Chino AL4000 series Instructions Manual

INST.No. INE-844E
AL4000 (Multi-point type) Hybrid Memory Recorder
[ General ]
1. Introduction .................................................................................................................... 1
2. For Safe Use ................................................................................................................... 4
2-1. Preconditions for Use ......................................................................................................................................... 4
2-2. Symbol Mark....................................................................................................................................................... 4
2-3. Label ................................................................................................................................................................... 4
2-4. Important Explanation ......................................................................................................................................... 5
3. Model Code List ............................................................................................................. 6
4. Mounting and Wiring ..................................................................................................... 7
4-1. External Dimensions ........................................................................................................................................... 7
4-2. Mounting ............................................................................................................................................................. 7
4-3. Wiring ................................................................................................................................................................. 9
5. Part Names ................................................................................................................... 26
5-1. Front Section of Internal Unit ............................................................................................................................ 26
5-2. Operation/Set Keys .......................................................................................................................................... 27
6. Operation ...................................................................................................................... 28
6-1. Preparation for Operation ................................................................................................................................. 28
6-2. Basic Operation ................................................................................................................................................ 30
6-3. Operation .......................................................................................................................................................... 33
7. Factory Default Settings .............................................................................................. 37
7-1. List of Factory Default Settings ......................................................................................................................... 37
8. Setting Method ............................................................................................................. 38
8-1. Basic Rules....................................................................................................................................................... 38
8-2. Input Type Settings “Range” ............................................................................................................................. 40
8-3. Alarm Settings “Alarm” ..................................................................................................................................... 43
8-4. Calculation Settings “Calc” ............................................................................................................................... 50
8-5. Formula Settings “Formula” ................................................................ .............................................................. 54
8-6. Broken Line Approximation Table Settings “Seg.Tbl” ........................................................................................ 61
8-7. Chart Speed Settings “Chart” ........................................................................................................................... 62
8-8. Dot Printing Settings “Dot” ................................................................................................................................ 63
8-9. Subtract Printing Settings “Sub Prt” .................................................................................................................. 64
8-10. Dot Printing Interval Settings “Dot.Int” .............................................................................................................. 66
8-11. Periodic (Data Interval) Data Printing Settings “DataInt” ................................................................................... 67
8-12. Periodic (Specified Time) Data Printing Settings “PrtTime” ............................................................................... 68
8-13. List Printing Settings “ListPrt” ........................................................................................................................... 69
8-14. Message Printing 1 Settings “MsgPrt1” ............................................................................................................ 70
8-15. Message Printing 2 Settings “MsgPrt2” ............................................................................................................ 71
8-16. Recording Format Settings “PrtForm” ............................................................................................................... 72
8-17. Auto Range Settings “A.Range” ....................................................................................................................... 73
8-18. Compressed/Expanded Printing Settings “Cmp&Exp” ...................................................................................... 75
8-19. Zone Printing Settings “ZonePrt” ...................................................................................................................... 77
8-20. SD Card “SD CARD” ........................................................................................................................................ 79
8-21. USB Engineering Port Settings “USB” .............................................................................................................. 85
8-22. Calendar Timer Settings “Timer” ....................................................................................................................... 86
8-23. Fail Output Settings “FailOut” ........................................................................................................................... 87
8-24. Display Settings “Display” ................................................................................................................................. 89
8-25. Measured Value Display Order Settings “D.Order” ........................................................................................... 90
8-26. Date and Time Settings “Date” ......................................................................................................................... 91
8-27. System Settings “System” ................................................................................................................................ 92
8-28. System Information Display “SysInfo” ............................................................................................................... 93
Table of contents
9. Adjustment ................................................................................................ ................... 94
9-1. Trace Printing (Dot Printing) Position Adjustment “Rec Adj” ............................................................................. 94
9-2. Input Adjustment “Inp Adj” ................................................................................................................................ 95
9-3. Input Shift Adjustment ....................................................................................................................................... 96
9-4. Wiring and Environment for Input Adjustment................................................................................................... 97
10. Engineering Port (Mini-USB Terminal) ..................................................................... 98
11. Troubleshooting......................................................................................................... 99
11-1. Problems and Remedies .................................................................................................................................. 99
11-2. Abnormal Measured Value ............................................................................................................................. 100
12. Inspection and Maintenance ................................................................................... 101
12-1. Routine Inspection .......................................................................................................................................... 101
12-2. Consumable Parts and Replacement Guideline ............................................................................................. 101
12-3. Disposal .......................................................................................................................................................... 102
13. Option ....................................................................................................................... 104
13-1. External Operation Settings “Dig Inp” ............................................................................................................. 104
13-2. Operation Recording Settings “Ope.Rec” ....................................................................................................... 107
13-3. COM Port Settings “COM1” and “COM2” ....................................................................................................... 108
13-4. IP Address etc… Settings “Ether” ................................................................................................................... 109
13-5. SNTP Settings “SNTP” ................................................................................................................................... 110
13-6. E-mail Settings “E-mail” ................................................................................................................................... 111
14. Specifications ........................................................................................................... 114
- 1 -
1. Introduction
Thank you for purchasing AL4000 series (Multi-point Type) with 100mm recording width. This industrial use instrument records input signals to the chart paper and stores data into the SD card. Mount this instrument on the indoor instrumentation panel etc. and record signals of temperature sensor, pressure gauge, hygrometer and flow meter. Reading signals of the recorder are thermocouple, resistance thermometer, DCmV and DCV. Make sure to read this instruction manual in advance to understand this unit well and prevent troubles from occurring. This manual is a “General” Instruction manual. For specifications with communications, read the “Communicationsinstruction manual separately.
