Chaffoteaux & Maury System plus 60, System plus 40, Britony System plus Series, Britony System plus 40, Britony System plus 60 Installation And Operating Instrictions

Page 1
Heating boiler compatible with indirect cylinder
Faned Flue system
SYSTEM PLUS BOILER
Installation and
System plus 40
Operating instructions
System plus 60
u
Page 2
These instructions are suitable for the following boilers :
BRITONY System plus 40 BRITONY System plus 60
Page 3
CUSTOMER CARE Chaffoteaux et Maury Ltd , as a leading manufacturer of domestic and commerctal water heating appliances, is committed to providing high quality products and a
high qualrty after sales service If it is necessary to contact an engineer, then telephone your local Chaffoteaux Service Centre The number can be obtained from the leaflet enclosed in the customer care pack with your boiler or by telephoning the Chaffoteaux Customer Services Department at Telford.
Advrce on installatron or servicing can also be obtained by contacting the Chaffoteaux Customer Services Department at Telford CUSTOMER SERVICES DEPARTMENT
Tel 01952 222288
Fax 01952260915 GUARANTEE The manuiacturer’s guarantee IS for 12 months from the date of purchase. The guarantee is voidable if the appliance is not installed in accordance with the
recommendations made herem or in a manner not approved by the manufacturer To assist us in providing you with an efficient after sales service, please return the guarantee regtstratron card enclosed with the boiler without delay
STATUTORY REQUIREMENTS The installation of this appltance must be carried
Safety (Installatton and Use) Regulations
out by a Registered
or other competent person and in accordance requirements of the Gas
In addition, the installation must also comply with the current byelaws of Local Water Undertakings, Building Regulations, IEE Wiring Regulations, Local Authority
Building Standards (Scotland) Regulations and the Safety Document 635 The Electricity at work Regulation.
It should also be carried out in accordance with current editions of the following British Standards Codes of practice: BS 6891, BS 5440 parts 1 and 2, BS 5449 part
1. BS 7593, BS 6798, BS 5546, BS 4814, BS 7074 part 1 and 2, BS 7671 and BG DM2
If there IS a possibility of the incommg mains water pressure exceedtng IO bar then a suitable pressure limiting valve must be fitted
Precauttons. During servicing, keep the dust generation to a minimum and avoid inhaling any dust and contact with the skin and eyes. Normal handling and use will
not present any dtscomfort, although some people with a history of skin complatnts may be susceptible to irritation. When disposing of the lining, ensure that it is
securely wrapped and wash hands after contact
Page 4
CUSTOMER CARE ...............................................
Guarantee.. ............................................................
Statutory Requirements.. ......................................
Contents ................................................................
INTRODUCTION ...................................................
DESCRIPTION ......................................................
Location of components.. .......................................
TECHNICAL DATA.. ..............................................
DIMENSIONS.. ......................................................
OPERATION.. ........................................................
Domestic Hot Water Mode..
...................................
Central Heating Mode.. ..........................................
INSTALLATION REQUIREMENTS..
.....................
Location .................................................................
Flue.. ......................................................................
Ventilation ..............................................................
Gas Supply ............................................................
Electrical Supply ....................................................
INSTALLING THE BOILER
...................................
Installation.. ............................................................
Fitting the horizontal flue..
......................................
Making the electrical connections..
........................
Page
3 3 3 4 5 6 6
8 10 12 12 12 14 14 14 15 15 15 16 16 17 19
COMMISSIONING AND TESTING
........................
Pre-commissioning
................................................
Domestic Hot Water.. .............................................
Central Heating.. ....................................................
Lighting the boiler ..................................................
Post Commissioning..
............................................
Handing over to the Householder.. ........................
SYSTEM GUIDANCE..
..........................................
Showers .................................................................
Flushing and Water Treatment
..............................
System Controls ....................................................
Bypass and pump.. ................................................
Expansion Vessel
..................................................
Filling Point
............................................................
USER’S INSTRUCTIONS..
....................................
Control panel .........................................................
Isolating taps.. ........................................................
Switching on ..........................................................
Hot water ...............................................................
Heating and hot water.. ..........................................
Turn off the boiler..
.................................................
