Chaffoteaux & Maury Mira system FF, System plus FF Installation And Operating Manual

Page 1
C
COMBINATION BOILER
Heating only (system)
Heating + sanitary hot water together (system plus)
Fanned Flue System
Installation and Operating Manual
GB
Page 2
2
Page
13 - controls................................................................................................................ 16
14 - operation ............................................................................................................. 17
15 - maintenance........................................................................................................ 18
16 - safe evacuation of combustion products ............................................................. 18
17 - warranty............................................................................................................... 18
18 - practical advice ................................................................................................... 18
19 - operating faults.................................................................................................... 19
20 - technical specifications ....................................................................................... 20
Page
1 - description........................................................................................................... 3
2 - dimensions .......................................................................................................... 4
3 - water specifications............................................................................................. 4
4 - installation requirements ..................................................................................... 5
5 - air intake and burnt gas outlet connections......................................................... 6
6 - fitting the boiler.................................................................................................... 8
7 - electrical connections.......................................................................................... 9
8 - starting up ........................................................................................................... 10
9 - fitting the casing .................................................................................................. 12
10 - gas conversion .................................................................................................... 13
11 - fault codes .......................................................................................................... 14
12 - points to note....................................................................................................... 15
Installer’s instruction
User’s instruction
Contents
Page 3
3
INSTALLER’S INSTRUCTION
1.- sheet steel frame with expansion vessel
2.- sealed casing
3.- hood with extractor fan
4.- copper main heat exchanger
5.- combustion chamber
6.- multigas burner comprising:
a removable injector manifold
an ignition electrode
a flame detection electrode
7.- gas valve assembly comprising:
two safety solenoid valves
a control solenoid valve
8.- circulating pump with automatic vent
9.- overheat sensor
10.- main heat exchanger inlet thermistor
11.- main heat exchanger outlet thermistor
12.- electronic control unit
14.- flue gas pressure control switch
15.- ignitor
16.- central heating pressure relief valve
19. - heating circuit pressure gauge
20. - ON/OFF push button and ON indicator light
21.- sanitary accumulation start button and tank
temperature setting button
22.- heating function ON and heating temperature
adjustment knob
23.- heating temperature and operating faults indicator
24.- orange burner operating indicator light
25.- reset push button and red locking indicator light
1
2
14
4
5
6
12
3
10
8
9
11
Fig.1
1. Description
Fig.3
20
21
23
25
22
24
19
C
15
16
Fig.2
7
(system plus)
Page 4
4
Fig.4
54 54 54 54
JKLMN
I
JKLMN
32
296
141
289
21
720
691,5
121,5
I
172,5
4,7
Measurements in mm
Weight with packaging:
24 kW: 32 kg 30 kW: 33 kg
Fig. 5
Fig. 6
Water content diagram.
Pf = Cold pressure in bar C = System capacity in litres
The boiler is fitted with an automatic by-pass as standard.
The graph (fig. 5) shows the development of the pressure available in relation to flow (on exit from the boiler).
To ensure correct operation, the minimum flow of the installation must be 300 l/h. (Thermostatic taps closed).
Capacity of the installation.
The boiler is fitted with an expansion vessel.
Maximum. volume of expansion vessel: 6 litres.
Pressure: 0,7 bar.
The volume of the expansion vessel in a pressurised installation varies according to:
- the average operating temperature in °C
- the static height (which is the difference in metres between the highest point of the installation and the expansion vessel axis).
The minimum cold filling pressure of the installation is 0,7 bar (recommended pressure between 1.2 and 1.7 bar).
The pressure of the expansion vessel should always be greater than the static height (in metres) divided by 10.
