CIRCUTOR CEM-C31-T1, CEM-C31-T1-MID, CEM-C31-485-T1, CEM-C31-485-T1-MID, CEM-C31-485-DS Instruction Manual

...
Multifunctional energy meter
CEM-C31-T1, CEM-C31-T1-MID
CEM-C31-485-T1, CEM-C31-485-T1-MID
CEM-C31-485-DS, CEM-C31-485-DS-MID
INSTRUCTION MANUAL
(M017B01-03-20B)
CEM-C31
2
CEM-C31

SAFETY PRECAUTIONS

Follow the warnings described in this manual with the symbols shown below.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of  re. Read the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout the unit’s working life. Pay special attention to the installation stan­dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.

DISCLAIMER

CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device speci cations and the most updated manuals.
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.
3
CEM-C31

CONTENTS

SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3 DISCLAIMER ����������������������������������������������������������������������������������������������������������������������������������������������������������3 CONTENTS ������������������������������������������������������������������������������������������������������������������������������������������������������������� 4 REVISION LOG �������������������������������������������������������������������������������������������������������������������������������������������������������5 SYMBOLS ��������������������������������������������������������������������������������������������������������������������������������������������������������������� 5 1�- VERIFICATION UPON RECEPTION ����������������������������������������������������������������������������������������������������������������� 6 2�- PRODUCT DESCRIPTION �������������������������������������������������������������������������������������������������������������������������������� 6 3�- DEVICE INSTALLATION ����������������������������������������������������������������������������������������������������������������������������������� 7
3�1�- PRELIMINARY RECOMMENDATIONS ����������������������������������������������������������������������������������������������������7 3�2�- INSTALLATION �����������������������������������������������������������������������������������������������������������������������������������������8 3�3�- DEVICE TERMINALS �������������������������������������������������������������������������������������������������������������������������������� 8
3�3�1� MODEL CEM-C31-T1 �������������������������������������������������������������������������������������������������������������������������8 3�3�2� MODEL CEM-C31-485-T1 ������������������������������������������������������������������������������������������������������������������ 9
3�3�3� MODEL CEM-C31-485-DS �����������������������������������������������������������������������������������������������������������������9 3�4�- CONNECTION DIAGRAM ����������������������������������������������������������������������������������������������������������������������� 10 3�5�- CONNECTIONS ��������������������������������������������������������������������������������������������������������������������������������������� 11
4�- OPERATION ���������������������������������������������������������������������������������������������������������������������������������������������������13
4�1�- BUTTON FUNCTIONS ����������������������������������������������������������������������������������������������������������������������������13 4�2�- DISPLAY ��������������������������������������������������������������������������������������������������������������������������������������������������14 4�3�- LED INDICATORS ����������������������������������������������������������������������������������������������������������������������������������� 15 4�4�- IMPULSE OUTPUT (CEM-C31-T1 and CEM-C31-485-T1 models) ������������������������������������������������������15 4�5�- DIGITAL INPUT (CEM-C31-485-DS) ������������������������������������������������������������������������������������������������������� 16
5�- DISPLAY ����������������������������������������������������������������������������������������������������������������������������������������������������������17
