Chino KR3000 Series Instruction Manual

Page 1
INST.No.INE-815E
Thank you for purchasing the KR3000 series graphic recorder. Before using your new recorder, please be sure to read this instruction manual that will advise you on how to use the instrument correctly and safely and how to prevent problems.
General
Graphic Recorder
Instruction Manual
KR3000
Page 2
Page 3
CONTENTS
PREFACE
1
For safe use
3
Main features and functions
5
Before use
6
3.1 Exterior check
6
3.2 Model check
6
3.3 Checking attachments
7
Installation
8
4.1 Mounting location
8
4.2 External dimensions
8
4.3 Method of mounting the panel
9
Connections
10
5.1 Terminal board arrangement
10
5.2 Precautions while connections
12
5.3 Connection of power and Protective conductor terminals
13
5.4 Connection of measuring input terminals
14
5.5 Connection of alarm output
terminals (option)
15
5.6 Connection of digital input terminals
and function selection (option)
17
5.7 Connection of communication I/F
terminal (partly option)
18
Operation
24
Name of each part
25
7.1 Name of the front panel and its
major function
25
7.2 Names of keys and their functions
26
7.3 Character entering method
27
7.4 Touch panel operation method
28
7.5 Operation method of 4 separate screens
31
Screen switching method
33
Names and functions of the
operation screen
35
9.1 Common operation of the
operation screen
35
9.2 Status bar
36
9.3 Real time trend screen
39
9.4 Bar graph screen
39
9.5 Data screen
39
9.6 Historical trend screen
40
9.7 Dual trend screen
41
9.8 Alarm display screen
42
9.9 Internal memory screen
43
9.10 CF card/USB memory screen
45
9.11 Marker list screen
46
9.12 Controller display screen
9.13 Controller bar graph screen
9.14 Conroller text screen
Initial settings
47
Flow chart of HOME settings and MENU settings
51
HOME settings
53
12.1 Setting with HOME settings
53
12.2 Confirming the specifications with HOME settings screen
55
MENU settings
56
13.1 Setting MENU settings screen
56
13.2 Input operation settings
60
13.3 Display settings
70
13.4 Alarm settings
78
13.5 File settings
80
13.6 Totalizer reset settings
84
13.7 Schedule settings
85
13.8 Marker text settings
86
13.9 Memory operation
87
13.10 Network settings
89
13.11 System settings
99
Setting/displaying on Web screen
107
14.1 Display and settings using Web screen
107
Recording in a USB memory
114
15.1 Outline
114
15.2 Connectable media
114
15.3 Usage
114
Low order communications
(read) (option)
115
16.1 Outline
115
16.2 Procedure of connection setting to low order instrument
116
Low order communications
(write) (option)
121
17.1 Outline
121
17.2 Register to the instrument
121
Scale calibration
123
18.1 Scale calibration
123
18.2 Calibration environment
123
18.3 Preparation
123
18.4 Connections
124
18.5 Zero and span adjustment
126
Recommended part s replacement interval
130
19.1 Operation conditions
130
19.2 Reference of parts exchange intervals
130
Tr oubleshooting
131
Specifications
132
Appendix A. Report application (Sample)
135
13
11
12
14
15
19
18
16
17
2 3
10
20
21
Page 4
1
PREFACE
Thank you for purchasing the KR3000 series graphic recorder.
Before using your new recorder, please be sure to read this instruction manual that will advise you on
how to use the instrument correctly and safely and how to prevent problems.
1. Separate instruction manuals
This instruction manual describes the optional specifications of alarm output and report application of
appendix as well as the operation of standard specifications. When the instrument is with the high order
or low order serial communications interfaces (option), the separate instruction manual for
communications interfaces is attached. For other options you specified, their instruction manuals are
attached respectively. Read these instruction manuals together with this manual.
2. Request
Request to instrumentation engineers, constructors, and sale agents
Make sure to deliver this instruction manual to the operator of this instrument.
Request to the operator of this instrument
This instruction manual is necessary for maintenance, too. Keep this manual with care until the
instrument is discarded.
3. Attention while unpacking
Do not drop the recorder while taking it out of the box
When transporting this recorder, pack the instrument in the original box and then put it with cushions
in another box. We recommend keeping the original box for transport.
When not using the recorder for a while after taking it from the panel, put the recorder in the original
box and store at room temperature and in a dust free atmosphere.
4. Disposal
4-1.Disposal
Separate the box, plastic bags, and cushioning materials the recorder is packaged in according to the
garbage collection method of the each community, and please cooperate to recycle.
1. A small amount of hazardous substance below the specified level with RoHS directive is included in this recorder.
2. When disposing the recorder always request a professional to do it or contact your dealer or our nearest office.
Caution
3. This recorder includes a lithium battery. When disposing the lithium
battery, first remove the battery and always request a professional to do it.
Perchlorate Material
This instrument uses battery with Perchlorate Material.
Special handling may apply, see
http://www.dtsc.ca.gov/hazardouswaste/perchlorate
Warning
Page 5
2
4-2.Battery removal method
Do not replace the battery. Doing so might cause damage or malfunction. Do not remove the battery,
except when disposing the recorder.
(1) Open the key cover and remove the 2
retaining screws.
(2) Pull the bottom of the front display panel
toward you and lift up to remove the front
display.
(3) The front display is connected to PWB-A by 1
type of cable. Disconnect it.
(4) PWB-A is connected by 3 types of cables.
Disconnect them.
(5) Remove the 4 screws holding PWB-A, and
pull it out.
(6) Remove the screw of the mounting bracket
under PWB-C.
(7) Disconnect the connector for the power
switch cable on the left side of PWB-C and
pull out both PWB-B and –C as a set.
(8) Remove the 2 screws holding PWB-B and –C
together, and separate PWB-B from PWB-C.
(9) The battery holder is attached to the
underside of PWB-B. Lift the front of the
battery with a tool having a nonconductive tip
and pull the battery out of the holder.
Bracket
PWB-C
PWB-B
PWB-A
PWB-A
Display panel
Page 6
3
1. For safe use
This section “For safe use” has been compiled to promote the correct use of the instrument in
order to prevent human injury or damage to property before they occur. Please read the following information carefully and be sure to observe the warnings and cautions in it.
1. Preconditions for use
This instrument is designed for indoor use by mounting it on an indoor instrumentation panel.
2. Labels on this instrument
The following labels are used for safe use.
Label Name Meaning
Alert symbol mark
Indicates the location which should refer to the manual in order to prevent an electric shock and injury.
Protective conductor
terminal
A terminal is provided for connection to the protective conductor of the power supply facility for the prevention of an electric shock.
3. Symbols in this manual
The cautions to be observed for preventing the damage of this instrument and unexpected
accidents are sorted by the following symbols according to their importance degrees for enabling
operators to use this instrument safely.
The nonobservance of information under this symbol may result in hazardous, critical or serious injury to the user.
The nonobservance of information under this symbol may result in a hazardous situation or a light injury to the user or in physical damage to the property.
This symbol shows a caution when the instrument dose not function as specified or when such a possibility exists.
This reference servers as a supplement for handling and operation, and it may be convenient for the user.
Warnin
g
Caution
Remarks
Reference
Front glass
The front of display part is made by glass. To avoid injuries due to broken glass, do not blow
the glass hard.
Do not rub or push the touch panel by a sharp edged tool or a sharp material. For dirt on the front glass, wipe it lightly with a soft cloth infiltrated with neutral detergent or
alcohol into soft cloth.
Coordinates cannot read normally if two points are pushed simultaneously. Push one point in
operations.
Caution
Page 7
4
This paragraph covers important warning for safety to be observed before reading the instructions.
Fully understand the following warning before reading this manual. These warnings are important for
preventing the damage to human bodies as well as accidents.
1. Switch and overcurrent protective device
This recorder is not provided with a replaceable overcurrent protective device. Prepare a switch and an overcurrent protective device for the power supply (circuit breakers, circuit protectors or the like) within 3m of this recorder in a location where the operator can access easily Use a switch and an overcurrent protective device conforming to IEC947-1 and IEC947-3.
2. Be sure to ground this instrument
Before turning the power on, connect the protective conductor terminal of this recorder to the protective conductor of the power supply facility. In order to prevent an accident by electric shock, do not disconnect this connection during operations.
3. Before turning on the power supply
In order to ensure safety, before turning on the external power switch, make sure that the power voltage is within the range indicated on the power supply label.
4. Don't repair or modify this instrument
Make sure that any persons other than service engineers approved by CHINO CORPORATION do not repair or modify this instrument by replacing parts. Otherwise it may be damaged or will not function normally or an accident such as electric shock may occur. For ordinary operation, it is not necessary to pull out the internal unit.
5.Use this recorder following this instruction manual
Use this recorder correctly and safely by following this instruction manual. CHINO CORPORATION will not be responsible for any injury, damage, lost profit or any other claim, which may result from its wrong use.
6. Turn off the power supply if an abnormal symptom occurs
Turn off the power supply immediately and contact your local CHINO’s sales agent if any abnormal odor, noise or any smoke occurs, or if this recorder becomes high temperature that is too hot to be touched.
W
arning
The following fuse is mounted in the power
supply unit of this recorder for safety use.
However, this fuse is not replaceable.
Maker: Daito Communication Apparatus Co., Ltd
Model: SBL32
Fuse in the power supply
Reference
100-240V AC 50/60Hz 65VA MAX
Power supply label
Power terminal/ Protective conductor terminal
Power/protective conductor terminal
To the protective conductor of power supply facility
Power suppl
y
Switch
Overcurrent protective device (250V 3A)
LN
Page 8
5
2. Main features and functions
Besides measuring temperature and various industrial quantities of multi channels and displaying real
time trends, bar graphs, numeric values, etc. in various formats on 12.1 inch TFT color LCD, this recorder
can store data into the internal memory or a memory card (a CF card) and replay them if required.
Stored data can be used using commercial software like EXCEL, etc.
Easy management
of measurement
result
The monitoring of measurement results is easy since the data are displayed on various formats of screens. The previous data stored in the CF card can be read and the stored data can be managed using commercial software like EXCEL (Registered trademark of Microsoft Corporation), etc.
Various screen
displays
Real time trends, bar graphs, data (in a table format) and combined displays of “real time trends and bar graphs”, “real time trends and numeric values” and “real time trends and historical trends” can be arbitrarily selected and monitored with most suitable screens to meet your requirements. As alarm display screen displaying past alarm activation status collectively and a marker list screen are also available. In addition, up to 6 groups can be registered. With easy operation, these screens can be switched and 4 separate screens can be displayed.
Various memory
functions
Start/stop of data storage can be executed by arbitrary condition settings like key operation, alarm settings, time settings, etc. and the simultaneous storage to maximum 6 files can also be executed. In normal operations, data are stored into the internal memory and can be saved on the CF memory card.
Analog recorder
feeling
As the trend screen displays data on a chart with scale plates and pointers, the data can be monitored like an analog recorder.
Marker function
Markers and marker texts (alphanumeric characters, maximum 30 characters) can be written on the trend screen. A marker text is written arbitrarily, and also 50 types of marker texts can be registered in advance and these marker texts can be written with key operations. The marker texts can be written on the historical trend screen (replay), too. Markings only without marker texts are also available.
MODBUS
communication
Parameter settings, data acquisition and operation can be executed with the optional high order communication. As the communication protocol utilizes MODBUS, this recorder can communicate with a program indicator equipped with the MODBUS protocol without creating any communication software and the configuration of a system is easy. (MODBUS: The registered trademark of Schneider Electric SA)
Consumables not
required
Since consumables like charts, pens and inks as used in recorders are not required, this recorder is clean and less time consuming.
Easy setup
The easy interactive parameter setting offers parameter settings by selecting a setting item from the menu screen with key or touch-panel operation and then by opening a window. Also the operation can be executed easily with the required parameter settings on the ”Simple settings (HOME)” screen.
Software
package is
available
Data analysis can be executed easily on the PC as software package for data analysis is available.
● Software for analysis : (Windows98,Me,2000,XP version)
Page 9
6
3. Before use
Check the following items before using the recorder. If something is wrong, contact your local CHINO's
sales agent.
3.1 Exterior check
Check that the instrument is not broken on the outer side.
3.2 Model check
The model number and serial number of this recorder can be confirmed by the label on the upper side of the case. Check the model of your instrument from the model code before use.
Model code
KR31 - A
Measurement point/Sampling rate
20: Universal input 12 points (100ms) 40: Universal input 24 points (100ms) 60: Universal input 36 points (100ms) 80: Universal input 48 points (100ms) 21: Universal input 12 points (1s) 41: Universal input 24 points (1s) 61: Universal input 36 points (1s) 81: Universal input 48 points (1s)
Communication interface (option)
N: None R: High order communication (RS-232C) S: High order / Low order communication (RS-422A/RS-485)
Alarm output, Contact iutput (option)
0: None 1: Mechanical relay output (12 points ‘a’ contact) 2: Mechanical relay output (6 points ‘c’ contact) 3: Mechanical relay output (24 points ‘a’ contact) 4: Mechanical relay output (12 points ‘c’ contact) 5: Mechanical relay output (12 points ‘a’ contact) + Mechanical relay output (6 points ‘c’ contact) A: No-voltage contact input (8 points) B: Mechanical relay output (12 points ‘a’ contact) + No-voltage contact input (8 points) C: Mechanical relay output (6 points ‘c’ contact) + No-voltage contact input (8 points) D: Mechanical relay output (24 points ‘a’ contact) + No-voltage contact input (8 points) E: Mechanical relay output (12 points ‘c’ contact) + No-voltage contact input (8 points) F: Mechanical relay output (12 points ‘a’ contact) + Mechanical relay output (6 points ‘c’ contact) + No-voltage contact input (8 points)
KR31- K3

MADE IN JAPAN
Model (Check with model code.)