Page
21 24 21 21 21 22 22 23 23 23 23 24 25 25 26 26 26 27 27 27 27
q
.
chaffot-v
M-u
Page 5
The BRITONY SYSTEM PLUS is a fully automatic, wall mounted, low water content boiler. It is a room sealed, fan assisted, balanced flued appliance . The appliance includes a diverter valve and so can provide central heating and hot water flow for an indirect cylinder. It has electronic ignition and is suitable for use with all modern electrical control systems. The boiler is designed for sealed systems only and a circulating pump, expansion vessel together with a pressure gauge and safety valve are included within the boiler.
The standard horizontal flue kit is suitable for lengths 300 mm minimum to 680 mm maximum and includes an elbow adapter that can be rotated through 360”. The horizontal flue can be extended (refer to Flue Installation Instructions), 45” and 90” flue bends are also available as accessories.
The BRITONY SYSTEM PLUS is also suitable for concentric vertical and twin pipe flueing. Adapters and accessories are available.
The boiler is packed in three cartons:
1. the boiler,
2. the flue assembly and the pre installation kit,
3. additional accessories kit.
Page 6
Location of components
1. Air pressure switch
1
2. Steel chassis complete with expansion vessel
3. Main heat exchanger
4. Combustion chamber
5. Multi- gas burner assembly comprising ignition and ionisation electrodes
6. Automatic air separator and automatic vent
7. Heating circuit flow switch
8. Pump
9. Electrical box
11. Overheat thermostat
12. Gas valve assembly
13. Sealed chamber
14. Flue hood with fan
16. Primary circuit control thermistor
17. Three way valve
18. CH Flow isolating valve
19. Three position Selector switch
20. User’s instruction panel.
21. Heating flow temperature adjustment
22. Green indicator - Power ON
23. Orange indicator - Burner ON
24. Red indicator - Lock out /flame failure
11
9-
Fig.
-
4
-
5
-8
Page 7
25 Reset button
26. Pressure gauge
27. Gas service tap
28. Hot water flow isolating valve
29. CH Return isolating valve
30. Pressure relief valve
32. By pass
33. By pass adjustment screw
34. Location of central heating filter
33
Page 8
BRITONY SYSTEM PLUS type
40 60
Appliance category . . . . . . . . . . . . . . . . . . . . .
Cat II 2H 3+ Cat II 2H 3,
Heat input C/H & DHW
Maximum in kW .~....~.-........
13.41 20.22
Maximum in Btulh . . .._............ 45764 69005
Heat output C/H & DHW
Maximum in kW . . . . . . . . . . . . . . . . . . . .
12 18
Maximum in Btu/h . . . . . . . . . . . . . . . . .
40952 61428
C/H circuit pressures
Min operating in bar
0.7 0.7
in lb/in*
10 IO
Max operating in bar 2.5 2.5
in lb/in’
36.3 36.3
Compartment ventilation is not required
BRITONY SYSTEM PLUS type
40
Natural gas G20
Gas rate
Maximum in ma/h
................... 1.42
Maximum in ftVh
.................... 50
inlet pressure
Nominal in
mbar
.................... 20
Nominal in in wg.. .................. 8
Burner pressure
Nominal in
mbar
.................... 2.9
Nominal in in wg .................... 1.2
Burner injector diameter
Natural gas G20 in mm
........ 1.18
PROPANE L.P.G. G31
Gas rate
Maximum in kg/h
................... 1.03
Maximum in ftVh..
.................. 2.27
Inlet pressure
Nominal in mbar
.................... 37
Nominal in in wg..
.................. 14.8
Burner pressure
Nominal in
mbar
.................... 9.2
Nominal in in wg..
.................. 3.7
60
2.14 76
20 8
6.7
2.7
1.23
1.55
3.42
37
14.8
21.0
8.4
Page 9
BRITONY SYSTEM PLUS type
40
BUTANE L.P.G. G30
60
BRITONY SYSTEM PLUS type
40
Safety discharge
Gas rate
inbar.. ................. 3
Maximum in kg/h.. 1.05
1.58
in lb/in* ..................
43.5
.................
Maximum in Lb&h..
...............
2.32
3.48
Expansion vessel
Inlet pressure
Pre-charge pressure in bar . 0.7
Nominal in mbar . . . . . . . . . . . . . . . . . . . . 28 28
Pre-charge pressure in IbAn* 9.4
Nominal in in wg . . . . . . . . . . . . . . . . . . . . 11.2
11.2
Net capacity at 3 bar in liter
5.44
Burner pressure
Adjustable by-pass
Nominal in mbar . . . . . . . . . . . . . . . . . . . .
