Cisco Nexus 3000 Series Hardware
Installation Guide
December, 2013
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883
Text Part Number: OL-25338-04
Send document comments to nexus3k-docfeedback@cisco.com
THE SPECIFICATIONS AND INFORMATION REGARDING THE PRODUCTS IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL
STATEMENTS, INFORMATION, AND RECOMMENDATIONS IN THIS MANUAL ARE BELIEVED TO BE ACCURATE BUT ARE PRESENTED WITHOUT
WARRANTY OF ANY KIND, EXPRESS OR IMPLIED. USERS MUST TAKE FULL RESPONSIBILITY FOR THEIR APPLICATION OF ANY PRODUCTS.
THE SOFTWARE LICENSE AND LIMITED WARRANTY FOR THE ACCOMPANYING PRODUCT ARE SET FORTH IN THE INFORMATION PACKET THAT
SHIPPED WITH THE PRODUCT AND ARE INCORPORATED HEREIN BY THIS REFERENCE. IF YOU ARE UNABLE TO LOCATE THE SOFTWARE LICENSE
OR LIMITED WARRANTY, CONTACT YOUR CISCO REPRESENTATIVE FOR A COPY.
The following information is for FCC compliance of Class A devices: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio-frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case users will be required
to correct the interference at their own expense.
The following information is for FCC compliance of Class B devices: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If the equipment causes interference to radio or television reception, which can be
determined by turning the equipment off and on, users are encouraged to try to correct the interference by using one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Modifications to this product not authorized by Cisco could void the FCC approval and negate your authority to operate the product.
NOTWITHSTANDING ANY OTHER WARRANTY HEREIN, ALL DOCUMENT FILES AND SOFTWARE OF THESE SUPPLIERS ARE PROVIDED “AS IS” WITH
ALL FAULTS. CISCO AND THE ABOVE-NAMED SUPPLIERS DISCLAIM ALL WARRANTIES, EXPRESSED OR
LIMITATION, THOSE OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OR ARISING FROM A COURSE OF
DEALING, USAGE, OR TRADE PRACTICE.
IN NO EVENT SHALL CISCO OR ITS SUPPLIERS BE LIABLE FOR ANY INDIRECT, SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES, INCLUDING,
WITHOUT LIMITATION, LOST PROFITS OR LOSS OR DAMAGE TO DATA ARISING OUT OF THE USE OR INABILITY TO USE THIS MANUAL, EVEN IF CISCO
OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this
URL:
www.cisco.com/go/trademarks. Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership
relationship between Cisco and any other company. (1110R)
Any Internet Protocol (IP) addresses and phone numbers used in this document are not intended to be actual addresses and phone numbers. Any examples, command display
output, network topology diagrams, and other figures included in the document are shown for illustrative purposes only. Any use of actual IP addresses or phone numbers in
illustrative content is unintentional and coincidental.
Cisco Nexus 3000 Series Hardware Installation Guide
Send document comments to nexus3k-docfeedback@cisco.com
CONTENTS
Prefacevii
Audiencevii
Organizationvii
Conventionsviii
Related Documentationxiii
Release Notesxiv
Configuration Guidesxiv
Installation and Upgrade Guidesxiv
Licensing Guidexiv
Command Referencesxiv
Technical Referencesxiv
Error and System Messagesxiv
CHAPTER
Obtaining Documentation and Submitting a Service Requestxv
1Overview of the Cisco Nexus 3000 Series Switches1-1
Cisco Nexus 3016 Switch1-1
Chassis for the Cisco Nexus 3016 Switch1-2
Ports for the Cisco Nexus 3016 Switch1-3
Power Supply for the Cisco Nexus 3016 Switch1-4
Fan Tray for the Cisco Nexus 3016 Switch1-5
Port Connections for the Cisco Nexus 3016 Switch1-5
Cisco Nexus 3048 Switch1-6
Chassis for the Cisco Nexus 3048 Switch1-6
Ports for the Cisco Nexus 3048 Switch1-8
Power Supply for the Cisco Nexus 3048 Switch1-9
Fan Tray for the Cisco Nexus 3048 Switch1-10
Port Connections for the Cisco Nexus 3048 Switch1-10
Cisco Nexus 3064 Switch1-11
Chassis for the Cisco Nexus 3064 Switch1-12
Ports for the Cisco Nexus 3064 Switch1-13
Power Supply for the Cisco Nexus 3064 Switch1-14
Fan Tray for the Cisco Nexus 3064 Switch1-14
Port Connections for the Cisco Nexus 3064 Switch1-15
OL-25338-04
Cisco Nexus 3132Q Switch1-16
Cisco Nexus 3000 Series Hardware Installation Guide
iii
Contents
Send document comments to nexus3k-docfeedback@cisco.com
Chassis for the Cisco Nexus 3132Q Switch1-17
Ports for the Cisco Nexus 3132Q Switch1-18
Power Supply for the Cisco Nexus 3132Q Switch1-18
Fan Tray for the Cisco Nexus 3132Q Switch1-19
Transceiver and Cabling Options for the Cisco Nexus 3132Q Switch1-20
Cisco Nexus 3172PQ Switch1-21
Chassis for the Cisco Nexus 3172PQ Switch1-21
Ports for the Cisco Nexus 3172PQ Switch1-23
Power Supply for the Cisco Nexus 3172PQ Switch1-23
Fan Tray for the Cisco Nexus 3172PQ Switch1-24
Transceiver and Cabling Options for the Cisco Nexus 3172PQ Switch1-24
Cisco Nexus 3548 and Cisco Nexus 3524 Switches1-26
Chassis for the Cisco Nexus 3548 Switch1-27
Ports for the Cisco Nexus 3548 Switch1-28
Power Supply for the Cisco Nexus 3548 Switch1-29