- To the persons doing instrumentation, installation, and sales -
Make sure to provide this instruction manual to the person who uses the unit.
- To the users of this unit -
Store this instruction manual with care until you scrap the unit. Also, write down the parameter contents set in the product and keep it for your record.
Perchlorate Material
This instrument uses battery with Perchlorate Material. Special handling may apply, see http://www. dtsc.ca.gov/hazardouswaste/perchiorate
Warning
Request
1. Microsoft, Windows, Windows XP, Windows Vista, Windows 7, and NET Framework are trademarks of Microsoft Corporation and the related company.
2. SD Memory Card is the trademark of Panasonic Corporation, SanDisk Corporation in USA, and TOSHIBA CORPORATION.
3. Other described company names and product names are trademarks and registered products of the respective companies.
4. Please note that the marks TM and “®” are omitted throughout this manual.
Trademark
1. No part of this manual can be reproduced or copied in any form without permission.
2. The contents of this manual may be altered without prior notice.
3. This manual has been documented by making assurance doubly sure. However, if any question arises or if any error, an omission, or other deficiencies are found, please contact your nearest our sales office.
4. CHINO is not responsible for any operation results of this software.
Notice
This product is warranted for one year from the date of delivery. If it is damaged during the warranty period, when used normally based on the cautions in the instruction manual labels attached to the product, etc., it will be repaired without any charge (only in Japan). In the case, we are sorry to trouble you, but please contact your dealer or nearest our sales office. However, in cases of the followings, it will be repaired at your expense even during warranty period.
1. Failure or damage caused by improper use or connection, or invalid repair or modification.
2. Failure or damage caused by fire, earthquake, wind or flood, thunderbolt, or other extraordinary natural phenomena, or pollution, salt, harmful gas, abnormal voltage, or use of unspecified power.
3. Replacement of parts or accessories that have reached the end of their life.
Furthermore, the term warranty in this sense covers only a CHINOs product itself. Therefore, we are not responsible for compensation for whatever the damage that is triggered by failure of our product.
Product warranty scope
- 2 -
Before use
Make sure to check the following before use after unpacking the unit. If you have any question, please contact your dealer or our nearest office.
1. Exterior check
Check that the appearance of the product has no damage.
2. Model code check
Check that the model code of the purchased product is correct.
Model code label and application place
The label as follows is attached on the upper surface of the product case and the chassis.
A L 4 7 -- Model code R 3 Serial number
M A D E I N J A P A N
3. Accessories check
Check the following accessories attached to the product.
Item
Q'ty
Remarks
Instruction manual
1
CD-R
Instruction manual [Wiring/Installation]
1
Booklet
Bracket
2 (1 set)
For panel mounting, 22025-029001
Terminal screw
5
M3.5, for input terminal (spares for missing)
Chart paper
1
The type depends on the specifications.
Ribbon cassette
1
84-0044
In addition, if accessories are purchased additionally, those products may be attached.
1. Do not drop the product while take it out of the box
2. When transporting the unit, pack in the dedicated package box, and put the box in an outer case with a bed of cushion. With the consideration to the case above, it is recommended that the dedicated package box for the unit is stored.
3. When the unit is removed from the panel and not used for a long time, put it in the dedicated package box, and store it in a place with normal ambient temperature and less dust.
Request
- 3 -
4. About attached chart paper
For the unit, the chart paper No.EM001 (50 equal divisions) is available and delivered. For the case that the chart paper is to be specified, various scales are available as follows.
Chart Paper for Standard Scale
Standard scale (linear)
Chart paper No.
Standard scale (linear)
Chart paper No.
0 to 50C 0 to 100C 0 to 150C 0 to 200C 0 to 250C 0 to 300C 0 to 400C 0 to 500C 0 to 600C 0 to 800C 0 to 1000C 0 to 1200C 0 to 1400C 0 to 1600C
EL05014 EL05052 EL05034 EL05047 EL05096 EL05124 EL05009 EL05048 EL05168 EL05121 EL05157 EL05116 EL05137 EL05147
-20 to 80C
-50 to 50C
-50 to 150C
0 to 10mV 0 to 20mV 0 to 50mV
-5 to 5mV
-10 to 10mV 1 to 5V
Double to triple scale
Nonstandard scale
EL05035 EL05006 EL05019
EM001*
(Scale with 50-equal divisions) * Scale marks
without numeric values and unit
* The chart paper has the same printed linear scale as the standard scale.
Therefore, it can be shared in regardless of input types (thermocouple, resistance thermometer, or others).