5�1�- DISPLAY IN STANDBY MODE ����������������������������������������������������������������������������������������������������������������17 5�2�- DISPLAY IN READING MODE ����������������������������������������������������������������������������������������������������������������20 5�3�- INSTANTANEOUS VALUE DISPLAY ������������������������������������������������������������������������������������������������������21 5�4�- PARTIAL ENERGY DISPLAY ������������������������������������������������������������������������������������������������������������������ 23 5�5�- IMPULSE COUNT DISPLAY (CEM-C31-485-DS) ����������������������������������������������������������������������������������� 26 5�6�- MANUFACTURER INFORMATION SCREEN ����������������������������������������������������������������������������������������� 27
6�- CONFIGURATION ����������������������������������������������������������������������������������������������������������������������������������������29
6�1�- RELEVANT PARAMETERS CONFIGURATION ������������������������������������������������������������������������������������� 29
6�1�1� VOLTAGE PRIMARY TRANSFORMATION RATIO ������������������������������������������������������������������������� 29
6�1�2� VOLTAGE SECONDARY TRANSFORMATION RATIO ������������������������������������������������������������������� 30
6�1�3� CURRENT PRIMARY TRANSFORMATION RATIO ������������������������������������������������������������������������30
6�1�4� CURRENT SECONDARY TRANSFORMATION RATIO ������������������������������������������������������������������ 31
6�1�5� EXITING THE SETUP MENU �����������������������������������������������������������������������������������������������������������31 6�2�- GENERAL CONFIGURATION MENU ����������������������������������������������������������������������������������������������������� 32
6�2�1� IMPULSE OUTPUT WEIGHT ����������������������������������������������������������������������������������������������������������� 32
6�2�2� IMPULSE OUTPUT TYPE ���������������������������������������������������������������������������������������������������������������� 33
6�2�3�- DIGITAL INPUT TYPE ��������������������������������������������������������������������������������������������������������������������� 33
6�2�4� PERIPHERAL ADDRESS ����������������������������������������������������������������������������������������������������������������� 34
6�2�5� TRANSMISSION SPEED ( BAUD RATE) ���������������������������������������������������������������������������������������� 35
6�2�6� TYPE OF COMMUNICATIONS �������������������������������������������������������������������������������������������������������� 35
6�2�7� DISPLAY ������������������������������������������������������������������������������������������������������������������������������������������� 36
6�2�8� BACKLIGHT ������������������������������������������������������������������������������������������������������������������������������� 38
6�2�9� ENERGY COST ��������������������������������������������������������������������������������������������������������������������������������38
6�2�10� CO2 EMISSIONS ����������������������������������������������������������������������������������������������������������������������������� 39
6�2�11� PARTIAL ENERGY METER DELETION ����������������������������������������������������������������������������������������40
6�2�12� EXITING THE SETUP MENU ���������������������������������������������������������������������������������������������������������40
7�- COMMUNICATIONS ���������������������������������������������������������������������������������������������������������������������������������������� 41
7�1�- INFRARED COMMUNICATIONS PORT (Model CEM-C31-T1) ������������������������������������������������������������� 41 7�2�- RS-485 COMMUNICATIONS PORT (Models CEM-C31-485-xx)����������������������������������������������������������� 41
7�2�1�- CONNECTION ��������������������������������������������������������������������������������������������������������������������������������� 41
7�2�2�- MODBUS PROTOCOL �������������������������������������������������������������������������������������������������������������������� 42
7�2�3�- VARIABLES MODBUS �������������������������������������������������������������������������������������������������������������������� 43
8�- TECHNICAL FEATURES �������������������������������������������������������������������������������������������������������������������������������� 48 9�- MAINTENANCE AND TECHNICAL SERVICE ������������������������������������������������������������������������������������������������ 51 10�- GUARANTEE �������������������������������������������������������������������������������������������������������������������������������������������������51 11�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������ 52
4
CEM-C31

