication
LED Off
Internal sound
Sound description
NOTE: In general a flat beep is an indication of an incorrect key press.
External devices
Strobe
Bell
System indications
Day
Powe
- Unset system indication
Powe
- Set system indication
To enter Engineer program mode
Note: The factory configured engineer’s access code is 9999. If however this code is changed then enter the appropriate code.
Prog
ZONE1-8 Momentarily On
9 9 9 9
Acknowledge
Tamper
Day
To Exit Engineer program mode
Reset
Day
To reset panel to Factory set conditions
Caution: All configurations of the panel are restored to factory ‘default’ conditions.
Within 5 seconds of powering up the panel
Reset Reset
Testing the system
reset beeps
To exit
Reset
Quit the current function Leave program menu D
4188-693 issue 1_8/01 11
l
Engineering information Citadel XR1G3 Intruder system
Access Codes
There are three codes used in the system, all are 4 digit and can be set to any number from 0000 to 9999. The access codes ensure that only authorised users can operate the system.
User 1 and 2 codes
The user 1 and user 2 codes have the same operation for testing, Setting and Unsetting, but user 1 code which is usually considered to be the Managers code has the authority to add, change or delete the user 2 code.
Engineer code
Accesses the Engineer Program mode to allow the system to be programmed. The engineer code will not set or unset the system.
If configured the Engineers access code can be used to reset the system after an alarm.
Note: Entering an invalid user code will operate the code tamper. After nineteen incorrect key pushes a full alarm
Access Codes
condition will be generated.
Example: To change User 1 code to 3457 Press:
Prog
3
9 9 9
4
5 7
9
8 1
Reset Reset
Enter Engineer program mode
Codes
8
Attack
Change User code 1
1
Change User code 2
2
Change Engineer code
9
Day
ZONE 1-4
n n n n
NOTE - The sounder will produce
a flat beep if the code is rejected. The Code is rejected if it is already in use.
Rising beeps
ZONE 1-4
Day
New code
Reset
Exit codes
Reset
Leave engineer mode
Day
Acknowledge
Attack
Tamper
12 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Programs
The panel uses 3 Part Set routines known as Programs. In each Program the exit mode can be changed and the zone may be set up to have a different function.
The examples below show how 3 typical Programs could be used in a house.
Program 1 : To arm all of the zones and
ÿ
become Set as the user leaves the property and closes the final door.
Program 2 : To protect the perimeter of the
ÿ
property in the evening and become Set after say 20 seconds.
Program 3 : To protect the downstairs areas
ÿ
of the house at night and become Set instantly and silently.
Note: The above are purely examples. The installer must program the panel to configure all the circuits to the customer’s exact requirements.
Zone Function per Program
Timed : This function would be used to protect the main entry/exit door of the entry route.
Exit Modes program
Timed A timed Program will become Set as the Exit timer expires.
Terminated Set
This sets an infinite time out, which will only set once the PTS input is operated.
Final Door A final door program will be Set 5 seconds after a timed zone has opened and closed.
Silent Set This operates exactly the same as ‘Timed’ but completely silent without the internal sounder signal.
Note: If a program is not selected when the user Sets the system, Program 1 will automatically Set. Therefore Program 1 is usually considered as the Full Set Program containing all of the zones.
Programs
Time inhibited : This is a zone which, on setting the panel, allows access to the Entry / Exit zone. However, if the panel is set and an time inhibited zone is triggered before an Entry /Exit zone then an alarm will be generated immediately.
Immediate: This is a zone which will, when entered, go into alarm when the panel is set.
Unused : A zone that is programmed as an Unused zone by the Engineer, then is ignored by the panel. Primarily used for Part set options.