Minimum flow rate in I/h . . . 100
Nominal in in wg . . . . . . . . . . . . . . . . . . . .
Minimum flow rate in gal/min 0.36 Maximum flow rate in I/h . . . 700
Burner injector diameter
Maximum flow rate in gal/min 2.56
LPG G30 and G31 in mm . . 0.70 0.70
Electrical characteristics
Compartment ventilation not required
Supply . . . . . . . . . . . . . . . . . . 230 v
Consumption , , , . . . . . . . . . 150 w
Protection . . . . . . . . . . . . . . . IP 44
Fuse no1 . . . . . . . . . . . . . . . . 2A
Fuse no2 . . . . . . . . . . . . . . . . 1.25 A
External controls . . . . . . . . . 24 v
60
3
43.5
0.7
9.4
5.44
100
0.36 700
2.56
50Hz
15ow IP 44
2A
1.25A
24v
Page 10
Weights
With packaging :
- BRITONY SYSTEM PLUS 40 :
- BRITONY SYSTEM PLUS 60 :
Without packaging :
- BRITONY SYSTEM PLUS 40 :
- BRITONY SYSTEM PLUS 60 : Lift weight :
- BRITONY SYSTEM PLUS 40 :
- BRITONY SYSTEM PLUS 60 :
43.2 kg
43.2 kg
41.2 kg
41.2 kg
35.2 kg
35.2 kg
Tails diameter
I Safety valve outlet
015mm J Heating flow 022mm K H.W. flow 022mm L Gas supply
022mm N Heating return
022mm
Outer case dimensions :
-Width 440 (minimum space required 450)
- Height
850
- Depth 380
6
:
cent& line
All dimensions in mm
Fig. 4
Page 11
Minimum clearances :
- Both sides
5mm
- Above casing
170 mm
- Below casing 200 mm
- Front ( for servicing)
500 mm
- Front (in operation)
5 mm
TYPE Cl2 or C42
Fig. 5 Dimensions in mm
The boiler is suitable for the 3 flue types :
l
typeC 12orC42
l
type C 22
l
tvoeC32xxorC32xv
TYPE C32 xx TYPE C32 xy
Page 12
Domestic Hot Water Mode
To be able to supply hot water, the selector switch (19 fig.
6) must be in either in ,C or ‘1111 ,i position. This will be
confirmed by the green indicator light 0 (22 fig. 6).
When the cylinder thermostat is calling for heat, it
switches the 3 way valve (17 fig. 7) to hot water position. Then the hot water from the primary circuit is diverted through the cylinder coil to heat DHW.
The first stage solenoid (12a fig. 7) and safety solenoid
(12~ fig. 7) open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is
detected the orange indicator bulb (4 (23 fig. 6) will light
and the second stage solenoid (12b fig. 7) opens to allow the full gas rate.
If a flame is not detected, after 8 seconds, the security
solenoid closes and shuts off the gas. The red lockout indicator bulb & (24 fig. 6) will light.
The hot water flow temperature is controlled by the
primary circuit control thermistor (16 fig. 7).
When the cylinder thermostat is satisfied, the burner is
extinguished and the pump stops.
25
Fig. 6
‘20
The boiler will now stay in the hot water mode for three minutes. Priority will be given to a demand for reheating the cylinder. Central Heating Mode To be able to supply central heating, the selector switch (19 fig. 6)
must be in ‘1111 ,i position. This will be confirmed by the green indicator light 0 (22 fig. 6)
Page 13
When there is a demand for heating (either from the room thermostat or the external programmer) and the boiler temperature control is calling for heat. The pump starts and at a flow rate of 4 Itrlmin the central heating flow switch operates allowing the ignition sequence to begin. The first stage solenoid (12a fig. 7) and safety solenoid (12~ fig. 7) open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected the orange indicator bulb 4 (23 fig. 6) will light. After 45 seconds the second stage solenoid (12b fig. 7) opens to allow the full gas rate. If a flame is not detected, after 8 seconds, the security solenoid closes and shuts off the gas. The red lockout indicator bulb 0 (24 fig. 6) will light.
The central heating flow temperature is controlled by the central heating control thermistor (16 fig. 7). The boiler has been designed to minimise cycling and will not attempt to relight for at least 3 minutes after the boiler thermostat has been satisfied I (this MTAC delay), can be set to 30 seconds if required, see maintenance and service guide). When the room thermostat is satisfied the burner will switch off and the pump will remain
running for a further 3 minutes.
