Chaffoteaux & Maury Sterling FF Installation And Servicing Instructions

Page 1
STERLING
Room Sealed Fanned Balanced Flue
Combination Boiler
GAS SAFETY ~INSTALLATION AND USE) REGULATIONS.
It is the law that all gas appliances are installed by a competant person
in accordance with the above regulations
(For use on natural gas only. G20)
from serial number . . . . . . . . . . . .
FF
Installation and
Senrkhg Instructions
(leave these instructions with the user)
Looking Good.Heatfng Better
Page 2
Page 3
Page No.
Health and Safety Information
1. INTRODUCTION
1.
1.1.
1.2.
1.3.
1.4.
1.4.1.
1.4.2.
1.4.3.
1.4.4.
1.5.
1.6.
1.6.1.
1.6.2.
1.6.3.
1.6.4.
1.6.5.
1.6.6.
1.6.7.
General Description, Special Features, Guarantee Dimensions Fig. 1 Technical Data Ckarances Wall Thickness Rear Flue Outlet Fig. 2 Side Flue Outlet Fig. 3, Fig. 3a, Fig. 3b Other Flue Arrangements, Horizontal Fig. 3c Vertical Flue Arrangements, Fig. 3d, Fig. 3e, Fig. 3f Fig. 3g Description of Components and Location Fig. 4 Description of Operation Central Heating Fig. 5
Hot Water Fig. 6 Gas (also see 2.7) Functional Flow Diagram Fig. 7
Safety Controls Functional Flow Wiring Diagram Fig. 8
Illustrated Wiring Diagram Fig. 9
1
2 2 3 3 3 4 4 4 5 6 7 7 7 8 8 8 9
10
2. INSTALLATION REQUIREMENTS
2. 1. General
2.2. Location
2.3.
2.4. Siting the Flue Terminal Fig.
2.5. Air Supply
2.6. Electrical Supply
2.7. Gas Supply
3. SYSTEM
3.1.
3.2
3.3.
3.4.
3.5.
3.6.
3.7.
3.8.
3.9.
3.9.1.
3.9.2.
3.10
3.11
3.12
3.13
3.14
Water Circulation System
GUIDANCE
General
System Controls Pump Fig. 11 Expansion Vessel
Mains Water Connection Filling and Recharging
Make up System Pipework
Domestic Expansion Vessel
Boiler Replacement
Existing Systems
Cylinder
Inhibitors and Water Conditioners
Add on Devices
Heating and Hot Water Systems Fig. 14, Fig. 15,
Shower Application Fig. 17a
Fig. 12, Fig. 13 (page
10
12)
Fig. 16,
Fig. 17
11 11 11 11 12 12 12
12 13 13 13 13 13 13 13 13 14 14
14 14
14
15 16
(4
Page 4
4. INSTALLING THE BOILER
CONTENTS (cant)
No. Page
General Information
4.1.
4.2.
4.3.
4.4
4.5.
4.6. 47
4.8.
4.9.
4.10.
4.11.
4.12
4.13.
4.14.
Positioning the Boiler Fig. 18 Rear Outlet Flue Fig. 19 Side Outlet Flue Fig. 20 Jig Plate Fig. 21 Gas and Water Connections Fig. 22 Water Connections Gas Connection Fitting the Boiler Fig. 23 Fitting the Safety Valve Fig. 24 Fitting the Flue (up to 700 mm long) Fig. 25 Fitting the Flue (over 700 mm long) Connection the Pressure Switch Fig. 26 Electrical Connections Fig. 27 Vertical Flue Figs. 28.28a, & Fig. 29
5. EXTERNAL CONTROLS
5.1. Programming and Zone Valves
5.2. Honeywell & Satchwell Controlled Zones Fig. 31
5.3. Frost thermostat Fig. 32
5.4. Room Thermostat Fig. 32a
17 17 17 18 18 18 18 18 19 19
19 20 20 20 21
Fig. 30 22
22 22 22
6. COMMISSIONING
6.1.
6.2.
6.3.
6.4.
6.5.
6.6.
6.7.
6.8.
6.9.
6.10.
6.11.
Hot Water Circuits. Filling Fig. 33 Central Heating Circuits, Filling, Fig. 34 G Lighting the Boiler Fig. 35 Gas Rate Adjustment Fig. 36,37 & Fig. 38 Domestic Hot Water, Flow Rate Adjustment (see also 6.7, Fig. 393) Adjusting the Heating System By-Pass Fig. 39 Domestic Hot Water. flow Rate Adjustment Fig. 39a Pump Switching Adjustment Fig. 39b Central Heating Temperature Differential Setting Adjustment Fig. 39c Fitting the Casing Fig. 40 Time Clock Operating Instructions
7. ROUTINE SERVICING General Requirements
7.1.
