Chamberlain LM21XP User Manual

OO WW NN EE RR SS MM AA NN UU AA LL
MM OO DD EE LL
LL MM 22 11 XX PP
EEXXTTEENNDDEEDD PPEERRFFOORRMMAANNCCEE RREELLEEAASSEE DDEEVVIICCEE
The Chamberlain Group, Inc. 845 Larch Avenue Elmhurst, Illinois 60126-1196
www.liftmaster.com
When you see this Signal Word on the following pages, it will alert you to the possibility of damage to your door and/or the door operator if you do not comply with the cautionary statements that accompany it. Read them carefully.
Mechanical
Electrical

TABLE OF CONTENTS

WARNING
WARNING
WARNING
WARNING
CAUTION
WARNING
WARNING
2

INTRODUCTION

General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSTALLATION
Important Installation Warnings . . . . . . . . . . . . . . . . . . . . . . . . . .4
Mount the Release Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
WIRING
Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Connections of Initiating Devices and Accessories . . . . . . . . . .7-8
Optional Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-9
TESTING
Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
TROUBLESHOOTING
Operational Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
MAINTENANCE
Maintenance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Enclosure Mounted LEDs Status Indicators . . . . . . . . . . . . . . . .12
ACCESSORIES AND REPLACEMENT PARTS
. . . . . . . .13
APPENDIX
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
OPERATOR NOTES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
IMPORTANT NOTES:
• BEFORE attempting to install, operate or maintain the release device, you must read and fully understand this manual and follow all safety instructions.
• DO NOT attempt repair or service of your release device unless you are an Authorized Service Technician.
GENERAL DESCRIPTION
The LiftMaster®LM21XP Release Device is UL/ULC listed normally energized fail-safe device designed for use on rolling doors, single-slide and center-parting level and inclined track doors. All models are normally energized fail-safe releasing devices incorporating state-of-the-art electronic control circuitry. The release devices respond to emergency conditions generated from an automatic initiating device and are used in conjunction with a temperature fuse link system.
This device is designated to be used with manual doors, but can be used on motorized doors incorporating a fusible link assembly and drop-out mechanism.
The release device must be powered from 24Vdc received from an approved UL 1481 regulated power supply with battery backup. The devices can be activated via a smoke detector or an alarm relay from the panel’s Form C dry contact relay. The release device features include a 10-, 20-, 30- or 60-second delay on alarm, closed door detection capabilities, Form C relay outputs for the transmission of alarm and trouble signals transmitted to the fire alarm control panel, an audible trouble sounder, and diagnostic feedback LEDs.
INTRODUCTION
INTRODUCTION
3

AGENCY REQUIREMENTS

Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
SPECIFICATIONS
To prevent possible SERIOUS INJURY or DEATH:
• DO NOT use this device without fuse links installed.
• Test every 90 days to assure proper operation of release
device.
WARNING
WARNING
LOAD RATING: Support and Release 40 lbs. Max. PHYSICAL DIMENSIONS: 9.7" x 7.5" x 5" (h x w x d)

PREPARATION

It is imperative that the wall or mounting surface provide adequate support for the release device.
Refer to the door manufacturer’s recommendations for use of this product with specific door being utilized. Use only hardware approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.
Additional items may be required to complete the installation:
• Concrete anchors or fasteners
• Sash chain or 1/16 cable
• Eyebolts-hook
• Fuse links
• Turnbuckles
• Smoke detectors (up to 4 may be installed with this device)
Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices shall be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
Smoke Detector
Releasing Unit
Fuse Links
Eyebolt
Turnbuckle
Chain
Chain End Link
Fire Door
ELECTRICAL SPECIFICATIONS
MECHANICAL SPECIFICATIONS
COMMON ALARM AND TROUBLE RELAY:
.5A 125Vac, 60Hz
(MAX. CONTACT RATING) 1A 24Vdc Resistive
WEIGHT: Approximately 8 lbs.
VOLTAGE RATING: 24Vdc STANDBY CURRENT: .100A ALARM CURRENT: .15A INITIATING DEVICE: Maximum line impedance 20 ohm;
Maximum current not to exceed .010A.; Maximum voltage 28Vdc
4

INSTALLATION

Classification:
Releasing device as defined by Underwriters Laboratories.
Installation Requirements:
Intended for “Indoor Dry” locations; all wiring must be performed in accordance with the most current version of NFPA 72 - National Fire Alarm Code and the National Electric Code.

