Chief PAC526FWP4 Installation Guide

Page 1
INSTALLATION INSTRUCTIONS
PAC525FxP2
PAC526FxP2
PAC526FxP4
PAC526FxP6
Powered In-Wall Storage Boxes
German Product Description
Portuguese Product Description
Italian Product Description
Dutch Product Description
French Product Description
PAC525FxP2 / PAC526FxP2 /
PAC526FxP4 / PAC526FxP6
ADDENDUM
Page 2
PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6 Installation Instructions
DISCLAIMER
Milestone AV Technologies, and its affiliated corporations and subsidiaries (collectively, "Milestone"), intend to make this manual accurate and complete. However, Milestone makes no claim that the information contained herein covers all details, conditions or variations, nor does it provide for every possible contingency in connection with the installation or use of this product. The information contained in this document is subject to change without notice or obligation of any kind. Milestone makes no representation of warranty, expressed or implied, regarding the information contained herein. Milestone assumes no responsibility for accuracy, completeness or sufficiency of the information contained in this document.
Chief® is a registered trademark of Milestone AV Technologies. All rights reserved.
IMPORTANT SAFETY INSTRUCTIONS
WARNING alerts you to the possibility of
serious injury or death if you do not follow the instructions.
WARNING: TO REDUCE THE RISK OF
BURNS, FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS:
Always turn off power at source before servicing or removing the outlet.
Do not use outdoors - For indoor use only.
Route cables as shown in these installation instructions.
To disconnect, turn off power at source.
WARNING: RISK OF ELECTRIC SHOCK!
Make sure the outlet is properly grounded. See grounding instructions.
WARNING: Failure to provide adequate
structural strength for this outlet can result in serious personal injury or damage to equipment! It is the installer’s responsibility to make sure the structure to which this product is attached can support the weight of the box.
CAUTION: This equipment must be installed
and assembled by qualified service personnel in accordance with local building and electrical codes.
CAUTION alerts you to the possibility of
damage or destruction of equipment if you do not follow the corresponding instructions.
WARNING: F AILURE TO READ AND
FOLLOW THE FOLLOWING INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL INJURY, DAMAGE TO EQUIPMENT OR VOIDING OF FACTORY W ARRANTY. It is the installer’s responsibility to make sure all components are properly assembled and installed using the instructions provided.
READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT!!!!
DANGER: TO REDUCE THE RISK OF
ELECTRIC SHOCK:
1. Always turn off power at source before installing the outlet.
NOTE: Knockouts are provided for ease of installation. Any
unused knockouts that have been punched are to be closed up with a metal plug.
NOTE: Ambient Temperature - The manufacturer’s maximum
ambient temperature is 104°F (40°C) and minimum ambient temperature is 30°F (-1°C) so that the installer is able to determine acceptability of use of Accessories and components.
--SAVE THESE INSTRUCTIONS--
2
Page 3
Installation Instructions PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6
PAC526FxP2 PAC526FxP4
PAC526FxP6
PAC525FxP2
DIMENSIONS: INCHES [MILLIMETERS]
PAC526FxP2/P4/P6
DIMENSIONS
3
Page 4
PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6 Installation Instructions
DIMENSIONS: INCHES [MILLIMETERS]
PAC526FxP4/P6
PAC526FxP2
DIMENSIONS - continued
4
Page 5
Installation Instructions PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6
Tighten Fastener
Apretar elemento de fijación Befestigungsteil festziehen Apertar fixador Serrare il fissaggio Bevestiging vastdraaien Serrez les fixations
Loosen Fastener
Aflojar elemento de fijación Befestigungsteil lösen Desapertar fixador Allentare il fissaggio Bevestiging losdraaien Desserrez les fixations
Phillips Screwdriver
Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme
Adjust
Ajustar Einstellen Ajustar Regolare Afstellen Ajuster
Grounding screw installed at factory (see below)
10-32 grounding screw
Earthing symbol IEC 60418 No. 5019 affixed adjacent to grounding terminal
PAC525FxP2
PAC526FxP2
PAC526FxP4
PAC526FxP6
OR
OR
OR
grounding screw (located on two sides of PAC526 box)
grounding screw (located on one side of PAC525 box)
LEGEND
TOOLS REQUIRED FOR INSTALLATION / PARTS
5
Page 6
PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6 Installation Instructions
1
x 2
2
(PAC526FxP6 shown as example)
(Reverse view)
Tab on power kit
In-wall box tabs
Power kit
4
Isolated Ground Receptacle
This product incorporates an isolated ground receptacle, identified by the orange triangle on its face. This feature may be useful to reduce common noise in the connected equipment. Its intended use is to reduce electrical noise (electromagnetic interference) by purposely insulating the grounding circuit from any metallic wiring system. The ground pin of the receptacle is connected to the green/yellow wire and is isolated from the metal mounting yoke of the receptacle. The accessible metal of the product is connected to the green wire. If it is not desired to use this feature, connect the green/yellow and green wires together.
References
Application Guide for Isolated Ground Wiring Devices 2007, National Electrical Manufacturers Association (NEMA)
IEEE Std 1100-2005, “IEEE Recommended Practice for Powering and Grounding Electronic Equipment” (Emerald Book), Section 8.5.3.2.
IEEE Std 142™-2007, “IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems” (Green Book), Sections 5.5.1, 5.5.2
NFPA-70, “National Electrical Code”, Article 250.146 Connecting Receptacle Grounding Terminal to Box.