Serial No.
Page 10
7
3.3 Checking attachments
Package contains the following attachments. Please confirm.
Parts name Quantity Remarks
1
INE-815 (General) CD-ROM INE-817 (Communications interfaces)
(1 copy)
INE-816 (Mounting/connections edition) A4 Booklet
Instruction manual
1
RZMC-01- (CF card)
Mounting bracket
1set
Wrench
1
For panel mounting
Terminal screw
5
For input and alarm (digital input) terminals (M3.5) (Spares for missing)
CF card
1 RZ-CMC128 (128MB)
⑥ Touch pen
1 For touch panel operation
Mounting bracket
Terminal screws
CF card
Wrench
Instruction manual
Touch pen
Page 11
8
4. Installation
4.1 Mounting location
In order to avoid unfavorable effects on the measurement accuracy and recording operation, install this recorder at the following locations.
1) Industrial environment Select a place away from a source generating an electric field and/or a magnetic field and where mechanical vibrations/shock is not existed.
 Over voltage category     II (EN standard)  Altitude        2000m or less
 Pollution degree         2 (EN standard)  Place of use     Indoor
2) Ambient temperature/humidity Keep away from direct sunlight and do not close an area around this recorder to avoid temperature increase.
Place with stable ambient temperature of around 23°C and humidity 50%RH Place not exposed to hot blast (50°C or more) for avoiding deformation of the front panel Place where there are no wind and no heat source near terminals for avoiding measurement errors.
3) Atmosphere
Avoid a place where flammable gases exist. Avoid a place with dust, smoke, vapors etc.
4) Mounting angle
Lateral tilting    0° Longitudinal tilting    Forward tilting: 0°, Backward tilting: 0-20°
Mounting angle other than the above angles will have unfavorable effects on recording operation.
4.2 External dimensions
The following figure shows the dimensions of this recorder with its mounting brackets.
Unit : mm
Page 12
9
4.3 Method of mounting the panel
1) Panel cutout size
2) Mounting method
(1)Insert this recorder into the panel cutout part of an instrument panel.
(2)Since there is a screw hole each (a total of two holes) in the right and left sides of this recorder, screw 2
fixing screws attached in two holes lightly.
(3)Next, put the hexagon head of this screw to the circular hole of the fixing metal and push the recorder
to the instrument panel firmly (from front) while making the fixing metal slide as shown in the figure. On
this condition, tighten the fixing screw with the attached wrench or a Phillips screwdriver.
In addition, be careful that the mounting metals differ by right and left. (Install the recorder by two
persons.)
パネルカット
281
281
+1 0
+1
0
(mm)
360
360
(mm)
Panel
cutout
Minimum interval for installation of multiple instruments
Mount on the panel and use
(1) This instrument has been designed to be mounted on an indoor instrumentation panel. (2)
Use a panel made of a steel plate of 2mm to 6mm in thickness or a panel equivalent in strength.
Warning
Slide
Page 13
10
5. Connections
5.1 Terminal board arrangement
The following diagram shows the terminal board arrangement in which option (Alarm relay output [12
points ‘a’ contact], [6 points ‘c’ contact], communication interface) are mounted. Connecter for Ethernet is
a standard mounting.
[Option terminal block (* May be changed.)]
Communications terminals (option)
[CH 1 ~ 12]
Power termi nals
Ethernet connector
SG
Protective conductor terminal
N.O terminals
COM terminals
Terminal No.
1 ~ 12
No-voltage contact input
Terminal No.
1 ~ 8
COM terminal
RS-422A/485
RS-232C
TC,m V(+),RTD (A) term inals
TC,mV
(-)
,RTD (B) terminals
RTD
(B)
terminals
[CH13 ~ 25]
[CH25 ~ 36]
[CH37 ~ 48]
Measurement terminals
Alarm output (2 kinds of options ) ‘a’ contact output:
12 points/terminal block
‘c’ contact output:
6 points/terminal block
* When using
KR31□□-5A or KR31□□-FA : 1 terminal block for ‘a’ contact output, arranged lower and 1 terminal block for ‘c’ contact output, arranged upper.
Remote contacts input (option) No-voltage contact input 8 points (same
common terminal)
N.C terminals
COM terminals
N.O terminals
Terminal No.
1 ~ 6
Digital input (No-voltage contact input, 8 points)
Alarm relay output (6 points ‘c’ contact)
Alarm relay output (12 points ‘a’ contact)
TC,m V(+),RTD (A) term inals
TC,mV
(-)
,RTD (B) terminals
RTD
(B)
terminals
TC,m V(+),RTD (A) term inals
TC
,mV(-)
,
RTD (B) terminals
RTD
(B)
terminals
TC,m V(+),RTD (A) term inals
TC
,mV(-)
,
RTD (B) terminals
RTD
(B)
terminals
Page 14
11
Alert symbol marks ( ) and places
The alert symbol mark ( ) is pasted at danger places where may cause electric shock. (See
the following table.)
Name of terminals Power terminals
Measuring
input terminals
Mechanical relay
‘c’ contact alarm
terminals
Mechanical relay
‘a’ contact alarm
terminals
Places marked with
the symbol
Lower left of
power terminals
Lower right of
terminal cover
Lower right of
terminal cover
Lower right of
terminal cover
Warning
Thermocouple input terminal block cannot be replaced by terminal block of other instrument.
If re
p
laced measurement error occurs.
Replacement of thermocouple input terminal block
The input terminal block and alarm terminal block (including the contact terminal block) are removable for easy connections.
(1) Each terminal block can be removed by removing two mounting screws. (2) Each terminal block is connected to the recorder by a
connector.
Turn off the power supply in advance
For mounting or dismounting the terminal block, turn off the external power switch to prevent the electric circuits from being damaged.
Caution
Input terminal and alarm terminal blocks are removable
Reference
Terminal
blocks
Mounting
screws
Remarks
Page 15
12
5.2 Precautions while connections
Observe the following cautions during connections for securing safety and reliability.
1) Power supply
Use a single-phase power supply having a stable voltage without any waveform distortion for the purpose of preventing wrong operations.
2) Keep the input/output connections away
from a high voltage power circuit
Don’t place the input/output cables close or in parallel with any strong power circuits including power line. Place the cables 50 cm or more away from high voltage power circuits when they are placed close or in parallel to other circuits.
3) Keep the thermocouple input away from a
heat source
For thermocouple inputs, keep the input terminals away from a heat source (a heating body) to reduce a reference junction compensation error. Don’t expose the input terminals to direct sunlight, etc.
4) Keep all connection cables away from noises
Keep all connection cables away from noise source as far as possible, otherwise unexpected malfunction may occur. Provide a solution if the cables cannot be separated from a noise source due to unavoidable circumstances.
Major noise
sources
Electromagnetic switch, etc. Power line having waveform distortion Inverter Thyristor regulator
Counter
measures
Insert noise filters between power terminals and input/output terminals. A CR filter is often used.
5) Use crimp style terminals
(1) Fix crimp style terminals to termination of
connection cables for preventing the looseness or disconnection of terminals and a short-circuit failure between terminals.
(2) Use the crimp style terminals with insulation
sleeve for preventing an electric shock.
6) Unused terminals
Don’t use any unused terminals for relaying; otherwise the electric circuits may be damaged.
Kinds of terminals and termination
Terminal name
Screw
diameter
Tightening
torque
Termination (Unit: mm)
Power and
protective
conductor and
communication
terminals
M4 1.2N • m
Terminals other
than described
above
M3.5 0.8N • m
*Use Type O whenever possible.
(1)
A switch and an overcurrent protective device
Prepare a switch and an overcurrent protective device (3A) to the power supply for preventing an electric shock accident during connection work. This recorder is not provided with any replaceable fuse.
(2)
Turn off the power supply before connections.
Be sure to turn off the power supply before connecting cables to the power and the input/output terminals to prevent an electric shock.
Warning
Secure the connected cables properly.
Secure the connected cables so as not to allow them to be hooked by a person or a substance, otherwise the connections may be cut and disrupted that may cause an electric shock or other accidents.
Warning
Type O
Less than 8.5
More than 4.3
t: 0.8
With an insulation sleeve
t: 0.8
With an insulation sleeve
Type O
t: 0.8
Type Y
Less than
8
More than 3.7
Less than
8
More than 3.7
Page 16
13
5.3 Connection of power and protective conductor terminals
1) Power and protective conductor terminals
2) Connection of power terminals
For connection to the power terminals, use a 600 V PVC insulated cable terminated by the crimp style terminals with insulation sleeve. Note) Use the cords approved by the following
standards.
(1) IEC 227-3 (2) ANSI/UL817 (3) CSA C22.2 No.21/49
3) Connection of protective conductor terminal
Be sure to connect this terminal to the protective conductor of the power supply facility. For this connection, use a cable terminated by the crimp style terminals with insulation sleeve.
• Grounding wire: Copper wire 2 mm
2
or more (green/yellow)
Power
terminals
100-240 V AC 50/60 Hz 65 VA MAX
L N
Power supply (voltage, frequency, power consumption)
Protective conductor terminal
Turn off the power supply.
Be sure to turn off the power supply before connecting cables to the power and protective conductor terminals to prevent an electric shock.
Warnin
g
mark at power terminals
A voltage of 100 to 240 V AC is applied to the
power terminals after connections. Be sure to
mount the power terminal cover to prevent an electric shock.
Warning
This indication conforms to the CSA standard, Canada. The live side of the single-phase AC power supply is indicated as L, and the neutral side is indicated as N. Observe the L and N connections for obtaining satisfactory performance.
Remarks
L/N indication of power terminals
Be careful with the power voltage
and noises.
The power voltage of this instrument is indicated beside the power terminals. Don’t apply any voltage other than indicated; otherwise a malfunction may result. If noise is generated at the power supply, provide a noise reduction transformer, etc.
Caution
L
N
A copper wire with 2 mm
2
or more (green/yellow)
Be sure to connect to the protective conductor of the power supply facility.
600 V vinyl insulated cable
Power supply
Mount the power terminal cover after connections.
Page 17
14
5.4 Connection of measuring input terminals
1) Measuring input terminals
Be sure to turn off the power supply to prevent an
electric shock. For the connections to the input terminals, use
cables terminated by the crimp style terminals with insulation sleeve
2)
Connections of DC voltage (current) input
Use twisted cables for instrumentation as the input cables for the purpose of suppressing noises. For current inputs, mount shunt resistors to the channels to be measured before connections.
3) Connections of thermocouple (TC) inputs
Be sure to use thermocouple wires (or extension wires) to the input terminals of this recorder. If a copper wire is used halfway, a noticeable measuring error occurs. Don’t use a pair of thermocouple wires in parallel with other instruments (controller, etc.), otherwise a malfunction may occur.
4) Connections of resistance thermometer (RTD) inputs
Use a 3-core cable where each lead wire has an equal resistance value. Don’t use one resistance thermometer in parallel with other instruments (controller, etc.).
Allowable input voltage
Input type
Allowable
input voltage
Voltage, thermocouple input
±10 V DC*
Resistance
thermometer input
±6 V DC
* ±60 V DC with channel settings to the ±5 V
or higher range.
Caution
Twisted cable for instrumentation
DC voltage input
(+)
(-)
1 2 3 4 5 6
DC voltage (current) input
Extension wire
Thermocouple
Red (+)
White
1 2 3 4 5 6
Thermocouple
(TC) input
3 core cable (Same diameter, same length)
Note: The resistance of each cable is less than 10 . All the 3 wires should be of the same resistance value.
1 2 3 4 5 6
Resistance thermomete
r
A
B
B
Resistance
thermometer (RTD) input
mark of measuring input terminals
A high voltage may be applied to the measuring input terminals due to common mode noises. The allowable noise value is lower than 30 V AC or lower than 60 V DC. Make sure that the noises are lower than the allowable values. Mount the terminal cover after connections for the purpose of preventing an electric shock and to protect the input wires. In the case of thermocouple input, the mounting of the terminal cover can reduce the reference junction compensation error.
Warning
TC, mV(+), RTD(A) terminal and TC, mV(-), RTD(B) terminal are insulated each channels but RTD(B) terminal is short-circuited between channels. KR31*0 is short-circuited between channel 1 to 4, 5 to 8, 9 to 12 of each input terminal unit, and KR31*1 is short-circuit channel 1 to 12 of each unit.
Isolation of measured input terminal
Remarks
Page 18
15
5.5 Connection of alarm output terminals (option)
This is for the recorder with alarm output terminals (option).
1) Alarm output terminals
The terminal arrangement depends upon the type of alarm output.
Alarm relay output (1a)
Alarm relay output (1c)
N.O terminals (M3.5)
COM terminals (M3.5)
Alarm relay output (12 points)
N.C terminals (M3.5)
COM terminals (M3.5)
N.O terminals (M3.5)
Alarm relay output (6 points)
Page 19
16
2) Connections
Turn off the power supply and buffer relay power supply before connections to prevent an electric shock.
(1) Connect cables to the load via a buffer relay.
(2) Use cables with the crimp style terminals with insulation sleeves for the alarm output terminals. (3) If a voltage of more than 30 VAC or 60 VDC is to be applied to the output terminals, use type O
crimp style terminals with insulation sleeves. Furthermore, use double-insulated wires (dielectric strength of 2300 VAC or more) for the signal wires on which a voltage of more than 30 VAC or 60 VDC is to be applied. For all other wires, use basic insulated wires (dielectric strength of 1390 VAC). Be sure to mount the terminal cover to prevent an electric shock.