7.2
7.3
7.4.
7.5.
7.6.
7.7.
To Remove Front Casing Fig.41 To Remove Combustion Chamber Fig.42
To Remove Burner Assembly Fig.43 To Remove Pilot Fig.44 To Clean Heating Return Filter Fig.45 Cleaning and Replacement of Parts To Check Operation of Safety Valve Fig.46
23 23 23 24 25 25 25 25 26 26
27 & 28
29 29 30
30 30 30 30 30
(ii)
Page 5
8. REPLACEMENT OF PARTS
iZQNWXG (con0
Page No,
8.1. To Replace Electrodes Fig. 46
8.2.
8.3. To Replace Safety Overheat Thermostat 105°C Fig. 47
8.4.
8.5.
8.6.
8.7.
8.8.
8.9.
8.10. To Replace Pump Head Fig. 55
8.11.
8.12.
8.13. To Replace Air Separator Fig. 59
8.14.
8.15. To Replace Boiler Limit Thermostat Fig. 61
8.16.
8.17. To Replace High Tension Transformer Fig.63
8.18.
8.19. To Replace Solenoids Valves Fig. 66
8.20.
8.21. To Replace Fan Assembly Fig. 68
8.22. To Replace Pressure Switch (Horizontal Flue) Fig. 69
8.23.
8.24. To Re-pressurise Expansion Vessel Fig. 70 .
8.25. To Replace Pressure Gauge Fig. 7 1
8.26.
8.27.
8.28.
8.29.
8.30.
8.31.
8.32. To Replace the Thermometer Fig. 78
8.33.
8.34. To Replace Safety Valve Fig. 80
To Replace Probe Fig. 46a
To Replace Overheat Thermostat 110°C Fig. 48 To Replace Change Over Valve Microswitch Fig. 49 To Replace the Flow Switch Assembly Fig. 50 To Replace Venturi Fig. 5 1 To Replace Primary Heat Exchanger Fig. 52 To Remove Electrical Control Box Fig. 53, Fig. 54
To Replace Change Over Valve Fig. 56 & Fig. 57 To Replace Secondary Heat Exchanger Fig. 58
To Replace Thermistor Fig. 60
To Replace D.H.W. Thermostat Fig. 62 To replace Printed Circuit Board Fig. 64, Electrical box layout Fig. 65
To Replace Heating Body Linings Fig. 67
To Replace Pressure Switch (Vertical Flue) Fig. 69a
To Replace the Domestic Expansion Vessel Fig. 72 To Replace Main Burner Fig. 73 To Replace Burner Manifold Assembly Fig. 74 To Replace Expansion Vessel Fig. 75 To Replace Viewing Window Fig. 76
To Replace Main Gas Valve Body Fig. 77
To Replace the Time Clock Fig. 79
31 31 31 31 32 32 32 33
33 34 34 34 35 35 36 36 38 37 38 38 38
39 39 39
39 40 40 40 41 41 42 42 42 43
9. FAULT FINDING
9.1.
9.2.
9.3. Domestic Hot Water Operation
9.4. Fault Finding Tabular Chart SHORT SPARE PARTS LIST
Logic Sequence Central Heating Operation
44 45 46 47
Rear cover
(iii)
Page 6
Page 7
CONTROL OF SUBSTANC-RMFUJ, TO w
To comply with the Control of Substances Harmful to Health Regulation 1988 we are required to provide information on the following substance that is contained in this appliance.
Descriution platerial Precautionq
Combustion Chamber Lining Alumino Silicone Fibre During servicing, keep the dust generation to a minimum and avoid
inhaling any dust and contact with the skin and eyes. Normal handling and use will not present any discomfort, although some people with a history of skin complaints may be susceptible to irritation.
When disposing of the lining ensure that it is securely wrapped and wash hands after contact.
Page 8
The STERLING FF is a wall mounted, low water content
fanned balanced flue appliance suitable for central heating and hot water via a non storage water to water heat exchanger. The maximum output is 23 kW (78480 Btuih). The boiler is designed for sealed systems only and included in the appliance are the expansion vessel, circulating pump, temperature and pressure gauges, safety valve, electric connection box, domestic expansion vessel and time clock.