MOUNT THE RELEASE DEVICE

Installation procedures vary according to door types. Refer to door manufacturer’s recommendation that applies to your door.
1. Mount the release device on a vertical surface with chain end link exiting side of enclosure.
2. Secure the release device enclosure with fasteners (#10 is the minimum size recommended). If installing in masonry, use concrete anchors (not provided).
3. Install hardware (sash chain or 1/16 cable, eyebolts-hook, fuse links, turnbuckles—not provided) according to door manufacturer’s recommendations. NOTE: The end link direction
of pull must be perpendicular to the side of the release device enclosure. Install an eyebolt a minimum distance of 12" from the release device to adequately redirect sash chain pull.
4. Install end link by pressing mechanical reset to allow insertion of end link. Push end link completely in and release mechanical reset to latch end link.
5. Remove sash chain or cable slack by adjusting turnbuckle.
IMPORTANT INSTALLATION INSTRUCTIONS
To reduce the risk of SEVERE INJURY or DEATH:
WARNING
WARNING
WARNING
1. READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS.
2. NEVER connect release device to power source until instructed to do so.
3. DO NOT install this device on a motorized door without an electric safety edge.
4. DO NOT use this device without fuse links installed.
5. Concrete anchors MUST be used if mounting release device into masonry.
6. DO NOT exceed maximum pull rating of 40 lbs. on releasing device.
Mechanical Reset Plunger
End Link
Smoke Detector
Releasing Unit
Eyebolt
Chain End Link
Fuse Links
Turnbuckle
Chain
Fire Door
5

WIRING

WIRING INSTRUCTIONS
Verify wiring configuration with that recommended by door manufacturer for use of this product with specific door and accessories being utilized. 18-gauge wire is recommended.
1. Turn off power supply sources for the release device as well as the door operator, if applicable, before beginning.
2. Verify voltage rating of release device to power source being utilized. Voltage is indicated on the side of the unit. Verify that power is disconnected before proceeding.
3. Connect 24Vdc power to terminal board positions 1 and 2 (Figure 2). Observe proper polarity. 24Vdc power input from an approved UL 1481 regulated power supply with battery backup.
To reduce the risk of SEVERE INJURY or DEATH:
• ALL electrical connections MUST be made by a qualified individual.
• Disconnect power at the fuse box BEFORE proceeding. Release device MUST be properly grounded and connected in accordance with local electrical codes.
• ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.
• ALL power and control wiring MUST be run in separate conduit.
• Installation of ALL wiring and connections, including Class 1 and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, ALL installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
WARNING
WARNING
FIGURE 2
FIGURE 1
To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type.
WARNING
CAUTION
WARNING
WARNING
Mechanical Reset Plunger
Option DIP Switch
+
1
2
24Vdc from an Approved UL 1481 Regulated Power Supply with Battery Backup
6
WIRING

WIRING DIAGRAM

Field Wiring shall consist of 22-18 AWG wiring.
1. Supervised, power limited circuit, 20 Ohm maximum line impedance.
2. Unsupervised, power limited circuit, 20 Ohm maximum line impedance.
3. Maximum of 4 Class B Style A detectors.
4. Power from an approved UL1481 regulated supply with battery backup.
2-Wire Detector Initiation Loop (1) (3) Keep 10k Ohm resister between 5 & 6 if unused.
Resistor
10k Ohm EOL
014G0962B
+ In
- In/Out
+ Out
+ In
- In/Out
+ Out
Normally Closed
Initiation Loop (1) (3)
Keep jumper between
3 & 4 if unused.
External power required.
NC
COM
Solenoid
(GY)
(YE)
Input Power
(4)
PTC1
C2
U2
C4
3
4
2
+
SW1
1
LED 3
R6
DISABLE
P2
U4
C1
LED 1
U3
K1
POWER ON
2W_OP
2W_FAULT
NC_FAULT
CL_LIMIT
GND_FAULT
D1
K2
K3
SW3
LED4
LED5
LED6
LED2
LED7
SW2
12
3
45
6
7
89
10
11
12
13
15 14
16
P1
+ 24Vdc
Common Relay Connections
Alarm NC Alarm Com Alarm NO Trouble NC Trouble Com Trouble NO
N.O. Close Door Proximity Switch (2)
7

CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES

A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
NOTE: For low voltage wiring #18 AWG is recommended.
Normally Open “2-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O initiating device loop to positions 3 and
4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained within the accessory pack. (Figure 3). Observe proper polarity, 3 (+), 4 (–) when attaching to the release device’s terminal board.
NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a
supervised, current-limited circuit.
OR
Normally Open “4-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O 4-Wire initiating device loop to positions 3 and 4, making sure an end-of-line supervisory resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4 or 5, depending upon the type of smoke detector being used. Observe proper polarity, 3 (+), 4 (–) when attaching to the release device’s terminal board. NOTE: Make certain that the factory-
installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.
OR
Normally Closed “4-Wire,” Class B Style A Initiating Devices
After removing the factory-installed jumper between terminal positions 5 and 6, connect wiring from N/C 4-Wire initiating device loop to positions 5 and 6 (Figure 6). This option is a supervised, current-limited circuit. NOTE: Make certain that the
factory-installed resistor between positions 3 and 4 remains in place.
NOTE: End-of-line devices must be installed adjacent and after the last initiating device. Initiating device loops are supervised and cannot be direct series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signaling for simultaneous closure on multiple doors, call technical support, 1-888-528-7870. Incorrect wiring between devices may cause damage to the release control circuit and void warranty.
OR
Relay Module Installation as described on the following page.
WIRING
To prevent possible SERIOUS INJURY or DEATH:
• End-of-line devices MUST be installed for supervision of electrical power to 4-wire smoke detector.
• DO NOT install this device on a motorized door without an electric safety edge.
WARNING
WARNING
FIGURE 4
FIGURE 5
FIGURE 3
FIGURE 6
24Vdc Power from Terminal Strip
3
4
(–)
Power from Control Panel
(+)
Terminal Strip
3
4
(+)
Power from Control Panel
(–)
Terminal Strip
(+)
3
4
(–)
(–)
Power from Control Panel
(+)
Terminal Strip
– IN/OUT
+ OUT
+ IN
NOTE: Follow this method of attachment when using LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors.
NO
– IN/OUT
+ OUT
+ IN
NOTE: Follow this method of attachment when using LM1424, LM1412, or other N/O 4-wire smoke detectors.
(+)
Alarm Contacts Style A
(
N/O
IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.
N/C
(–)
)
(+)
(–)
C
COM
N/C
+ IN
(+)
(+)
C
10k Ohm @1/2 watt Supervisory Resistor (LMEOLRES-10)
– IN/OUT
+ OUT
NOTE: Follow this method of attachment when using LM2W-B, LM2WT-B, or other 2-wire 24Vdc smoke detectors.
10k Ohm @ 1/2 watt
COM
NO
– IN/OUT
+ OUT
+ IN
(–)
NOTE: Generic version of a N/C 4-wire smoke detector is shown.
(–)
Purple
Supervisory Resistor (LMEOLRES-10)
LMEOLR1224 12/24 Vdc EOL Relay
10k Ohm @ 1/2 watt Sup
ervisory Resistor
(LMEOLR
LMEOLR1224 12/24 Vdc EOL Relay
LMEOLR1224 12/24 Vdc EOL Relay
ES-10)
5
6
IMPORTANT: When using 4-wire smoke detectors with this
device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.
8
WIRING
FIGURE 7
CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES (cont’d)
Relay Module Installation
In lieu of smoke detectors, the release device may be put into alarm by the fire alarm control panel. Most commonly, a relay module is used as an interface between the fire alarm control panel and the release device. The relay module must provide Form C dry contacts for connection to the appropriate terminals on the release device (Figure 7).
NOTE: When choosing a relay module to activate the release device in an alarm condition, always select one that provides Form C dry contact relays. Do not use any relay module providing or passing any (control) voltage through the contacts into the release device. The passage of voltage through such a relay module into the release device will cause problems with the operation of the device and may damage the device’s terminals and/or circuit board.