Fan Tray for the Cisco Nexus 3548 Switch1-29
Port Connections for the Cisco Nexus 3548 Switch1-30
CHAPTER
CHAPTER
2Installing the Cisco Nexus 3000 Series Switches2-1
Preparing for Installation2-2
Installation Options with Racks and Cabinets2-2
Airflow Direction2-2
Chassis Weight2-3
Installation Guidelines2-3
Required Equipment2-4
Unpacking and Inspecting the Switch2-5
Installing the Switch2-5
Grounding the Switch2-10
Proper Grounding Practices2-11
Establishing the System Ground2-12
Required Tools and Equipment2-13
Grounding the Cisco Nexus 3000 Series Chassis2-13
Preventing Electrostatic Discharge Damage2-14
Starting the Switch2-17
3Connecting to the Network3-1
iv
Preparing for Network Connections3-2
Connecting to the Console Port3-2
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Contents
Send document comments to nexus3k-docfeedback@cisco.com
Connecting to the Management Port3-3
Connecting to a Server3-3
Installing and Replacing SFP or SFP+ Transceivers3-4
Installing an SFP or SFP+ Transceiver3-4
Replacing an SFP or SFP+ Transceiver3-5
Installing Optical Cables into SFP or SFP+ Transceivers3-5
Installing an Optical Cable into an SFP or SFP+ Transceiver3-6
Replacing an Optical Cable for an SFP or SFP+ Transceiver3-6
Maintaining SFP and SFP+ Transceivers and Fiber-Optic Cables3-7
CHAPTER
APPENDIX
APPENDIX
4Replacing Components4-1
Replacing a Power Supply4-1
Removing an AC Power Supply4-1
Installing an AC Power Supply4-2
Removing a DC Power Supply4-3
Installing a DC Power Supply4-4
Replacing a Fan Tray4-4
Removing a Fan Tray4-5
Installing a Fan Tray4-6
ACabinet and Rack SpecificationsA-1
Cabinet and Rack RequirementsA-1
General Requirements for Cabinets and RacksA-1
Requirements Specific to Perforated CabinetsA-2
Requirements Specific to Standard Open RacksA-2
Cable Management GuidelinesA-3
BTechnical SpecificationsB-1
APPENDIX
OL-25338-04
Switch SpecificationsB-1
Environmental SpecificationsB-1
Power SpecificationsB-2
CCable and Connector SpecificationsC-1
Console CableC-1
Console PortC-2
Supported Power Cords and PlugsC-2
Jumper Power CordC-8
Cisco Nexus 3000 Series Hardware Installation Guide
v
Contents
Send document comments to nexus3k-docfeedback@cisco.com
APPENDIX
APPENDIX
DLED DescriptionsD-1
Chassis and Module LEDs for the Cisco Nexus 3000 Series SwitchesD-1
Chassis and Module LED DescriptionsD-2
Power Supply StatusD-3
Port LEDsD-3
ESite Planning and Maintenance RecordsE-1
Site Preparation ChecklistE-1
Contact and Site InformationE-3
Chassis and Module InformationE-4
vi
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Send document comments to nexus3k-docfeedback@cisco.com
Preface
This preface describes the audience, organization, and conventions of the Cisco Nexus 3000 Series
Hardware Installation Guide. It also provides information on how to obtain related documentation.
Audience
To use this installation guide, you must be familiar with electronic circuitry and wiring practices and
preferably be an electronic or electromechanical technician.
Organization
This guide is organized as follows:
Chapter and TitleDescription
Chapter 1, “Overview of the
Cisco Nexus 3000 Series
Switches”
Chapter 2, “Installing the Cisco
Nexus 3000 Series Switches”
Chapter 3, “Connecting to the
Network”
Chapter 4, “Replacing
Components”
Appendix A, “Cabinet and Rack
Specifications”
Appendix B, “Technical
Specifications”
Appendix C, “Cable and
Connector Specifications”
Appendix D, “LED
Descriptions”
Appendix D, “Site Planning and
Maintenance Records”
Provides an overview of the Cisco Nexus 3000 Series switches.
Describes how to install the Cisco Nexus 3000 Series switches.
Describes how to connect the Cisco Nexus 3000 Series switches
to the Network.
Describes how to replace the field replaceable units (FRUs) on
Cisco Nexus 3000 Series switches.
Provides guidelines for selecting an enclosed cabinet or rack for
your Cisco Nexus 3000 Series switch.
Lists specifications for the Cisco Nexus 3000 Series switches and
components including modules, power supplies, and transceivers.
Lists cable and port specifications for the Cisco Nexus 3000
Series switches.
Describes the statuses indicated by the Cisco Nexus 3000 Series
chassis and component LEDs.
Provides site planning and maintenance records.
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
vii
Preface
Send document comments to nexus3k-docfeedback@cisco.com
Conventions
This document uses the following conventions for notes, cautions, and safety warnings.
Notes and Cautions contain important information that you should be aware of.
NoteMeans reader take note. Notes contain helpful suggestions or references to material that are not covered
in the publication.
CautionMeans reader be careful. You are capable of doing something that might result in equipment damage or
loss of data.
Safety warnings appear throughout this publication in procedures that, if performed incorrectly, can
cause physical injuries. A warning symbol precedes each warning statement.