4188-693 issue 1_8/01 13
Engineering information Citadel XR1G3 Intruder system
Programs 1,2 and 3
Example: To configure Program 1 Exit mode to Final door set, Press:
Zone 1
Zone 2
Zone 3
Prog
Day
1
6
Reset Reset ResetReset
3
0
Deselect all zones
1
Zone 1
2
Zone 2
Appropriate Zone indicator
3
Zone 3
is lit to show selected zones
4
5
6
7
Zone 4
Zone 5
Zone 6
Zone 7
Zone n selected
Zone n deselected
Prog
9 9 9 9
Enter Engineer program mode
Set up
Prog
program
Attack
Zones 1,2 and 3
1
Program 1
2
Program 2
3
Press number button to select
Program to be configured
1
Program 3
Used Zones
Factory defaults
All Zones
Timed Zones
2
Programs 1,2 and 3
Time inhibit
3
zones
Zone 1
Zone 2
Day
Day
8
Press number button to select / deselect zone
Zone 8
Input Entry/Exit time respectively
Entry time
4
0
1
10 seconds duration
0
2
20 seconds duration
0
3
30 seconds duration
5
Exit time
6
Exit mode
Day
Zone 1
Zone 2
Day
(factory default)
Acknowledge
Acknowledge
Day
Day
Attack
Tamper
Press a number button to select
the appropriate Exit mode
Disabled
0
Timed
1
Terminated set
2
Final Door Set
3
Silent set
4
(use exit time)
Factory default
For Programs 2 and 3
Zone 1 for Program 1
Zone 2
Zone 3
Zone 4
Exit to Program and
Reset
complete used zone set up
Reset
Exit to Setup program
Reset
Exit Set up program
Reset
Leave engineer mode
Day
14 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Alarm and Walk tests
Example: To start bell test and thereafter to stop bell test.
Prog
9 9 9 9
Enter Engineer program mode
1
Alarm test
Attack
2
Strobe test
Strobe On
3
Press zero to turn off options 2,3,4 and 5 before selecting a new one
Day
0
Reset1Reset
3
Bell test
Low volume
4
sounder
High volume
5
sounder
6
Walk test
Bell on
internal low volume sound
internal high volume sound
Strobe
x1 for zone 1 x2 for zone 2
x4 for zone 4 flat x1 for zone 5 flat x2 for zone 6
flat x4 for zone 8
Rapid for PA
Rapid for Tamper
OFF
0
Reset
Reset
Day
Exit current level
Leave engineer mode
Day
Acknowledge
The alarm test function allows you to test the Strobe, Bell, Low and High volume sounders of the system.
Day
|
|
Attack
Tamper
Day
Day
Strobe On
Appropriate zone lights are lit(latched)
Zones
Attack
Tamper
Day
Alarm and Walk tests
The walk test function allows each detector to be checked in order to verify that they are functioning correctly.
4188-693 issue 1_8/01 15
Engineering information Citadel XR1G3 Intruder system
‘Flag A’ Options
Example: To set the panel for engineer reset, Press:
Prog
9 9 9 9
Reset3Reset
Enter Engineer program mode
3
Flags A
Attack
Zones 1-8 Momentarily On
1
Silent PA
Appropriate Zone indicator is lit to show flag setting
Factory defaults
3
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Attack
Tamper
Press number button to
select / deselect flag setting
‘Flag A’ Options
RKP PA enable
2
Engineer reset
3
Anti-code reset
4
Enable Door bell
5
on PTS
Enable single
6
key setting
Enable strobe
7
on setting
Enable Bell
8
in Fire
Reset
Exit current level
Reset
Leave engineer mode
Day
Acknowledge
Flag A descriptions:
Silent PA : When this flag is set and on operating PA will cause a Silent PA alarm.
RKP PA Enable: When this flag is set the keypad PA buttons are enabled.
Engineer Reset: When this flag is set an Engineer code must be entered to reset the system after a full alarm. When the flag is clear the system can be reset by the user.
Anti-code Reset: When this flag is set it enables the anti code reset function.
Enable Door bell on PTS: When this flag is set it allows a zone circuit programmed as PTS to operate as a door bell.
Enable single key setting:When this flag is set it allows the panel to be set by pressing the SET button (ie code entry is not needed), however a 4 digit code is needed to Unset the panel.