OPTIONAL CONNECTIONS

CLOSE DOOR DETECTION OPTION
Connect wiring from N/O electrical loop, using a proximity switch or other similar device with dry contacts, to 7 and 8 (Figure 8). The switch should be placed to engage when the door is in the closed position and so that it will toggle states from its N/O condition (switch closed when door is closed) to a closed condition indicating that the door edge has made contact with desired down position. When the switch is closed by contact from the door, the release device will not activate on alarm, thereby eliminating nuisance gravity drops through the inadvertent release of the fusible link assembly. This option only works as long as power is available to unit. Fail-safe operation is maintained under all operating conditions, and if power is not available to the unit, the fusible link assembly will be released. This is a power-limited, unsupervised circuit. The proximity switch and the release device MUST be mounted in the same room.

RELAY AND TROUBLE OUTPUTS OPTION

Connect wiring from the Alarm Relay Outputs (#11 N/C or #13 N/O and #14 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel when the release device is in an alarm state. Connect wiring from the Trouble Relay Outputs (#14 N/C or #16 N/O and #15 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel that the release device is in a trouble state (Figure 9). If these features are desired, coordinate the interconnection between the Release Device and the Fire Alarm Control Panel with the fire alarm installer.
FIGURE 9
FIGURE 8
To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type.
WARNING
CAUTION
WARNING
WARNING
Relay Module
5
6
Terminal Strip
Common
Normally Closed
Red
Black
Fire Alarm Control Panel
+
7
8
11
N/C Alarm Relay Output
12
Common
13
N/O Alarm Relay Output
14
N/C Trouble Output
15
Trouble Common
16
N/O Trouble Output
Attach to Common on N/O Proximity Switch
Attach to N/O Position on Proximity Switch
Proximity Switch Part No. LM56A
Make all necessary connections to the Fire Alarm Panel as required by the project specifications and the Authority Having Jurisdiction
9
WIRING
OPTIONAL CONNECTIONS (cont’d)

DIP SWITCH SELECTION

The release device will provide a factory default delay of 10 seconds (to minimize nuisance alarms) before releasing the fusible link chain upon alarm or power loss. A 4-position DIP Switch found on the PC board within the release device can be used to adjust the length of the delay to one of four preset delays. The optional delay settings are as follows:
FIGURE 10
Delay Setting Switch Position
1234
10 Seconds Off Off Off Off
20 Seconds Off On Off Off
30 Seconds On Off Off Off
60 Seconds On On Off Off
NOTE: Set all DIP switch options before applying power to the system.
NOTE: Position 4 is unused and should remain in the OFF position. Position 3 is used to select one of the two available voice messages.
ON
1 2 3 4
Factory default setting of 10 seconds shown.
10

TESTING

TEST PROCEDURES

TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! CLEAR FIRE DOOR OPENING AND PROHIBIT TRAFFIC THROUGH DOOR OPENING WHILE TESTING!
Testing does not affect normal operation of alarm system when connected to release device/control panel. Testing of the release device is independent of, and shall in no way be interpreted as an alternative method of, testing of a central fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. Complete testing and normal operation can only be accomplished with power applied to unit. Door must be in open position with power applied to unit to begin testing. The following procedures describe testing of all options. Verify options ordered and installed with unit. All tests may not apply. Refer to Figure 1 for location of all the LEDs and switches mentioned in this section.
INITIAL POWER UP
1. Apply line power to the release device.
2. Power LED (red) will be lit on the bottom of the release device.
MECHANICAL RELEASE
1. Depress and continue to hold test button on side of release device. After the selected delay expires, the device will release the end link and allow door to drop. Release test button.
2. Reset the door per door manufacturer’s instructions. Raise door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link.