Warning
Waarschuwing
Varoitus
IMPORTANT SAFETY INSTRUCTIONS
This warning symbol means danger. You are in a situation that could cause bodily injury. Before you
work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar
with standard practices for preventing accidents. Use the statement number provided at the end of
each warning to locate its translation in the translated safety warnings that accompanied this
device.
SAVE THESE INSTRUCTIONS
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Dit waarschuwingssymbool betekent gevaar. U verkeert in een situatie die lichamelijk letsel kan
veroorzaken. Voordat u aan enige apparatuur gaat werken, dient u zich bewust te zijn van de bij
elektrische schakelingen betrokken risico's en dient u op de hoogte te zijn van de standaard
praktijken om ongelukken te voorkomen. Gebruik het nummer van de verklaring onderaan de
waarschuwing als u een vertaling van de waarschuwing die bij het apparaat wordt geleverd, wilt
raadplegen.
BEWAAR DEZE INSTRUCTIES
TÄRKEITÄ TURVALLISUUSOHJEITA
Tämä varoitusmerkki merkitsee vaaraa. Tilanne voi aiheuttaa ruumiillisia vammoja. Ennen kuin
käsittelet laitteistoa, huomioi sähköpiirien käsittelemiseen liittyvät riskit ja tutustu
onnettomuuksien yleisiin ehkäisytapoihin. Turvallisuusvaroitusten käännökset löytyvät laitteen
mukana toimitettujen käännettyjen turvallisuusvaroitusten joukosta varoitusten lopussa näkyvien
lausuntonumeroiden avulla.
Statement 1071
viii
SÄILYTÄ NÄMÄ OHJEET
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Preface
Send document comments to nexus3k-docfeedback@cisco.com
Attention
Warnung
Avvertenza
IMPORTANTES INFORMATIONS DE SÉCURITÉ
Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une situation pouvant
entraîner des blessures ou des dommages corporels. Avant de travailler sur un équipement, soyez
conscient des dangers liés aux circuits électriques et familiarisez-vous avec les procédures
couramment utilisées pour éviter les accidents. Pour prendre connaissance des traductions des
avertissements figurant dans les consignes de sécurité traduites qui accompagnent cet appareil,
référez-vous au numéro de l'instruction situé à la fin de chaque avertissement.
CONSERVEZ CES INFORMATIONS
WICHTIGE SICHERHEITSHINWEISE
Dieses Warnsymbol bedeutet Gefahr. Sie befinden sich in einer Situation, die zu Verletzungen führen
kann. Machen Sie sich vor der Arbeit mit Geräten mit den Gefahren elektrischer Schaltungen und
den üblichen Verfahren zur Vorbeugung vor Unfällen vertraut. Suchen Sie mit der am Ende jeder
Warnung angegebenen Anweisungsnummer nach der jeweiligen Übersetzung in den übersetzten
Sicherheitshinweisen, die zusammen mit diesem Gerät ausgeliefert wurden.
BEWAHREN SIE DIESE HINWEISE GUT AUF.
IMPORTANTI ISTRUZIONI SULLA SICUREZZA
Questo simbolo di avvertenza indica un pericolo. La situazione potrebbe causare infortuni alle
persone. Prima di intervenire su qualsiasi apparecchiatura, occorre essere al corrente dei pericoli
relativi ai circuiti elettrici e conoscere le procedure standard per la prevenzione di incidenti.
Utilizzare il numero di istruzione presente alla fine di ciascuna avvertenza per individuare le
traduzioni delle avvertenze riportate in questo documento.
Advarsel
Aviso
CONSERVARE QUESTE ISTRUZIONI
VIKTIGE SIKKERHETSINSTRUKSJONER
Dette advarselssymbolet betyr fare. Du er i en situasjon som kan føre til skade på person. Før du
begynner å arbeide med noe av utstyret, må du være oppmerksom på farene forbundet med
elektriske kretser, og kjenne til standardprosedyrer for å forhindre ulykker. Bruk nummeret i slutten
av hver advarsel for å finne oversettelsen i de oversatte sikkerhetsadvarslene som fulgte med denne
enheten.
TA VARE PÅ DISSE INSTRUKSJONENE
INSTRUÇÕES IMPORTANTES DE SEGURANÇA
Este símbolo de aviso significa perigo. Você está em uma situação que poderá ser causadora de
lesões corporais. Antes de iniciar a utilização de qualquer equipamento, tenha conhecimento dos
perigos envolvidos no manuseio de circuitos elétricos e familiarize-se com as práticas habituais de
prevenção de acidentes. Utilize o número da instrução fornecido ao final de cada aviso para
localizar sua tradução nos avisos de segurança traduzidos que acompanham este dispositivo.
GUARDE ESTAS INSTRUÇÕES
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
ix
Preface
Send document comments to nexus3k-docfeedback@cisco.com
¡Advertencia!
Varning!
INSTRUCCIONES IMPORTANTES DE SEGURIDAD
Este símbolo de aviso indica peligro. Existe riesgo para su integridad física. Antes de manipular
cualquier equipo, considere los riesgos de la corriente eléctrica y familiarícese con los
procedimientos estándar de prevención de accidentes. Al final de cada advertencia encontrará el
número que le ayudará a encontrar el texto traducido en el apartado de traducciones que acompaña
a este dispositivo.
GUARDE ESTAS INSTRUCCIONES
VIKTIGA SÄKERHETSANVISNINGAR
Denna varningssignal signalerar fara. Du befinner dig i en situation som kan leda till personskada.