C
390
450 min. for maintenance
Pressure available
Minimum flow rate with the heating thermostatic valves closed
Heating circuit pressure when cold (bar)
Maximum system capacity (litres)
Pf
2. Dimensions
3. Hydraulic characteristics
I
Safety valve outlet
J
Heating flow and tank
K
Tank backflow (system plus)
L
Gas inlet
M
Cold water supply
N
Heating backflow
Page 5
5
4.1 REGULATIONS
PRIVATE HOMES
STATUTORY REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
Installation and maintenance of the equipment must be car­ried out by a qualified professional in accordance with cur­rent legislative texts and state of the art, including:
- law of 2 August 1977
Technical and Safety rules applicable to combustible gas and liquefied gas petroleum installations located inside buildings or outbuildings
- law of 5 February 1999 modifying the law of 2 August 1977
after replacing a boiler with an identical one (same align­ment and area as the previous equipment), the installer must make out a "model 4" certificate of conformity
- Standard DTU P 45-204 ­gas installations (previously DTU N°61-1 - Gas
Installations - April 1982 + additional clause N°1 of July
1984)
- Regional Health Regulations
Protection of the drinking water network:
• articles 16-7 and 16-8 of the Regional Health Regulations require the installation to have a CB type disconnection device with various non-controllable pressure zones, conforming to the functional requirements of French Standard NF P 43-011, to prevent heating water being returned to the drinking water network
• an NF backflow preventer is fitted in the boiler's tap fit­tings unit
French Standard NF C 15-100 - Low voltage electrical installations - Rules
PUBLIC BUILDINGS
STATUTORY REQUIREMENTS FOR INSTALLATION
Installation and maintenance of the equipment must be car­ried out by a qualified professional in accordance with cur­rent legislative texts and state of the art, including:
- fire safety and panic control regulations for public buildings:
a) General requirements
for all equipment:
• GZ articles
combustible gas and liquefied gas petroleum installations
• CH articles
heating, ventilation, refrigeration, air conditioning, steam and domestic hot water production
b) Special requirements for each type of building with
public access (hospitals, shops, etc.)
Recommendation:
if the area is exposed to the risk of lightning (isolated ins­tallation at the end of an electricity line, etc.) install a light­ning conductor
Our warranty is subject to this requirement.
4.2 BOILER LOCATION
- the centre line of the external flue duct must be placed at a distance of at least 0.40 m from any opening window and a distance of at least 0.60 m from any ventilation hole (depending on the type of outlet chosen, refer to the flue kit instructions)
- if the boiler is installed in a bathroom, comply with the spe­cial safety regulations in French standard NF C 15-100 (section 7)
- never install the boiler above hot-plates or ovens or in general over any equipment producing greasy vapours which could make the boiler dirty and affect its operation
- prepare a wall and mountings able to support the weight of the boiler (weight: approx. 35 kg)
- take precautions to reduce noise
4.3 DESIGNING AND CARRYING OUT THE INSTALLA-
TION
Domestic hot water circuit (system plus)
- Avoid excessive loss of charge in preheating circuit
- if the water hardness is more than TH 25, install a water softener
- if a non-return valve is present, a device allowing for expansion is required (available as an option)
See domestic hot water technical directive (DTU)
Central heating circuit
Circulation flow rate:
- when working out the measurements, be careful to main­tain a minimum flow rate of 300 I/h with the thermostats closed
Precautions against corrosion
Operating faults due to corrosion are likely to occur if the system is built with components made of different materials.
To prevent such problems it is advisable to use a corrosion inhibitor.
Take every precaution to prevent the treated water from becoming corrosive.
Old installation:
- fit a sediment trap to the lowest point on the return and treat the system correctly
Recommendation:
- fit bleed valves on all radiators and to high points of the installation; also fit drain cocks to low points
4. Installation requirements
Page 6
6
5.1 TYPE OF COAXIAL OUTLET (C12, C32, C42) xx
The boiler should only be installed with a fresh air inlet and smoke outlet device supplied by the boiler manufacturer. The kits are supplied separately from the boiler to meet the requirements of various types of installation. For more information about inlet/outlet accessories, refer to the accessories catalogue and the installation instructions inside the kits. The boiler is pre-equipped for connection to coaxial or twin flow air intake and burnt gas outlet systems.
Warning
The exhaust gas ducts should not be in contact with or close to inflammable material and should not pass through building structures or walls made of inflammable material. When replacing an old appliance, the gas intake and exhaust duct system will also have to be changed.