Example of mechanical relay ‘a’ contact outputs Example of mechanical relay ‘c’ contact outputs
3) Precautions for connection
Be careful with the following cautions for connections.
Item Contents
Contact rating of
Mechanical relay outputs
(Common to ‘a’ contact
and ‘c’ contact)
Mounting of contact
protective element Z
Mount a contact protective element conforming to the buffer relay. The
relay is broken, if a signal exceeding the contact rating is applied even if momentarily.
To prevent a malfunction being caused by a light load, the most effective
mounting position for the element is on the coil side of the buffer relay ('a' in the connection diagrams under (2) on 5.5)
Selection of buffer relay
(1) Coil rating ........... Less than the contact rating of output terminals
(2) Contact rating ....... More than twice the load current
A coil surge absorption element built-in type relay is recommendable. Mount an additional buffer relay if a buffer relay satisfying the load rating is not available.
Selection of contact
protective element
Mount a contact protective element if a surge absorption element built-in buffer relay is not available. This element is generally composed of C (capacitor) and R (resistor).
<Reference values of C•R> C : 0.01 µF (Rating about 1 kV)
R :100 to 150 (Rating about 1 W)
Power Supply
Load
b
a
Buffer relay
This recorder
N. O
COM
: Contact protective element
(It is recommended to mount this element on the a side)
b
a
N. O
COM
N. C
Power Supply
Load
Buffer relay
This recorder
: Contact protective element (It is recommended to mount this element on the a side)
N.C terminal - Open relay contact at alarm activation
that is the reverse action to N.O terminal.
mark of alarm output terminals
Connect a load not exceeding the specified contact capacity to the alarm output terminals. A buffer relay power supply is applied to the alarm output terminals after connections. Do not touch these terminals since an electric shock will occur. Be sure to mount the terminal cover after connections.
Warning
Take a safety measure.
An alarm output of this recorder may become defective caused by wrong operation, failures, and other abnormal inputs. Take a safety measure against an output failure before use as occasion calls.
Caution
Power supply Resistive load Inductive load
100 V AC 0.5 A 0.2 A 240 V AC 0.2 A 0.1 A
30 V DC 0.3 A 0.1 A
(Minimum load)
100μA 100mVDC
Page 20
17
5.6 Connection of digital input terminals and function selection (option)
This is for the recorder with digital input terminals (option)
1) Digital input terminal
2) Connections
Turn off the power supply before connections to prevent an electric shock.
(1) Apply a no-voltage contact signal to digital input
terminals.
(2) Use cables terminated by crimp style terminals
with insulation sleeves for the digital input terminals.
Voltage when the contact is open.
: Approx. 5 V
Current when the contact is short.
: A
p
p
rox. 2 mA
Features of digital input terminal
Remarks
Connection example
DI 1 2 3 4 5 6 7 8 COM
No-voltage contacts
For the contacts to be connected to the Digital
input terminals, use a switch or relay driven at
lower than 30 V AC or lower than 60 V DC, or manual contacts for very light loads.
Caution
Functions of terminals
(1) Digital input ON/OFF (short/open) state can be measured. Select the range type as DI.
(Refer to Para.13.2 Input operation settings.)
(2) Pulse input Used as the pulse input. Select the range type as Pulse (+) and Pulse (-).
(Refer to Para.13.2 Input operation settings.)
(3) Totalizer reset The reset of totalizer is executed. When the digital input terminal specified
becomes ON, the totalizer reset is executed.
(Refer to Para.13.6 Totalizer reset settings.)
(4) Marker The writing of marker. The marker can be written on the trends when the digital
input terminals become ON.
(Refer to Para. 13.8 Marker text settings.)
(5) File drive The recording start/stop of data file in the internal memory is executed.
The recording starts or stops when the digital input terminals become ON or
OFF. (Refer to Para. 13.5 File settings.)
Each function requires a short circuit of 0.1 second or more between the COM terminal and each terminal.
No-voltage contact input
DI 1 to 8
COM terminals
Page 21
18
5.7 Connection of communication I/F terminal (partly option)
The KR3000 can be communicated with a master unit via Ethernet and RS-232C, RS-422A or RS-485, and with a slave unit via RS-422A or RS-485.
*RS-232C /422A /485 terminal and serial communication function are optional.
1) In case of high order communications via Ethernet
[In case of connection with a PC by 1 to 1]
For the connection of a PC and the Ethernet IF by 1 to 1, use the STP crossover cable.
[In case of connections with PCs by N to N]
For the connection to multiple PCs or an existing LAN, use a switching hub and an STP straight cable
between the hub and the Ethernet IF.
2) Types of communication terminals
Ethernet connector
RS-422A/485 terminal
RS-232C connector
STP crossover
cable
KR3000
PC
(With LAN function)
PC
(With LAN function)
Hub
Twist-pair
straight cable
STP straight
cable
KR3000
SGRDB
RDA
SDB
SDA
RS-422A/RS-485
High order or low order communication
RS-232C
High order communication only
Page 22
19
3) Connections of High order communication RS-232C
The communication terminals of this recorder are three terminals of SD, RD and SG and a control signal is
not used. General personal computers use the control signal. Wiring processing for control signal in a
connector depends upon how the control signal is used in a personal computer. For details, refer to the
instruction manual for your personal computer.
(1) Example of 9-pin connector
(2) Example of 25-pin connector
PC
This recorder
CD
RD
SD
ER
SG
DR
RS
CS
1
2
3
4
5
6
7
8
Within 15m
CD
RD
SD
ER
SG
DR
RS
CS
1
2
3
4
5
6
7
8
This recorder
PC (Example 1)
Within 15m
SD
RD
RS
CS
DR
SG
CD
ER
2
3
4
5
6
7
8
20
CD
RD
SD
ER
SG
DR
RS
CS
1
2
3
4
5
6
7
8
Page 23
20
4) Connections of High order communication RS-422A
The RS-422A communications interface is connected to a personal computer via a protocol converter (our Model SC8-10: sold separately). Three signals of SD, RD and SG are used between the protocol converter and a personal computer and a control signal is not used.
PC
(9-pin or 25-pin)
RD SD SG
RDA RDB SDA
SDB
1
2
3
4
5
6
7
8
Protocol converter
(SC8-10)
Within 15m
Total length within 1.2km (max 10set)
Termination
resistor
1001/4W
The above figure
shows an example
of 9-pin.
RD SD ER SG DR RS CS
2
3
4
5
6
7
8
This recorder1
SDA SDB RDA RDB
SD SDB RDA RDB
This recorder2
SG
SG
Transmitting
data
SDB
Receiving
data
SDA
Internal
circuit
RDB
RDA
For wiring process of connector, refer to “3) Connection of High order communication RS-232C”.
To ensure the transmission of data via RS-422A communications, mount a termination resistor at the ends of receiving lines. When the protocol converter (SC-8) is at an end of a transmission circuit, short the terminals of
4 and 5 of the unit to insert the termination resistor automatically.
Mounting termination resistor
Remarks
Page 24
21
5) Connections of High order communication RS-485
The RS-485 communications interface is connected to a personal computer via a protocol converter (our Model SC8-10: sold separately). Three signals of SD, RD and SG are used between the protocol converter and a personal computer and a control signal is not used.
PC
(9-pin or 25-pin)
RD
SD SG
RDA
RDB
SDA
SDB
1
2
3
4
5
6
7
8
Protocol converter
(SC8-10)
Within 15m
Total length within 1.2km (max 31set)
Termination
resistor
1001/4W
The above figure
shows an example of
9-
p
in.
RD SD ER SG DR RS CS
2
3
4
5
6
7
8
This recorder
SDA
SDB
SG
RDA
RDB
Other model
SA
SB
SG
To ensure the transmission of data via RS-485 communications, mount a termination resistor at both ends of transmission lines. When the protocol converter (SC-8) is at an end of a transmission circuit, short the terminals of
4 and 5 of the unit to insert the termination resistor automatically.
Mounting termination resistor
Remarks
Transmitting
data
SDB
Receiving
data
SDA
Internal
circuit
RDB
RDA
For wiring process of connector, refer to “3) Connection of High order communication RS-232C”.
Page 25
22
6) Connections of Low order communication RS-422A
Example of connection 1
KR3000
Low order
communication terminal
KE3000 etc.
SE3000, MELSEC etc.
SG
SDB
SDA
RDB
RDA
SG
Termination
resistor
1001/4W
SG
RDB
RDA
SDB
SDA
SDB
SDA
RDB
RDA
Example of connection 2 (SYSMAC)
KR3000
Low order
communication terminal
SYSMAC
SG
SDA(-)
SDB(+)
RDA(-)
RDB(+)
SG
SG
RDB
RDA
SDB
SDA
SYSMAC
Termination
resistor
1001/4W
SDA(-)
SDB(+)
RDA(-)
RDB(+)
Please note that the polarity of A and B of the communication terminal is different from
SYSMAC and this product.
To ensure the transmission of data via RS-422A communications, mount a termination resistor at the ends of receiving lines.
Mounting termination resistor
Remarks
Page 26
23
7) Connections of low order communication RS-485
Example of connection 1
KR3000
Low order
communication terminal
AL3000 etc.
SE3000,MELSEC etc.
SG
RDB
RDA
SDB
SDA
SG
SB
SA
Termination
resistor
1001/4W
SG
RDB
RDA
SDB
SDA
To ensure the transmission of data via RS-485 communications, mount a termination resistor at both ends of transmission lines. When the protocol converter (SC8-10) is at an end of a transmission circuit, short the terminals of
4 and 5 of the unit to insert the termination resistor automatically.
Mounting termination resistor
Remarks
RD
SD
SG
RDA RDB
1
2
3
4
5
6
7
8
Protocol converter
(SC8-10)
Within 15m
Within 1.2km
RD
SD
SG
2
3
9
This recorder
SDA SDB
SG
RDA
RDB
Example of connection 2 (SYSMAC)
SYSMAC CPU unit
Internal RS-232C port
(D-SUB 9-pin receptacle)
RS-232C
RS-485
SDA
Transmitting
data
SDB
Receiving
data
SDA
Internal
circuit
RDB
RDA
T
ermination
resistor
1001/4W
Page 27
24
6. Operation (Be sure to read Para. for safety.)
Default setting values have been set at the factory. For actual operation, be sure to execute the following
settings.
This recorder temporarily stores measurement/calculation data in the internal memory for data processing, indication, etc. For saving data, set a file and save the data to the external memory.
On part of the LCD screen, some pixels may always be lit or not lit, and unevenness
in brightness may arise from the characteristic of the liquid crystal, but these are not malfunctions.
Start
o
p
eration
Power ON
Settings
For operation, set the following parameters.
(1) Initial settings at power ON (10 Initial settings  Be sure to set them.) (2) Set all parameters on the HOME setting mode screen (12.1 Setting with the HOME settings)
together, or set each channel following the next steps. (3) Input-related-settings (13.2 Input operation settings) (4) Display-related-settings (13.3 Display settings) (5) Set each channel individually by the recording-related-settings (13.5 File settings).
Operation end Power OFF
Storing data into a
memory card
13.5 File setting
Start
Start/end operations
of recording
13.5 File setting
Preparation
(1) Install this recorder to the panel. ( Installation)
(2) Complete the connections. ( Connections)
Operation screen
switching
Screen switching method
8
Page 28
25
7. Name of each part
7.1 Name of the front panel and its major function
Key cover
Display
12.1 inch TFT color LCD
Operation screen:
Refer to
Key cover opened
Key board
CF card drive Power switch
Touch panel
USB connector
9
Front glass
The front of display part is made by glass. To avoid injuries due to broken glass, do not blow
the glass hard.
Do not rub or push the touch panel by a sharp edged tool or a sharp material. For dirt on the front glass, wipe it lightly with a soft cloth infiltrated with neutral detergent or
alcohol into soft cloth.
Coordinates cannot read normally if two points are pushed simultaneously. Push one point in
operations.
Caution
Page 29
26
7.2 Names of keys and their functions
Usage and functions of keys differ depending on the operation screen and the setting screen.
Operations of all keys can be performed on the touch panel. Therefore, all operations enable with the key
cover closed.
Keys and major usage/functions of each screen
Key
Operation screen Setting screen
The recording starts. Not used
The recording stops. Not used
Used for switching of the
scroll mode and for moving to the historical trend screen.
Not used
Used for switching the
cursor mode in the historical trend screen.
Not used
Used to write a marker
on the trend screen.
Not used
Used to display the DISP
menu.
A snapshot is taken by pressing this key for a long time.
Used to display the
HOME settings menu.
Used to quit the Home screen.
Used to display the MENU settings menu.
Used to return a previous screen.
Used for cancelling menus or for returning to a previous screen.
Used to return from the setting screen to the operation screen or return to a previous screen.
Used to enter a menu item or display the ENTER menu.
Used to open a selected menu or enter a numeric value, a character, etc. selected by the cursor. Also, used to store a parameter when the setting screen returns to the operation screen.
Direction keys
Used to select a menu item or change a display group and a channel.
Used to move the cursor to the left, right, up and down.
START
STOP
SCROLL
CURSOR
MARKER
DISP
HOME
MENU
ESC
ENTER
Page 30
27
7.3 Character entering method
This screen is used for setting a tag name, a marker text character string and setting/entering a password.
When the character input screen is displayed, by pressing the “ABC” or the “abc”, keys arranged on the
lower column are changed to indications corresponding to the key pressed. Press a character to enter.
Then, the character selected is displayed on the character display column. When a character is touched
on the character display column, the cursor moves to its position and a character can be inserted (or
overwritten) at the cursor position.