Innan du utför arbete på någon utrustning måste du vara medveten om farorna med elkretsar och
känna till vanliga förfaranden för att förebygga olyckor. Använd det nummer som finns i slutet av
varje varning för att hitta dess översättning i de översatta säkerhetsvarningar som medföljer denna
anordning.
SPARA DESSA ANVISNINGAR
Cisco Nexus 3000 Series Hardware Installation Guide
x
OL-25338-04
Preface
Send document comments to nexus3k-docfeedback@cisco.com
Aviso
Advarsel
INSTRUÇÕES IMPORTANTES DE SEGURANÇA
Este símbolo de aviso significa perigo. Você se encontra em uma situação em que há risco de lesões
corporais. Antes de trabalhar com qualquer equipamento, esteja ciente dos riscos que envolvem os
circuitos elétricos e familiarize-se com as práticas padrão de prevenção de acidentes. Use o
número da declaração fornecido ao final de cada aviso para localizar sua tradução nos avisos de
segurança traduzidos que acompanham o dispositivo.
GUARDE ESTAS INSTRUÇÕES
VIGTIGE SIKKERHEDSANVISNINGER
Dette advarselssymbol betyder fare. Du befinder dig i en situation med risiko for
legemesbeskadigelse. Før du begynder arbejde på udstyr, skal du være opmærksom på de
involverede risici, der er ved elektriske kredsløb, og du skal sætte dig ind i standardprocedurer til
undgåelse af ulykker. Brug erklæringsnummeret efter hver advarsel for at finde oversættelsen i de
oversatte advarsler, der fulgte med denne enhed.
GEM DISSE ANVISNINGER
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
xi
Preface
Send document comments to nexus3k-docfeedback@cisco.com
xii
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Preface
Send document comments to nexus3k-docfeedback@cisco.com
Related Documentation
Documentation for the Cisco Nexus 3000 Series Switch is available at the following URL:
Subscribe to the What’s New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed
and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free
service and Cisco currently supports RSS
technical documentation, at:
New in Cisco Product Documentation, which also lists all new and
Ve r si o n 2.0.
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
xv
Preface
Send document comments to nexus3k-docfeedback@cisco.com
xvi
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Send document comments to nexus3k-docfeedback@cisco.com
CHAPTER
1
Overview of the Cisco Nexus 3000 Series
Switches
This chapter provides an overview of the Cisco Nexus 3000 Series switches, which includes the Cisco
Nexus 3016, 3048, and 3064 switches. You can order these switches with fan trays and power supplies
that provide forward or reverse airflow for cooling and power supplies that connect to AC or DC power
sources.
This chapter includes the following sections:
•Cisco Nexus 3016 Switch, page 1-1
•Cisco Nexus 3048 Switch, page 1-6
•Cisco Nexus 3064 Switch, page 1-11
•Cisco Nexus 3132Q Switch, page 1-16
•Cisco Nexus 3172PQ Switch, page 1-21
•Cisco Nexus 3548 and Cisco Nexus 3524 Switches, page 1-26
Cisco Nexus 3016 Switch
The Cisco Nexus 3016 switch is a 1 rack unit (RU) switch that supports 16 fixed 40-Gigabit Ethernet
downlink (host-facing) and uplink (network-facing) ports, two fixed 100/1000 management ports, one
RS-232 console port, and one USB port. The switch includes one or two AC or DC power supply units
and one fan tray module, both of which provide either forward or reverse airflow for cooling. The switch
includes the Layer 3 license. To specify the appropriate Cisco Nexus 3016 switch bundle, see
Ta b l e 1-1Cisco Nexus 3016 Switch Bundles
Power SupplyAirflow DirectionLayer 3 LicensePart Number
Select when orderingSelect when orderingNoN3K-C3016-10GE
ACForwardYesN3K-C3016-FA-L3
ACReverseYesN3K-C3016-BA-L3
DCForwardYesN3K-C3016-FD-L3
DCReverseYesN3K-C3016-BD-L3
OL-25338-04
Tabl e 1-1.
Cisco Nexus 3000 Series Hardware Installation Guide
1-1
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3016 Switch
Send document comments to nexus3k-docfeedback@cisco.com
This section includes the following topics:
•Chassis for the Cisco Nexus 3016 Switch, page 1-2
•Ports for the Cisco Nexus 3016 Switch, page 1-3
•Power Supply for the Cisco Nexus 3016 Switch, page 1-4
•Fan Tray for the Cisco Nexus 3016 Switch, page 1-5
•Port Connections for the Cisco Nexus 3016 Switch, page 1-5
Chassis for the Cisco Nexus 3016 Switch
The 1-RU Cisco Nexus 3016 chassis (part number N3K-C3016-40GE) is 1.72 inches (4.37 cm) high,
17.3 inches (43.9 cm) wide, and 19.7 inches (50.8 cm) deep. This switch is designed for 19-inch (48.3
cm) racks. Its switch ports are at the rear of the chassis in close proximity to server ports, and the power
supplies and fan tray modules are accessible from the front for easy replacement. You can order this
switch with forward airflow or reverse airflow depending on whether the front of the switch is on a cold
aisle (forward airflow) or on a hot aisle (reverse airflow).
Fully populated with two power supplies and a fan tray, the switch weighs 20.5 pounds (9.3 kg) and can
be easily installed by one or two people.
Figure 1-1 shows the front of the Cisco Nexus 3016 chassis and identifies the components that you use
to install and connect the chassis. Figure 1-2 shows the rear of the chassis and identifies the components
that you use to install and connect the chassis.