5. Restriction of digital recording/printing function
(1) Data printing requires approximately two minutes. Note that when data printing is executed, the trace printing
stops until the printing is finished.
(2) When the chart speed is set to 251mm/H or more, power-on printing, data printing, list printing, and printing
function for other than time line are disabled.
(3) The trace printing executes dot printing with five seconds interval (standard); however, if time printing is
executed during the trace printing, the dot interval may become longer. The dot interval is extended with the inserted printing. Therefore, this is not abnormal.
(4) Printing is formed with dots of one pin. Therefore, if the power is turned off while characters are being formed,
they cannot be formed correctly. This is not abnormal.
- 4 -
2. For Safe Use
If the unit is used in a manner not specified by manufacturer, the protection provided by the unit may be impaired. For safe use of the unit, please read and understand the following cautions.
2-1. Preconditions for Use
The unit is a component type general product to be used mounted on an indoor instrumentation panel. Avoid using under other conditions. Use after the system safety is implemented such as the fail-safe design and periodical inspection on the final product side. Also, for wiring/adjustment/operation of the unit, ask professionals with instrumentation knowledge to perform. Furthermore, also the person who actually uses the unit is required to read this instruction manual to fully understand various cautions and basic operation.
2-2. Symbol Mark
This instruction manual includes the following symbol marks. Make sure to fully understand the meaning of them.
Symbol mark
Meaning
Cautions are explained to avoid causes for death or serious injuries of users.
Cautions are explained to avoid causes for slight injuries of users or damages of the unit or peripheral devices.
2-3. Label
For safe use of the unit, the following labels are used.
Label
”Name” and place
Meaning
“Alert symbol mark”
Various terminals
(back side)
Place to be handled with cautions to avoid “electric shock”, “injuries”, etc.
“Protective conductor
terminal”
Right side of power terminal
(back side)
Terminal to be grounded to avoid electric shock
100 to 240V AC
50/60Hz, 40VA
“Power source specification”
Power conductor terminals
Specification of power (voltage range, frequency, and power consumption) used for the unit
!
!
Warning
!
Caution
- 5 -
2-4. Important Explanation
To avoid severe accidents, make sure to read and understand the following.
1. Switch and overcurrent protection device
This unit is not provided with a replaceable overcurrent protective device. Prepare a switch and an overcurrent protective device for the power supply (circuit breakers, circuit protectors or the like) within 3m of this unit in a location where the operator can access easily. Use a switch and an overcurrent protective device conforming to IEC60947-1 and IEC60947-3.
2. Be sure to ground this instrument
To avoid electric shock, before turning the power on, connect the protective conductor terminal of this recorder to the protective conductor of the power supply equipment, and do not remove it during use.
3. Before turning on the power supply
For safety, first check that the power source is within the range indicated on the power label, and then turn on the external power switch.
4. Avoid repair and modification
Avoid repair and modification with parts replacement by persons other than service personnel authorized by CHINO. Not only damage or malfunction of this recorder may occur, but also dangers such as electric shock may occur. In addition, the inner unit does not have to be pulled out in the normal use.
5. Use the unit following the instruction manual
For safe use, use the unit following the instruction manual. Please note that CHINO does not have any responsibilities for any claims for failures or damages occurred with abuse or misuse of this recorder.
6. Installing the safety device
Regarding the use of a device that anticipates a big loss due to failure of the controller and the peripheral device, always install a safety device for preventing these losses and implement fail safe design in the final product. Do not use it in important in facilities like, human life,atomic energy, aviation and space.
7. Turn off the power supply if abnormality occurs
Turn off the power supply immediately and contact your local CHINO’s sales office if any abnormal odor, noise or any smoke occurs, or if this unit becomes high temperature that is too hot to be touched.
8. Do not put hands in this product
Do not put your hands or tools inside of this product. It may cause electric shock or injuries. There is no operation such as pulling out an inner unit or using tools when using this product.
Overcurrent protection device
Switch
!
Warning
Power terminal Protective conductor terminal
Power label
100 to 240V AC 50/60Hz 40VA
To the protective conductor of power supply facility
Power/protective conductor terminal
Power source
For safety, the fuse below is included in the power unit of the unit. It cannot be replaced.
Manufacturer:Daito Communication Apparatus Co.,Ltd Model: SBL32
Fuse in power unit
Reference
- 6 -
3. Model Code List
AL47□□-□□□-□□□
Input point
06: 6 points
Communications
N: None E: Ethernet R: RS232C A: RS422A/RS485 Q: RS232C + RS485 C: RS422A/RS485 + RS485 G: Ethernet + RS422A/RS485 + RS485 F: Ethernet + RS422A/RS485 + RS485 + Low-order communications
Alarm output + remote contacts
0: None 2: 2 mechanical relay 'a' contact alarm outputs 4: 4 mechanical relay 'c' contact alarm outputs + 5 remote contacts A: 6 mechanical relay 'a' contact alarm outputs + 5 remote contacts
Power
A: 100 to 240V AC
For OP/SP
NNN: None NNP: SD card playback
- 7 -
4. Mounting and Wiring
4-1. External Dimensions
Following dimensions are measured while the brackets are attached to the unit.