CLOSE DOOR DETECTION (OPTIONAL)

1. Using the chain hoist or motor operator, lower the door to fully closed position.
2. Verify that Close Door Detection LED (yellow) is lit indicating door closure. Depress and continue to hold test button on side of release device for 10 seconds. Close Door Detection logic will prohibit the release device from energizing and releasing the end link. Reset the test button.
3. Raise door to fully open position.
SUSPENSION OF POWER
1. Make sure door is in fully open position. Turn off all power to release device. Immediately upon loss of power to the release device, a mechanical release will be initiated.
2. Reset the door per door manufacturer’s instructions. Raise the door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link. Press the “Reset” button on the side of the device to reset the alarm loop.
After completing all tests, make sure the door is in its normal condition (open or closed) and all power required for normal operation is restored to unit. The release device is designed to operate with power applied.
NOTE: Testing shall be performed and witnessed for proper operation.
To prevent possible SERIOUS INJURY or DEATH:
• Clear fire door opening and prohibit ALL traffic through door opening while testing.
• Test every 90 days to assure proper operation of release device.
WARNING
WARNING
FIGURE 1
Mechanical Reset Plunger
Front of Release Device
Bottom of Release Device
Electronic Reset Button
Test Button
Red LED (Line Power Present)
Yellow LED (Close Door Detection Release Disabled)
End Link
N/O Detector
Trouble
Yellow
(LED 4)
If lit, indicates a trouble condition (a short) within the N/O 2-wire (or 4-wire) smoke detector loop (emanating from terminal board positions 3 and 4), resulting from either incorrect wiring or incorrect placement of the end-of-line resistor, and the smoke detector loop is inactive. Refer to the Smoke Detector Installation section on pages 7 and 8 of this manual for correct wiring instructions.
N/O Detector
Alarm
Red
(LED 5)
If lit, indicates that the N/O 2-wire (or 4-wire) smoke detector loop (emanating from terminal board positions 3 and 4) is in alarm. When lit during testing, press the Auxiliary Reset Button at the bottom of the release device to reset the loop.
N/C Detector
Trouble
Red
(LED 6)
If lit, indicates an open circuit within the N/C 4-wire smoke detector loop (emanating from terminal board positions 5 and 6), resulting from either incorrect wiring or incorrect placement of the end­of-line relay or the detector(s) are in alarm. If in alarm, cycle power off and then on to the smoke detectors to reset, then depress the auxiliary reset button to reset. Refer to the Smoke Detector Installation section on pages 7 and 8 of this manual for correct wiring instructions.
Close Door
Detection
Green
(LED 2)
If lit, indicates that the fire door or shutter is closed and activating the proximity switch. If not lit, refer to the Close Door Detection section of this manual for correct wiring instructions.
Ground Fault Yellow
(LED 7)
If lit, indicates that one of the ancillary devices/loops (smoke detector, annunciator, etc.) is not grounded properly, and a short to earth ground exists.

TROUBLESHOOTING

OPERATIONAL CHECKLIST

POWER
Is the red LED, labeled “Power,” located on the bottom of the enclosure lit?
CHECK THE ALARM
Are the alarm (smoke detection) inputs correct? If not, the release device will not release the fusible link assembly in a fire condition. Conversely, the release device will always release the fusible link assembly when powered or reset.

CIRCUIT BOARD DIAGNOSTIC LEDS

View diagnostic LEDs present on the circuit board located behind the terminal board. Refer to the table below for the status LED indications.
Is the Red LED Lit?
Yes Move on.
No Check power connections at terminal board positions 1 and 2.
Check voltage; voltage should be 24Vdc received from an approved UL 1481 regulated power supply.
Are the Alarm Inputs correct?
Yes Move on.
No Check that it is a dry contact input. There should not be any
voltage on the alarm lines when they are disconnected from the unit.
Check to see if it is tied into an addressable relay module of an alarm panel. At times, noise can be picked up from these modules.
CHECK THE CLOSE DOOR DETECTION
Is the Yellow LED on the bottom of the enclosure lit? If lit, the close limit is active and the device is disabled and will not release the tension on the door spring as the door is in the closed position, activating the proximity switch. If not lit, check wiring instructions in Figure 8.
LED LED Color Description
11
Disable Yellow The Yellow LED will light when the door reaches the close
limit and activates a proximity switch attached to terminal positions 7 and 8 on the release device. This configuration results in the device not releasing the fusible link assembly in alarm or power loss situations and should only be used when the fire door is kept in a constant closed position.
If the LED does not light when the door reaches the close limit and activates the proximity switch, then check that the proximity switch has been activated and that the switch is set to normally open (N.O.). Check to make certain that the switch is attached to terminal positions 7 and 8 on the release device.
Power Red If the Red LED is lit, then the line power is connected and
switched “on.”
If the LED does not light when power is applied, check that power is connected as described in the installation manual electrical connections.