Figure 1-1Front View of the Cisco Nexus 3016 Switch
1-2
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3016 Switch
Send document comments to nexus3k-docfeedback@cisco.com
1AC or DC power supply (2) (AC power supply shown)5Status LED
2Fan tray (1)6USB port (1)
3Management ports (2)7Console port (1)
4ID LED
Figure 1-2Rear View of the Cisco Nexus 3016 Switch
1ID LEDs340-Gigabit uplink or downlink ports (16)
2Status LED4Grounding pad
Ports for the Cisco Nexus 3016 Switch
The Cisco Nexus 3016 switch chassis includes the following ports:
•40-Gigabit Ethernet uplink or downlink ports (16 ports)
•100/1000 Ethernet management ports (2 ports)
•Console port (1 port)
•USB port (1 port)
The chassis has 16 40-Gigabit Ethernet ports that you can connect to hosts (uplink connections) or
servers (downlink connections), which are often in the same rack or a nearby rack. Each of these ports
uses a QSFP+ transceiver which is connected to one or four optical or copper cables. If one cable is used,
it has a QSFP+ transceiver on the other end. If four cables are used, each of those cables has an SFP+
transceiver on the other end. The ports are numbered from left to right from 1 to 16 with the
odd-numbered ports on top and the even-numbered ports on the bottom.
Two 100/1000 Ethernet management ports enable you to manage switch operations. You can connect to
the switch through these two ports by using an RJ-45 connector on a copper cable.
One console port enables you to initially configure the switch and to perform troubleshooting operations.
You use an RJ-45 connector with a copper cable to connect to this port.
One USB port enables you to save or load switch configurations.
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
1-3
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3016 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Power Supply for the Cisco Nexus 3016 Switch
The Cisco Nexus 3000 Series switch has two slots for power supplies that are initially installed with one
or two AC or DC power supplies that have forward or reverse airflow for their cooling. The switch
requires only one power supply for its operations, but you can include a second one for redundancy.
To determine which part number to use when ordering replacement power supplies, see Tab le 1-2.
Ta b l e 1-2Cisco Nexus 3016 Power Supply Part Numbers
Power SourceAirflow DirectionPower Supply Part Number
ACForwardN2200-PAC-400W=
ACReverseN2200-PAC-400W-B=
DCForwardN2200-PDC-400W=
DCReverseN3K-PDC-350W-B=
If the chassis has two power supplies, you can hot swap one of the power supplies during operations. If
the chassis has only one power supply, you can install the new power supply in the open slot, turn on that
power supply, and then remove the original power supply during operations.
CautionYou can order replacement power supplies with forward airflow or reverse airflow. Be sure to order the
same direction of airflow as is used with the switch. If there is a black stripe across the front of the fan
trays and power supplies, the switch is running reverse airflow and you must order power supplies with
reverse airflow (each module has a black stripe). If there is no black stripe across the front of these
modules, the switch is running forward airflow and you must order replacement modules with forward
airflow (modules that do not have a black stripe).
CautionThe switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
NoteNever leave a power supply slot empty. If you remove a power supply, replace it with another one. If you
do not have a replacement power supply, leave the non functioning one in place until you can replace it
or fill the slot with a filler blank module (part number N2200-P-BLNK).
For power supply specifications, see the “Power Specifications” section on page B-2. For information
about the power supply LEDs and what they indicate, see the “Power Supply Status” section on
page D-3.
1-4
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3016 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Fan Tray for the Cisco Nexus 3016 Switch
The Cisco Nexus 3016 switch ships with one fan tray, which is the same fan tray used by the Cisco Nexus
3064 switch (part number N3K-C3064-FAN for forward airflow or N3K-C3064-FAN-B for reverse
airflow). You can hot swap the fan tray during operations but must replace it within two minutes or the
switch can reach an overtemperature condition and shut down.
CautionYou can order a replacement fan tray with forward airflow or reverse airflow. Be sure to order the same
direction of airflow as is used with the switch. If there is a black stripe across the front of the fan trays
and power supplies, the switch is running reverse airflow and you must order a fan tray with reverse
airflow. If there is no black stripe across the front of these modules, the switch has forward airflow and
you must order replacement modules with forward airflow.
CautionThe switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
Port Connections for the Cisco Nexus 3016 Switch
You use QSFP+ transceivers with the 16 networking ports used for uplinking and downlinking. For
low-cost connections to switches in the same or adjacent racks, use QSFP+ transceivers with copper
cables. For long distance connections, use the QSFP transceivers connected to optical cables.
Tabl e 1-3 describes the QSFP+ transceivers and cable connections that you can use with the 16 ports
used for uplinks and downlinks.
Ta b l e 1-3QSFP+ Transceivers and Cables Used with the Cisco Nexus 3016 Switch Uplink and
Downlink Ports
Part NumberTransceivers and Cables
QSFP-40G-SR440-Gigabit SR4 QSFP transceiver on both ends of an optical cable. Used for
distances up to 100 meters.