Enable strobe on setting: When this flag is set the external strobe will flash for 3 seconds once the panel has successfully set.
Enable external Fire bell: When this flag is set the system bell will sound 2 seconds On / 2 seconds Off during a fire alarm.
16 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
‘Flag B’ options Viewing the event log
Example: To set the panel for user to reset PA, Press:
Prog
9 9 9 9
Reset
Reset
Enter Engineering program mode
4
Flags B
Attack
Zones 1-8 Momentarily On
1
Not applicable
2
Not Applicable
4
Appropriate Zone indicator is lit to show flag setting
Factory defaults
3
Zone 1
Zone 2
Example: To view up to 8 previous events and thereafter to stop the event scroll, Press:
Prog
9 9 9 9
Reset
Chime
Enter Engineer program mode
Chime
View the event log
Tamper
Automatic event scroll Starting from event 1 to 8
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Attack
Tamper
Press number button to
select / deselect function
User Reset PA
3
User Reset Fire
4
5
Not Applicable
Not Applicable
6
7
Not Applicable
8
Entry deviate
Reset
Exit current level
Reset
Leave engineer mode
Day
Acknowledge
Flag B descriptions:
User Reset PA: When this flag is set it permits the user code to reset the system after a PA alarm, even if Engineer reset flag is set.
User Reset Fire: When this flag is set it permits the user code to reset the system after a Fire alarm, even if Engineer reset flag is set.
Entry deviate: When this flag is set it permits an immediate zone to be activated during the entry period without causing a full alarm.
To manually scroll
View event 1
1
(oldest event)
View event 2
2
View event 3
3
View event 4
4
5
View event 5
6
View event 6
7
View event 7
View event 8
8
(Newest event)
Resume
Chime
automatic scroll
Reset
Stop event scroll / view
Leave engineer mode
Day
Acknowledge
Zone, PA and Tamper indicators will be lit to show zone in alarm. Flashing indicates the first zone in alarm. Day indicates status of panel at the time of alarm
‘Flag B’ options
Tamper
Tamper
4188-693 issue 1_8/01 17
Engineering information Citadel XR1G3 Intruder system
P
Zone Type
The panel is not supplied with wire links to terminate unused zones. Therefore all unused zones must be programmed out by setting them to disabled using the Zone Type function.
Example: To disable an unused zone 8, Press:
Prog
9 9 9 9
Enter Engineer program mode
Zone
5
Configuration
Attack
All Zones
Zone 1 type
1
Zone 2 type
2
Zone 3 type
ress a number button to select
Zone to be configured
3
Zone 4 type
4
5
Zone 5 type
6
Zone 6 type
7
Zone 7 type
8
Zone 8 type
Zone Type
Day
5
8
0
1
2
3
4
Press a number button to
select zone type
5
Reset Reset Reset
0
Disabled
Security
Fire
24h Fire
PTS
Keyswitch
Appropriate Zone indicator is lit to show Zone type
Factory default
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Acknowledge
Reset
Exit to zone type
Reset
Exit zone configuration
Reset
Leave engineer mode
Day
Acknowledge
18 4188-693 issue 1_8/01
Day
Attack
Tamper
Citadel XR1G3 Intruder system Engineering information
Zone Attributes
Example: To configure zones 4 and 5 for ‘Double knock’ operation, Press:
Prog
9 9 9 9
Enter Engineer program mode
Zone
6
Attributes
Attack
Double Knock
1
6
1 4
Reset Reset Reset
5
Omit Prevent
2
Zone Delay
3
Press number button to
select / deselect
zone delay, Omit zone or Double knock
0
Deselect all zones
1
Zone 1
2
Zone 2
3
Zone 3
4
Zone 4
5
Zone 5
6
Zone 6
7
Zone 7
8
Zone 8
ZONE1-8 Momentarily On
Day
Appropriate Zone indicator is lit to show zone having 800mS delay, Omit prevent or double knock.