Unit: mm
4-2. Mounting
(1) Use the recorder mounting on an indoor installed instrumentation panel. (2) Brackets can be attached to a panel of steel with thickness of 2 to 6mm or
equivalent strength.
Select thickness of a panel considering weight and depth of the unit with panel
formation for actual use.
(3) For mounting the recorder on the panel, be careful of injury by dropping it.
1. Panel cutout and mounting method
Unit: mm
138
+1 0
138
200
200
Minimum interval on multiple units mounting
!
Caution
216 When alarm output/remote contacts unit and communication unit are added
- 8 -
(1) Insert the unit into the panel cutout from the front of the panel. (2) Fix the unit to the panel using the brackets (tightening torque: 1.0Nm). Brackets are attached to the top and
bottom surfaces.
2. Mounting condition
To avoid accidents, make sure to read and understand the following.
Industrial environment
Select a location distant from sources of electric field or magnetic field and without mechanical vibration or shock.
Overvoltage category ...... II (EN standard) ● Altitude ........................... 2000m or less
Pollution degree .............. 2 (EN standard) ● Working place ................ Indoor
Normal operating condition
Ambient temperature ··· 0 to 50(20 to 65%RH,non-condensing)
Ambient humidity ········· 20 to 80%RH,non-condensing(5 to 45)
Power voltage ············· General specification : 100 to 240V AC ±10%
Power frequency ········· General specification : 50/60Hz ±2%
Atmosphere
For safety, avoid a location with corrosive gas, explosive gas, flammable gas and combustible gas.
Avoid a location with dust, smoke, or steam.
Mounting angle
Lateral tilting ················ 0 to 10°
● Longitudinal tilting ······· Forward tilting: 0°Backward tilting: 0 to 30°
● View angle ··················· -10 to +30°with the horizon as the standard
Angles other than the above affect the recording operation.
!
Caution
Indicator
View angle
About 30°
About 10°
Panel thickness (2 to 6mm)
Brackets
- 9 -
4-3. Wiring
1. Terminal board diagram
The figure below is the diagram of the terminal board with the option [Alarm relay output (6 points ‘a’ contact) + remote contacts and communication interface].
The figure below is the diagram of the terminal board with the option [Alarm relay output (4 points ‘c contact) + remote contacts (20 points) and communication interface].
- 10 -
The figure below is the diagram of the terminal board with the option [Alarm relay output (2 points ‘a’ contact) and communication interface].
- 11 -
Alert symbol mark ( ) and location
mark is attached to the location to which if human body touches, an electric shock
may be generated.
Terminal name
Location of attached mark
Power terminal
Lower left of power terminal
Measurement input terminal
Upper left of terminal cover
Mechanical relay c contact alarm terminal
Upper left of terminal cover
Mechanical relay a contact alarm terminal
Lower left of N.O terminal
!
!
!
Warning
For easy wiring, the input unit, alarm output/remote contacts unit, and communication unit are removable.
(1) Every unit can be removed when two mouting screws are removed. (2) The recorder and each unit are connected with a connector.
Turn off the power and then remove/attach
Make sure to turn off the external power switch before units are removed/attached to prevent damages on electric circuits.
Input terminal block and alarm terminal block are removable.
Reference
Only thermocouple input unit cannot be replaced with other instrument unit. If done so, measurement errors are generated.
Note
Thermocouple input unit replacement
!
Warning
[Alarm output/remote contacts unit]
[Input unit]
[Communications unit]
Mounting screws
Mounting screws Mounting screws
- 12 -
2. Precautions on wiring
Precautions on wiring are described below. Observe them to maintain safety and reliability.
1) Feed power source For the power source for the unit, use the single-phase power source with stable voltage and without waveform strain to prevent malfunctions.
(1) Switch and overcurrent protective device
Add a switch and overcurrent protective device (250V,3A) to the feed power source to prevent an electric shock on wiring. The unit has no replaceable fuse.
(2) Connect after the power source is turned OFF
When performing power and input/output wiring, make sure to turn OFF the feed power source to prevent an electric shock.
2) Separate from strong power circuits For input/output wiring, avoid adjacency or parallel with strong power circuits such as power lines. Separate 50cm or more for adjacency or parallel.
3) Separate thermocouple input from heat sources. To reduce reference junction compensation errors for thermocouple input, especially separate terminals from heat sources (heating body). Also, avoid radiation such as direct sunlight.
4) Separate from noise sources. Separate from noise sources as much as possible. Unexpected troubles may occur. If separation from noise sources is disabled, implement countermeasures.
Main source
Countermeasures
Electromagnetic switch or others Power line with distortion of wave Inverter Thyristor regulator
Insert noise filters between power source and input/output terminals. CR filters are used in many cases.
!
Warning
- 13 -
5) Use crimping terminals. (1) To prevent looseness or disconnection of terminals and short circuit between terminals, install
crimping terminals to termination of connection cables.
(2) To prevent an electric shock, use crimping terminals with insulation sleeves.
