CS5463: Determining No-load Condition Without
Violating Starting Condition Standards
1. INTRODUCTION
AN337
When the CS5463 is used in power meter application s, some customers use the I
threshold for the external microprocesso r to decide if the meter is under the no-load condition, and then find
the meter can not pass the starting test. This applications note gives the reason and the correct solution.
2. NO-LOAD AND STARTING CONDITIONS
According to the standard IEC 62053-22, the definition of a no -load condition is defined as: "Wh en the voltage is applied with no current flowing in the current circuit, the test output of the meter shall not produce
more than one pulse.". The test of starting condition is defined as: "The meter shall start and continue to
register at 0.001In and unity power factor.".
To meet these requirements, a power meter has to use the corre ct no-load threshold in order to restrain the
pulse output and energy accumulation when there is no load current but resume pulse output and energy
accumulation when the load is above the starting current (I
).
st
3. DETERMINING A NO-LOAD CONDITION CORRECTLY
The CS5463 has three energy pulse outputs (E1, E2, and E3). The pulse outputs un der no -loa d o r starting
condition has been well manipulated by the CS5463. In addition, the CS5463 has a no-load threshold register (LOAD
magnitude of the P
Different from the energy pulses, the energy register, either mechanical or electronic, is normally manipulated by a microcontroller. The microcontroller needs to use a variable and a thre shold value to decide if the
meter is under a no-load condition, in which case the values in the power registers should be discarded.
) to help disable the active energy pulse output under some specified condition. When the
Min
register is less than LOAD
Active
, the active energy pulse output is disabled.
Min
residual value as the
RMS
There are two options to select the variable and the threshold.
Variable
Used
I
RMS
P
Active
Threshol d Value
R es idu a l va lue (A C of fs et) wi th
inputs of U
Less than the value with inputs of U
and starting current
an d no cu r re nt
n
Table 1: Variable & Threshold Values Comparison
Because I
to determine the no-load condition.
http://www.cirrus.com
exhibits much more system noise than P
RMS
Copyright © Cirrus Logic, Inc. 2008
(All Rights Reserved)
Active
Com pare
Result
BAD
n
GOOD
, I
should not be used as a variable
RMS
DEC '08
AN337REV1
AN337
For example, assume a 10(60)A Class 0.5 watt-hour meter using a 200 uΩ shunt as the current sensor. The
voltage on the CS5463 I-channel input (IIN±) with the starting current (I
well below the I-channel noise level. Therefore, if I
was used to decide the no-load condition, the meter
RMS
will not pass the no-load and starting tests. Even though the meter has lower than 2 uV noise level and passes the no-load test, this application can not be used as a 5(60)A meter because the noise level is fixed within
the application, however the starting current would be 50% lower.
=0.1%Ib) will be 2 uV which is
st
In the next example, P
is used as the variable.
Active
Assume the following:
• A 5(60)A Class 0.5 watt-hour meter, AC gain calibrated, with inputs of U
•P
•P
•P
Typically, the residual value in the P
_Imax = 0.36 (decimal register value, same below) with inputs of Un and I
Active
_Ib = 0.03 with inputs of Un and I
Active
_Starting = 0.00003 with inputs of Un and starting current (Ist = 0.1% Ib)
Active
Active
b
register P
_Residual is less than 0.000002 (with 150 mVrms
Active
and I
n
max
max
on VIN± and no signal on IIN±, HPFs enabled, N = 4000).
Because P
_Residual and P
P
Active
_Starting >> P
Active
_Starting (a threshold of 0.00001, for example) to allow th e meter pa ss the n o-
Active
_Residual, the threshold can easily be selected between
Active
load and starting tests.
Furthermore, if the meter is well designed and has very low system noise, the threshold can be set even
lower (e.g. 0.000005) to allow much smaller starting current which is more welcomed by electric utilities.
The meter current dynamic range (I
max/Ib
) can also be extended.
Contacting Cirrus Logic Support
For all product questions and inquiries contact a Cirrus Logic Sales Representative.
To find one nearest you go to http://www.cirrus.com
IMPORTANT NOTICE
Cirrus Logic, Inc. and its subsidiaries ("Cirrus") believe that the information contained in this document is accurate and reliable. However, the information is subject
to change without not ice and is provi ded "AS IS" wi thout warran ty of any kind (express or implied). Customers are advised to obtain the latest version of relevant
information to verify, before placing orders, that information being relied on is current and complete. All products are sold subject to the terms and conditions of sale
supplied at the time of order acknowle dgment, including tho se pertaining to warranty, ind emnification, and limita tion of liability. No responsibility is assumed by Cirrus
for the use of this information, including use of this inform ation as the b asis for ma nufacture or sale of any item s, or for infringement of patents or other rights of third
parties. This document is the property of Cirrus and by furnishing this information, Cirrus grants no license, express or implied under any patents, mask work rights,
copyrights, trademarks, trade secrets or other intellectual p roperty rights. Cirrus owns the copyr ights associated with the information con tained herein and gives consent for copies to be made of the information only for use within your organization with respect to Cirrus inte grated circu its or other products of Cirrus. This consent
does not extend to other copying such as copying for general distribution, advertising or promotional purposes, or for creating any work for resale.
CERTAIN APPLICATIONS USING SEMICONDUCTOR PRODUCTS MAY INVOLVE POTENTI AL RISKS OF DEATH, PERSONAL INJURY, OR SEVERE PROPERTY OR ENVIRONMENTAL DAMAGE ("CRITICAL APPLICATIONS"). CIRRUS PRODUCTS ARE NOT DESIGNED, AUTHORIZED OR WARRANTED FOR USE
IN PRODUCTS SURGICALLY IMPLANTED INTO THE BODY, AUTOMO TIVE SAFETY OR SECU RITY DEVICES, LIFE SUPPO RT PRODUCTS OR OTHE R CRITICAL APPLICATIONS. INCLUSION OF CIRRUS PRODUCTS IN SUCH APPLICATIONS IS UNDERSTOOD TO BE FULLY AT THE CUSTOMER'S RISK AND
CIRRUS DISCLAIMS AND MAKES NO WARRANTY, EXPRESS, STATUTORY OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR PARTICULAR PURPOSE, WITH REGARD TO ANY CIRRUS PRODUCT THAT IS USED IN SUCH A MANNER. IF THE CUSTOMER OR
CUSTOMER'S CUSTOMER USES OR PERMITS THE USE OF CIRRUS PRODUCTS IN CRITICAL APPLICATIONS, CUSTOMER AGREES, BY SUCH USE, TO
FULLY INDEMNIFY CIRRUS, ITS OFFICERS, DIRECTORS, EMPLOYEES, DISTRIBUTORS AND OTHER AGENTS FROM ANY AND AL L LI ABI LI TY, I NCLUDING ATTORNEYS' FEES AND COSTS, THAT MAY RESULT FROM OR ARISE IN CONNECTION WITH THESE USES.
Cirrus Logic, Cirr us, and t he Cir rus Logi c lo go desi gns are tr ademark s of Ci rrus Logic, Inc. All othe r brand and product names in this
document may be trademarks or service marks of their respective owners.
2 AN337REV1