Chamberlain CSL24V, CSL24VH Addendum

AUXILIARY RELAY SWITCHES

ADDENDUM
FOR CSW AND CSL GATE OPERATORS
AUX RELAY switches
AUX RELAY
SETTING
SWITCH
SETTINGS
Set the AUX RELAY switches as needed to obtain the desired function:
123
Off (no feature
OFF OFF OFF
Relay always off. Use this Aux Relay setting to conserve
selected)
Open Limit
OFF OFF ON
Energizes at open limit. Use with SAMS (Sequenced Access Management
Switch
Close Limit
OFF ON OFF
Energizes when not at close limit. Connect “Gate Close/Secure” indicator
Switch
Gate Motion
Pre-Motion
Delay
Power
OFF ON ON
ON OFF OFF
ON ON OFF
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
Energizes 3 seconds before gate motion and remains energized during gate motion. Connect “Gate In Motion” indicator (e.g. warning light or sounder).
Energizes when AC power or solar power is present. There is approximately
a 10-12 second delay before relay cutoff, after AC shutdown.
Tamper
Cycle Quantity
ON OFF ON
ON ON ON
Energizes if gate is manually tampered with by being pushed off of close
The OPEN, CLOSE, and STOP LEDs will blink out the cycle count
Feedback*
CYCLE COUNT
* First, note the current Aux Relay switch positions. To
determine the actual cycles that the gate operator has run (in thousands), set all three Aux Relay switches to the ON setting for Aux Relay 1. The Expansion Board’s OPEN, CLOSE, and STOP LEDs will blink out the cycle count, with OPEN LED blinking 1000’s, CLOSE LED blink 10,000’s, STOP LED blinking 100,000’s, and simultaneously all three LED’s blink 1,000,000’s (e.g. Open blinks 3 times, Close blinks 6 times, and Stop blinks once. Cycle count is 163,000.). Cycle count displayed is between 1,000 and 9,999,000 cycles. After servicing, set Aux Relay switches back to their appropriate positions. Cycle count cannot be reset or changed. If under 1,000 cycles the Open, Close, and Stop LEDs will turn on for 10 seconds, then turn off.
battery power.
System, jointly with barrier gate)
(e.g. light).
indicator (e.g. warning light or sounder).
limit. Connect alert (e.g. light or sounder).
See below.
Shadow Loop
Interrupt Loop
Exit Loop
Relay always off. Use this Aux Relay setting to conserve battery power.
Energizes when at open limit. Use with SAMS (Sequenced Access
Management System, jointly with barrier gate)
Energizes when not at close limit. Connect “Gate Not Closed/Secure”
indicator (e.g. light).
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
indicator (e.g. warning light or sounder).
Not used.
Energizes when on battery power. There is approximately a 10-12
second delay before relay cutoff, after AC shutdown.
Energizes if gate is manually tampered with by being pushed off of close
limit. Connect alert (e.g. light or sounder).
Not used.
Single Button Control Station
3-Button Control Station
AUX Relay 1 N.O.
AUX Relay 1 N.C.
Com
AUX Relay 2 N.O.
AUX Relay 2 N.C.
Com
SBC
Com Open
Close
Stop Com

RESET SWITCH

MODELS CSL24V AND CSL24VH
The reset switch is located on the front of the operator and serves several functions. Toggling the reset switch will stop a moving gate during a normal open/close cycle,
like a stop button. The operator does not need to be reset after doing this. The reset switch will disable the gate in the present position and will energize the solenoid lock for two minutes and disable the maglock for two minutes.
MANUAL DISCONNECT
Press the reset switch to RESET/DISCONNECT to allow the gate to be opened and closed manually. To resume normal operation press the reset switch to NORMAL OPERATION.
NORMAL OPERATION
RESET/DISCONNECT
1
MODELS CSW24V AND CSW24VH
MANUAL DISCONNECT
Press the reset switch to RESET/DISCONNECT. Release the handle on the operator arm
Manual Disconnect Handle
to allow the gate to be opened and closed manually. On a dual gate application the handle must be released on both operators. To resume normal function tighten the handle by pushing it down.
RESET SWITCH
The reset switch is located on the front of the operator and serves several functions. Toggling the reset switch will stop a moving gate during a normal open/close cycle,
like a stop button. The operator does not need to be reset after doing this. The reset switch will disable the gate in the present position and will energize the solenoid lock for two minutes and disable the maglock for two minutes.

LOOP DETECTOR

WIRING TROUBLESHOOTING
EXPANSION BOARD
Shadow Loop
Exit Loop
Interrupt Loop
OPERATION
BLUE LED WHITE LED EXPLANATION
1 Blink (every 10
seconds) 2 Blinks Rapid Blinks (active fault)
3 Blinks Rapid Blinks (active fault)
4 Blinks Rapid Blinks (active fault) Failed Authentication (see
OFF 2 Blinks Successful Reset OFF Slow Blinks Loop detector is in TEST or PROG mode
Solid Solid Active Loop
DIAL SETTINGS EXPLANATION
TEST Mode Used to test the loop detector
1-8 Determines the sensitivity setting for the loop detector:
PROG Mode Used to change the frequency of the loop detector
White LEDs (located under dial)
OFF Normal Operation
Open Loop (see TROUBLESHOOTING)
or OFF
Shorted Loop (see TROUBLESHOOTING)
or OFF
TROUBLESHOOTING)
1 is the lowest sensitivity (large vehicle) setting and 8 is the
highest sensitivity (small vehicle). Default setting is 4.
Open or Shorted Loop (2 and 3 Blink errors):
Test the loop detector (refer to TEST THE LOOP DETECTOR section). If the loop detector passes the test, this indicates the loop detector is working properly and there is an issue with the loop wiring.
Failed Authentication (4 Blink error):
• Check the wire connecting the expansion board to the main board or
• Unplug the loop detector then plug it back into the same slot (clears all faults and keeps the current frequency settings, authenticates) or
• Unplug the loop detector. Then unplug the J15 plug on the operator’s control board and plug it back in after 2-3 seconds. This allows the loop detector to be plugged into a different slot (clears all faults and keeps the current frequency settings, authenticates).
To clear a fault:
• Press the reset button on the operator (clears all faults) or
• Unplug the loop detector then plug it back into the same slot.
The loop is making false detections:
• There is crosstalk between the LOOPDETLM and the alternate loop detector or
• Change the frequency or lower the sensitivity setting of the loop detector.
The loop will not activate when a vehicle passes over it:
• Turn the boost switch ON or increase the sensitivity of the loop detector or
• If the blue and white LEDs are solid, indicating an Active Loop, and the operator does not activate, there could be a fault. Once the loop is inactive, check the LED codes for a fault (refer to LED table above).
TEST THE LOOP DETECTOR
1
Turn the dial to TEST. The loop detector will send a signal to the main board simulating a vehicle over the loop.
Exit: If the gate is closed, it will open or if the gate is already open it will remain open. Shadow: Active ONLY when the gate is in the open position. If the gate is open, it will remain open. Interrupt: If the gate is closing, it will open.
2
Turn the dial back to the desired sensitivity setting.
NORMAL OPERATION
RESET/DISCONNECT
Frequency Button
Blue LED (located under dial)
Boost Switch
Dial
2
Loading...
+ 2 hidden pages