Terminal Type and Termination Treatment
Terminal board
Diameter
Tightening torque
Termination treatment (Unit: mm)
Power/Protective
conductor
M4
1.2Nm
O type
Terminals other than the above
M3.5
0.8Nm
O type Y type
* Be sure to use O type for the alarm output terminals. * For other terminals, use also O type as possible.
Communications
terminal
M3
0.5Nm
O type Y type
* Use O type as possible.
6) Unused terminals Avoid using unused terminals for relaying. Electric circuits may be damaged.
Treat properly the wired cables.
Treat surely wired cables not to get hung up on people and things. Disconnection of wiring with hanging up may cause an electric shock.
8.5 or less
4.3 or less
t: 0.8
With an insulation sleeve
8 or less
3.7 or more
With an insulation sleeve
8 or less
3.7 ormore
t: 0.8
With an insulation sleeve
5.2 or less
3.2 or more
t: 0.8
With an insulation sleeve
5.2 or less
3.2 or more
With an insulation sleeve
t: 0.8
!
Warning
- 14 -
After wiring, install the terminal cover.
L
N
Copper cable (green/yellow) with 2mm2 of wire or more
Make sure to connect to protective conductor of power facility.
600V vinyl insulated cable
Power source
3. Power/protective conductor terminals wiring
1) Power/protective conductor terminals
Turn OFF feed power source.
Before power/protective conductor terminals wiring, make sure to turn off the feed power source to prevent an electric shock.
2) Power terminal wiring Using 600V vinyl insulated cables as the power line, install crimping terminals with insulation sleeves to the termination for wiring. Note: Use the following standard cables. (1) IEC 60227-3 (2) ANSI/UL817 (3) CSA C22.2 No.21/49
3) Protective conductor terminal wiring Make sure to connect to the protective conductor of the power equipment. Install crimping terminals with insulation sleeves for wiring. Grounding wire: Copper cable with wire diameter
2mm2 or more (green/yellow)
mark at power terminals
After wiring the power terminals have power supply voltage applied. Make sure to install power terminal covers after wiring to prevent an electric shock.
Pay attention to power supply voltage and noise.
The power supply voltage of the unit is indicated on power terminals. Applying power other than the indicated one causes accidents or malfunction. In addition, if the power has noise interference, implement countermeasures such as noise cut transformer installation.
!
!
Warning
!
Warning
!
Caution
Display based on CSA standard in Canada. The live side of single-phase AC power supply is L, and the neutral side is N display. To get sufficient performance, observe the L/N wiring.
L/N display of power terminal
Note
Power terminal
L
N
Protective
conductor terminal
100 to 240V AC 50/60Hz 40VA MAX
Power (voltage, frequency, and power consumption)
!
- 15 -
4) Measurement input terminals wiring
1) Measurement input terminal Turn OFF the feed power source before wiring to prevent an electric shock. Install crimping terminals with insulation sleeves to input terminals for wiring.
2) DC voltage (current) input wiring Use instrumentation twisted cables for measures against noise as input cables. For current input, connect the shunt resistor for current input to the channel to be measured before wiring.
3) Thermocouple (TC) input wiring Make sure to wire thermocouple cable (or compensation lead wire) to input terminals of the unit. If a copper conductive wire is connected halfway, big measurement error will be generated. In addition, avoid parallel connection of a pair of thermocouple wires with other instruments (controller or others) that causes troubles.
4) Resistance thermometer (RTD) input wiring To prevent measurement errors, use 3-core cables as the input cable in which lines have the same resistance. In addition, one resistance thermometer cannot be connected in parallel with other instruments (a controller or others).
mark on measurement input terminals
High voltage may be applied to the measurement input terminals due to common mode noise. Allowable noise value is 30VAC or 60VDC or less. Check that the voltage is equal to or less than the allowable value. Install terminal covers after wiring to prevent an electric shock and protect input cables. For thermocouple input, installing terminal covers reduces reference junction compensation errors.
!
Instrumentation twisted cable DC voltage input
(+)
(-)
1 2 3 4 5 6
DC voltage (current) input
!
Resistance thermometer (RTD) input
3-core cable (Same line diameter, same length)
Note: Cable resistance per 1 cable is 10Ω or less.
3 lines have the same resistance.
1 2 3 4 5 6
Resistance thermometer
A
B
B
!
TC,mV(+) and RTD(A) terminals and TC,mV(-) and RTD (B “middle”) terminals are insulated for each channel, and RTD (B”lower”) terminal shorts internally between channels.
Measurement input termiinsulation
Note
Allowable input voltage
Input type
Allowable input voltage
Voltage, thermocouple input
±10VDC *
Resistance thermometer input
±6VDC
*±60VDC for channels specified with ±10V range or more
Caution
!
Compensation leas wire Red (+)
White (-)
1 2 3 4 5 6
Thermocouple (TC) input
!
Thermocouple
!
Warning
- 16 -
5) Input unit terminal cover mounting/removing (1) Raise the cover to the direction of the arrow. (2) Turn to the direction of the arrow. (3) Pull it to the direction of the arrow to remove.