Alphabet capital letters, symbols and numeric can be entered.
Inserting or overwriting can be selected.
(Inserting and overwriting are switched each time this key is pressed.)
A character selected on the character input column is deleted.
The character being one position before the character selected on the character input column is deleted.
Inputted characters are entered. Inputted characters are also entered by pressing the ENTER key after moving the focus to the character input column.
Alphabet small letters, symbols and numeric can be entered.
Page 31
28
7.4 Touch panel operation method
All operations of this recorder can be executed on the touch panel.
In case of abnormality in the touch panel or same operation as the KR2000 series is required, execute
operations with the keyboard.
On this recorder, operations can be executed sensuously by tapping the touch panel. In this paragraph,
the basic screen operation method is described. For special operations of each screen, read the
explanations about each screen in Para. 9.
7.4.1 Tapping on the operation screen
[Operation] button
Displays the operation
menu.
Disk icon
Recording starts or
stops by touching it.
Alarm icon When an alarm is activated, the alarm is acknowledged by touching it. (Refer to Para. 9.2)
[MARKER] button
Writes a marker on the
trends (Refer to Para. 9.3
[Hist] button
Displays a historical trend graph
When the historical trends are displayed, the button is
changed to [Real] and, when the historical trends are
displayed from a file list, etc., it is changed to [Return].
[DISP] button
Displays the DISP menu
Channel switching button
This button appears when all of
registered channels cannot be
displayed. Displayed channels are
switched by pressing this button.
Group switching button
This button appears when
multiple groups are used. Groups
are switched by pressing this
Separate screen button
Displays 4 separate screens.
[PEN] button
Handwriting of a memo is enabled
on the trends.(Refer to Para.7.4.3)
Page 32
29
< [Operation] menu >
Menu item Operation START The recording starts. Same function as the START key STOP The recording stops. Same function as the STOP key. HOME settings The HOME settings open. Same function as the HOME key MENU settings The MENU settings open. Same function as the MENU key
< [DISP] menu>
Menu item Operation Select display Used to change the operation screen type. Select group Used to change the display group. Auto switching Used to turn or off the automatic switching of the group and channel.
The switching becomes active by checking. When the automatic switching time is set to 0, this switching is not valid.
Snapshot Used to save a hard copy of a screen to the CF card (SNAPSHOT
folder).
Pause Screen updates are stopped except status bar. When press any key,
the screen is displayed again. All operations except describing of data recording and recording processing are performed during pause. When the DISP key is pushed in the Pause, the Snapshot is executed.
Display OFF Used to turn off LCD display. The LCD is turned on again by pressing
any of buttons. 4 screens Used to display 4 separate screens. Magnify/reduce
The trends are displayed by compressing the time axis. (Same
magnification to 1/60)
<Tapping operation on 4 separate screens>
By tapping the DISP button, the display type and group can be selected in each frame.
For the details of operation, refer to Para. 7.5.
In addition, by pressing the group switching button and the marker button on each frame, their operations
for each frame are executed.
Page 33
30
7.4.2 Tapping operation on the setting screen
On the MENU setting and the HOME setting screens, setting operations can be executed more smoothly by tapping each item. For inputting into each item, tap a button with the mark.
For returning to a previous screen, press the [Set] button.
On a screen with a scroll bar, information can be scrolled with tapping the scroll button. The screen is
scrolled one by one by tapping the scroll bar above or below the scroll bar.
Do not rub or push the touch panel by a sharp edged tool or a sharp material. Avoid storing and using the touch panel in the environment with water, organic solvent or acid, or
in the condition of touching them.
Avoid using the touch panel in a place with direct sunlight.
For dirt on the front glass, wipe it lightly with a soft cloth infiltrated with neutral detergent or
alcohol into soft cloth. When medicine, etc. adheres to the touch panel accidentally, wipe off it
immediately in the state where there is no influence in a human body.
The dew condensation generated inside the touch panel is not unusual since the dew
condensation is a natural phenomenon. When the temperature of the touch panel reaches to the
room temperature, the dew condensation will disappear automatically, but avoid using the touch
panel with the dew condensation since it causes failure.
Cautions for using the touch panel
Remarks
Scroll button
Scroll bar
Page 34
31
7.4.3 Handwriting operations on the trend screen
On the real time trend screen and the historical trend screen, handwriting operations can be executed with free handwriting feeling by tapping and skimming the display.
For executing the handwriting operations, tap
once to enable the handwriting.
When the handwriting is enabled,
is displayed as shown in the figure below.
By tapping the pen button again, a drawn content
is fixed and saved, and the handwriting is switched to disable. After then, the normal tapping operations can be executed. The drawn contact can be read again by a CF card or a USB memory in addition to the internal memory. (Ref. Para. 9.10 CF card/USB memory screen)
(Erasing operation)
When
is tapped in the handwriting operations, the content written just before is erased. When a drawn content is by continuous trajectory
, the whole content is erased at once. When the content is by discontinuous trajectory, the trajectory written just before is erased first and the drawn trajectory is erased in an order from a new one.
Caution: When the content is saved once by t
apping the pen button, the retroactive trajectory
cannot be erase.
Continuous
Disontinuous
Handwriting example
The drawn content is erased.
Drawing thickness and color can be set.
The handwriting enabling or disabling can be selected,
Page 35
32
(Setting operation)
When
is tapped in the handwriting operations, the thickness and the color of the
drawn point can be changed from the dialog box shown below.
← Thin Thick
Example
The thickness
can be selected 1
to 10 steps.
The color can be
selected from 16
colors.
Supplement
The number of handwriting points is the one got by detecting and sampling, periodically at a fixed cycle, the coordinate data when the touch panel is touched. On the performance, 8000 points are the upper limit of input, and when the number is
exceeded, the point is erased from the oldest one. It is difficult to distinguish the number of inputs visually directly by seeing the drawing. Since the number of points is the one sampled at a fixed cycle, slow pen writing consumes
the number of points more and quick wiring makes consumption of number of points few. The length of a trajectory, the thickness of a font, and a color are not directly related to consumption of number of points. The figure below shows the reference figure about the number of points confirmed by treatment of the instrument.
About the number of handwriting input points
1 tap 3 points are used.
Quick handwriting: About 8 points are used.
Slow handwriting: About 80 points are used.
Page 36
33
7.4.4 Automatic scroll operation on the historical trend screen
In Para 7.4.2, the tapping operations on the screens with the scroll bar are described. Furthermore, on the
historical trend screen (Ref. "9.6 Historical trend screen" for details) that can reproduce record data and
on the dual trend screen (Ref. "9.7 Dual trend screen" for details), when the scroll bar is displayed, the
scroll bar can be flowed automatically by taking eliminating action like turning over a screen while tapping
on the trend screen along the direction that the trend flows. Accordingly the trend screen moves
automatically and the automatic scroll stops by tapping anyplace on the screen again.
In addition to the internal memory, the automatic scroll is available on the historical trends read from an
external memory.
The automatic scroll is enabled with the cursor displayed. The cursor position follows in each case.
1 Turning tap oeration
2 The bar flows automatically.
Page 37
34
7.5 Operation method of 4 separate screens
This recorder can split a screen into 4 and can display 4 screens divided simultaneously. On the separated screens, display types selectable are restricted. Only the screens of the real time trend, the numerical display and the bar graph are selectable.
< Switching method from 1-screen display to 4-screen display >
Select the [4 screens] from the DISP menu.
Tap the
icon lower right.
The screen can be switched to the 4-screen display in one of the above methods.
< Switching method from4-screen display to 1-screen display >
Tap inside the frame required to expand the display. Tap the DISP button of the frame required to expand the display and select the [1 screen].
After pressing the DISP key to move to the frame selection mode (*), select the frame required to
expand the display by pressing the direction key and then press the ENTER key.
The screen can be switched to the 1-screen display in one of the above methods.
(* Frame selection mode) By pressing the DISP key at the 4-screen display, the mode is switched to the frame selection mode. In
the frame selection mode, the frame is shifted with the direction key for selection and the following key operation enables.
Frame selection mode: The frame selected is enclosed with the blue frame.
ENTER The frame selected is displayed with 1-screen display. DISP The DISP menu for the frame selected is displayed. The
contents selected with this DISP menu are reflected to the frame selected.
ESC The frame selection mode is cancelled.
Selected frame
Page 38
35
8. Screen switching method
When the power is turned on, the operation screen is displayed after
performing the initial operation for about 10 to 30 seconds. (Default
settings at the factory: Real time trend screen). When the power is turned
on after changing the operation screen, the “operation screen that was
selected when the power was turned off” is displayed.
Tap the [Operation] button and then tap the [HOME settings]. Or press the [HOME] key.
About 10 to 30 seconds
Initial operation
screen
Open the key cover. (For key operations)
Switching to the setting screen When the key shown in the right is pressed on the operation screen, the screen is switched to the setting screen for setting each parameter.
Tap the [Operation] button and then tap the [MENU settings]. Or press the [MENU] key.
The operation screen switching is executed by selecting the DISP menu. Switch to a desired screen with the following procedures.
(1) Tap the [DISP] button or press the [DISP] key to display the DISP menu.
(2) Select a menu by tapping operations, or with the direction key and press the [ENTER] key to
display a screen selected.
Display selection: For selecting the display type (Real time trend, numeric display, etc.) of
the screen
Group selection: For selecting the group to be displayed.
* When the [Auto switching] is selected (with checking), the display group is automatically switched at
a fixed interval.
Operation screen switching method
Page 39
36
<HOME settings>
The settings are used to execute same settings to all channels easily. The items settable are limited. The settings cannot be used during recording.
<MENU settings>
The settings are used for normal settings. All items can be set and seen during recording, but there are some items not settable. The items not settable are displayed in gray.
Page 40
37
9. Names and functions of the operation screen
9.1 Common operations of the operation screen
(Using method of each key)
The recording is started. The data of the groups, of which recording conditions are established, are stored into the internal memory. The groups, of which recording conditions are not established, become the standby state and their recording starts at the time of establishment of conditions. The groups, of which recording conditions cannot be established, become the standby state for recording. The storing into the CF card is automatically executed at certain storing intervals when the saving to a file is completed.
(Tapping operation)
Tap the [Operation] button. Then tap the [START] or the disk icon.
The recording is stopped. The recording of all groups becomes the stop state. The file in saving is completed and data is stored into the CF card.
(Tapping operation)
Tap the [Operation] button. Then tap the [STOP] or the disk icon.
The DISP menu is displayed.
Menu item Operation Select display Used to change the operation screen type. Select group Used to change the display group. Auto switching Used to turn or off the automatic switching of the group and channel. The switching
becomes active by checking. When the automatic switching time is set to 0, this
switching is not valid. Snapshot Used to save a hard copy of a screen to the CF card (SNAPSHOT folder). Pause Screen updates are stopped except status bar. When press any key, the screen is
displayed again. All operations except describing of data recording and recording
processing are performed during pause.
When the DISP key is pushed in the Pause, the Snapshot is executed. Display OFF Used to turn off LCD display. The LCD is turned on again by pressing any of buttons. 4 screens Used to display 4 separate screens. Magnify/reduce The trends are displayed by compressing the time axis. (Same magnification to 1/60)
(Tapping operation)
Tap the [DISP] button.
Each setting screen is displayed. (Refer to Para. 7.2.)
(Tapping operation)
Tap the [Operation] button and then tap the [HOME settings].
Tap the [Operation] button and then tap the [MENU settings].
The ENTER menu is displayed. Menu contents differ depending on the screens.
(Tapping operation)
The operation differs depending on the screens.
The screen is returned to a previous screen. In case of the screens of the real time trend,
the bar graph and the numerical display, the screens do not return to a previous screen.
(Tapping operation)
Tap the [Return] button. (On the setting screen)
START
STOP
DISP
HOME MENU
ENTER
ESC
Page 41
38
(Tapping operation)
Not available
(Displayed data) Measured data displayed on each screen
Measured data Contents (Numeric value) The values are displayed based on the display scale settings of each channel.
The values are displayed with the number of digits after decimal point of the maximum and minimum values of the display scale.. When the type is “Exponent”, the values are displayed in such exponential format as”1.2E+3”. In this case, up to 2 digits after the decimal point of the significand can be set but only 1 digit is displayed depending on the screen.
BURN
Open between terminals
OVER
A value above the measurable high limit value (upper limit value + 5% of range) is inputted. Or calculated value is above the value that can be indicated (*).
UNDER
A value below the measurable low limit value (lower limit value - 5% of range) is inputted. Or calculated value is below the value that can be indicated (*).
CAL ER
Calculation error
RJ ERR
The recorder is abnormal.
* Range that can be indicated for calculated result as follows.
Display format is “standard”
Numeric value that exclude decimal point is within ±30000 (Example: -30.000 to +30.000)
Display format is “index”
1.00E-15 to 9.99E+15
Excluding the historical data displayed part of the historical trends and the dual trends, the current data
(with 0.5 second interval) irrespective of the recording interval, etc. is displayed as the numeric displayed
data. For slowing down the updating speed, change “Numeric value display update interval”. (Refer to
Para. 13.3.3.)
9.2 Status bar
The status bar is displayed on the top of the screen and displays the status, etc. of this recorder.
Normally the back color is green but, when the schedule (Refer to Para. 13.7) is set, the back color
becomes gray for the period other than the scheduled period.
The screen type currently selected
Disk icon showing recording status, etc.*
The recording interval of the group currently displayed , time ruler interval value and the remaining recordable time estimation are displayed alternatively.
Current time
Alarm icon *
For the vertical trend
The display group is switched with the up and down keys and the displayed
channel is switched with the left and right keys.