NB
It is possible to override the TAC delay by pressing the RESET
button (25 fig. 6).
Page 14
Location The boiler can be installed on any suitable internal wall.
Provision must be made to allow the correct routing of the flue and siting of the terminal to allow the safe and efficient removal of the flue products. The appliance may be installed in any room, although reference must be made to the IEE regulations if it contains a bath or shower. A compa~ment or cupboard may be used provided that it has been purpose-built or modified for the purpose. It is not necessary to provide permanent ventilation for cooling purposes. Detailed recommendations are given in BS 5440 pt 2. If it is proposed that it is installed in a timber framed building then reference must be made to British Gas Document DM2, or advice sought from CORGI.
Flue The boiler must be installed so that the flue terminal is
exposed to the free passage of external air at all times. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to. The minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc
300 mm
- B Below gutters soils pipes or drain pipes
75 mm
- C Below eaves
200mm
- D Below balconies or car port roof
200 mm
- E From a vertical drain pipe or soil pipe
75 mm
- F From an internal or external corner
300 mm
- G Above ground roof or balcony level
300 mm
- H From a surface facing the terminal
600 mm
- I From another terminal facing the terminal
600 mm
- J From an opening into the dwelling when under a car port
1200 mm
- K Vertically from a terminal on the same wall
1500 mm
- L Horizontally from a terminal on the same wall
300 mm
- M fixed by the flat roof ubbink rolux 4GM flue terminal
- N fixed by a pithed roof ubbink rolux 4GM flue terminal
Page 15
-
--
It may be necessary to protect the terminal with a guard if it is accessible and could be damaged. Reference should be made to the Building Regulations for guidance. Suitable guards may be obtained from the following maufacturer:
Quinnel Barret & Quinnel Wireworks Old Kent Road London SE15 1NL
Tel: 0171 639 1357
Ventilation
The room in which the boiler is installed does not require specific ventilation. IF IT IS INSTALLED IN A CUPBOARD OR COMPARTMENT PERMANENT VENTILATION IS NOT
REQUIRED FOR COOLING PURPOSES. If vents are installed, they must communicate with the same room or be on the same wall to outside air.
Gas Supply The gas installation and soundness testing must be in
accordance with the requirements of BS 6891.The boiler requires a 22 mm supply. Ensure that the pipe size is adequate for the demand including other gas appliances on the same supply.
Electrical Supply The appliance requires an earthed 230V - 50 Hz supply and
must be in accordance with current I.E.E. It must also be possible to be able to completely isolate the appliance electrically. Connection should be via a 3 amp fused double­pole isolating switch with contact separation of at least 3 mm on both poles. Alternatively, a fused 3 Amp. 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower. It should only supply the appliance.
Page 16
Please check that you are familiar with the installation requirements before commencing work.(section 6)
Installation The installation kit included with the flue components
comprise following items :
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances, fitting instructions and commissioning instructions)
- Connection tails
- Screws and wall plugs
- Connection washers
- Pre-piping jig
- Installation manual
Also required is the additional accessories kit r-r” 1014574 contain 15 to 22 mm bush and tail.
Method of positionning the boiler on the wall.
The paper template can be used to ensure the correct
positioning of kitchen cabinets etc. It also details the
commissioning instructions. The paper template has to be fixed to the wall and used to fix
the position of the hanging bracket, the centre for the flue hole
and, if required, the fixings for the pre-piping jig.
Drill and plug the wall and secure the hanging bracket using the screws provided (refer to the paper template drawings). Remove the boiler from its packaging as shown in fig. 13 and remove the outer case as shown in fig.14. Place the boiler on the wall on the hanging bracket after removing the pre­installation jig. If required, there is space for all piping to pass behind the
Fig. 13
Fig. 14
Page 17
boiler. Using fig. 15 for reference, connect the gas and water pipes to the valves located at the base of the appliance using the tails provided. There is a 190 mm space between the valves and the wall to make these connections.
Provision must be made to fill and recharge the system
Fig. 15
I Safety valve outlet 015mm
J Heating flow
022mm
K
H.W. flow 022mm
L Gas supply
022mm
N Heating return
022mm
pressure. This can be achieved using a filling loop or other methods approved by the local water authority. The pressure relief should terminate below the boiler over a tundish or 22 mm pipe (see I fig 15) which should in turn discharge safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
The system should be carefully checked for leaks, as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger.