Zone n selected
Zone n deselected
Reset
Reset
Reset
Factory defaults:
No zones are in double knock
No Zones are set as omit prevent
All zones have delay of 300mS
Exit to zone type
Exit zone attributes
Leave program mode
Day
Acknowledge
Zone Attributes
Day
Attack
Tamper
Zone attribute descriptions
Double knock: The panel will require 2 activations of the same detector before causing an alarm condition. This setting is used as a false alarm measure.
Note: Double knock must not be used on
Omit Prevent: The panel will prevent the zone
from being omitted by the user when setting the system.
Zone Delay: The panel programs a zone delay to 800mS to give extra immunity to false alarms.
zones having magnetic door/window contacts.
4188-693 issue 1_8/01 19
Engineering information Citadel XR1G3 Intruder system
Bell and Service Timers
Example: To set bell timer for 10 minutes duration, Press:
Bell and Service Timers
Prog
9 9 9 9
Enter Engineer program mode
Timers and
7
Counters
Attack
Bell timer
1
Bell delay timer
2
Service timer
3
Re-arm counter
4
(00 to 99)
Anti-code
5
reset site code
ZONE1-8 Momentarily On
Day
Service timer disabled
0
(Factory default)
100 Set/Unset
1
Zone 1
7
Zone 1
Zone 2
Day
Zone 1
Zone 2
Day
1 1
0
0
0
0
2
9
0 0
0 1
0 2
0 3
2 0
9 9
Reset Reset
0
0
Continous operation
1 minute bell duration
1
2 minute bell duration
2
3 minute bell duration
3
20 minute bell duration
0
(factory default)
99 minute bell duration
9
No delay (Factory default)
1 minute bell delay
2 minute bell delay
3 minute bell delay
20 minute bell delay
99 minute bell delay
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Appropriate Set / Unset values LED is lit
Lit when selected
Day
Reset
Reset
Reset
Exit
Exit Timer and counters
Leave engineer mode
Day
Acknowledge
Acknowledge
Attack
Tamper
Press a number button to
select Service timer
200 Set/Unset
2
300 Set/Unset
3
400 Set/Unset
4
500 Set/Unset
5
600 Set/Unset
6
700 Set/Unset
7
800 Set/Unset
8
20 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Re-arm and Anticode reset code
Example: To set panel re-arms to 10 times before panel is shut down, Press:
Prog
9 9 9 9
Enter Engineer program mode
Timers and
7
Counters
Attack
Bell timer
1
Bell delay timer
2
Service timer
3
Re-arm counter
4
(00 to 99)
Anti-code reset site code
5
7
4 1
Reset Reset
0
Re-arm
After an alarm the panel will automatically reset itself when the bell timer has expired. Any zones which still remain open at that time will be omitted automatically.
Note: By default there are 3 automatic re-arms before the panel is shut down.
Anti code reset (Engineer reset)
If the system has been programmed to be engineer reset, after an alarm it will lock out and the RKP will continually display the cause of the alarm. The engineer would then be required to attend the site and use the engineer code to reset the system.
Zone 1
Zone 2
Day
Zone 1
Zone 2
Day
Reset
Reset
0 0
0 1
0 3
9 9
0 0
0 1
2 0
9 9
Acknowledge
Day
Exit to Timer and counters
Leave program mode
Day
Acknowledge
No re-arm
1 re-arms
3 re-arms (factory default)
99 re-arms
factory default code
01
20
99
Tamper
Where anti-code reset has also been enabled, the RKP will still show the alarm cause and also display a 4 digit 'quote code' by sequentially flashing zone indicators 1-8.
At this point the end user would contact the engineer. After determining the cause of the alarm and deciding that a engineer call was not necessary, a 6 digit anti-code would be given to the user which would reset the system.
This anti-code is generated from a small computer program which is installed at most UK Alarm receiving Centres, or alternatively can be run on a PC by the engineer.
Security of the anti-code reset system is maintained by a 2 digit site code which is set up in the anti-code generator programme. The same 2 digit site code must also be set up in the
Attack
control panel during installation.