For the horizontal trend
The display group is switched with the left and right keys and the displayed channel is switched with the up and down keys.
Page 42
39
The icon shows the activation status and the confirmation status of alarms. The confirmation (ACK) of
alarm is executed with the ENTER menu or by tapping on the alarm icon on the operation screen.
Icon status Alarm status Confirmation (ACK)
status
Lit Activated Confirmed Icon inside blinking Activated Not confirmed yet Icon blinking Not activated Not confirmed yet Not displayed Not activated
Alarm icon
The arrow indication shows the recording status of the group currently displayed.
Arrow Status Displaying
vertically.
Recording
Blinking. The START key was pressed but the recording is in the standby state
since recording conditions are not established.
Not displayed. The START key is not pressed. (In the state that the recording is stopped
by pressing the STOP key)
The back color shows the state of the CF card.
Back color Status Gray Normal Yellow The remaining space of the CF card is less than 10%. [When the overwriting
mode (Para. 13.11.4) has been set, the back color does not become yellow.]
Red The CF card has no space. [When the overwriting mode (Para. 13.11.4) has
been set, the back color does not become yellow.]
When X is displayed on the disk mark, the CF card is not inserted.
The circle on the upper right of the icon shows the access status to the CF card. If the CF card is
removed when the color is red, data may be damaged. Remove the CF card when the circle is
gray.
Color Status Gray Not accessing to the CF card Yellow Writing in the CF card is executed within about 5 seconds. Red Accessing to the CF card
When the “USB memory” is selected in the “Select external memory”, the “USB” is displayed on the
icon. In this case, the data are stored into the USB memory connected. For the USB memory, refer
to “15. Storing data into the USB memory”.
Disk icon
Page 43
40
9.3 Real time trend screen
The trends of measured values can be seen like an analog recorder. The pens are displayed on the scale
plates corresponding to the values of “Position” parameters of each channel. When the same “Position” is
set to multiple channels, the scale plates, trends and pens are displayed in the contents of the display
scale of the smallest channel number in the group.
ENTER menu function
Magnify/reduce
The trends are displayed by compressing the time axis. (Same magnification to 1/60)
(Tapping operation)
In the DISP menu, the same item is available.
Key operations other than the common operations (Para. 9.1)
The historical trend (or the dual trend) screen is displayed. This key operation is same as selecting the
Historical trend (or the Dual trend) in the DISP menu. When the Historical trend is selected in the DISP
menu, the trends are displayed from then and, when the dual trend is selected, the trends are displayed
from then.
(Tapping operation)
Tap the [Hist] button.
The marker-write dialog box is displayed. The marker writing cannot be
executed during the record stop. Select a marker text registered with the
MENU settings beforehand and write the text on the trends by pressing
the ENTER key. When the “Input Text” is selected, the keyboard screen
is displayed for writing a text desired.
(Tapping operation)
Tap the [MARKER] button.
The measured data of the channel in alarm activated is displayed in red.
This part can be selected from the data display (with/without tag), the bar graph and non-display.
Maker display
SCROLL
MARKER
Page 44
41
9.4 Bar graph screen
The measured values of the channels are displayed with the bar graphs in real time and can be seen
visually. The length of the bars and scale plates is displayed in the contents of the display scale with the
smallest channel number in the group.
ENTER menu function
Not available
Key operations other than the common operations (Para. 9.1)
Same as Real time trend
9.5 Data screen
The “Measured data of channels” and the “Alarm activation status” are displayed. Depending on the “Data
display frames” or the number of groups registered, data of 1,2,3,4,6,8,9,10,12,24,36,48 or 56 channels
are displayed.
ENTER menu function
Not available
Key operations other than the common operations (Para. 9.1)
Same as Real time trend
This part can be selected from the data display (with/without tag) and non-display.
The measured data of the channel in alarm activated is displayed in red.
When the number of displayed channels is less than 12, maximum and minimum values of these channels can be displayed. The values are reset at the record start. Non-display of these values is available.
(Refer to Para. 13.3.3)
SCROLL
SCROLL
Page 45
42
9.6 Historical trend screen
The recorded data are replayed and displayed as the trend display. When the “Historical trend” is selected
in the DISP menu (or when the “SCROLL” key on the real trend screen is pressed), data in the internal
memory are displayed. When a file is selected in the “Internal memory” screen, the “CF card” screen, or
“USB memory” screen, data of the selected file are displayed. The historical trend operation method is the
same for each selection. The display method of the scale plates, trends and pens is same as the real time
trend screen.
ENTER menu function
Magnify/reduce
The trends are displayed by compressing the time axis. (Same magnification to 1/60)
(Tapping operation)
In the DISP menu, the same item is available.
Key operations other than the common operations (Para. 9.1)
Press this key to switch to the scroll mode. When this key is pressed once, the scroll bar is enclosed with a yellow frame and the scroll mode becomes ON. In this status, by pressing the direction key, the trends are scrolled one screen by one screen. When the scroll key is pressed again, the scroll mode becomes OFF and the trends are scrolled one dot by one dot by pressing the direction key.
Press this key to switch to the cursor mode. When this key is pressed once, the cursor line is displayed in yellow color and the cursor mode becomes OFF. In this status, by pressing the direction key, the cursor line moves without scrolling and the data at the cursor position are displayed on the numeric value display (or bar).
(Tapping operation) Switching the displayed channel Tap channel switching buttons at left and right of the data display part. Moving the cursor Tap on a trend. Scroll Operate the scroll bar.
SCROLL
CURSOR
For vertical trend
Left and right keys: Switching the displayed channel Up and down keys: Scrolling the trend graph and moving the cursor when the
cursor mode is ON
For horizontal trend
Left and right keys: Switching the displayed channel Up and down keys: Scrolling the trend graph and moving the cursor when the
cursor mode is ON
Data at the cursor position are displayed.
Marker display
Cursor
Page 46
43
The marker-write dialog box is displayed. Select a marker text registered with the MENU settings beforehand and write the text at the cursor position by pressing the ENTER key. When the “Input Text” is selected, the keyboard screen is displayed for writing a text desired.
(Tapping operation)
Tap the [MARKER] button.
When the “data format” of the file to be displayed is
“Maximum/Minimum”, the values displayed in the numeric
value display (or bar) are switched to the maximum and
minimum values. Other operations are same as the HOME
key.
Either of the current display is shown in H or L display on the status bar.
(Tapping operation)
Tap the H or L icon on the status bar.
9.7 Dual trend screen
The real time trends and the historical trends are displayed by dividing the screen up and down, and the
current data and the past data can be compared. Also the data display displays the current values and
values at the cursor position of the historical trends by dividing the screen up and down.
The displaying method of the trends and positions of pens is same as the real time trend screen. However,
in case of the setting that multiple scale plates are displayed, only 1 scale plate is displayed, and the
numeric values on the scale plate are not displayed.
The operation method is the same as the historical trend screen.
ENTER menu function
Same as the historical trends (Refer to Para. 9.6.)
Key operations other than the common operations (Para. 9.1)
Same as the historical trends (Refer to Para. 9.6.)
MARKER
HOME
Up: Current measured values Down: Display of data at the cursor position
on the historical trends
Page 47
44
9.8 Alarm display screen
The alarms being activated are displayed as a list. Activation date/time, cancel date/time (cancelled alarms
only), channels (tag names) and alarm types are displayed in the reverse chronological order (latest on the
top). Irrespective of the groups, all alarms being activated in this recorder are displayed.
Maximum 1000 alarm data are recorded. When the alarm data exceeds 1000, the data are deleted in
chronological order.
ENTER menu function
Trend
display
The screen is jumped to the trend at the activated date/time of the selected row. When the alarm was not recorded at its activation or the file is not found, the screen cannot be jumped. The file search in this case is executed in the order of the internal memory the CF card.
(Tapping operation)
By tapping a row in the list, the ENTER menu appears.
Key operations other than the common operations (Para. 9.1)
Press this key to switch to the scroll mode. When this key is pressed once, the scroll bar is enclosed with a yellow frame and the scroll mode becomes ON. In this status, by pressing the direction key, the trends are scrolled one screen by one screen. When the scroll key is pressed again, the scroll mode becomes OFF and the trends are scrolled one line by one line by pressing the direction key.
(Tapping operation)
Operate the scroll bar.
The selected row is displayed in yellow.
SCROLL
Up/down keys: Moving the row for selection
Left/right keys: Not used
Page 48
45
9.9 Internal memory screen
The list of files recorded in the internal memory is
displayed. The start date and time, the end date
and time (the latest data time for a file being
recorded) and the data count are displayed. The
files are displayed in the reverse chronological
order (latest on the top). All files only of the
selected group are displayed.
ENTER menu function
Trend display The trends recorded in the file of the selected row are displayed.
(Tapping operation)
By tapping a row in the list, the ENTER menu appears.
Key operations other than the common operations (Para. 9.1)
Press this key to switch to the scroll mode. When this key is pressed once, the scroll bar is enclosed with a yellow frame and the scroll mode becomes ON. In this status, by pressing the direction key, the trends are scrolled one screen by one screen. When the scroll key is pressed again, the scroll mode becomes OFF and the trends are scrolled one line by one line by pressing the direction key.
(Tapping operation)
Operate the scroll bar.
The selected row is displayed in yellow.
CROLL
Up/down keys: Moving the row for selection
Left/right keys: Not used
SCROLL
Page 49
46
This recorder records all recorded data into the internal memory as a file. The data are copied to the CF card at a certain storing interval when the recording to this file is completed
<Limitations of internal memory> (File capacity) 1 file is completed with maximum volume (refer to the following list). The file size can be calculated with the followings.
Data volume x Number of channels x Number of records
(Usually the data volume is 4 bytes. When the data format is “Maximum/minimum”, the data volume is 6 bytes.) When the recording is stopped due to recording conditions not established, by pressing the STOP key or by power off, etc. the file is completed at the time before reaching to maximum volume of file.
Number of
groups used
Maximum volume of file
KB
Recording frequency
when 12 points are used
4 byte data
1
3904 83280
2
1920 40960
3
1216 25940
4
896 19110
5
704 15010
6
576 12280
(Number of files) The number of files that can be saved in the internal memory is maximum 250 files (In each group, “250 ÷ Number of groups used” [Fraction is rounded down.]).
(Volume of all files) The total volume of files that can be saved in the internal memory is 64KB x (125 ÷ (Number of groups used) – 2). If the volume exceeds it, the files are deleted in chronological order.
Internal memory
Page 50
47
9.10 CF card/USB memory screen
The list of files stored in the CF card or the USB
memory is displayed. The start date and time, the
end date and time (the latest data time for a file
being recorded) and the data count are displayed.
The files are displayed in the reverse chronological
order (latest on the top). All files only of the
selected group are displayed.
ENTER menu function
Trend display
The trends recorded in the file of the selected row are displayed. (Binary
only)
Delete The file of the selected row is deleted.
FTP transmission The file of the selected row is transferred with FTP.
Copying to USB memory (CF card screen only)
The file of the selected row is copied to the USB memory. When the USB memory is not inserted, this menu is not displayed.
(Tapping operation)
By tapping a row in the list, the ENTER menu appears.
Key operations other than the common operations (Para. 9.1)
Press this key to switch to the scroll mode. When this key is pressed once, the scroll bar is
enclosed with a yellow frame and the scroll mode becomes ON. In this status, by pressing
the direction key, the trends are scrolled one screen by one screen. When the scroll key is
pressed again, the scroll mode becomes OFF and the trends are scrolled one line by one
line by pressing the direction key.
(Tapping operation)
Operate the scroll bar.
SCROLL
Up/down keys: Moving the row for selection Left/right keys: Not used
The selected row is displayed in yellow.
Page 51
48
9.11 Marker list screen
The list of markers recorded on the trends is
displayed. The date and time and the marker text
are displayed in the reverse chronological order
(latest on the top). The markers recorded in the
selected group are displayed.
Maximum 200 markers are recorded. When the
recorded marker exceeds 200, the markers are
deleted in chronological order.
ENTER menu function
Trend display
The screen is jumped to the trend position of the marker of the selected row. When the file is not found, the screen cannot be jumped.
Delete The marker of the selected row is deleted.
Delete all All markers in the list are deleted.
(Tapping operation)
By tapping a row in the list, the ENTER menu appears.
Key operations other than the common operations (Para. 9.1)
Press this key to switch to the scroll mode. When this key is pressed once, the scroll bar is
enclosed with a yellow frame and the scroll mode becomes ON. In this status, by pressing
the direction key, the trends are scrolled one screen by one screen. When the scroll key is
pressed again, the scroll mode becomes OFF and the trends are scrolled one line by one
line by pressing the direction key.
(Tapping operation)
Operate the scroll bar.
Up/down keys: Moving the row for selection Left/right keys: Not used
The selected row is displayed in yellow.
SCROLL
Page 52
49
9.12 Controller display screen
When controllers are connected with low order communications and registered in a group, the controllers can be displayed. By dividing the channel registered in the group selected into a frame for each controller, PV, SV, and MV are displayed. Moreover, RUN/READY selection, SV1/2 selection, AUTO/MANUAL selection, PID, etc. in each frame can be set.
The controllers up to 16 sets can be displayed and up to 8 sets are displayed on 1 screen. In case of 9 sets or more, the controllers are displayed by switching with the arrow buttons displayed on right and left.
Contents of each function button For DP-G series controllers, function buttons are not displayed. Data display is only enabled.
RUN/READY Selects RUN/READY of a controller
SV1/2
Selects execution SV1/2 of a controller This button is not displayed for LT series controllers except LT400 series.