Important
Ensure that the gas intake and exhaust passages are not blocked. Ensure that the exhaust gas ducts do not have leaks.
5.2 TWIN FLOW FLUE TYPE (C12, C32, C42, C52, C82) xy
There is also the possibility of using an exhaust gas duct with separate tubes by using an adaptor on the outlet header and by inserting the tube in the air intake envisaged for this purpose. In order to use the air intake, you should:
1) Take the air intake cover off
2) Assemble the flange on the header supplied with the boiler
3) Assemble the membrane, if necessary, on the tube or the elbow
4) Insert the header on the tube or the elbow up until the lower stop (you do not have to use the washer).
5) Insert the elbow/header in the boiler air intake hole and fasten it with screws.
If the two elbows or in the same lateral direction and if you need to reduce the required space, the minimum 230 mm measurement can be reduced by carefully cutting the elbow below the air inlet by 25 mm.
Concentric outlet
60/100
Restrictor Ø 41 - 24 kW Ø 42 - 30 kW
Restrictor
ø 45
Without Restrictor
24 kW L 0.3 to 0.75 m L = > 0.75 to 2.5 m L = > 2.5 to 4 m
30 kW L 0.3 to 0.5 m L = > 0,5 to 2 m L = > 2 to 4 m
Lmax = 4 m
60/100 mm
5. Connecting gas intake and exhaust ducts
Page 7
7
In the special case where the connection is with separate tubes and with the boiler installed at a minimum distance of 6 cm from the wall, make a 10 cm ø hole, thus enabling better assembly between the fresh air elbow and the tube outside the wall (see diagram).
L = total length of air intake and burnt gas exhaust ducts. If the burnt gas flue length is over 5.5 m, install a condensate trap.
The maximum development value L, mentioned in the table includes the exhaust gas/fresh air terminal and for the coaxial system also takes into account an elbow. The C52 outlets should respect the following instructions: 1- Keep the same 80 mm ø for the gas intakes and exhaust gas ducts. 2- If you need to insert elbows in the gas intake and exhaust gas ducts, you should consider for each one the equivalent length to be included in the calculation of developed length. 3- The exhaust gas duct should jut above the roof by at least 0.5 m. 4- The intake and exhaust gas ducts in C52 cannot be installed on opposite walls of the building.
Diagrams illustrating some typical coaxial and twin flow installations. For more detailed information concerning exhaust gas ducts and fresh air intakes, consult our accessory catalogues.
Warning
If the selected exhaust gas duct is planned to be fitted with a restrictor as indicated in the corresponding tables, then the installation of the restrictor is compulsory.
5.3 FITTING THE RESTRICTOR
Concentric
twin flow
24 kW twin flow outlet Ø 41 Restrictor Ø 45 Restrictor Without Restrictor
C12, C32, C42 80/80 L = 0 to 5.5 m L = 5.5 to 21 m L = 21 to 33 m
C52, C82 80/80
Fresh air intake length 1 m.
L = 0 to 9 m L = 9 to 43 m L = 43 to 67 m
30 kW twin flow outlet Restrictor ø 45 Without Restrictor
C12, C32, C42 80/80 L = 0 to 5,5 m L = 5,5 to 20 m
C52, C82 80/80
Fresh air intake length 1 m.
L = 0 to 17 m L = 17 to 43 m
Page 8
8
- place the paper installation jig in the selected position on the wall
- fit the hanging bracket
- bring the water pipes and the electrical connection to the locations shown on the fitting template
- remove the 2 locking screws A which secure the front panel (fig. 7)
- remove the front panel
- offer the boiler up to its bracket and allow it to drop into position while pressing on it (fig. 8)
- ensure water and gas connections using the various seals required (rubber seal for gas) and position the metal filter in the heating backflow connection.
Safety valve drain hole 16 MUST be connected to a waste water pipe.