QSFP-H40G-CU1M40-Gigabit transceiver with a 1-meter passive copper cable
QSFP-H40G-CU3M40-Gigabit transceiver with a 3-meter passive copper cable
QSFP-H40G-CU5M40-Gigabit transceiver with a 5-meter passive copper cable
QSFP-4SFP10G-CU1M 40-Gigabit transceiver connected to four 1-meter passive copper cables, each
connected to an SFP+ transceiver
QSFP-4SFP10G-CU3M 40-Gigabit transceiver connected to four 3-meter passive copper cables, each
connected to an SFP+ transceiver
QSFP-4SFP10G-CU5M 40-Gigabit transceiver connected to four 5-meter passive copper cables, each
connected to an SFP+ transceiver
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
1-5
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3048 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Cisco Nexus 3048 Switch
The Cisco Nexus 3048 switch is a 1 rack unit (RU) switch that supports 48 fixed 10/100/1000 Ethernet
downlink (server-facing) ports, four fixed 10-Gigabit Ethernet uplink (network-facing) ports, two fixed
100/1000 management ports, and one console port. The switch includes one or two AC or DC power
supply units and one fan tray module, both of which provide either forward or reverse airflow for
cooling. The switch includes a Layer 3 license. To order the appropriate Cisco Nexus 3048 switch
bundle, see
Ta b l e 1-4Cisco Nexus 3048 Switch Bundles
Power SupplyAirflow DirectionLayer 3 LicensePart Number
Select when orderingSelect when orderingNoN3K-C3048TP-1GE
ACForwardYe sN3K-C3048-FA-L3
ACReverseYesN3K-C3048-BA-L3
DCForwardYe sN3K-C3048-FD-L3
DCReverseYesN3K-C3048-BD-L3
Tabl e 1-4.
This section includes the following topics:
•Chassis for the Cisco Nexus 3048 Switch, page 1-6
•Ports for the Cisco Nexus 3048 Switch, page 1-8
•Power Supply for the Cisco Nexus 3048 Switch, page 1-9
•Fan Tray for the Cisco Nexus 3048 Switch, page 1-10
•Port Connections for the Cisco Nexus 3048 Switch, page 1-10
Chassis for the Cisco Nexus 3048 Switch
The 1-RU Cisco Nexus 3048 chassis (part number N3K-C3048TP-1GE) is 1.72 inches (4.37 cm) high,
17.3 inches (43.9 cm) wide, and 19.7 inches (50.8 cm) deep. This switch is designed for 19-inch (48.3
cm) racks. Its switch ports are at the rear of the chassis in close proximity to server ports, and the power
supplies and fan tray forward airflow or reverse airflow depending on whether the front of the switch is
on a cold aisle (forward airflow) or on a hot aisle (reverse airflow). You can also order the switch with
AC or DC power supplies.
Fully populated with two power supplies and a fan tray, the switch weighs 20.5 pounds (9.3 kg) and can
be easily installed by one or two people.
Figure 1-3 shows the front of the Cisco Nexus 3048 chassis and identifies the components that you use
to install and connect the chassis. Figure 1-4 shows the rear of the chassis and identifies the components
that you use to install and connect the chassis.
1-6
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3048 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Figure 1-3Front View of the Cisco Nexus 3048 Switch
1AC or DC power supply (2) (AC power supplies shown)5Status LED
2Fan tray (1)6USB port (1)
3Management ports (2)7Console port (1)
4ID LED
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
1-7
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3048 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Figure 1-4Rear View of the Cisco Nexus 3048 Switch
1ID and Status LEDs31- and 10-Gigabit Ethernet uplink ports (4)
210/100/1000 Ethernet downlink ports (48)4Grounding pad
Ports for the Cisco Nexus 3048 Switch
The Cisco Nexus 3048 switch chassis includes the following ports:
•10/100/1000 Ethernet downlink ports (48 ports)
•1- and 10-Gigabit Ethernet uplink ports
•100/1000 Ethernet management ports (2 ports)
•Console port (1 port)
•USB port (1 port)
The chassis has 48 10/100/1000 Ethernet downlink ports that you connect to servers, which are often in
the same rack or a nearby rack. You use RJ-45 connectors with copper cables to connect the switch to
the servers. The ports are numbered from left to right from 1 to 48 with the odd-numbered ports on top
and the even-numbered ports on the bottom.
You use up to four 1- and 10-Gigabit Ethernet uplink ports to connect the switch to one to four hosts or
switches. You use an SFP or SFP+ transceiver for each of these ports.
Two 100/1000 Ethernet management ports enable you to manage switch operations. You can connect to
the switch through these two ports by using an RJ-45 connector on a copper cable.
One console port enables you to initially configure the switch and to perform troubleshooting operations.
You use an RJ-45 connector with a copper cable to connect to this port.
1-8
One USB port enables you to save or load switch configurations.
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3048 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Power Supply for the Cisco Nexus 3048 Switch
The Cisco Nexus 3000 Series switch has two slots for power supplies that are initially installed with one
or two AC or DC power supplies that have forward or reverse airflow for their cooling. The switch
requires only one power supply for its operations, but you can include a second one for redundancy.
To determine which part number to use when ordering replacement power supplies, see Tab le 1-5.
Ta b l e 1-5Cisco Nexus 3048 Power Supply Part Numbers
Power SourceAirflow DirectionPower Supply Part Number
ACForwardN2200-PAC-400W=
ACReverseN2200-PAC-400W-B=
DCForwardN2200-PDC-400W=
DCReverseN3K-PDC-350W-B=
If the chassis has two power supplies, you can hot swap one of the power supplies during operations. If
the chassis has only one power supply, you can install the new power supply in the open slot, turn on that
power supply, and then remove the original power supply during operations.
CautionYou can order replacement power supplies with front-to-back airflow or back-to-front airflow. Be sure
to order the same direction of airflow as is used with the switch. If there is a black stripe across the front
of the fan trays and power supplies, the switch is running back-to-front airflow and you must order power
supplies with back-to-front airflow. If there is no black stripe across the front of these modules, the
switch is running front-to-back airflow and you must order replacement modules with front-to-back
airflow.