REVISION LOG

07/14 M017B01-03-14A Initial Version
11/14 M017B01-03-14B
06/15 M017B01-03-15A
01/17 M017B01-03-17A
10/17 M017B01-03-17B
07/18 M017B01-03-18A
10/19 M017B01-03-19A
01/20 M017B01-03-20A
05/20 M017B01-03-20B
Table 1: Revision log�
Date Revision Description
Changes in the following sections:
4.2. - 4.6
Changes in the following sections:
2 - 3.5. - 4.4.1. - 4.4.2. - 4.5. - 4.6. - 4.7. - 5
Changes in the following sections:
2 .- 5. - 8.
Changes in the following sections:
5.
Changes in the following sections:
2.- 3.3. - 4.7.3. - 4.7.4. - 4.7.5. - 4.8. - 4.12. - 5.
Changes in the following sections:
2. - 3.3. - 3.5. - 4.2. - 4.5. - 5.1. - 5.2. - 5.3. - 5.4. -
5.5. - 5.6. - 6.2. - 7.2.2.2. - 7.2.3. - 8.
Changes in the following sections:
3.2. - 3.5.
Changes in the following sections:
8.

SYMBOLS

Table 2: Symbols�
Symbol Description
Compliant with the relevant European standards.
Device covered by European directive 2012/19/EC. At the end of its useful life, do not leave the unit in a household waste container. Follow local regu­lations on electronic equipment recycling.
DC current
~
AC current
Note: The images of the devices are solely for the purpose of illustration and may differ from the original device.
5

1�- VERIFICATION UPON RECEPTION

Check the following points upon receiving the device:
a) The device meets the specications described in your order. b) The device has not suffered any damage during transport. c) Perform an external visual inspection of the device prior to switching it on. d) Check that it has been delivered with the following:
- An installation guide.
- Safety label (terminal cover).
If any problem is noticed upon reception, immediately contact the transport company and/or CIRCUTOR's after-sales service.

2�- PRODUCT DESCRIPTION

CEM-C31
The CEM-C31 static three-phase energy meter measures class B active energy (EN50470) / class 1(IEC 62053-21) and (optional) class 2 reactive energy (IEC 62053-23). The current is measured with the transformer.
The device features:
- 2 buttons that allow you to browse the different screens and program the device.
- 2 Verication LEDs.
- LCD display, displays all parameters,
- 2 connection seals,
- 2 terminal covers, to cover the top of the terminal box and the xing screws.
- RS-485 communications (CEM-C31-485-xx models).
- Optical communications port for communications with other modules installed on a DIN rail with a service port (CEM-C31-T1 model).
- Impulse output (models CEM-C31-T1 and CEM-C31-485-T1).
- Digital input (model CEM-C31-485-DS).
6
CEM-C31

3�- DEVICE INSTALLATION

3.1.- PRELIMINARY RECOMMENDATIONS

In order to use the device safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment, and pay attention to the vari­ous warnings indicated in this instruction manual.
The CEM-C31 device must be installed by authorised and qualied staff.
The power supply plug must be disconnected and measuring systems switched off before handling, altering the connections or replacing the device. It is dangerous to handle the device while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal injury and damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to observe the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.
If an anomaly or malfunction is detected in the device, do not use the device to take any meas­urements.
Inspect the work area before taking any measurements. Do not take measurements in danger­ous areas or where there is a risk of explosion.
Disconnect the device from the power supply (device and measuring system power supply) before maintaining, repairing or handling the device's connec­tions. Please contact the after-sales service if you suspect that there is an opera­tional fault in the device.
7
CEM-C31
3.2.- INSTALLATION
On the side of the device are all of the indications adjusted to the CEI 62052-11 standard.
The device is installed on a DIN rail. All electrical con nections must be covered by the plastic
covers, and only the display and keypad should remain exposed.
Terminals, opening covers or removing elements can expose parts that are hazardous to the touch while the device is powered. Do not use the device until it is fully installed.
3.3.- DEVICE TERMINALS

3�3�1� MODEL CEM-C31-T1

Table 3:List of CEM-C31-T1 terminals�
Device terminals
1 : S1, Current input L1 8 : L3, Voltage input L3
2 : L1, Voltage input L1 9 : S2, Current output L3
3 : S2, Current output L1 11 : N, Neutral connection
4 : S1, Current input L2 13 : Auxiliary Power Supply
5 : L2, Voltage input L2 14 : Auxiliary Power Supply
6 : S2, Current output L2 21 : Impulse output (Collector)
7 : S1, Current input L3 22 : Impulse output (Emitter)
Figure 1:Terminals of the CEM-C31-T1�
8
CEM-C31

3�3�2� MODEL CEM-C31-485-T1

Table 4:List of CEM-C31-485-T1 terminals�
1 : S1, Current input L1 9 : S2, Current output L3
2 : L1, Voltage input L1 11 : N, Neutral connection
3 : S2, Current output L1 13 : Auxiliary Power Supply
4 : S1, Current input L2 14 : Auxiliary Power Supply
5 : L2, Voltage input L2 21 : Impulse output (Collector)
6 : S2, Current output L2 22 : Impulse output (Emitter)
7 : S1, Current input L3 23: B(-), RS-485
8 : L3, Voltage input L3 24: A(+), RS-485
Device terminals
Figure 2:Terminals of the CEM-C31-485-T1 and CEM-C31-485-DS�

3�3�3� MODEL CEM-C31-485-DS

Table 5:List of CEM-C31-485-DS terminals�
1 : S1, Current input L1 9 : S2, Current output L3
2 : L1, Voltage input L1 11 : N, Neutral connection
3 : S2, Current output L1 13 : Auxiliary Power Supply
4 : S1, Current input L2 14 : Auxiliary Power Supply
5 : L2, Voltage input L2 21: Digital input
6 : S2, Current output L2 22: Digital input (common)
7 : S1, Current input L3 23: B(-), RS-485
8 : L3, Voltage input L3 24: A(+), RS-485
Device terminals
9

3.4.- CONNECTION DIAGRAM

CEM-C31
Power
Supply
LOAD
S2 S1
P1
P2
P1
S2 S1
P2
S2 S1
P2
P1
Figure 3: Connection diagram, CEM-C31�
L1
L2
L3
N
10
CEM-C31

3.5.- CONNECTIONS

The CEM-C31 has terminal covers to cover the top of the terminal box and the xing screws (Figure 4).
Figure 4: Terminal covers of the CEM-C31�
The xing screws are of the mixed type, allowing the use of PZ2 and at head screwdrivers.
Table 6:CEM-C31 connections�
Connections
Measurement terminals (1, 2� 3, 4, 5, 6, 7, 8, 9, 11)
Maximum cable cross-section 16 mm2 ( 10 mm2 with end sleeve ) 1.2 Nm
Screwdrivers head PZ2
Impulse output terminals / Digital input (21, 22), Power supply (13, 14) and RS-485 (23, 24)
Maximum cable cross-section 1.5 mm2 ( 1.5 mm2 with end sleeve ) 0.6 Nm
Screwdrivers head at head (3 x 0.5 mm)
Once connected, the device can be protected with two connection seals (Figure 5).
Figure 5: Seal of the CEM-C31�
11
CEM-C31
Once the device is powered, attach the safety label (Figure 6) to terminals 13 and 14 to seal the device.
13 14
13 14
Figure 6: Attaching the safety label�
12
CEM-C31

4�- OPERATION

The CEM-C31 is an energy meter capable of measuring:
Imported and exported active energy and reactive energy in the four quadrants. (according to version).
Active, reactive and apparent power (according to version). RMS voltage and current. Power factor, PF

4.1.- BUTTON FUNCTIONS

The CEM-C31 has 2 buttons that allow you to browse the different screens and program the device.
The button can be sealed to prevent access to the programming of the most relevant pa­rameters.
To seal the button, insert the seal through the slot found under the button, Figure 7.
Figure 7: Sealing the button�
Button functions on the measuring screens (Table 7):
Table 7: Button functions on measuring screens�
Button Short press Long press (> 2 s)
For the cyclic movement. Next screen.
Enters reading mode.
Enter the programming menu -
13
CEM-C31

4.2.- DISPLAY

The device has an LCD where all parameters are displayed. The display is divided into three areas (Figure 8):
COM MAX DEM
HOURS kgC0
2 COST PAR
T1 T2
Data line
Indicator
kWh
kVArh
Figure 8: CEM-C31 Display areas
Data line, displaying the values measured by the device.
Units, where the unit of the magnitude being viewed is shown.
Indicators, which shows other parameters:
COM, indicates that there is a communications module connected. It ashes when the communications are established.
HOURS, displays the time in hours.
kgCO2, displays the quantity of kgCO2 released into the atmosphere according to the
energy consumed.
%
L
PF
C
Units
COST, indicates that the variable displayed in the data line is a cost.
PAR, indicates that the variable displayed in the data line is a partial meter.
T1 and T2, indicate the tariff corresponding to the on-screen information.
L1 - L2 - L3 - Indicates the presence of voltage in each phase, with its corresponding
current direction:
- “ is used to show the power yielded to the network. “ “ is used to show the power absorbed by the network.
Indicates that the energy being viewed is generated.
Indicates that the energy being viewed is consumed.
Indicates that the energy is inductive.
Indicates that the energy is capacitive.
14
Reactive LED
CEM-C31