5. Alarm output terminals wiring (option)
1) Alarm output terminals The terminal configuration depends on the output specification.
Alarm relay output 6 points (a contact)
Alarm relay output 4 points (‘c’ contact)
Alarm relay output 2 points (‘a’ contact)
(1)
(2)
(3)
N.O terminal (M3.5)
COM terminal (M3.5)
Alarm relay output (6 points)
COM terminal (M3.5)
N.O terminal (M3.5)
COM terminal (M3.5)
N.O terminal (M3.5)
ALARM RELAY
1
2
N.O terminal (M3.5)
COM terminal (M3.5)
Alarm terminal (4points)
1 2
3 4
N.C terminal (M3.5)
- 17 -
2) Wiring Turn OFF the feed power source and the power source for buffer relay before wiring to prevent an electric shock. (1) Wire the cable to the load via the buffer relay. (2) To the alarm output terminals, type O crimp style terminal with insulation sleeve which is connected to
double insulated signal wire should be connected. ( Refer to P13 )
Mechanical relay a’ contact output example
Mechanical relay ‘c’ contact output example
* N.C terminal is opened on alarm occurrence in opposite way to N.O terminal.
mark on alarm output terminals
Maximum of 240VAC can be connected to the alarm output terminals of this unit. Basic insulation (dielectric strength 1390V) is carried out between the alarm output
channels, however, from the malfunction etc. 240VAC may be output to each alarm output terminals. Double insulation or reinforced insulation to the outside circuit connected to an alarm output terminal should be set.
A buffer relay power supply is applied to the alarm output terminals after connections and so creates a risk of electric shock if touched. Terminal cover must be mounted after connection. Moreover, safety measures to the outside circuit should be set.
Implement safety measures.
The alarm output of the unit may generate output failure with wrong operation, failure, abnormal input, or others. Double insulation or reinforced insulation in outside circuit side of all the channels should be set in any system for safety ensuring.
!
!
Caution
!
Warning
: Contact protective element (Attachment to a side is desirable.)
N.O
COM b a Z Z
Buffer relay
Recorder
Power
Load
: Contact protective element (Attachment to a side is desirable.)
Buffer relay
Recorder
Power
Load
Z Z N.C
N.O
COM
b
a
240VAC Max
Load
240VAC Max
Load
Recorder
Basic insulation between output channels
Double insulation or Reinforced insulation
- 18 -
3) Precautions on wiring The following are precautions on wiring.
Item
Description
Mechanical relay output specification contact capacity (Common to ‘a’ contact and ‘c’ contact)
Power supply
Resistance load
Inductive load
100VAC
2A
1A
240VAC
2A
1A
30VDC
2A
1A
Contact protective element Z installation
Install the contact protective element which fits the buffer relay. It is effective to install the element to the coil side of the buffer relay (see the figure
of mechanical relay a contact output example) and prevents wrong operation with light load.
Selection of buffer relay
Coil rating: Contact capacity or less of output terminals Contact rating: Double of load current or more
In addition, the coil surge absorption element built-in type relay is recommended. If there is no buffer relay which meets the load rating, implement another stage of buffer relay.
Selection of contact protective element
If there is no surge absorption element built-in buffer relay, install this element. The element of C/R (capacitor + resistor) is general. <C/R standard> C: 0.01μF (Rating about 1kv)
R: 100 to 150Ω (Rating about 1W)
(Minimum load) 100μA100mVDC
- 19 -
6. Remote contacts terminals wiring and operation selection (option)
Only with remote contacts terminals (option).
1) Remote contacts terminals
2) Wiring Turn OFF the feed power source before wiring to prevent an electric shock. (1) Use no voltage contact signals to be given to the
remote contacts terminals.
(2) Install crimping terminals with insulation sleeves
to remote contacts terminals for wiring.
No voltage contact
For contacts connected to the remote contacts terminals, use switches or relays driven with voltage level 30VAC or 60VDC or less or manual contacts which support light load.
Wiring example
Voltage on contact open: About 5V Current on contact short: About 10mA
Note
Characteristics of contact input terminals
!
Warning
Upper row Remote contacts terminals
Remote contact enabled operation name
(1) Recording ON/OFF and three chart speed selection (two terminals of EX1 and EX2 are used) (2) Messages (No. 01 and 02) selection and printing execution (two terminals of EX1 and EX2 are
used) (3) Messages (No. 01 to 05) selection and execution (four terminals of EX1 to EX4 are used) (4) Digital data printing (arbitrary one terminal) (5) List printing (No. 1 to 3) (arbitrary one terminal for each) (6) Integration reset (arbitrary one terminal) (7) Messages No. 01 to 20 printing execution (each arbitrary one terminal) (8) Time correction execution (arbitrary one terminal) Each function requires short-circuit for one second or more between COM terminal and each terminal.
Operation allocation
Setting of allocation of operations to each terminal (EX1 to EX5) is required.
Name of operations which require setting
(1) Recording ON/OFF and three chart speed selection (See 8-7. Chart Speed Settings.) (2) Message selection and printing execution (See 8-14. Message Printing 1 Settings.)