(D) Isolated Ground Receptacles. Where installed for the reduction of electrical noise (electromagnetic interference) on the grounding circuit, a receptacle in which the grounding terminal is purposefully insulated from the receptacle mounting means shall be permitted. The receptacle grounding terminal shall be connected to an insulated equipment grounding conductor run with the circuit conductors. This equipment grounding conductor shall be permitted to pass through one or more panel boards without a connection to the panel board grounding terminal bar as permitted in 408.40, Exception, so as to terminate within the same building or structure directly at an equipment grounding conductor terminal of the applicable derived system or service. Where installed in accordance with the provisions of this section, this equipment grounding conductor shall also be permitted to pass through boxes, wire ways, or other enclosures without being connected to such enclosures.
Informational Note: Use of an isolated equipment grounding conductor does not relieve the requirement for grounding the raceway system and outlet box.
C22.2 No. 1, “Canadian Electrical Code, Part 1”, Rule 10-906 Bonding conductor connection to circuits and equipment.
(6) A bonding jumper shall be installed to connect the bonding conductor to the grounding terminal of a receptacle and in such a manner that disconnection or removal of the receptacle will not interfere with, or interrupt grounding continuity.
(7) In the case of metallically enclosed systems where the grounding path is provided by the metal enclosure, a bonding jumper shall be installed to bond the grounding terminal of the receptacle to the enclosure.
(8) Notwithstanding Sub-rules (6) and (7), the bonding jumper, in the case of receptacles having grounding terminals isolated from the mounting strap required for special equipment, shall be permitted to be extended directly back to the distribution panel.
WARNING: IMPROPER INSTALLATION CAN RESULT IN
DEAT H OR SERIOUS PERSONAL INJURY! This enclosure should be installed by qualified personnel.
IMPORTANT ! : In addition to the PAC525/PAC526 Series installation instructions accompanying the products, the following steps must also be taken when installing the PAC525FxP2 / PAC526FxP2 /
PAC526FxP4 / PAC526FxP6. NOTE:
The PAC525FxP2, PAC526FxP2, PAC526FxP4, and PAC526FxP6 must be connected to a 15 Amp branch circuit.
Prepare for Wiring
1. Remove and save two Phillips head screws holding power kit within box. (See Figure 1)
2. Remove the power kit from the in-wall box, detaching the tab on the power kit from the tabs in the in-wall box. (See Figure 1)
Figure 1
6
Page 7
Installation Instructions PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6
4
GREEN
(box ground)
5
x 2
(PAC526P6 kit shown as example)
WHITE
(neutral)
BLACK
(line)
GREEN/YELLOW
(isolated ground)
"PROTECTED"
indicator light
(PAC525P2 kit shown as example)
3. Wire the outlet box(es) as required. Refer to T able 1 and T able 2 for input and output specifications. (See Figure 2)
Table 1: Input Specifications
Input
Input voltage, frequency Input connection type
Input Wire colors
Input wire length (ft.)
Table 2: Output Specifications
Output
Output Power consumption Fuses
Quantity/Type Color/Markings
125 V AC, 60 Hz 4x14 AWG stranded, UL Style
1015, CSA TEW Black - Line White - Neutral
Green - Box Ground Green/Yellow - Isolated Ground 1 (with a 3/4" stripped end)
15 A, 1875 W <0.5 watt Thermal current interrupting circuits
are in MOVs Duplex NEMA 5-15R Isolated Ground
Receptacle Grey with protection symbol (Orange
triangle)
Figure 2
CAUTION: Isolated ground-mounting means NOT
grounded. Grounding wire connection required.
IMPORTANT ! : If a separa te isolated green/yellow ground wire is installed in the building wiring, attach it separately to the green/yellow isolated ground wire on box. If there is no separate green/yellow isolated ground wire, connect green ground wire to both green/yellow isolated ground wire and green box ground wire on box.
NOTE:
NOTE: An insulated grounding conductor that is identical in
NOTE: Pressure terminal or pressure splicing connectors and
The grounding conductors serving this outlet are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. Connections should be made with minimum AWG 14 copper wire intended for use on a 15 Amp circuit. The conductors used to connect the outlet to the line or bus and ground shall not be any longer than necessary and shall avoid unnecessary bends.
size and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed as part of the circuit that supplies the outlet. Refer to Table 250-122 of the National Electrical Code regarding the appropriate size of the grounding conductor.
soldering lugs used in the inst allation of th e outlet shall be identified as being suitable for the material of the conductors. Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors unless the device is identified for the purpose and conditions of use.
4. Replace the power kit into the in-wall box, joining the tab on the power kit with the tabs in the in-wall box. (See Figure 1) and (See Figure 2)
5. Tighten two Phillips screws to secure power kit in the in-wall box. (See Figure 2)
Outlet Box Use
NOTE: The "PROTECTED" light indicates that the surge
protection circuitry is active and operational.
Figure 3
6. Complete the installation following the PAC525/526 installation instructions.
7
Page 8
PAC525FxP2 / PAC526FxP2 / PAC526FxP4 / PAC526FxP6 Installation Instructions
Chief, a products division of Milestone AV Technologies
8800-002796 Rev00 2016 Milestone AV Technologies
www.milestone.com
03/16
USA/International A 6436 City West Parkway, Eden Prairie, MN 55344
P 800.582.6480 / 952.225.6000 F 877.894.6918 / 952.894.6918
Europe A Franklinstraat 14, 6003 DK Weert, Netherlands
P +31 (0) 495 580 852 F +31 (0) 495 580 845
Asia Pacific A Office No. 918 on 9/F, Shatin Galleria
18-24 Shan Mei Street
Fotan, Shatin, Hong Kong
P 852 2145 4099 F 852 2145 4477
Loading...