CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
Camber
LED emergency exit signage
from Channel Safety Systems
CHANNEL SAFETY SYSTEMS t: 0845 884 7000
Peters eld Business Park f: 0845 884 6000
Bedford Road
Peters eld
Hampshire e: sales@channelsafety.co.uk
GU32 3QA w: www.channelsafety.co.uk
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 1
INSTRUCTION MANUAL

CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
CAMBER LED EXIT SIGN
Instructions for Self Test option
Install LED exit sign according to installation instruction sheet
Once the unit is powered up it will automatically initiate a self-test and diagnostics as follows:
• Every 4 seconds: Checks for battery disconnection, charger board fault, lamp failure and transformer failure
• Every month: Performs a 3 minute duration test
• Every year: Performs a 3 hour duration test
All test functions are factory preset and do not need eld adjustment
Dual colour indicator LED status meanings
Green Solid on - Normal operation
Flashing - Testing
Red Requires service
One ash, 4 second pause Battery not connected
Two ashes, 4 second pause Battery short or low battery voltage
Three ashes, 4 second pause Charger board fault
Four ashes, 4 second pause Transformer fault
NOTE: After repairing a service fault, press and hold the test button for 2 seconds to reset the ashing indicator light to green.
MANUAL TESTING
Press test button once 30 second duration test
Press test button twice within 2 seconds 3 minute duration test
Press test button three times within 2 seconds 30 minutes duration test
Press test button four times within 2 seconds 3 hours duration test
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 2

CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 3

CHANNEL SAFETY SYSTEMS t: 0845 884 7000
Peters eld Business Park f: 0845 884 6000
Bedford Road
Peters eld
Hampshire e: sales@channelsafety.co.uk
GU32 3QA w: www.channelsafety.co.uk
INSTRUCTION MANUAL