Fitting the Horizontal Flue The instructions for the elevated horizontal, vertical and biflux (twin pipe) flue options are included with the relevant adapter kits,
The standard flue supplied with the appliance is suitable for lengths from 300 mm minimum to 610 mm maximum. This means for rear flueing, the standard kit will accommodate a maximum wall thickness of 490 mm, and for side flueing a maximum wail thickness of 477 mm. This takes into account the minimum appliance side clearances of 5 mm.
If the fixing is a rear exit flue, the template provides the position of the centre for drilling the flue hole with a core drill. If the flue is a side exit installation then calculate the position of the hole with a slope of 5 mm / metre to the terminal.
q
chaffoteaux~
e-U
Page 18
Connecting the boiler to the system
- Hinge down the electrical box to gain access to the valves connections. Push in the tabs (P Fig 19) on either side of the boiler and pivot the box forward.
- Remove the yellow caps from connecting pipes and connect the boiler to the taps using gaskets provided in the plastic bag.
Rubber washer “R” for gas connection. Provision must be maid to reduce as much as possible the
distance A from the cylinder coil return to the boiler and
B
should be greater than 200 mm to avoid gravity effects.
Fig 16
I return
mini
heating return
Fig 17
q
:
cygggv
U
Page 19
Making the Electrical Connections
Hinge down the electrical box to gain access to the electrical connections. Push in the tabs (P fig 19) on either side of the boiler and pivot the box forward.
Undo the two retaining screws (A fig 19), lift the cover and turn over, and remove cable clamp (see fig. 19a).
Connect the live and neutral wires to the multipin plug <CDS> (fig 20) of the PCB -Ea, leaving sufficient earth wire to connect to the earthing point. (B fig 21) Note: The connections should be made so that should the lead be pulled from its anchorage, the current carrying wires become taut before the earth wire.
Fig. 19
Fig. 19a
Page 20
-
--
Earth pillar
B
If using a room thermostat or other external control, they can be connected in place of the link on the multipin plug -Ct> (fig 20) Note: Use only controls designed for voltage free switching or 24V supply.
Socket for connector
C
Connect multipin plug c<Cbb onto into the socket on the power board. Connect m&ipin plug <CDS) to the interface PCB inside the cover (see fig. 20). Secure the cables using the cable clamp and replace the cover. To prevent damage, the cables should then be routed through the cable support on the right hand side of the chassis.
ALL
Fig. 21
Page 21
Pre-commissioning Ensure that the system has been adequately flushed.
Purge gas supply of air and test for soundness. Carry out final electrical tests to ensure the correct polarity and earthing continuity.
DHW Open the hot flow tap (28 fig. 22).
Check for water soundness. Central Heating
Open flow and return valves on the boiler.(l8 and 29 fig. 22) Open the automatic air vent (6 fig. 23) Fill system and vent radiators. Set system pressure and remove filling loop.
Lighting the Boiler
e
: -
. *
. .
: .
Fig. 22
Check for leaks.
Manually check pump is free to turn.
Connect gas pressure gauge to test point ( 43 fig. 23).
Switch on electrical supply.
Turn on the gas supply and boiler gas tap ( 27 fig. 22).
Turn selector switch (19 fig. 23) to heating and hot water
Ensure electrical supply is on.
position ‘1111 Z .
Ensure all external controls are calling for heat.
Allow pump to run for several minutes.
Isolate electrical supply. Drain boiler and check water filter (34 fig. 2) for installation
debris.
Replace filter and recharge system.
Page 22
43
19
21
,6
Fig. 23
Turn selector switch ( 19 fig. 23) to heating and hot water
position ‘1111 ,$ Turn the boiler thermostat to maximum (21 fig. 23). The boiler will light. Allow the boiler to heat system.
Check that the inlet gas pressure (working pressure) while the
boiler is operating. (refer to technical data).
Check the operation of the boiler controls and safety devices (see separate servicing leaflet for details). Re-flush the system to remove any dissolved oils and fluxes. Recharge system pressure and introduce any water treatment as required.
Post Commissioning Ensure system pressure has been set correctly.
Set the by pass. Set boiler thermostat and controls. Set programmer to householder’s requirements. Set external controls.