1) The standard flue assembly supplied with the boiler is
100 mm (4 in) dia pipe, can be directed to the rear or to the lef or right and can be extented to a maximum length of 3 m, or 1.6 metres horizontally using the available 90” bend (see sections 1.4.1, 1.4.2 and 1.4.3 figures 2. 3, 3a, 3b, 3~).
2) Vertical flue option (see section 1.4.4.).
Guarantee
The manufacturer’s guarantee on this appliance is for 12 months from the date of purchase. The guarantee is void, if the. appliance is not installed in accordance with the recommendations made herein.
1.1 DIMENSIONS
Special features include :
-Output to central heating fully range rated between l/3 and full output.
-High efficiency.
-Special jig plate enabling all pipework to be
installed before installiig appliance.
-Independent control over central heating flow
temperature and hot water.
-Fully adjustable central heating flow temperature.
-regulation between 40” C and 82” C.
-High limit thermostat for both boiler and hot water.
-Water flow switch to protect appliance.
-Suitable for showers with compatible mixer valves.
- 7 day programme time clock.
~\_
B
c ’ --
I\
t-1
---
---- -
2%
_--
-1 -2
r-
‘KI
w
I ; I
1 I
+
LI
1 L
.,- -. ,
X-3
-I
--+
I
REAR OUTLEl
/ -f
~
_-
SIDE OUTLET
1
mm
A
B C D E F
G
H
J
K L M N P
R
S T
820.5
391.0
365.0
100.0
169.5
654.5
43.0
50.0
75.0
260.0
150.0
972.5
13.0
61.0
30.0
152.0
112.0
-7
in
32.3
15.4
14.4 4 61‘1
25.7
1.7
2.0
3.0
10.2
6.0
38.3
0.5
2.4
1.2
6.0
4.4
Fig.1
2
Page 9
1.2 Technical Data
1.2
1.3
Hot water
Input . .._....................................... 28.90 kW 98612 Btulh
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.00 kW 78480 Btulh
Water flow raised 45 “C (81 Water iIow raised
35 ‘C (63 “F) .............................. 9.5 Vmin
Water flow raised
30 “C (54 “F). ............................. 11.1 Ymin
Maximum temperature.. ............. 60 T
Maximum pressure.. ................... 10 bar
Minimum working pressure.. ...... .6 bar
Gas rate ...................................... 2.743 m3/h
Burner pressure .......................... 11.8 mbar
Central heating
Maximum input.. ........................ 27.64kW 94313 Btti
Maximum output.. ...................... 22.00 kW 75068 Btti
Gas rate (maximum) ................... 2.63 m3/h 92.98 @lh
.lrner pressure.. ........................ 11.2 mbar 4.5 in wg
.,rinimum input
Minimum output.. ....................... 7.64 kW 26062 Btu/h
Gas rate (minimum)
Burner pressure.. ........................ 1.5 mbar 0.6 in wg
Minimum flow rate
Maximum pressure.. ...................
At the maximum pressrrre loss of the fiue Temperature of the products of
combustion : . . . . . . . . . . . . . . . . . . . . . . . . . 98 T 208 OF
The CO content of the dry free air
products of combustion : . . . . . . . .
Manifold injectors 14 of . . . . . . . . . 1.28 mm 0.05 in
Gas section restrictors 213 valves
"F)
.............................. 7.4 I/min
...........................
................... 1.0 m3/h
..................... 300 lib 1.1 gal/min
l/3 valve.. .... 2.3 mm 0.09 in
security valve ...... no restricior fitted
10.85 kW 37020 Btuih
2.5 bar 36.5 psi
0.0136%
Natural gas
4.4 mm 0.17 in
1.7 ga.I/min
2.1 gaI/min
2.5 gaI/min 140 OF
150 psi
9 psi
96.87 fi3h
4.7 in wg
35.31 ft3/h
Connections Gas
..............................................................
Heating flow Heating return.. Mains cold water inlet.. Hot water outlet..
Electrical supply 240 V - 50 Hz, fused at 3A.
Electrical consumption . . . . . . . . . . . . . . . . . .._.............