AUTO/MANUAL
Selects the modes of AUTO/MANUAL of a controller This button is not displayed for LT series controllers except LT400 series.
SET
The following setting screen is displayed to enable settings.
SV,MV,P,I,D: Each parameter of
a controller is set.
Auto-tuning: Starts auto-tuning
For this screen, settings can be executed on the touch panel only.
Page 53
50
9.13 Controller bar graph screen
When controllers are connected with low order communications and registered in a group, the controller bar graph screens can be displayed. By dividing the channel registered in the group selected into a frame for each controller, PV, SV, and MV are displayed with bar graphs.
The controllers up to 16 sets can be displayed and up to 8 sets are displayed on 1 screen. In case of 9 sets or more, the controllers are displayed by switching with the arrow buttons displayed on right and left.
9.14 Controller text screen
When controllers are connected with low order communications and registered in a group, the controller text screens can be displayed. By dividing the channel registered in the group selected into a frame for each controller, PV, SV, and MV are displayed with texts. Moreover, alarm activation state (EV) of a controller can be confirmed.
The controllers up to 16 sets can be displayed.
Page 54
51
10. Initial settings
When the power supply is turned on under the default settings at the factory or when the settings are
initialized, the initial settings screen is displayed. Set the indispensable following parameters on use.
You can exit without setting the parameters. In that case, this recorder operates with the default settings at
the factory.
Language
Power frequency 50Hz/60Hz
Setting of the usage group count
Clock settings
Input settings
Display settings
File settings
By pressing the ENTER key or touching the [OK] button, the message disappears and the
settings are enabled.
(1) Setting of the language
By tapping the button of the Language, the pulldown menu is displayed.
Tap English or Japanese in the pulldown menu for setting.
10
Page 55
52
(2) Setting of the power frequency
By tapping the button of the 50Hz/60Hz, the pulldown menu is displayed.
Tap 50Hz or 60Hz in the pulldown menu for setting.
Confirm and set the power frequency being used.
(3) Setting of the usage group count
By tapping the button of the item of the usage group count, the pulldown menu is displayed. Select usage group count in the pulldown menu and press the ENTER key.
This setting is set for noise (Industrial frequency) filter of the input. Please switch whenever it uses with 60Hz band and the industrial frequency noise influences it and use it.(The noise removal characteristic might improve it by the thing adjusted to 60Hz side.)
参考
About the setting of the power supply
Page 56
53
(4) Clock settings
By tapping the [Set] button of the clock settings, the following clock settings screen is displayed.
* For detailed settings, refer to [13.11.1 Clock settings].
(5) Input settings
By tapping the [Set] button of the input settings, the following input settings screen is displayed.
* For detailed settings, refer to [13.2 Input operation settings].
Page 57
54
(6) Display settings
By tapping the [Set] button of the display settings, the following display settings screen is displayed.
* For detailed settings, refer to [13.3.1 Channel parameters].
(7) File settings
By tapping the [Set] button of the file settings, the following file settings screen is displayed.
* For detailed settings, refer to [13.5 File settings].
Page 58
55
11. Flow chart of HOME settings and MENU settings
MENU settings screen (MENU key) Input operation settings
Display settings
Alarm settings
File settings
Totalizer reset settings
Schedule settings
Marker text settings
Memory operation
Network settings
System settings
Settings screen
Operation
screen
HOME settings screen (HOME ke
y)
11
Page 59
56
Detailed settings
Detailed settings
LCD settings
Detailed settings
Detailed settings
Detailed settings
ON/OFF settings
Detailed settings
Detailed settings
Key lock
Password settings
High order communications
Clock settings
Detailed settings
ON/OFF settings
Detailed settings
Detailed settings
Ethernet settings
FTP client settings
SNTP settings
E-MAIL settings
Forwarding address
Transmission condition selection
Attached data
Account
Detailed settings
Writing the settings to the external memory
Reading the settings from the external memory
Initializing the settings
Writing from the internal memory to the external memory
Copy the data from CF to USB
Erasing the internal memory data
Saving of settings
Reading of settings
OK/Cancel settings
OK/Cancel settings
OK/Cancel settings
OK/Cancel settings
Detailed settings
Channel parameters
Group parameters
List
Common parameters
Settings of group
Detailed settings
Settings of display
Input parameter settings
Recording interval settings
Confirmation o specifications
Instrument specifications display
DNS settings
Scale adjustment
Detailed settings
Touch panel correction
Other settings
Detailed settings
FTP server settings
Format the USB memory
Format the CF card
OK/Cancel settings
OK/Cancel settings
Group parameters 2
Web server settings
Low order communications
(
Displayed at pertinent option)
Detailed settings
Page 60
57
12. HOME settings
12.1 Setting with HOME settings
When the [HOME settings] is used, the inputs and recordings of all channels together can be set for the
confirmation of input/recording simply.
Operation screen
Press the key or tap [Operation] – [HOME settings]
HOME settings screen
Setting the range type
DC voltage 13.8mV, 27.6mV, 69mV, 200mV, 500mV, 2V, 5V, 10V, 20V, 50V
Thermocouple
K, E, J, T, R, S, B, N, W-WRe26, WRe5-WRe26, PR40-20, NiMo-Ni, CR-AuFe, Platinel2, U, L
Resistance thermometer
Pt100, JPt100, Pt50, Pt-Co
Setting the range
Set the range. (It is decided by the range type.)
HOME
Press the HOME key on the operation
screen to move to the HOME settings. For
the settings, move the cursor (blue) to the
desired item with the direction key and press the ENTER key, or tap the button of the
desired item. Then a selection screen is
displayed for setting.
12
Page 61
58
Setting the scale
Set the scale. (It is decided by the range type.)
Since the number of digits after decimal point set here becomes the number of digits after decimal point for the measured value, enter a value correctly.
Setting the RJ (Reference junction compensation)
Set whether the RJ is internal or external.
Setting the burn out
None The burnout function is not used. UP Set to the upscale burnout. DOWN Set to the downscale burnout.
Setting the recording cycle
Second 0.1 second, 0.2 seconds, 0.5 seconds, 1 second, 2 seconds, 3 seconds,
5 seconds, 10 seconds, 15 seconds, 20 seconds, 30 seconds
Minute 1 minute, 2 minutes, 3 minutes, 5 minutes, 10 minutes, 15 minutes,
20 minutes, 30 minutes, 60 minutes
Page 62
59
12.2 Confirming the specifications with HOME settings screen
The information of specifications of this recorder can be confirmed. When you have any question on this recorder, contact your nearest distributor after confirming
specifications by this screen.
Operation screen
 HOME setting screen
Specifications confirmation screen
Tap .
In the specifications confirmation screen, the followings can be confirmed.
Model Serial number Software version MAC address
HOME
Tap [Operation] – [HOME settings] or press the key.
Page 63
60
13. MENU settings
13.1 Setting MENU settings screen
Operation screen
Setting menu screen
Input operation settings screen
Selection in the “Input operation settings”
For setting parameters, tap the [Operation] button on the operation screen and then tap the [MENU settings] to display the parameter items. By tapping an item, the screen is switched to the parameter settings screen of this item.
Click.
The list box of the parameters is displayed. Tap the parameter item to be set.
Input operation settings
Refer to “13.2 Input operation settings”.
MENU
Tap [Operation] – [MENU settings] or press the key.
13
Page 64
61
Display settings screen
Selection in the “Display settings”
Alarm settings screen
Selection in the “Alarm settings”
File settings screen
Selection in the “File settings”
Alarm settings
Refer to “13.3 Alarm settings”.
Display settings
Refer to “13.3 Display settings”.
File settings
Refer to “13.5 File settings”.
Page 65
62
Totalizer reset settings screen
Selection in the “Totalizer reset settings”
Schedule settings screen
Selection in the “Schedule settings”
Marker text settings screen
Selection in the “Marker text settings”
Totalizer reset settings
Refer to “13.6 File settings”.
Marker text settings
Refer to “13.8 Marker text settings”.
Schedule settings
Refer to “13.7 Schedule settings”.
Page 66
63
Memory operation screen
Selection in the “Memory operation”
Network settings screen
Selection in the “Network settings”
System settings screen
Selection in the “System settings”
Network settings
Refer to “13.10 Network settings”.
Memory operation
Refer to “13.9 Memory operation”.
System settings
Refer to “13.11 System settings”.
It displays it only at the Low order communication option.
Page 67
64
13.2 Input operation settings
13.2.1 Setting contents
Proceed from the MENU settings. By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the “Input operation settings” on the setting menu screen, the following screen is displayed.
*When Low order communication(read) option is effective, the item for the low order
communication registration is added. Please see "16. Low order communication(read) setting (option)" also.
By touching a CH number, the detailed setting screen for this channel is displayed.
Page 68
65
Setting the range type
(Analog input)KR3120,KR3121: CH1 to 12, KR3140,KR3141: CH1 to 24
KR3160,KR3161: CH1 to 36, KR3180,KR3181: CH1 to 48
DC voltage 13.8mV, 27.6mV, 69mV, 200mV, 500mV, 2V, 5V, 10V, 20V, 50V
Thermocouple
K, E, J, T, R, S, B, N, W-WRe26, WRe5-WRe26, PR40-20, NiMo-Ni,
CR-AuFe, Platinel2, U, L Resistance thermometer
Pt100, JPt100, Pt50,Pt-Co
(Digital input) *For the optional digital input specified CH121 to 128
Digital input DI Pulse input Pulse(+), Pulse(-)
Setting the range
Set the range. (It is decided by the range type.)
Setting the scale
Set the scale. (It is decided by the range type.)
Since the number of digits after decimal point set here becomes the number of digits after decimal point for the measured value, enter a value correctly.
Page 69
66
Setting the sensor correction
Set a value (shift value) added to the input value.
Setting the RJ (Reference junction compensation)
Set whether the RJ is internal or external.
Setting the burn out
None The burnout function is not used. UP Set to the upscale burnout. DOWN Set to the downscale burnout.
Setting the filter level
The input filter level can be set from 0 to 3. 0 means no-filter, and 3 means the strongest filter.
When [system settings] is selected, settings are following [system settings] – [other settings].
Setting the tag
Setting a tag name (Setting for displaying the tag name instead of the channel number)
When the display of the data of a [Display settings]-[Common parameters] is set with tag,
it is effective.
Setting the unit
Set the engineering unit of its channel.
Setting the usage of calculation
OFF
The input data are displayed and recorded as the measured date of its channel.
ON
The results processed by the calculation formula are displayed and recorded as the measured data of its channel.
Setting the formula
When the calculation usage is ON, set the formula of its channel.
Copying the parameters with the copy function
The above shows the setting for copying Channel 01 from Channel 02 to Channel 05. By tapping the [Go], the parameters of Channel 01 are copied from Channel 02 to Channel 05.
Page 70
67
13.2.2 Setting method of formula
1) Formula types
Mathematical calculation
Four arithmetic operations are performed.
* X and Y indicate the formula or the numeric value.
Comparison calculation
The comparison calculation is performed and the result is;
1 (established) or 0 (not established)
* X and Y indicate the formula or the numeric value.
Logic operation
The logic operation for 1 or 0 is performed and the result is returned as 1 or
0.
* X and Y indicate the formula or the numeric value. Express X and Y as 0 or 1.
General calculation functions
The function calculation is performed.
* X indicates the formula or the numeric value.
Symbol Example Remarks
Addition + X +Y
Subtraction
-
X -Y
Multiplication * X *Y
Division / X /Y
Reminder % X %Y
Exponential ^ X ^Y
Symbol Example Remarks
Equal value == X ==Y
Unequal value != X !=Y
More than >> X >>Y
Less than << X <<Y
Equal or more than >= X >=Y
Equal or less than <= X <=Y
Symbol Example Remarks
Logical AND AND X ANDY
Logical OR OR X ORY
Exclusive OR XOR X XORY
Negation NOT NOT(X ) Put the object being negative
in brackets.
Symbol Example Remarks
Round up after the decimal CEL CEL(X )
Round down after the decimal FLR FLR(X )
Absolute value ABS ABS(X )
Square root SQR SQR(X )
Power of e EXP EXP(X )
Natural logarithm (The base is e.) LOG LOG(X )
Common logarithm (The base is 10.) LOG10 LOG10(X )
Page 71
68
Channel data calculation functions
The function calculation is performed. When an error data (OVER, UNDER, etc.) is included in the measured data, it becomes “CAL ER”.
* X indicates the channel number.
* When the channel data calculation is specified for executing with the settings of the designated channel number, the calculated results of the designated channel number are used. In addition, when the designated channel number is greater than the channel number for calculation, the calculation results obtained previously at the designated channel are used.
System information acquisition function
Other function
Symbol Example Remarks
Measured data
CH CH(X)
Calculation result
data
PCH PCH(X)
X is channel No.
Previous calculated
result data
OCH OCH(X)
Data at the previous scanning (before 0.1 seconds)
Totalizer
ITG ITG(X)
Refer to 2) Totalizing operation
24-hour totalizing
ITG24 ITG24(X)
Refer to 2) Totalizing operation
F value
FV FV(X#To#Z#R) Refer to 3) F value
Relative humidity
RH RH(D#W) Refer to 4) Relative humidity
Dew-point
temperature
DEW DEW(T#H)
Refer to 5) Dew-point temperature
Moving average
(an hour)
AVE AVE(X#T) Refer to 6) Moving average
Moving average
(5 minutes)
AVEH AVEH(X#T) Refer to 6) Moving average
Past data
(an hour)
OLD OLD(X#T) Refer to 7) Past data
Past data
(5 minutes)
OLDH OLDH(X#T) Refer to 7) Past data
First-order leg filter
IIR IIR(X#T) Refer to 8) First- order filter
Increment per time PLS PLS(X#T )
Refer to 9) Increment per time
Symbol Example Remarks
CF card remaining
space
CF CF(A )
A = Unit of remaining space
0: MB 1: Minute 2: Hour 3: Day
Symbol Example Remarks
Wind display AZI AZI(A) Refer to 10) Wind display
Page 72
69
2) Totalizing operation
For the totalizer, the ITG function or the ITG24 function is used. Do not use the totalizing function more than two times in one formula. The results are not calculated correctly. The totalizing function can be used in calculations other than the totalizer. Example: ITG(1)+ITG(2), ITG24(1)-ITG(1), ITG(1)/100 For the totalizer reset, refer to Para. 13.6.