Remote contact
Reference
- 20 -
3) Operation for which terminal No. is decided automatically ON: Short-circuit OFF: Open
Operation name
Terminal contact signal
(1) 3 chart speed
selection
3 chart speed setting other than the setting here is required. (See 8-7. Chart Speed Settings.)
Recording ON/OFF and 3 chart speed selection
Between COM and EX terminals
EX1
EX2
Recording
ON
CS1
OFF
OFF
CS2
ON
OFF
CS3
OFF
ON
Recording OFF
ON
ON
Chart recording must be ON.
(2) Message printing
(No.01 and 02)
Message setting other than the setting here is required. (See 8-14. Message Printing 1 Settings.)
Message No. 01
COM and EX1
Message No. 02
COM and EX2
At the point when the trigger signals (1 second or more) are given, the selected message is printed. Message printing with key is available.
(3) Message printing
(No. 01 to 05)
Message setting other than the setting here is required. (See 8-14. Message Printing 1 Settings.)
Message
Between COM and EX terminals
EX1
EX2
EX3
EX4 *
No.01
OFF
OFF
OFF
For trigger
No.02
ON
OFF
OFF
No.03
OFF
ON
OFF
No.04
ON
ON
OFF
No.05
OFF
OFF
ON
* After message No. is selected, when the trigger signals (1 second or more)
are given, the selected message is printed. Chart recording must be ON. Message printing with key is available.
4) Operation which can be allocated to arbitrary terminal No. ON: Short-circuit OFF: Open
Operation name
Terminal contact signal
(4) Digital data printing
Turn ON the terminal No. specified to Digital data printing. Chart recording must be ON. Digital data printing with key is enabled. Even during execution, the acceptance can be repeated only once.
(5) List printing
(List No.1, 2, and 3)
Turn ON the terminal No. specified to “List 1, List 2, or List 3 printing.” Chart recording must be ON. List printing with key is available. (See 8-13. List Printing Settings)
(6) Integration reset
When Collective reset with remote contacts (EX) is selected with Calculation programming, turning ON the terminal No. specified to Integration reset resets the integration value. (See 8-4. Calculation Settings.)
(7) Message printing
(No.01 to No.20)
Message setting other than the setting here is required. (See 8-14. Message Printing 1 Settings.) Turn ON the terminal No. specified to “Message printing (No. 01 to 20).” Chart recording must be ON. Message printing with key is available.
(8) Time correction
When the current time (second) is within 0 to 30 seconds, the time is corrected to zero second. When it is within 31 to 59 seconds, the time is put forward one minute and corrected to zero second.
1 sec.or more
For trigger
1 sec.or more
1 sec.or more
- 21 -
7. Communication I/F terminal wiring (option)
AL4000 can be connected for communications with RS232C, RS422A, RS485, and Ethernet.
1) Communications terminal type (option)
1 2 3 4 5 6 7
8
COM1
RS232C *
SG
SD RD
RS422A *
SG
SDA
SDB
RDA
RDB
RS485 * SG
SA
SB
Short with
SA
Short with
SB
COM2
RS485
SA
SB
SG
* RS232C and RS422A/485 of COM1 are to be specified on purchase.
2) Communications cables Please prepare communication cables before wiring in advance. Since exclusive cables are available from us, place an order.
(1) RS232C
Connection between PC and the unit or a line converter
Cable
9-pin connector Crimp type ring terminals RS232C cable
Shape
Internal
wiring
Model
code
RZ-CRS6□□
Cable length: 01 to 15m (specified)
RD SD SG
PC side
9-pin connector
Cable for RS232C (Max.15m)
RD SD SG
1
2
3 4 5
6 7 8
9
Ethermet connector
Communications terminals
- 22 -
(2) RS422A
Connection between a line converter and the unit
Cable
Crimp type ring terminals ↔ Crimp type ring terminals RS422A cable
(for a line converter)
Shape
4-core cable of twisted 2-core cables of twisted VCTF lines. Each side has a SG (signal ground) line. Since the line converter has no SG terminal, cut and use the cable.
Internal
wiring
Model
code
RZ-CRA2□□
Cable length: 01 to 99m (specified)
Connection between the unit and other devices
Cable
Crimp type ring terminals ↔ Crimp type ring terminals RS422A cable (for parallel)
Shape
4-core cable of twisted 2-core cables of twisted VCTF lines. Each side has a SG (signal ground) line.
Internal
wiring
Model
code
RZ-CRA1□□
Cable length: 01 to 99m (specified)
Line converter side
Recorder side
RDB
RDA
SDA
SDB
SG
SDB
SDA
RDA
RDB
SG
Device side
Recorder side
SDB
SDA
RDA
RDB
SG
SDB
SDA
RDA
RDB
SG
(black) (white) (red)
(green) (blue)
RDA RDB SDA SDB SG
SDA SDB RDA RDB
SG
(black) (white) (red)
(green) (blue)
(black) (white) (red)
(green) (blue)
SDA SDB RDA RDB SG
SDA SDB RDA RDB SG
(black) (white) (red)
(green) (blue)
- 23 -
(3) RS485
Connection between the unit and other devices and between a line converter and the unit
Cable
Crimp type ring terminals ↔ Crimp type ring terminals RS485 cable
Shape
2-core cable of twisted CVVS lines. Each side has a SG (signal ground) line. Since the line converter has no SG terminal, cut and use the cable.