Fit the flue device according to the type of connection chosen, referring to section 5
Cleaning the appliance
Once the water has been connected, it is essential to clean the installation with an appropriate product (dispersing agent) to remove filings, solder, and various factory oils and greases.
The use of any solvent or aromatic agent (petrol, oil etc.) is forbidden.
We recommend treating the whole heating system as soon as it is commissioned to maintain a pH between 9 and 9.5.
A
Fig. 8
Fig. 7
A
6. Fitting the boiler
31. Central heating flow isolating valve and tank
32. Tank backflow (system plus)
33. Gas service tap
34. Cold water supply
35. Central heating return isolating valve
16
Fig. 9
31
32
33
35
34
Page 9
9
Location of connections:
- the 230 V supply lead and room thermostat inputs must be fitted on the wall at the height specified on the fitting template
• the boiler is supplied with 230 V by a twin and earth lead supplied with the appliance
• room thermostat (TA): prepare a free length of at least 50 cm where the TA lead meets the wall
Access to the boiler room thermostat connec-
tion:
- the room thermostat is connected behind the boi­ler control unit
Regulations:
- in accordance with the regulations, an all-pole iso­lating device with a contact opening gap of at least 3 mm must be installed in the boiler's stationary power supply installation
- the boiler must be connected to a fixed junction box using the cable supplied
230 V and earth connection via the lead provided at J1
Important: If the power supply cable is damaged, it should be replaced by the manufacturer, the after-sales service or a person with a similar status, in order to avoid potential danger.
Room thermostat connection
When it leaves the factory, the boiler is set to operate without a room thermostat: a shunt S is fitted on connector D. A room thermostat can be connected to this connector
- lower the electronic control unit by releasing the side locking pins P, to gain access to the rear side
- remove screws B and remove cover C (fig. 10)
The room thermostat connection can then be accessed.
- remove connector D
- connect the thermostat in place of shunt S
- reconnect connector D
Connector J12 shown (fig. 11), is ready to connect an optional programmer (refer to the relevant instructions if necessary).
7. Electrical connections
B
C
P
P
Fig.10
P1
A1
A2
A3
A4
B1
B2
B3
B4
E
Cylinder thermistor
System
System Plus
Shunt between 1 and 2
Shunt between 2 and 3
thermistor tank
Fig. 11
230 V 2P + E lead
Page 10
10
SETTINGS
The boiler is supplied with all the adjusting knobs set to OFF (fig. 13) and the potentiometers turned fully clockwise. It is possible to adjust these settings if required.
In that case, it is necessary to open the electronic control unit.
Switch off the boiler, remove the casing and open the unit by pressing the 2 tabs P (fig. 10). The adjusting knobs are on the electronic circuit board behind blanking cover E (fig. 11).
- A1 is used to set the Heating Anti-cycle Time (HAT) period to 30 seconds or 3 minutes
HAT: period during which restarting the burner is prohibited during a heating regulation phase
- A2 allows the speed of the pump in heating mode to be selected (high speed or adaptive speed)
- A3 is used to adjust the heating temperature setting to 40 °C whatever the position of the heating temperature adjustment knob 22 (fig. 3)
- A4 enables operation in modulating heating mode or all or nothing mode
- B1 allows the duration of post-circulation in heating mode to be adjusted
- B2 allows the domestic hot water time delay (TIC) to be adjusted
- B3 not used
- B4 not used
N.B. After a power cut or a board reset, the HAT is cancelled for 3 minutes.
- P1: potentiometer for reducing the heating power
(see table page 11)
- P2: potentiometer for adjusting the ignition power (12,7 kW - 24 FF / 16 kW - 30 FF)
- P3: not used
Once adjustments have been made, replace blanking cover E, close the control unit cover and refit the casing.