CautionThe switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
NoteNever leave a power supply slot empty. If you remove a power supply, replace it with another one. If you
do not have a replacement power supply, leave the non functioning one in place until you can replace it
or fill the slot with a filler blank module (part number N2200-P-BLNK).
For power supply specifications, see the “Power Specifications” section on page B-2. For information
about the power supply LEDs and what they indicate, see the “Power Supply Status” section on
page D-3.
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
1-9
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3048 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Fan Tray for the Cisco Nexus 3048 Switch
The Cisco Nexus 3048 switch ships with one fan tray, which provides forward airflow from the fan tray
to the port connector end exhaust (spares part number N3K-C3048-FAN=) or reverse airflow from the
port connectors end of the chassis to the fan tray for exhaust (spares part number N3K-C3048-FAN-B).
You can hot swap the fan tray during operations but must replace it within two minutes or the switch can
reach an overtemperature condition and shut down.
CautionYou can order a replacement fan tray with forward airflow or reverse airflow. Be sure to order the same
direction of airflow that is used with the switch. If there is a black stripe across the front of the fan trays
and power supplies, the switch is running reverse airflow and you must order a fan tray with reverse
airflow. If there is no black stripe across the front of these modules, the switch has forward airflow and
you must order replacement modules with forward airflow.
CautionThe switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
Port Connections for the Cisco Nexus 3048 Switch
You use RJ-45 connectors with copper cables for the downlink ports, management ports, and console
port, and you use SFP or SFP+ transceivers for the uplink ports.
The 4 uplink ports support SFP and SFP+ transceivers that are either connected to copper cables or can
be connected to optical cables.
can use. Tabl e 1-7 describes the SFP transceivers and cable connections that you can use.
Ta b l e 1-6SFP Transceivers and Cables for the Cisco Nexus 3048 Switch Uplink Ports
Part NumberTransceivers and Cables
GLC-T1000BASE-T SFP transceiver
GLC-SX-MMGigabit Ethernet multimode fiber (MMF) SFP transceiver with an LC connector of
type SX
GLC-LH-SMGigabit Ethernet single-mode fiber (SMF) SFP transceiver with an LC connector of
type LX/LH
Tabl e 1-6 describes the SFP+ transceivers and cable connections that you
1-10
Cisco Nexus 3000 Series Hardware Installation Guide
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3064 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Ta b l e 1-7SFP+ Transceivers and Cables for the Cisco Nexus 3048 Switch Uplink Ports
Part NumberTransceivers and Cables
SFP-10G-SR10-Gigabit Ethernet—short range SFP+ module
SFP-10G-LR10-Gigabit Ethernet—long range SFP+ module
SFP-H10GB-CU1M10-Gigabit Ethernet transceiver connected to a passive 1-meter copper cable
SFP-H10GB-CU3M10-Gigabit Ethernet transceiver connected to a passive 3-meter copper cable
SFP-H10GB-CU5M10-Gigabit Ethernet transceiver connected to a passive 5-meter copper cable
SFP-H10GB-ACU7M10-Gigabit Ethernet transceiver connected to an active 7-meter copper cable
SFP-H10GB-ACU10M 10-Gigabit Ethernet transceiver connected to an active 10-meter copper cable
Cisco Nexus 3064 Switch
The Cisco Nexus 3064 is a 1 rack unit (RU) switch that supports 48 fixed 1- and 10-Gigabit Ethernet
host ports, four fixed 40-Gigabit Ethernet network ports, two fixed 100/1000 management ports, and one
console port. The switch includes one or two AC or DC power supply units and one fan tray module,
both of which provide forward or reverse airflow for cooling. The switch includes a Layer 3 license. The
Cisco Nexus 3064 delivers ultra-low nominal latency and supports power-on auto provisioning and
consumes low power. To order the appropriate Cisco Nexus 3064 switch bundle, see
Tabl e 1-8.
Ta b l e 1-8Cisco Nexus 3064 Switch Bundles
Power SupplyAirflow DirectionLayer 3 LicensePart Number
Select when orderingSelect when orderingNoN3K-C3064PQ-10GE
N3K-C3064PQ-10GX
ACForwardYesN3K-C3064-E-FA-L3
N3K-C3064-X-FA-L3
ACReverseYesN3K-C3064-E-BA-L3
N3K-C3064-X-BA-L3
DCForwardYesN3K-C3064-E-FD-L3
N3K-C3064-X-FD-L3
DCReverseYesN3K-C3064-E-BD-L3
N3K-C3064-X-BD-L3
This section includes the following topics:
•Chassis for the Cisco Nexus 3064 Switch, page 1-12
•Ports for the Cisco Nexus 3064 Switch, page 1-13
•Power Supply for the Cisco Nexus 3064 Switch, page 1-14
•Fan Tray for the Cisco Nexus 3064 Switch, page 1-14
•Port Connections for the Cisco Nexus 3064 Switch, page 1-15
OL-25338-04
Cisco Nexus 3000 Series Hardware Installation Guide
1-11
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
1
2
1
239974
6
7
3
4
5
Cisco Nexus 3064 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Chassis for the Cisco Nexus 3064 Switch
The 1-RU Cisco Nexus 3064 chassis (part number N3K-C3064PQ-10GE or N3K-C3064PQ-10GX) is
1.72 inches (4.37 cm) high, 17.3 inches (43.9 cm) wide, and 19.7 inches (45.0 cm) deep. This switch is
designed for 19-inch (48.3 cm) racks. Its switch ports are at the rear of the chassis in close proximity to
server ports, and the power supplies and fan tray modules are accessible from the front for easy
replacement. You can order this switch with forward or reverse airflow depending on whether the front
of the switch is in a cold aisle (forward airflow) or in a hot aisle (reverse airflow). You can also order the
switch with AC or DC power supplies.