Internally fused, two at 2A (BS 4265)
Weight . . . . . . . . . . ._.._.._........_....... . . . . . . . . . . . . . . . . . . . 42 kg
Water capacity . . . . . . . . . . . . ._.,. . . . . . . . . . . . . . . . . . . . . . . . . 4 Iitres
Ignition - ANSTOSS continuous spark generator Ignition electrode - SAPCO Ignition probe - SAPCO
Thermistor - SIEMENS Boiler fiiit thermostat - SOPAC /JAEGER (85X) Hot water limit thermostat - SOPAC /JAEGER (57°C + 3°C)
Safety overheat thermostat (TOKOSWHCH - (105°C)
Overheat high- Iiit thermostat (TOKOSWITCH - (1lO’C)
Gas valve - AEMF Fan motor - SEL Pressure switch - DUNGS 88 Pa I 49 Pa Pump head - GRUNDFOS UP 15/60
I
C.H. expansion vessel initial charge pressure - 0.65 bar (9.6 psi) Domestic expansion vesseI initii charge pressure .
................................................
............................................
................................
.........................................
(manual reset)
(automatic reset) (ELMWOOD - (105’C)
(ELMWOOD
22 mm copper 22 mm copper 22 mm copper
15 mm copper 15 mm copper
195 watts
92.4 lb 7 pints
2 bar (30 psi)
3
1.4
Minimum clearances around Boiler
Top above air duct . . . . . . . . . 50 mm (2 in)
Bottom below case. . . . . . . . . . 150mm (6in)
. . . . . . . . . . . . . . . . . . . . . . 100mm (4in)
Sides
Front. . . . . . . . . . . . . . . . . . . . . . . . . .
6OOmm(24in)
Wall Thicknesses
The standard fIue assembly can accomodate the folrowing thicknesses.
Rear : from 55 mm to 576 mm Side : from 55 mm to 392 mm (this allows for a minimum dearance of 100 mm between the appliance and the side wall. As this dimension increases, so the maximum side waII thickness available decreases). Extension flue assemblies are available to accomodate waII thicknesses of:
Rear : from 577 mm to 2876 mm Side : from 393 mm to 2692 mm See figs. 2 and 3 for details of number of extensions required. IMPORTANT NOTE : The extension ducts supplied. up to a maximum of 3, wiII in fact permit a greater length than
indicated to be covered. The ducts MUST be cut so that the maximum length from the centre Iine of the flue turret to the outermost point of the air duct DOES NOT EXCEED 3 metres horizontal. Greater length must not be used.
See sections 1.4.1. 1.4.2. 1.4.3.
3
Page 10
Rear Flue Outlet Hobontal
should not exceed 1.6 metres
REAR OUTLET ASSEMBLY
To cut flue assembly to length
- Measure wall thickness (T).
- Add 74 mm, tthis will give required lentgh Q.
- Mark plastic air duct for length (L) and cut off surplus (from plain end).
N.B. If extension sections are used ensure these are fiily pushed together, see figs. 3b and 3c and a fall of 5 mm per metre length should be provided (see section
- Cut off same amount from aluminium flue duct
Flue extension accessory Part No. 62823.00
(G.C. 264459)
(1 metre length)
1.4.2
‘ig. 2
Side Flue Outlet Horizontal
Fig. 3
Fig. 3a
SIDE OUTLET ASSEMBLY
PLASTIC AIR DUCT
internal
To cut ffue assembly to length
- Measure from external wall face to centre line of STERLING FF and substract 37 mm (this will give required length “L”).
- Cut
off
surplus i?om plastic air duct (plain end).
N.B. If extension sections are used ensure these are filly pushed together, see figs. 3b and 3c and a fall of 5
- Cut off same amount from
I
Other Flue Arrangements Hotizontal
Fig. 3c
1. Distance from internal comer 300 mm without kit,107 mm with kit No 76216 (GC No 264 833).
2. Distance below balconies or eaves 200 mm without kit, 107 mm with kit No 76216 (GC No
264833).
3. Appliance is normally supplied packed with standard 650 mm staight flue section. Additional straight extension lengths of 1 metre, part No 62823 (GC No 264 459), can be use up to a total straight length of 3 metres. It is also possible to incorporate one bend in the flue using part No 65572 (GC No 264 835). In this case the length Ll + 12 should not exceed 1.6 metres horizontally.
4
Page 11
1.4.4 Vertical Flue Arrangements
a) Straight ffue (fig. 3 d)
1) Adaptor.
2) Extensions (9.5 m maximum).
3) Roof flashing.
4) Terminal.
6) Reducer.
Fig. 3 d
b) Flue with two 45O bends (fig. 3 e)
1) Boiler adaptor.
2) Extensions (8 m maximum).
3) Roof flashing.