(1) Standard totalizing operation
The totalized values are reset at the totalizer reset reference time or at every interval.
Entering method of the formula
ITG(d)
d: Channel number to be totalized
Calculation contents
n
= D
n-1
+[(PVn + PV
n-1
)×(Tn-T
n-1
)]÷2
n
: Totalized result D
n-1
: Previous totalized result
PV
n
: Data to be totalized PV
n-1
: Data totalized at the previous calculation
T
n
: Time of calculation T
n-1
: Time of the previous calculation (before 0.1 second)
When error data (OVER, UNDER, etc.) are included, the calculation is not performed and the previous results are used.
(2) 24-hour totalizing operation
The totalized values are reset only at the totalizer reset reference time or at every interval.
Entering method of the formula
ITG24(d)
d: Channel number to be totalized
The calculation contents are same as the standard totalizing operation.
3) F-value
Entering method of the formula FV (X#To#Z#R)
X: Channel to be calculated, To: F-value calculation reference temperature, Z: Z-value,
R: F-value calculation starting temperature
The following formula is used for the F-value calculation.
10
A
dt Provision: A=(T-To)÷Z T: channel data to be calculated
When T exceeds R, the F-value is reset to 0.
4) Relative humidity
Entering method of the formula
RH (D#W)
D: Dry bulb temperature, W: Wet bulb temperature
The following formula is used for the relative humidity calculation.
((B-0.000662×1013.0×(D-W))÷A)×100
Provision: A; Dry bulb saturated water vapor pressure, B: Wet bulb saturated water vapor pressure
The following formula is used for the calculation of the saturated water vapor pressure.
6.1121×EXP((17.502×T)÷(240.9+T)) T: Temperature
Page 73
70
5) Dew-point temperature
Entering method of the formula
DEW (#)
T: Temperature data channel, H: Relative humidity channel
The following formula is used for the dew-point temperature.
t: Temperature data
h: Relative humidity data
D: Dew-point temperature
1. K=t+273.15
2. In case of t≥0
W=EXP(-5800.2206/K+1.3914993+K×(-0.048640239+K×(0.41764768E-4
-0.14452093E-7×K))+6.5459673×LOG(K))/1000
In case of T<0
W=EXP(-5674.5359/K+6.3925247+K×(-9.677843E-3+K×(0.62215701E-6
+K×(0.20747825E-8-9.484024E-13×K)))+4.1635019×LOG(K))/1000
3. S=W×h/100
4. P=S×1000
5. Y=LOG(P)
6. In case of P≥611.2
D=-77.199+Y×(13.198+Y×(-0.63772+0.071098×Y))
In case of P<611.2
D=-60.662+Y×(7.4624+Y×(0.20594+0.016321×Y))
Page 74
71
6) Moving average
Entering method of the formula
AVE (X#T) AVEH (X#T) X: Data channel number, T: Time series interval (second)
Mean value of past T seconds is calculated. Difference between AVE and AVEH are the following.
AVE AVEH Sampling cycle 1 second 0.1 seconds Range of T 1 to 3600 1 to 300
7) Past data
Entering method of the formula
OLD (X#T) OLDH (X#T) X: Data channel number, T: Time in which go back (second)
Mean value of past T seconds is calculated. Difference between OLD and OLDH are the following.
OLD OLDH Sampling cycle 1 second 0.1 seconds Range of T 1 to 3600 1 to 300
8) First-order leg filter
Entering method of the formula
IIR (X#T) X: Data channel number, T: Time constant (second)
First-order calculate is performed in the data of channel X.
Contents of calculation
dt÷(dt+t)×x-d)+d
dt: Sampling cycle (0.1 seconds fixed), t: time constant, x: current value of channel X, d: previous
calculation result
9) Increment per time
Entering method of the formula
PLS (X#T)
X: Data channel number, T: Unit time (second)
Calculate increment per unit time T. X is specified from the channel that is set totalizer or the channel that is selected pulse range in 121 to 128.
As for the PLS function, when the totalized value is reset excluding reset by the overflow at time etc. , the data when resetting it becomes illegal (To do the same processing as overflow reset internally). Please do the operation construction noting the resetting operation when using it.
Page 75
72
10) Wind display
Entering method of the formula
AZI (A) A: Wind data
Display the compass point which is changed from direction. Relation of the displayed direction of wind data is in the following list. If A is fractional value, display closest direction. Example: 1.2 NNE
A Display
・ ・ ・
・ ・ ・
-3 WNW
-2 NW
-1 NNW 0 N 1 NNE 2 NE 3 ENE 4 E 5 ESE 6 SE 7 SSE 8 S 9 SSW
10 SW 11 WSW 12 W 13 WNW 14 NW 15 NNW 16 N 17 NNE 18 NE
・ ・ ・
・ ・ ・
In addition, scale plate which is registered channel that is used this calculation is displayed wind scale.
Display coordinate on the trend is same as normal numeric data.
Page 76
73
11) Example of formula combining calculations
(CH(1)*3-20)/6
(“Raw data of Channel 1”×3-20)÷6
(CH(1)+CH(2))<<
300
When the total of the raw data of Channel 1 and Channel 2 is less than 300, it becomes 1.
ABS(CH(1))>=50
When the absolute value of Channel 1 is 50 or more, it becomes 1.
(PCH(1)>=100)AND(PCH(2)<=50)
When the data of Channel 1 is 100 or more and the data of Channel 2 is 50 or less, it becomes 1.
The following functions can not be used together. The results are not calculated correctly.
ITG, AVE, AVEH, OLD, OLDH, IIR Example: AVE (OLD (1#10)#60) NG
Conbination of functions
Remarks
Page 77
74
13.3 Display settings
13.3.1 Channel parameters
Proceed from the MENU settings. By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the display settings on the setting menu screen and then selecting the channel parameters,
the following screen is displayed.
Set the wave pattern type, maximum/minimum values of the display scale, color and the display position
of each channel.
( Setting the display scale
The data are displayed on the screen with the setting contents of the display scale.
Item Contents
Type “Std.”: Minimum and maximum values can be set in the range of
±30000.
The screen is displayed in the standard format.
“Expo”: Minimum and maximum values are set in the exponent format.
The screen is also displayed in the exponent format. The significand of minimum and maximum values is 1 to 9.99 and the exponent part can be set in the range of ±15.
Minimum/maximum In the trend display, the minimum value is positioned at the extreme left
(low) and the maximum value is positioned at the extreme right (up) by coordinate calculation. ( ) for horizontal direction When there are multiple channels displayed at the same position, the minimum and maximum values of the channel with the smallest number are displayed on the scale plate and the maximum and minimum values of each channel are used for the coordinate for each pen.
The maximum and minimum values are displayed with the number of
digits after decimal point displayed in the screen.
Page 78
75
Setting the display position
The position (1, 2, 3 and 4) indicates the position of the scale plate.
For the vertical trend graph
For the horizontal trend graph
4 3 2 1
Copying the parameters with the copy function
The above shows the setting for copying Channel 1 from Channel 1 to Channel 5. By tapping the [Go],
the parameters of Channel 1 are copied from Channel 1 to Channel 5. Colors are not copied.
1
2
3
4
Page 79
76
13.3.2 Group parameters
Proceed from the MENU mode. By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the display settings on the setting menu screen and then selecting the group parameters, the following screen is displayed. The group being specified by the number in the upper left "Group" can be set.
Setting the group name
Set the group name. This group name is used in the screen display and used as the file name of
the recorded data.
Channel
Set the channel to be registered in the group. The registration is cancelled by setting blank.
Trend display
Every time the ENTER key is pressed after selecting “Y” and ”N” are switched alternatively. The
trend with N is not displayed even if the channel has been registered. The data of channel with N selected are not recorded in the file.
Size
It is the thickness of the trend line. It can be selected from 1 to 5.
Setting the trip line
Set the trip line (dotted line) to be displayed on the trends.
Position
Set the display position of the trip line in the range 0-99% of the display width.
Color
Select the color of the trip line.
Size
Select the thickness of the trip line from 1 to 5.
Page 80
77
13.3.3 Group parameter 2
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen
.
By selecting the display settings on the setting menu screen and then selecting the group parameter 2, the following screen is displayed. The group being specified by the number in the upper left "Group" can be set.
Time ruler
Select auto or specified. In case of auto, ruled line interval is decided by recording interval.
Time ruler interval
Time ruler interval of trend is specified. Even number of 12 to 510 can be set. This function is effected when select ‘specified’ in ‘time ruler’.
Page 81
78
13.3.4 Common parameters
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the display settings on the setting menu screen and then selecting the common parameters, the following screen is displayed.
Setting the data display
Set the upper side (or right side) display of the trend screen to indicate the tag name, the bar graph
or nothing.
No tag With tag Bar graph Nothing
Setting the trend direction
Set the waveform direction to be vertical or horizontal.
Setting the data display size adjustment
This is the function which automatically sizes up data display on the trend screen when registered
channel numbers are small. In the following cases, data is displayed by lager font.
Data display Trend direction Number of the registered CH No tag Vertical Less than 4 With tag Vertical Less than 5 No tag Horizontal Less than 7 With tag Horizontal Less than 5
Setting the trend label
Set the label for displaying on the trend.
OFF Channel Tag
Setting the scale text
Set the scale plate to display the numerical values or not.
Setting the bar graph direction
Set the bar graph direction on the bar graph screen to be vertical or horizontal.
Page 82
79
Setting the base position of the bar graph
Set the base position of the bar graph from 0 to 100 on the bar graph screen. When the base
position is 0, the bar is displayed based on leftmost (or bottommost). When the base position is 100, the bar is displayed based on rightmost (or uppermost).
Setting the zone usage
The display range of the measured/calculated data is called zone. When the zone is set to ON, the
display range can be divided into zones. The details are described in the next page.
Setting the data display frame count
Set the division number of the numeric display frame.
1 2 3 4 6 8 9 10 12 24 36 48 56
Minimum/maximum display (data display)
Select [ON] or [OFF]. When select [ON], display minimum and maximum of channel data on the
numeric display screen. However, if data display frame count is more than 24, minimum and maximum is not displayed.
Screen auto switch period
Set the switching period if the “Auto switching” has been set to ON with the DISP menu.
Data value update period
Select the numeric value updating period of measured data to be displayed on the screen.
0.5 second 1 second
Dual trend synchronization
When previous file is opened by dual trend during ‘ON’, the file is scrolled as fast as real trend.
When scroll end of the file, if there is continuous file, the file is opened automatically and scrolling is continued.
When standard position is 0 When standard position is 50
When standard position is 100
Page 83
80
The display range of the measured/calculated data is called zone. Since the data can be displayed by setting the zone for each channel, the data can be easily read by displaying the waveforms in separate zones.
Select “ON” in the zone usage. Then, selecting the display settings in the setting menu screen and selecting the channel parameters, the following screen with the zone added is displayed.
When the zone is set to either 1 or 2, the display of wave format in the trend screen is divided into 2. Channels set by 1 are displayed in Zone 1 and channels set by 2 are displayed in Zone 2.
Zone 1 Zone 2
Zone
Page 84
81
13.3.5 LCD settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the display settings on the setting menu screen and then selecting the LCD settings, the
following screen is displayed.
Setting the display off timer (minute)
The display-off timer for the LCD can be set from 1 to 60 minutes.
For canceling the display off, tap any key.
Setting the display brightness
Select the brightness of the LCD backlight from 4 steps. 1 is the brightest and 4 is the darkest.
Setting the back color
Select the back color of the screen from white or black.
Page 85
82
13.4 Alarm settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the alarm settings on the setting menu screen, the following screen is displayed.
Setting the type and the setting value
Set the alarm type and the setting value for judgment.
The alarms are activated by the following conditions.
None Not activated Upper The measured value is the set
value or more.
Lower The measured value is the set
value or less. Diff. upper
In case that the absolute value of the difference between the measured value and the reference CH is the setting value or more
Diff. lower
In case that the absolute value
of the difference between the
measured value and the
reference CH is the setting
value or less Error The measured value is not a numerical value. (BURN, OVER, UNDER, CAL
ER, RJ ERR)
Setting the reference CH
Set the reference channel for the differential high limit alarm/differential low limit alarm.
Setting the deadband
Set the alarm deadband between the alarm value and its release. (Refer to the next page.)
Setting the delay
Set the delay time for the alarm. (0 to 3600 seconds)
The alarm is not output until the delay time has elapsed after the data exceeds the alarm value.
Setting the relay
* The alarm output terminal (option) is necessary for outputting alarms actually.
The relays can be set regardless of whether the alarm output terminal is used. Set the relays with the alarm output terminal number 0 ~ 24. When 0 is set, the alarm is not
outputted.
Setting the alarm output mode
AND The relay becomes ON when all alarms set in one alarm output terminal are activated.
OR
The relay becomes ON when any of alarms set in one alarm output terminal are activated.