Fully populated with two power supplies and a fan tray, the switch weighs 20.5 pounds (9.3 kg) and can
be easily installed by one or two people.
Figure 1-5 shows the front of the chassis and identifies the components that you use to install and
connect the chassis. Figure 1-6 shows the rear of the chassis and identifies the components that you use
to install and connect the chassis.
Figure 1-5Front View of the Cisco Nexus 3064 Switch
1AC or DC power supply (2) (AC power supply shown)5Status LED
2Fan tray (1)6USB port (1)
3Management ports (2)7Console port (1)
4ID LED
Cisco Nexus 3000 Series Hardware Installation Guide
1-12
OL-25338-04
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3064 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Figure 1-6Rear View of the Cisco Nexus 3064 Switch
1
2
3
1ID and Status LEDs340-Gigabit Ethernet uplink ports (4)
21- and 10-Gigabit Ethernet downlink ports (48) 4Grounding pad
Ports for the Cisco Nexus 3064 Switch
The switch chassis includes the following ports:
•1- and 10-Gigabit Ethernet downlink ports (48 ports)
•40-Gigabit Ethernet uplink ports (4 ports, each handling 4 x 10-Gigabit Ethernet)
•100/1000 Ethernet management ports (2 ports)
•Console port (1 port)
•USB port (1 port)
The chassis has 48 1- and 10-Gigabit Ethernet downlink ports that you connect to servers, which are
often in the same rack or a nearby rack. You use Small Form factor Pluggable Plus (SFP+) transceivers
with copper or optical cables to connect the switch to the servers. The ports are numbered from left to
right from 1 to 48 with the odd-numbered ports on top and the even-numbered ports on the bottom.
You use up to four 40-Gigabit Ethernet uplink ports to connect the switch to one to four hosts or
switches. You use a Quad SFP+ (QSFP+) transceiver for each of these ports. That transceiver is either
already connected to four copper cables, each handling 10 Gigabits of data, with a SFP+ transceiver on
each cable, or you connect an optical cable to the QSFP+ transceiver and to another QSFP+ transceiver
on another switch.
4
239975
OL-25338-04
Two 100/1000 Ethernet management ports enable you to manage switch operations. You can connect to
the switch through these two ports by using an RJ-45 connector on a copper cable.
One console port enables you to initially configure the switch and to perform troubleshooting operations.
You use an RJ-45 connector with a copper cable to connect to this port.
One USB port enables you to save or load switch configurations.
Cisco Nexus 3000 Series Hardware Installation Guide
1-13
Chapter 1 Overview of the Cisco Nexus 3000 Series Switches
Cisco Nexus 3064 Switch
Send document comments to nexus3k-docfeedback@cisco.com
Power Supply for the Cisco Nexus 3064 Switch
The Cisco Nexus 3000 Series switch has two slots for power supplies that are initially installed with one
or two AC or DC power supplies that have forward or reverse airflow for their cooling. The switch
requires only one power supply for its operations, but you can include a second one for redundancy.
To determine which part number to use when ordering replacement power supplies, see Tab le 1-9.
Ta b l e 1-9Cisco Nexus 3064 Power Supply Part Numbers
Power SourceAirflow DirectionPower Supply Part Number
ACForwardN2200-PAC-400W=
ACReverseN2200-PAC-400W-B=
DCForwardN2200-PDC-400W=
DCReverseN3K-PDC-350W-B=
If the chassis has two power supplies, you can hot swap one of the power supplies during operations. If
the chassis has only one power supply, you can install the new power supply in the open slot, turn on that
power supply, and then remove the original power supply during operations.
CautionYou can order replacement power supplies with front-to-back airflow or back-to-front airflow. Be sure
to order the same direction of airflow as is used with the switch. If there is a black stripe across the front
of the fan trays and power supplies, the switch is running back-to-front airflow and you must order power
supplies with back-to-front airflow. If there is no black stripe across the front of these modules, the
switch is running front-to-back airflow and you must order replacement modules with front-to-back
airflow.
CautionThe switch must run with all of its power supply and fan tray modules taking in air from a cold aisle and
exhausting air to the hot aisle. If they take in air from a hot aisle, an overtemperature condition can occur
and the switch will shut down. If the airflow directions are mixed in the same switch, you will see an
error.
NoteNever leave a power supply slot empty. If you remove a power supply, replace it with another one. If you
do not have a replacement power supply, leave the non functioning one in place until you can replace it
or fill the slot with a filler blank module (part number N2200-P-BLNK).
For power supply specifications, see the “Power Specifications” section on page B-2. For information
about the power supply LEDs and what they indicate, see the “Power Supply Status” section on
page D-3.
Fan Tray for the Cisco Nexus 3064 Switch
The Cisco Nexus 3064 switch ships with one fan tray, which provide either forward or reverse airflow
for cooling. You can hot swap the fan tray during operations but must replace it within two minutes or
the switch can reach an overtemperature condition and shut down.
Cisco Nexus 3000 Series Hardware Installation Guide
1-14
OL-25338-04