4.3.- LED INDICATORS

The device has two verication LEDs:
To verify the active energy� To verify the reactive energy (according to version).
The weight of the LEDs is 20,000 imp/kWh (kvarh).
The LEDs will remain lit when the current is lower than the energy meter start-up current. Once the start-up current is exceeded (due to active or reactive power consumption) the LEDs are turned off and emit impulses that are proportional to the measured energy.
Active LED
Figure 9:LED Indicators of the CEM-C31�

4.4.- IMPULSE OUTPUT (CEM-C31-T1 and CEM-C31-485-T1 models)

The energy meter has optocoupler type outputs capable of generating impulses at a previous­ly programmed rate. (See “6.2.1. IMPULSE OUTPUT WEIGHT” and ”6.2.2. IMPULSE OUTPUT
TYPE” )
15
21
CEM-C31

4.5.- DIGITAL INPUT (CEM-C31-485-DS)

The CEM-C31-485-DS model features a impulse input (terminals 21 and 22 in Table 5), to calculate other supplies or select tariffs.
5 V DC
COMM
470 Ω
Active Tariff selection:
21
Figure 10: Digital input, CEM-C31-485-DS�
Table 8: Tariff selection�
Tariff Tariff selection
Tariff 1
21
22
22
22
Tariff 2
16
CEM-C31

5�- DISPLAY

The CEM-C31 has 2 display modes:
Display in standby mode Display in reading mode

5.1.- DISPLAY IN STANDBY MODE

With the display in standby mode, all of the information is presented in cyclic form without any need to perform any action on the CEM-C31 buttons.
This mode displays different parameters, see Table 9 and Table 10, that alternate every 6 seconds.
The device is in this mode by default when none of the buttons are pressed.
Short press the button to stop the cyclic movement of the parameter being shown at the time.
From then on, short press the button to browse all the parameters dened in Table 9 and
Table 10.
Table 9: Standby mode displays (Table 1)
Models CEM-C31-T1, CEM-C31-485-T1, CEM-C31-485-DS
(Impulse count option
Screen Parameters
Total imported active energy
Total exported active energy
Only displayed in the 4-quadrant version.
Reactive energy quadrant L+ total
(1)
)
(2)
Reactive energy quadrant L- total
(2)
Only displayed in the 4-quadrant version.
Reactive energy quadrant C- total
(2)
Only displayed in the 4-quadrant version.
17
Table 9 (Continuation): Standby mode displays (Table 1)
Screen Parameters
CEM-C31
Reactive energy quadrant C+ total
(1)
The impulse count option for the CEM-C31-485-DS model can be congured in section “6.2.3.-
(2)
DIGITAL INPUT TYPE
(2)
Only displayed if the reactive energy display option has been selected in the setup menu ( see
6�2�7�2� REACTIVE ENERGY DISPLAY”).
Table 10: Standby mode displays (Table 2)�
Model CEM-C31-485-DS (Tariff option
(3)
)
Screen Parameters
T1
Imported active energy Tariff 1
kWh
T1
Exported active energy Tariff 1
kWh
Only displayed in the 4-quadrant version.
kVArh
kVArh
kVArh
kVArh
kWh
T1
Reactive energy quadrant L+ Tariff 1
L
T1
Reactive energy quadrant L- Tariff 1
(4)
(4)
Only displayed in the 4-quadrant version.
L
T1
Reactive energy quadrant C- Tariff 1
(4)
Only displayed in the 4-quadrant version.
C
T1
Reactive energy quadrant C+ Tariff 1
C
T2
(4)
Imported active energy Tariff 2
18
kWh
T2
Exported active energy Tariff 2
Only displayed in the 4-quadrant version.