8. Operating
PRESSURISATION (fig. 12)
Heating circuit and tank:
- open cold water tap 34
- check that the heating flow 31, heating backflow 35 and tank backflow 32 taps (compy system plus) are open
- open filling tap 36
- close the tap again when the needle of pressure gauge 19 (fig. 3) is at the pressure specified in § 3
- drain the installation and re-establish the pressure
Gas circuit
- open gas tap 33
- flush the gas circuit
- check the whole gas line for leaks
Fig. 12
31
32
33
35
34
36
Page 11
11
Factory settings
Burner gas output setting
The values shown in the tables below are given for information purposes for a nominal gas distribution pressure, to allow any adjustments to the boiler heating output according to the requirements of the appliance. They cannot be used to calculate the precise regulated output of the water heater.
8. Operating (continued)
Fig.13
Adaptive speed pump
High speed pump
ON
OFF
ON/OFF operation Heating setting to 40 °C
Modulating Operation
Adjustable heating setting 35 to 85 °C
30 s anticycle
3 min anticycle
Post-circulation 30 s Post-circulation 3 min.
24 FF
Gas G20 PROPANE BUTANE
Working P.
(kW)
Pressure
plate
(mm CE)
10 25 74 55
12,7 38 117 89
16 57 182 137
20 86 276 204
24 120 390 282
30 FF
Gas G20 PROPANE BUTANE
Working P.
(kW)
Pressure
plate
(mm CE)
12 27 69 48
16 43 112 85
20 63 167 131
25 98 254 202
30 140 359 287
TIC 3 min. TIC 30 sec.
Page 12
12
Fig.15
Fitting the casing
Remove the protective film on the casing:
- offer the casing up (fig. 14)
- engage hooks N in notches R operation 1
- fit the top of the panel in place
- close the panel mounting clamps (fig. 15)
N.B. It is essential to refit the locking screw A
A
9. Fitting the casing
N
R
Fig.14
Page 13
13
When changing to a gas different from the one for which the boiler is equipped, you should replace the parts supplied with the conversion kit and adjust the gas valve in accordance with the method described below.
Adjusting the nominal output
• remove the protective cap from the adjusting screws (fig. 16).
• remove screw 2 and fit a tube connected to a pressure gaugeto the pressure connection point (fig. 16).
• start the boiler at maximum output (hot water tap on full) and maximum temperature setting.
• turn nut 3 using an 8-mm open-ended spanner (fig. 17) while holding screw 4 still and adjust the pressure to the value shown in the table
“nominal output table.”
Adjusting the minimum output
• disconnect a variable solenoid valve power supply cable (fig. 18)
• turn screw 4 using a 5-mm open-ended spanner while holding nut 3 (fig. 18) and adjust the pressure to the value shown in the table
“minimum output table.”
• when the adjustment is finished, refit screw 2 and test for leaks.
• put the protective cap back on the adjustment screws.
Adjusting the lighting power (only in FF) The potentiometer P2 (fig. 14) on the printed circuit is used for this adjustment (12,7 kW - 24 FF / 16 kW - 30 FF) (see tables page 11)
Fig.16
Fig.17
Fig.18
Nominal output
Minimun output
10. Gas conversion
mmCE G 20 G 30 G 31
24 kW FF 120 282 390
30 kW FF 140 287 359
mmCE G 20 G 30 G 31
24 kW FF 25 55 74
30 kW FF 27 48 69
Page 14
14
If the equipment has an operating fault, one or more LEDs (23) flash according to the type of fault listed in the table below.
11. Fault codes - Information
= LED off
= LED blinking
CODE FAULT INFORMATION
30 40 50 60 70 80
1
Locked - overheating.
3 Locked by ignition fault.
6 Frost protection.
7 Water circulation absent.
8 Input water circulation fault.
11 Main exchanger outlet sensor open.
12 Main exchanger outlet sensor short-circuited.
13 Main exchanger inlet sensor open.
14 Main exchanger inlet sensor short-circuited.
15
External sensor open.
16 External sensor short-circuited.
18 Disappearance of current flame.
20 Wiring fault (or 1.25 A fuse fault).
21 No extraction flow.
22
Extraction sensor fault.