MAINTENANCE

To avoid SERIOUS PERSONAL INJURY or DEATH from electrocution, disconnect ALL power BEFORE performing ANY maintenance.
WARNING
WARNING
MAINTENANCE REQUIREMENTS
The release device has no scheduled maintenance requirements. The unit has been designed and tested for use in dry, indoor locations. Testing of the unit at least once every 90 days is recommended, but test intervals shall ultimately be subject to criteria established by the Authority Having Jurisdiction (AHJ).
FIGURE 1

ENCLOSURE MOUNTED LEDS STATUS INDICATORS

12
LED Label LED Color Description Action Required
Mechanical Reset Plunger
Front of Release Device
Bottom of Release Device
End Link
Electronic Reset Button
Test Button
Red LED (Line Power Present)
Yellow LED (Close Door Detection Release Disabled)
ACCESSORIES
REPLACEMENT PARTS
13

ACCESSORIES AND REPLACEMENT PARTS

HOW TO ORDER REPAIR PARTS

OUR LARGE SERVICE ORGANIZATION SPANS AMERICA
Installation and service information
call our TOLL FREE number:
1-888-528-7870
ITEM PART # DESCRIPTION
1 LM8100 Smoke Detector - 120V Photo 2 LM8100T Smoke Detector - 120V Photo with
Thermal 3 LM8100I Smoke Detector - 120V Ion 4 LM2W-B Smoke Detector - 12/24Vdc 2-Wire
Photo 5 LM2WT-B Smoke Detector - 12/24Vdc 2-Wire
Photo with Thermal 6 LM4W-B Smoke Detector - 12/24Vdc 4-Wire
Photo
ITEM PART # DESCRIPTION
7 LM4WT-B Smoke Detector - 12/24Vdc 4-Wire
Photo with Thermal and Form C Relay 8 LM1424 Smoke Detector - 24Vdc Ion 9 LM1412 Smoke Detector - 12Vdc Ion
10 LMTH135 Heat Detector - 135 Degree Fixed
Temperature
11 LMTH194 Heat Detector - 194 Degree Fixed
Temperature
12 LMEOLR1224 End-of-Line Relay - 12/24Vdc 13 LMEOLR120 End-of-Line Relay - 120Vac
ITEM PART # DESCRIPTION
1 LMRK Reset Knob 2 LMELH End Link 3 01-32046 Owner's Manual 4 LMEOLRES-10 End-of-Line Resistor, 10 kOhm
NOTE: Certain accessories above will require a separate power source. Refer to product manual.
LM2W-B 24Vdc 2-Wire Photo 2W-B
LM2WT-B 24Vdc 2-Wire Photo with Thermal 2WT-B
LM4W-B 24Vdc 4-Wire Photo 4W-B
LM4WT-B 24Vdc 4-Wire Photo with Thermal & Form C Relay 4WT-B
LM1424 24Vdc Ion #1424
LMTH135 135 Degree Fixed Temperature #5603 #603 #283B-PL
LMTH194 194 Degree Fixed Temperature #5604 #604 #284B-PL
LMEOLRES-10 10 kOhm End-of-Line Resistor LMEOLRES-10
LMEOLR1224 End-of-Line Relay EOLR-1
LMEOLR120 End-of-Line Relay PAM-1
14

APPENDIX

ACCESSORY COMPATIBILITY GUIDE
MODEL NO. DESCRIPTION SYSTEM SENSOR SPACE AGE LIFTMASTER NO.
MODEL NO. ELECTRONICS NO.
MODEL NO. DESCRIPTION SYSTEM SENSOR
MODEL NO.
MODEL NO. DESCRIPTION SYSTEM SENSOR CHEMTRONICS EDWARDS SYSTEM TECHNOLOGY
MODEL NO. MODEL NO. (EST) MODEL NO.
NOTE: Certain accessories above will require a separate power source. Refer to product manual.
SMOKE DETECTORS
HEAT DETECTORS
END-OF-LINE DEVICE
15

OPERATOR NOTES

01-32046B © 2006, The Chamberlain Group, Inc. Issue Date 7/27/2006 All Rights Reserved
Loading...