4) Terminal.
5) 45’ bend.
6) Reducer.
Fig. 3 e
--I
Fig. 3 g
5
c) Flue with four 45’ bends (fig. 3 f and 3 g)
1) Adaptor.
2) Extensions (6 m maximum) tig. 3 f and 3 g including horizontal (2 m maximum) fig. 3 f.
3) Roof tlashiig.
4) Terminal.
5) 45’ bends (x 4 maximum) fig. 3 f and 3 g.
6) Reducer.
With the exception of (3) roof fIashing and (4)
terminal, all other fittings are designed for interd installation only.
N.B. In these two arrangements tigs. 3 f and 3 g, the total length of straight extensions m not exceed 6 meters with a maximum of 4 x 45” bends.
Horizontal run & not exceed 2 meters.
Page 12
1.5 Description of Components and Location
1
2
6
3
35
27
-
10
-
2i 22 20 31 19 23 17 18’25
Fig. 4
The appliance is mounted in a steel case which has a white epoxy resin paint finish.
1. Chassis: The chassis is a rigid plated mild steel pressing on which all components are mounted.
2. Flue hood: Is an aluminium alloy casting onto which the fan is
mounted.
3. Combustion chamber: This is assembled from a number of components
mounted onto the chassis. The front panel is simply removed for servicing complete with the expansion vessel, a hook is fitted below the appliance to accept and retain the panel during servicing.
4. Expansion vessel: The expansion vessel has a capacity of 5.4 litres (1.19 gal)
and is sized for a normal system water content where the load is equivalent to the maximum output of the boiler.
The charge pressure is 0.65 bar.
5. Flame supenrision device (not illustrated).
6. Multigas burner comprising: stainless steel blades (14) and a manifold with injectors (14).
7. Gas section including two stage solendid valves and security solendid valve.
6. Secondary heat exchanger : The secondary heat exchanger is a plate type heat
exchanger. A thermostat is fitted on the pipework limiting the domestic hot water temperature to a maximum of 57 f3” c.
9. Change over vaIve : The valve is activated by a demand for domestic hot
water, closes the heating circuits, and directs water to the secondary heat exchanger.
fO.EIectriciaI box containing : Mains connection Fuses Printed circuit boards Connections for external controls Connections for fan, pressure switch and flow switch
Connections for pump Connections for change over valve and for gas solenoid
valve
Indicator LEES.
.ll. Solenoid valve :
Block on which 4 valves are mounted :
l/3 valve - 1 st stage valve-heating and hot water (blue) 2/3 valve - full output to hot water (black) 2/3 valve - (variable valve) central heating (orange) Security valve (grey).
12. Grundfos pump motor
13. Air separator and vent directly connected to the pump
inlet (not illustrated).
14. Regtdation screw to adjust output to heating (2/3
valve).
15. Heating body compristig :
Copper finned tube heat exchanger protected with silicone resin paint. Combustion chamber in aluminium coated steel. Combustion chamber lining - ceramic fibre panels.
16. High limit thermostat (manual reset).
17. Water service tap (not illustrated).
18. Flow isolating valve - heating (not illustrated).
19. Gas service tap (not illustrated).
20. Domestic hot water outlet with regulator (not illustrated).
21. Safety valve with drain tap (not illustrated).
22. Heating return isoIating vaIve with filter (not illustrated).
23. Indicator LEDS.
24. Thermometer indicating boiler flow temperature.
25. Manual lock out reset.
26. Selector switch - hot water or&/OFF/heating and hot water.
27. Adjustment to regulate heating tlow temperature.
26. Pressure gauge.
29. Pressure switch (not illustrated).
30. Domestic expansion vessel (not illustrated).
31. Water flow switch (not illustrated).
32. Tiie clock.
33. Fuses.
34. Data badge position.
35. Control thermistor.
6
Page 13
~6 Descdption of Operation
1.6
The STERLING FF a is combination boiler providing central heating and hot water. Hot water is provided on a demand basis. For the duration of the demand for hot water the central heating is interrupted. The appliance operates in two modes. A hot water only
setting where it operates only on hot water demand and a hot water + central heating setting providing central heating and switching to hot water on demand.
1.6.1 Central Heating
The pump (21) circulates water which returns to the
boiler via the return valve (31) which incorporates a
filter (30) Before reaching the pump it passes through
an air separator and air purger (17). The return water
passes through the heat exchanger (2) where it is
heated. It then passes through the change over valve
(19) which in heating mode is in its rest position and
out via the flow valve (27) to the radiator circuits (34).