Re-arm and Anticode reset code
4188-693 issue 1_8/01 21
Engineering information Citadel XR1G3 Intruder system
Lighting controller
Example: To assign zones 1 and 2 to lighting controller channel 1, Press:
Lighting controller
Prog
9 9 9 9
Enter Engineer program mode
Lighting
9
Controller
Attack
All Zones
Channel 1
1
assigned zones
Channel 2
2
assigned zones
Channel 3
3
assigned zones
Channel 4
4
assigned zones
Channel 5
5
assigned zones
Channel 6
6
Press a number button to select
the appropriate light channel
assigned zones
Channel 7
7
assigned zones
9
1 1
To assign zones to channel press to select and again to deselect zone (Factory default: No zones are selected)
1
2
3
4
5
6
7
Reset Reset Reset
2
Appropriate Zone indicator is lit to identify its assignment to channel
Day
Zone n assigned to the channel
Zone n not assigned to the channel
Channel 8
8
assigned zones
Hold time
9
(20 seconds factory default)
Set the light threshold
Prog
level (0 - 99%)
Day
(0-99 seconds)
0 0
Zone 1
Zone 2
0 1
2 0
8
0% threshold or 0 second hold time
1% threshold or 1 second hold time
20% threshold or 20 seconds hold time
Reset
Exit current level
Reset
Exit Lighting controller
Attack
Reset
Leave program mode
Day
Acknowledge
acknowledge
Day
Reset
Exit Lighting controller
Attack
Reset
Leave program mode
Day
Tamper
Tamper
Acknowledge
22 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Faults
Fault conditions are often the result of minor installation errors or misinterpretation of the equipment being installed. The following points outline the most common installation and commissioning faults.
a.
As supplied the user code is 0123 and the engineer code is 9999. Both codes will revert back to these default settings on clearing the NVM.
b. The Engineer Program is accessed
directly from Day mode via the engineer code.
c. If a tamper, PA or 24Hr fire fault is
present on the system, it will go to a lock out condition (showing the appropriate indication). The keypad will not produce any audible responses and the system will not operate until the fault has been found and rectified.
d. The most common cause of a zone not
responding to detection is incorrect wiring. Normally closed detectors must be wired together in a series loop before connecting into the appropriate ZONE terminals. Tampers are series wired in the same manner.
e. Where a permanent zone fault is
showing and the loop resistance is found to be in order, the most probable cause is a short circuit between the zone wiring and the tamper wiring. When measured with a multimeter the series resistance between the zone and tamper wiring should be infinitely high.
f. If totally lost as to the cause of a fault,
remove ALL wiring from the PCB. Refit the 4-links and test the system. Never fit links to any positions other than those marked on the PCB.
g. Before testing or replacing any fuses,
ALL power must be removed. Fuses which fail continually are almost certainly the result of a short circuit or low resistance across the 13V supply or external bell supply (terminal D).
Whenever working close to the mains supply or connector, you should exercise extreme caution. Always isolate the mains supply before removing the control panel covers.
h. Where normally open detectors are
connected to adjacent zones two pull-up resistors (not supplied) of value 33kohms must be installed.
The example below shows how to wire normally open detectors on zones 3 and 4.
Panel
Board
J2
TAMP
PA
2
1
4
5
3
33K
ohms
Normally open detectors
6
8
7
+13V 0V
-
+
The example below shows how to wire normally open detector on zones 3 and a normally closed detector on zone 4.
Panel
Board
J2
TAMP
PA
1
33Kohms
Normally
open
detector
6
2
4
5
3
Normally closed detector
8
7
+13V 0V
-
+
Faults
4188-693 issue 1_8/01 23
Engineering information Citadel XR1G3 Intruder system
i. Where Pressure mats are being used
these must be connected to a zone in the manner shown. The example below shows pressure mats connected to zones 3.