Internal
wiring
Model
code
RZ-LEC□□□
Cable length: 001 to 200m (specified)
(4) Ethernet
Connection between PC and devices
For direct (one-to-one) connection, use crossover twist-pair cables with shield (available locally as STP cable).
Connection between HUB and devices (multiple devices can be connected)
For (one-to-N) connection between PC and devices via HUB, use straight twist-pair cables with shield (available locally as STP cable).
3) Communications line wiring
(1) RS232C wiring
PC and devices are connected one-to-one with RS 232C.
Example of terminal connection
RDA(black)
RDB(white)
SG(green)
(black)SA
(white)SB
(green)SG
Device side, Line converter side
Recorder side
RDA
RDB
SG
SA
SB
SG
SD
RD
SG
Cable for RS232C (Max.15m)
Device side
RZ-CRS6
Communications port
RD
SD
SG
PC side
- 24 -
(2) RS422A wiring
PC and multiple devices are connected with RS422A. A line converter is required. RS422A cable is within 1.2km of total extension and up to 31 devices can be connected. Install a resistor of 100Ω to the last edge of the transmission line device side. (General metal film resistors will be fine. They are available from us, place an order.)
Example of terminal connection
(3) RS485 wiring
PC and multiple devices are connected with RS485. A line converter is required. RS485 cable is within 1.2km of total extension and up to 31 devices can be connected. Install a resistor of 100Ω to the last edge of the transmission line device side. (General metal film resistors will be fine. They are available from us, place an order.)
Example of terminal connection
Turn the switch of RS422A/RS485 to RS422A.
Avoid connecting SG line to FG terminal or gound terminal of the device.
RDB
RDA
SDA
SDB
SG
Termination resistor 100Ω
Device side
Line converter
SC8-10
RDB
RDA
SDA
SDB
SD
RD
SG
1 2 3 4 5 6 7 8
Cable for RS232C (Max. 15m)
RZ-CRS6
Communications port
PC side
SD
RD
SG
RDB
RDA
SDA
SDB
SG
RDB
RDA
SDA
SDB
SG
SG
RDB
RDA
SD
RD
SG
Turn the switch of RS422A/RS485 to RS485.
Avoid connecting SG line to FG terminal or gound terminal of the device.
SA
SB
Termination resistor 100Ω
Device side
Line converter
SC8-10
1 2 3 4 5 6 7 8
Cable for RS232C (Max. 15m)
RZ-CRS6
Communications port
PC side
SD
RD
SG
SA
SB
SG
SA
SB
SG
- 25 -
(4) Ethernet wiring
Example of connection between PC and Ethernet devices (one-to-one connection)
Example of connection between PC and HUB/Ethernet devices (one-to-N connection)
Crossover twist-pair cable
with shield (Max.100m)
Device side
PC side
Device side
HUB
Straight twist-pair cable with shield (Max.100m)
PC side
HUB
Straight twist-pair cable with shield (Max.100m)
Straight twist-pair cable with shield (Max.100m)
- 26 -
5. Part Names
5-1. Front Section of Internal Unit
Enlarged view of power switch
Power switch Open the display board in the direction same as the unit door. The power switch is located at the upper left of the unit.
Display
Engineering port USB communication connector
SD card slot
Operation/set keys
The front of the door is made of glass. Avoid giving any shock to the glass or giving any strong force to the frame for preventing any injury due to breakage.
How to handle the door
Note 1
Avoid closing the door in the state of operation/set keys opened. If the door is closed in the state of the operation/set keys opened, the mechanism of the operation/set keys allows the operation/set keys to be lifted to the direction for closing to prevent damage; however, behavior for protection is not guaranteed. If the door is closed forcedly or fast, it may be damaged.
Operation/set key
Note 2
- 27 -
5-2. Operation/Set Keys
Status LED
REC
Lights in green while recording is on. Recording is turned ON/OFF by the
key.
Flashes when chart ends.
CARD
Lights in green when SD card is recognized by the unit, or flashes in a recognition process.
ALM
Flashes in red when alarm occurs.
Key names
Functions
REC
Record key
Turns ON/OFF recording. Used with the key. FEED
Feed key
Feeds chart at a speed of 600mm/min while this key is pressed.
DATAP
Data print
Prints the data at the time of pressing this key. Used with the key. FUNC1
Function 1 key
Switches and sets functions (function is shown on the display).
FUNC2
Function 2 key
Switches and sets functions (function is shown on the display).
MENU
Menu key
Displays various setting items.
ESC
Escape key
Returns to the previously displayed screen.
/ /
Up/Down Left/Right
Moves the cursor up/down and left/right. Used also to select setting items or values. Used also to advance the channel number.
ENTER
Enter key
Used to register various settings.
Loading...
+ 91 hidden pages