Handing Over to the Householder Demonstrate the lighting and operation of the boiler.
Demonstrate how to maintain the system pressure. Explain the benefits of annual maintenance by a competent person. Explain how to register guarantee.
Leave users instructions, installation manual and all other documentation with the householder.
Page 23
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 3 bar. All fittings and pipework connected to the appliance should be of the same standard.
Flushing and Water Treatment
Betz Dearborn Ltd Fernox Manufacturing
Foundry Lane Britannica Works Widnes Clavering Cheshire Essex WA8 8UD CBll 4QZ Tel: 0151 424 5351 Tel: 01799 550811
System Controls The boiler is electrically controlled and is suitable for most
modern electronic time and temperature controls. The addition of such external controls can be beneficial to the efficient operation of the system. The boiler connections for external controls are 230V and so only controls of 230V or that have voltage free contacts should be used.
la
chaffotealx~
-4LA
Page 24
By pass and Pump
The boiler is fitted with a pre-adjusted by pass. Although adjustment is not normally necessary, the by pass can be reset by turning screw ( D fig. 9 ) anticlockwise to open the by-pass using the chart below for guidance.
If used on a system with thermostatic radiator valves, the flow rate with the thermostatic valves closed should be adjusted to
at least 100 Mhr.The chart below indicates the residual head of the pump available for the system.
Fig. 9
Fig. 10
\\v vfy \p \ \ \
I I’
II II-II
D
Head and flow rate
m H20 I<- Minimum flow rate
available
5 4 3 2
1 0
0 1002003004005006007008009001wo1100
I/h
Page 25
Expansion Vessel
Filling Point
The expansion vessel is pre-charged to 0.7 bar (10 Ib/in2).
Provision must be made to be able to charge the system on
The vessel is suitable for systems up to 145 litres capacity.
commissioning and to make up any subsequent pressure loss.
For systems of greater capacity an additional expansion
The method of connection must utilise approved equipment
vessel will be required. Refer to the chart below and BS 7074
and must comply with the water regulations. A filling loop can
pt 1 or BS 5449.
be so installed as to be hidden beneath the boiler.
Pressure ’
System capacity chart
Litres
Fig. 11
Page 26
Control panel
19. Three position Selector switch l = Switched OFF
z
= Hot water only
* ‘1111 = Hot water + Central heating
20. User’s instruction panel.
21. ‘III1 Heating flow temperature adjustment
22. 0 Green indicator - Power ON
23. @ Orange indicator - Burner ON
24. 0 Red indicator - Lock out /flame failure 25 “RESET” Reset button
26. 0 Pressure gauge
Isolating Taps
18. CH Flow isolating valve
27. Gas service tap
28. Hot water flow isolating valve
29. CH Return isolating valve
25
c1
I
Fig. 25
Page 27
light and the heating will be on.
Switching on
When the heating is on, it will be interrupted while the
1) Check that the gas service tap is opened at the
cylinder is reheated. The boiler will switch back
gasmeter and main power is on.
automatically to heating when the cylinder is hot. This is
2) Check that pressure in central heating system is
normal. above 0.7 bar and below 2.5 bar with the pressure gauge 0
(26).
Note: If the boiler has been turned off for some time the
3) Open the gas tap (27) by turning from right to left. 0
first attempt to light it may result in a lockout 0 . If this
4) The boiler is now ready to use.
happens press the reset button (25) and the boiler will light.
Hot Water
1) Turn selector switch (19) to position
* . The green
To Turn Boiler Off Completely “power on” indicator 0 will light.
2) The orange “burner on” indicator P will light and the
1) Turn the selector switch (19) to the off
position l .
cylinderwill be heated.
2) Turn the gas tap (27) from left to right “STOP”.
Heating and Hot Water
1) Turn selector switch (19) to position
,C ‘1111.
The
green “power on” indicator 0 will light.
2) If the room thermostat (if fitted), the boiler temperature control ‘1111 and the clock (if fitted) are all calling for heat, the orange “burner on” indicator pI will
Page 28
Chaffoteaux et Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
o Chaffoteaux et Maury 1998
Chaffoteaux et Maury Ltd Trench Lock Trench Telford Shropshire TFl 4SZ
Tel: 01952 222727
Fax: 01952 243493
ESP 039
January 1999
chaffoteaux~
-4.A
Loading...