28 Clima Manager "Module Counter" memory card faulty.
29 Clima Manager room sensor open.
30 Clima Manager room sensor short-circuited.
31 Fault on display board.
32 Communication problem between main boards and display.
Page 15
15
By-pass valve assembly direction
12. Particular characteristics
Page 16
16
INSTRUCTIONS FOR THE USER
13. Controls
Control panel (fig. 20)
19. - heating circuit pressure gauge
20. - ON/OFF push button and ON indicator light
21.- domestic hot water function ON and hot water
temperature adjustment knob
22.- heating function ON and heating temperature
adjustment knob
23.- heating temperature and operating fault indicator
24.- orange burner operating indicator light
25.- reset push button (reset) and red locking indicator light
Taps and valves (fig. 21)
31. Central heating flow isolating valve and tank
32. Tank backflow (system plus)
33: Gas tap
34: Cold water supply tap
35: Central heating return isolating valve
36: Filling tap
16: Heating safety valve
Fig.20
Fig. 21
20
21
23
25
22
24
19
C
(system plus)
31
32
33
35
16
34
36
Page 17
17
14. Operation
Starting up
1. check that the appliance's general gas shut-off tap is open and that the boiler is supplied with power.
2. check that there is sufficient pressure in the heating circuit: pressure gauge needle at least 1.2 bar with 1.7 bar at max. cold
3. open gas inlet tap 33 (fig. 21)
Your boiler is now ready to operate.
Important
When the appliance is operated after a prolonged period of inactivity, the presence of air in the gas flues may hinder the first
attempts at igniting the gas.
See § 20 Operating faults
To obtain heating and hot water (system plus):
Press ON/OFF button 20; the button lights up green.
- turn knob 21 to preheat the sanitary tank (compy system plus). This button allows you to adjust the hot water
temperature. While the tank is pre-heating, LEDs 23 light up 2 by 2 in sequence.
- turn knob 22 to authorise heating ignition. This knob allows you to adjust the water temperature in the heating circuit
according to seasonal requirements. Indicator 23 displays the temperature.
• Turn knob 22:
- towards Max. in cold weather
- towards Min in mild weather
Furthermore, if your home is fitted with a room thermostat, set it to the desired indoor temperature.
N.B. Orange indicator light 24 lights up every time the burner ignites
Stopping the heating
- Set knob 22 to the OFF position. The boiler then produces only hot water.
Setting to pilot
- Set knobs 21 and 22 to the OFF position, leaving button 20 (fig. 20) l it. The function remains active unless the boiler freezes.
Turn off the boiler completely
- press push button 20 and the light goes out
- turn off the electricity supply to the boiler heater.
- shut off the gas supply by turning tap 33 (fig. 21)
Note:
In certain cases of installation it is possible that, after reheating the tank (system plus), the pipes (and possibly a radiator) may heat up slightly. To prevent this, simply close heating inlet tap
31 (
fig. 21).
Remember to re-open it at the start of the heating season, when you switch the heating back on by pressing button
22
(fig. 20)
Page 18
18
This boiler is equipped with a flue gas extraction flow detection system which authorises operation of the burner. If the flow is insufficient for a prolonged period of time, the boiler shuts down for safety reasons and indicator lights (23) 40, 60 and 80 flash. Warning: this flue gas checking device must not be disconnected or have unwarranted work carried out on it.If it needs to be replaced, only original parts may be used.
Your boiler is under warranty. The warranty certificate specifies the warranty conditions: check that the detachable section of this certificate has been returned to Chaffoteaux & Maury.
A qualified professional must have installed, adjusted and commissioned your installation if you wish to take advantage of the warranty. This assures you that the fitter complied with the installation manual and that regulatory and safety conditions have been met.
Your first boiler technical inspection will be carried out free of charge at your request by a qualified Chaffoteaux & Maury tech­nical station professional.
Current legislation requires a mandatory annual service of your water heater.
Once a year, have it checked by a qualified professional.
Annual service contract formats may be suggested to you by service providers for all boiler servicing. Contact your gas fitter or our commercial services.
The manufacturer's warranty, which covers manufacturing faults, should not be confused with servicing operations.
15. Maintenance
16.