Panel
Board
J2
TAMP
1
2
4
5
3
33Kohms
Pressure Mats
6
PA
8
7
-
+
Specification
Indicators on Control panel or RKPs
Specification
8 Zones
Tamper
PA +ve loop, always active
Bell Output
Strobe Output 12V latching
Extension Speaker
Exit/Entry timers seconds
Zone Input Delay 300 or 800mS
Set +ve Output
Current Consumption Control panel
Zone 1-8, Power, Attack, Tamper and Day
+ve loop, programmable function in each program
-ve loop, internal sounders in Day – Full alarm in Set
12V, adjustable timer (1-99 mins) or continuous
16 ohms (2 maximum) 130mA each
Programmable (10-990 seconds)
0V in Day (sinking 40mA)
12V in Set (sourcing 10mA)
Standby 80mA Alarm 250mA
Current consumption RKP
Low voltage output
Rechargeable Battery
Charge Voltage 13.8V dc (+/-5%)
PCB Fuses
+13V 0V
Mains Input fuse
Total Current Output
Mains Supply Voltage
Ambient Operating temperature
Enclosure construction
Dimensions
Standby 40mA Alarm 70mA
13.8V dc stabilised (+/- 5%) up to 350mA
Panel -12V, 1.2 or 2.1Ah
1.6A & 1A 20mm quick blow
125mA, 250V type T (anti-surge) type approved to IEC 127, part 2 sheet III
1A when supported by a fully charged battery
230V (+/-10%) 50Hz max load 0.2A
0ºC to 40ºC
3mm Polycarbonate
Panel H 200mm W 253mm D 55mm
RKP H 85mm W 122mm D 28mm
24 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information

Index

!
13V Supply . . . 8 24 hour fire zone . 1,6,9,18
3 Part Set ....13
A
AC terminals . . . 3 Access Codes. . . 12
Alarm test ....15
Anti Code Reset . 9,16,21
B
Battery ......10,24
Bell Delay ....9
Bell Duration . . 9
Bell in fire ....16
Bell Output ....8,24
Bell timer.....20
Board .......3
BS 4737 1986/87 . 1
C
Charge Voltage. . 24
Chime ......1
Codes .......1
Current
Consumption . . 24
D
Day mode ....10
Detectors .....2
Dimensions....24
Door bell .....9,16
Double knock . . 9,19
E
Engineer Code . . 9,12 Engineer program
mode .......11,23
Engineer Reset . . 9,16
Entry time ....9,14
Event log .....17
Exit Mode ....9,13,14
Exit time .....9,14
Exit/Entry timers . 24 Extension
speakers .....7
External bell
on Fire ......9
F
Factory set conditions. . . 9,11
Faults .......23
Final door set . . . 13,14
Fire zone .....6,18
Flag A ......16
Flag B ......17
Full Set ......13
Fuses .......3,23
H
Hold time.....22
I
Immediate zone . 13
K
Keyswitch zone . 9,18
L
light channel . . . 22 Light Hold Time . 9 Light threshold . . 9,22 Lighting
controller .....1,9,22
Local Authorit . . 3
M
Mains .......10,24
Managers code . . 12
N
NACOSS .....5
Normally closed
detectors .....23
Normally open
detector ......23
NVM.......1
O
Omit prevent . . . 9,19 Operating
temperature....24
P
PA ........1,7,24
PA fault......23
PCB Fuses ....24
Pressure mats. . . 24
Program 1 ....9,13
Program 2 ....9,13
Program 3 ....9,13
Programs
1,2and3.....14
PTS zone .....1,18
Push to Set ....5,9
Q
Quick set .....1
quote code ....21
R
Re-arm ......21
Rearm counter . . 9 Remote keypad . . 1,4 Remote
keyswitch.....6
RKP .......2,9,24
RKP PA enable. . 16
S
Security Zones . . 5,9,18 Service counter . . 9 Service timer . . . 20
Set........8
Set system ....11
Silent PA .....9,16
Silent Set .....13,14
Single key
setting ......9,16
Site Code .....9
Speakers .....2
Specification . . . 24 Standard
Fire zone .....6,9
Strobe on setting . 9,16
T
TADB .....8
Tamper ......24
Tamper fault . . . 23 Tamper network . 6 Terminated Set . . 5,13,14 Time inhibited
zone .......13,14
Timed.......13
Timed exit ....14
Timed zones . . . 14 Total current . . . 2
U
Unset system . . . 11 Unused zone . . . 13,14 User code 1 . . . 9
User 1 ......1
User 1 and 2
codes .......12
User 2 ......1
User code 2....9
User reset fire . . 9 User reset PA. . . 9
V
Volume ......7
W
Walk Test ....1,15
wire links .....3
Z
Zone Attributes. . 19 Zone debounce . . 9
zone delay ....19
Zone Input Delay. 24
Zone Type ....18
4188-693 issue 1_8/01 25
Engineering information Citadel XR1G3 Intruder system
Notes
26 4188-693 issue 1_8/01
Citadel XR1G3 Intruder system Engineering information
Servicing organisation Details
Servicing organisation name:
_______________________________________ Telephone number:
______________________________________ Date of installation:
______________________________________ Account Number:
_____________________________________
Resistance Area protection and equipment used (eg PIR, Contacts..)