When both of “AND” and “OR” are set to one relay channel, the relay becomes ON when either of
“AND” of all alarms set with “AND” or all “OR” of alarms set with “OR” is established.
Page 86
83
Setting the maker
Set the automatically written maker on the trend for alarm activation. When 0 is set, the maker is not
written.
Differential alarm
Alarm deadband
Alarm deadband
Low limit alarm
A
larm value
Deadband
ON
(Activated)
MIN
MAX
OFF
(Released)
MAX
MIN
U 警報値
A
t “Difference of measured values ≥ Alarm value: Differential high limit alarm activated
A
t “Difference of measured values ≤ Alarm value: Differential low limit alarm activated
(Differential low limit alarm)
A
larm value
(Differential high limit alarm)
larm value
A
larm activated
Difference of
measured
values
(Absolute value)
Differential alarm
Difference of
measured
values
(Absolute value)
A
larm activated
High limit alarm
Deadband
ON
(Activated)
OFF
(Released)
A
larm value
Page 87
84
About alarm DeLay
13.5 File settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the file settings on the setting menu screen, the following screen is displayed.
No.
By selecting the number and pressing the ENTER key, the file setting screen of the selected group is displayed. Detail of the setting method is explained in next page.
ON/OFF When ON is displayed, data is recorded, and when OFF is displayed, data is not recorded.
Delay time
Passage of time
State of alarm:ON
State of alarm:OFF
Alarm activated
Alarm no activated
Delay time
Page 88
85
<File settings screen>
Setting the recording cycle
Seconds 0.1 sec, 0.2 sec, 0.5 sec, 1 sec, 2 sec, 3 sec, 5 sec, 10 sec, 15 sec, 20 sec, 30 sec Minutes 1 min, 2 min, 3 min, 5 min, 10 min, 15 min, 20 min, 30 min, 60 min
Setting the data format
When the recording cycle is 0.1 second, the sampling is only selectable. In recording the data into the file, the average, maximum, minimum or maximum/minimum values in the period of the recording cycle can be recorded. When the maximum/minimum is selected, the data size becomes 1.5 times larger.
Sampling Average Maximum Minimum Maximum/minimum
Page 89
86
Setting the file size
Select the file size (period). When the file reaches specified size, the file is completed, and the data after completed is recorded by another name. When “Auto” is selected, recording is completed by. maximum file size. Pause of [minute] and [hour] is calculated based on 0:00, pause of 1 week is calculated based on 0:00 of Sunday, and pause of 1 month is calculated based on 0:00 of first day.
Minute 10 minutes, 15 minutes, 20 minutes, 30 minutes, 60 minutes Hour 2 hours, 3 hours, 4 hours, 6 hours, 8 hours, 12 hours, 24 hours
Other 1 week, 1 month When recording is stopped before reaching the file size, or the data reaches maximum file size (refer to 9.9 Internal memory), file is completed.
Setting the start trigger
The recording starts by the following trigger.
Key Alarm
Digital input
(option)
Trigger type Contents Key The recording starts without any conditions. Alarm The recording starts when the alarm relay becomes ON.
When this item is selected, the relay terminal number can be selected. Digital input (option)
The recording starts when the digital input terminal becomes ON.
When this item is selected, the input terminal number can be selected.
Setting the pretrigger (0 ~ 950) When the recording starts, the past data retroactive to the count set here are recorded.
Example: When the recording starts at 13:00:00 with the pretrigger “10” and the recording cycle “2
seconds”, the data from 12:59:40 to 12:59:58 are added to the beginning of the file.
Note: When the power is turned off or the settings are changed, the data for the pretrigger are
cleared, and the data in the interval specified here may not be enough. In this case, only the data being saved are added to the beginning of the file.
Setting the end trigger
Select the condition for the end of recording. The same contents as the start trigger are displayed in the first item.
Key (Alarm) Period (seconds)
Trigger type Contents Key (Alarm) The recording stops when the start conditions are not established. Period After recording the data for the specified period (seconds), the recording
stops. At the time, if the start trigger conditions are established, the recording starts again immediately (within 1 second).
Setting the period (seconds) (0 to 30000)
After starting record by start trigger, if trigger becomes OFF, the data is recorded for set period and then stopped. However, when recording is stopped by STOP key, recording is stopped despite of this setting.
Page 90
87
Setting the save format
Select the file format for recording the data into a CF card.
Binary CSV CSV
(continuance)
Save format Contents Binary The data are recorded with the binary file (extension “krf”). For the replay,
this recorder or analytical software is necessary.
CSV The data are recorded with the CSV formatted text file. The data can be
read with spreadsheet application software like Excel (Microsoft), etc. In addition, the data can be used in the attached report application software. When the decimal marker is set to “,”, the data becomes the tab-delimited
text file with the extension of “txt”. CSV (continuance)
The format is same as the above, however when recording is stopped by
trigger, the data is recorded same file continuously after restarting.
In above case, when recording is stopped, the file is completed, and the
data is recorded by new file after restarting.
Setting the auto save period
This is the interval for coping the file in the internal memory to an external memory. In addition to this interval, each file is copied to the CF card at its completion. (Refer to Para. 9.9.)
Minutes No settings, 1 min, 2 min, 3 min, 5 min, 10 min, 20 min, 30 min, 60 min
Setting the directory (Maximum length 16 characters)
For saving the data to an external storage media, the directory name for saving can be set. The hierarchy can also be specified. The delimiting symbol is “¥” (backslash).
Refer to Para. “7.3 Character entering method”.
Page 91
88
13.6 Totalizer reset settings
The totalizer is executed by the calculation settings of each channel. On this screen, set the procedure for resetting the totalized data to 0.
All calculations are reset in this setting except ITG24. ITG24 is reset only in base time and not reset every interval.
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the totalizer reset settings on the setting menu screen, the following screen is displayed.
■Setting method Select ‘all channels’ or ‘individual channel’.
In case of ‘all channels’, setting contents are accommodated all channels. In case of ‘individual channel’, individual reset setting is accommodated each channel.
CH
When select ‘individual channel’, setting is performed to specified channel.
Manual reset
The totalized data is reset to 0 manually.
Auto reset
When the auto reset of totalizer is used, set it to ON.
Set it to OFF when it is not used.
Base time and interval
The totalizer reset is executed at the following time.
Base time + (Interval x n) n = 0, 1, 2, 3, 
Example: When the base time is set at 0:00 and the interval is set at 04:00, the totalized value is
reset at 0 o’clock, 4 o’clock, 8 o’clock, 12 o’clock, 16 o’clock and 20 o’clock.
Reset by digital input (option)
*When the instrument has not the digital input option, this item is not displayed.
The totalizer reset is executed when the specified digital input terminal becomes ON.
Select “None” when it is not used.
Page 92
89
13.7 Schedule settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the schedule settings on the setting menu screen, the following screen is displayed.
When the schedule is set on this screen, the recording is executed for its set period only. Even though the conditions specified with the file settings are established, the recording cannot be executed if it is not in the scheduled period. The status bar is displayed in gray for out-of-scheduled period.
Setting the schedule
Select it from No settings, date or day. By these settings, the following settings become enabled.
Setting the parameters for the date settings
Set the start date/time and the end date/time.
Setting the parameters for the day setting
Check the day for using. Set the start time and the end time.
Page 93
90
13.8 Marker text settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the marker text settings on the setting menu screen, the following screen is displayed.
On this screen, up to 50 marker texts (max. 30 characters) to be written on the trends can be registered in advance. For writing the marker text, refer to Para. 9.3. Even when texts are not registered on this screen, texts can be created at the writing of markers.
By selecting the “Clear”, the marker text is erased. By selecting the message column, the character entering screen is displayed.
(Maker writing with the digital input (option))
The maker can be written on the trends with ON from the digital input terminal.
<Digital input --- Standard> When the input terminal designated for the [digital input] becomes ON, the corresponded maker is written on the trends of the specified group.
<Digital input --- Binary> Set the maker text number 1 to 50 by using the digital input terminal 1 to 7 (Binary expression of low bit at terminal 1 side and high bit at terminal 7 side). When terminal 8 is turned on under condition of the contact status of 1 to 50 at the terminal 1 to 7, the markers corresponding to the marker text numbers are written on the trends of the specified group.
Without optional digital input With optional digital input
Page 94
91
13.9 Memory operation
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the memory operation on the setting menu screen, the following screen is displayed.
Writing the settings to the external memory
Up to 100 current setting contents can be written in an external memory.
The dialog box shown above is displayed. By selecting which file to be read from the CF card or the USB memory, the list of the setting files in the “SETUP” folder in it is displayed. In case of overwriting the existing file, tap its file and in case of creating a new file, tap a vacant number, or press the ENTER key after selecting the file or the number. By entering a file name and pressing the [ENTER] key, the setting contents are written. The file with the extension of “.krs” is saved in the "SETUP" folder in the CF card. The setting file can also be read and used in other KR3000.
Page 95
92
Reading the settings from the external memory The setting file is read from the CF card and the current settings are overwritten.
The dialog box shown above is displayed. By selecting which file to be read from the CF card or the USB memory, the list of the setting files in the “SETUP” folder in it is displayed. Tap the line of the file to be read or press the ENTER key after selecting it.
Initializing the settings The current settings are overwritten with the default settings at the factory.
Writing from internal memory to the external memory All data in the internal memory are written in an external memory (CF card or USB memory).
Copy the data from CF to USB The data (files in the current writing destination directory) of all groups stored in the CF card are written in the USB memory.
Erasing the internal memory data All data in the internal memory are erased.
Format the CF card The CF card is quick formatted.
Format the USB memory The USB memory is quick formatted.
Page 96
93
13.10 Network settings
13.10.1 Ethernet settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the network settings on the setting menu screen and then selecting the Ethernet settings, the following screen is displayed.
Set IP address, etc. for using this recorder on the Ethernet.
IP address Set IP address of this recorder. The DHCP (automatic assignment of IP addresses) cannot be used. Ask the IP address to the administrator for the network to connect.
Subnet mask Set the subnet mask of this recorder.
Default gateway
If there is a gateway like a router, etc. on the network, set the default gateway address.
When this recorder is used in a small network without connecting to an interoffice LAN or Internet via a router, set the IP address as follows.
Instrument IP address Subnet mask KR3000 A 192.168.254.254 255.255.255.0 KR3000 B 192.168.254.253 255.255.255.0 PC A 192.168.254.1 255.255.255.0 PC B 192.168.254.2 255.255.255.0
Example of usage in a small network
Page 97
94
13.10.2 DNS settings
The DNS server is for converting the address specified with a name into the IP address. When the addresses of the FTP server, POP3 server, SMTP server, etc. are entered with names, make sure to set the DNS server.
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the network settings on the setting menu screen and then selecting the DNS settings, the following screen is displayed.
DNS ON/OFF
Select the DNS from ON (enabled) or OFF (disabled).
Primary server IP, Secondary server IP
Enter the address of the DNS server. If the primary server is not found, use the address of the
secondary server. When there is only one DNS server, it is no problem not to enter any address to the secondary server.
Page 98
95
13.10.3 Web server settings
Set the login user name and password for accessing web server.
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen
By selecting the network settings on the setting menu screen and then selecting the Web server settings, the following screen is displayed.
Select ‘Administrator user’ or ‘General user’.
Administrator user All items are operated.
General user
Recorder display and data display are operated. Only the screen update is operated on the recorder display.
Login user name
Set the login user name of administrator user/general user.
Login password
Ser the login password of administrator user/general user.
Page 99
96
13.10.4 FTP client settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the network settings on the setting menu screen and then selecting the FTP client settings, the following screen is displayed.
Execute the settings for using the FTP client function of this recorder.
Server address Specify the address of the server for transferring the file. When the address is set with a name (.co.jp,
.com, etc.), not the IP address, make sure to set the DNS (13.10.2).
Directory
Set the directory for writing the file. If there is no directory, the automatic creation cannot be executed.
Login user name Set the user name for logging into the FTP server.
Login password Set the password for logging into the FTP server.
PASV mode Set to ON when the file is transferred with the PASV mode.
Auto Forwarding
Set to ON for transferring the file created automatically at the switching of the file for recording.
Retry mode When FTP transfer is failed three times on ‘OFF’, error message is displayed on the screen and stop transfer. When retry mode is ‘ON’, try to transfer until succeeding. However, when transfer-waiting files become over 360, files after 360 are not transferred. When turns off the power of the instrument, transfer–waiting files are not transferred after tuning on the power.
Page 100
97
13.10.5 FTP server settings
Proceed from the MENU settings.
By tapping the button of the item for setting, the screen moves to the input screen.
By selecting the network settings on the setting menu screen and then selecting the FTP server settings, the following screen is displayed.
Execute the settings for using the FTP client function of this recorder.
FTP server ON/OFF When the FTP server is set to ON, the FTP server function is executed. Set it OFF when FTP server function is not in use.
Login user name Set the user name for logging into the FTP server.
Login password
Set the password for logging into the FTP server.
By using the function of the FTP server, the file in the CF card of this recorder can be read from a PC on the network. The followings are the connection method for using a Web browser (Internet Explorer, Netscape, Opera).
Note: In case of connecting to the FTP server by using the Web browser, if a user name
other than “anonymous” is set, the normal connection may not be possible.
(1) Enter “ftp://(IP address of this instrument)/ into the address bar in the browser and press the
ENTER key of the PC (2) The list of files and folders is displayed in the browser. (3) From then, like the Windows explorer, file operations of moving, copying, opening, etc. can be
executed. However, writing to this recorder is not permitted.
For the connection using a FTP client software other than the Web browser, set the software to log in by the user name and password set with this recorder and execute the connection.
Using method of FTP server