Overflow safety device
17. Warranty
18. Practical advice
• Pump degumming system
With the boiler switched on (indicator light 20 lit), the circulating pump operates for 1 minute after it has been stopped for longer than 23 hours, irrespective of the boiler's operating mode, to prevent the pump from sticking.
Precautions to take in freezing conditions
We recommend that you contact your gas fitter or After-Sales service, who will advise you of the measures to take according to your circumstances.
• Domestic hot water circuit
(system plus)
The hot water circuit is drained after closing the appliance's water counter and cold water tap:
- open a hot water tap
- Drain the tank
• Heating circuit
Take one of the following steps:
- 1) drain the circuit of the heating appliance
- 2) protect the heating installation with an antifreeze product. Periodically checking the level of protection provided by this antifreeze is an additional warranty requirement.
- 3) allow your installation to run at low load by setting the room thermostat to the antifreeze position (between 5 and 10°C).
- 4) leave the power to the boiler on. It is fitted with an antifreeze device which activates the circulation pump, then the burner.
Page 19
19
If all these actions are unsuccessful, call a qualified professional.
Fault Cause Solution
The boiler doesn’t start
No gas, no water or no electricity
Control gas, water and electrical
supply, fuses…
Air in the gas pipe Follow procedure in chapter 8
Room thermostat switched off Set up the room thermostat
Red indicator alight
Wait for a few minutes Press on reset button 25 (fig.20) the red led turn off and the boiler attempts to re­light. If red indicator alight too frequently, please call your localfaîtes service centre.
Noises in CH system
Air presence in CH system or. Insufficient pressure
Purge of air the system and rise up the system pressure (chapter 7)
19. Operating faults
Page 20
420010058000 - 09/2006
These boilers are designed to operate with natural gas or LPG. If the type of gas is changed, only a qualified professional is authorised to carry out this operation.
20. Technical specifications
Model 24 kW FF 30 kW FF
Heating power Pn
10 to 24 kW 12 to 30 kW
Variable tank pre-heating power Pn max
24 kW 30 kW
Category II 2E+3+
Fresh air flow rate required for combustion V 43 m3h. 54 m3h.
Associated BACD tank capacity 120 150 120 150
Specific domestic hot water flow rate (ΔT: 30 K) D 22,2 l/mn 24,6 l/mn 23,0 l/mn 25,3 l/mn
Minimum central heating circuit flow rate 300 I/h. 300 I/h.
Maximum heating circuit pressure Pw max
3 bar 3 bar
Adjustable heating flow temperature 35 to 85 °C 35 to 85 °C
Adjustable hot water temperature (system plus) 40 to 60 °C 40 to 60 °C
Electric voltage
230 volt, single phase
50 Hz
230 volt, single phase
50 Hz
Electrical power consumption 150 W 150 W
Electrical protection IP X4D IP X4D
Nominal gas flow rate (15 °C-1013 mbar) Gas rate max Gas rate mini Gas rate max Gas rate mini
Qn 26,0 kW 12,0 kW 32 kW 14 kW
G 20 (GN H -Lacq) 34,02 MJ/m3at 20 mbar Vr 2,75 m3/h 1,27 m3/h 3,44 m3/h 1,50 m3/h
G 30 (Butane) 45,6 MJ/kg at 28-30 mbar Vr 2,05 kg/h 0,95 kg/h 2,56 kg/h 1,12 kg/h
G 31 (Propane) 46,4 MJ/kg 37 at mbar Vr 2,02 kg/h 0,93 kg/h 2,52 kg/h 1,10 kg/h
Nat Prop Nat Prop
Feeder marking Marking NAT Gaz 135 LPG Gaz 80 NAT Gaz 130 LPG Gaz 80
Injector size in 1/100 of mm 135 80 130 80
No. of injectors 11 11 14 14
MTS sa Le Carré Pleyel 5 rue Pleyel 93521 SAINT DENIS Cedex Tél. 01 55 84 94 94 Fax 01 55 84 96 10 www.chaffoteaux-maury.fr
C
Loading...