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Parts
Below is a list of approved parts and accessories.
8EP 394 XR1 G3 panel 6EP 260 LED RKP 8EP 289 Extension Speaker 8EP 372 Opti-Cam Lighting Controller A range of detectors are also available, for more
information contact your supplier.
Servicing organisation Details
4188-693 issue 1_8/01 27
Engineering information Citadel XR1G3 Intruder system
(
)
Quick Reference
Reset
To exit engineer program mode
9
9
9
9
Quick Reference
Prog
Engineer Program Mode
Timers and Counters
(see page 20 & 21)
7
Zone Attributes
(see page 19)
6
Zone Type
(see page 18)
5
Not applicable
1
Flags B (see page 17)
4
Silent PA
1
Flags A (see page 16)
3
Bell timer
1
Double Knock
1
Zone 1 type
1
Bell delay timer
2
Omit Prevent
2
Zone 2 type
2
Not applicable
2
RKP PA enable
2
User Reset PA
3
Engineer reset
3
Service timer
3
Zone Delay
3
Zone 4 type
3
User Reset Fire
4
Anti-code reset
4
Re-arm counter
(00 to 99)
Anti-code reset
site code
5
4
Security
Disabled
Fire
1
2
0
Zone 6 type
Zone 5 type
5
4
Not applicable
Not applicable
5
6
Enable Door bell on PTS5Enable single key setting6Enable strobe on setting
24h Fire
3
Zone 7 type
6
Not applicable
7
7
PTS
4
Zone 8 type
7
Entry deviate
8
Keyswitch
5
Enable Bell in Fire
8
Reset
View the event log
(see page 17)
Chime
Set up program
(see page 13)
Prog
Lighting Controller
(see page 22)
9
Terminated set
Disabled
Timed
0
1
Timed Zones
Used Zones
1
Program 1
1
Channel 1
assigned zones
1
Time inhibit zones
2
3
Program 2
Program 3
2
3
Channel 2
assigned zones
Channel 3
assigned zones
2
3
Exit time
Entry time
4
Channel 4
assigned zones
4
Exit mode
5
6
Channel 5
assigned zones
Channel 6
assigned zones
Channel 7
5
assigned zones
7
6
Silent set
(use exit time)
Final Door Set
2
3
4
0 - 99%
Channel 9
Hold time (0-99s)
Channel 8
assigned zones
8
Set the light threshold
level
9
Prog
Walk test
sounder
High volume
sounder
6
5
The panel conform to the requirements of the
Codes
(see page 12)
8
Change User code 2
Change User code 1
2
1
Not applicable
3
Change Engineer’s code
9
For Technical Support
Alarm test
Low volume
Strobe test
Bell test
2
3
(see page 15)
1
4
European EMC and Low Voltage directives, and
: 0151 549 1550
carries the CE mark.
28 4188-693 issue 1_8/01
Loading...