An expansion vessel (13) is fitted in the primary circuit.
Temperature control is by means of a temperature
sensing thermistor and potentiometer. These signals are fed to a comparitor. When the flow approaches the set temperature, the variable gas valve is closed and the boiler continues to
fire on l/3 soleno?d valve (11). When the set
temperature is reached, the boiler switches off. If
flow temperature reduces, the l/3 solenoid valve
opens followed by the variable solenoid valve (10).
Temperature adjustment is between a minimum of
40°C approx. and a nominal maximum of 82°C.
The boiler is protected by high limit thermostats (4) and
(see fig.
5)
(38) the operation of which interrupts the electrical supply to the security solendid valve and extinguishes the burner.
1.6.2 Hot Water
When there is a demand water flows in from the cold mains supply (26) through the water section part (35) of the change over valve (19). The inclusion of a venturi (24) produces high pressure under the diaphragm (23) causing it to rise. This movement is transmitted to the change over valve closing the heating port and opening the hot water port, as shown (20). The primary water heated by the boiler now passes through the water to water heat exchanger (18) where it flows through alternate plates indirectly heating the DHW.
The rising of the change over valve spindle causes :
1. The opening of a microswitch stopping the pump. This circuit is remade by a second microswitch making when the hot water port is fully open.
2. The by-passing of the boiler thermistor brings the boiler under control of a fixed temperature thermostat
(32) which operates on the 23 fmed solenoid (12).
The D.H.W. flow rate is adjustable by a restrictor (25) and
a liiiting thermostat (32) reduces the gas rate when the domestic hot water reaches 57’C by interrupting the electrical supply to the hot water solenoid (12).
If the primary circuit reaches 85°C the limit thermostat (16) closes both solendids valves.
A domestic expansion vessel is fitted in the D.H.W. circuit
(see fig. 6)
(36).
Central Heating
17
I ILL
/I----.-.
3, ----lO.ll-
T
16
11 -111
IL 'I IL- I"
L*-l
‘---q ,*
16
Hot water
1
16
30
31
Fig. 5
27
27
Fig. 6
7
Page 14
1.6.4
1.6.5
Gas
(see figs. 5 and 6)
When the main gas tap (33) is turned to the on position gas is admitted to the gas section (7).
When there is a demand for heating or hot water, the
security solenoid valve (9) and the l/3 soleno’id valve
open together, which allows gas to pass to the burner.
Srrnultaneously the hight tension transformer is energised and produces a stream of sparks from the ignition electrodes (3) whitch light the main burner.
The flame supervision (5) is controled by ionisation
circuit.
r:
FUNCTIONAL FLOW DIAGRAM
Summer
If the main burner is not established after 5 seconds, the boiler falls safe to lock out and has to be reset manualy.
There are 4 solenoid valves : the right hand (grey) valve (9) is the security valve, the blue valve (11) fixed at l/3 of max rated output, the hot water (black) valve (12) fixed at 2/3 of maximum rated output, the left hand central heating (orange) valve (10) which is variable up top 2/3 maximum rated output.
The gas admitted by the orange valve is varied by adjuster
(6)
(see section 6.4).
D.H.W.
OFF
High Limit
-+ Stat + Pump --+ Flow
Water
Switch 2
I i-l
(manual reset)
I
Fan ON
113 gas
Security -
5” lockout time
no
I
85°C Limit
Thermostat
105 / 110°C High Limit
Thermostats
2l3 Orange
Solenoid
Thermistor
I+
F
-ig. 7
L
1.6.6 Safety Controls
In addition to the normal safety controls the STERLING FF incorporates the following feature.
Should the central heating water flow reduce to below 3OC’ Uh (1,l gal/min) the gas supply to the burner is turned 01 via the flow switch (No.31 - page 6). see figs 5 & 6 (37).
8
Page 15
1.6.7 FUNCTIONAL FLOW WIRING DIAGRAM
1.6.7
PRESSURE
WATER FLOW
BOILER
POTENTIOMETER
HEATING
bk
9e Y
L 3A L
­L-l
LINK or EXTERNAL
-......-,. _I.”
INTER SWITCH bk
2A 2A h­Y-
PRINTED CIRCUIT BOARD
,-CHANGE OVER VALVE,. .
MICROSWITCHES :
STAT -
HIGH LIMIT
SECURITY (2)
RESET
SWITCH
N N
k
P
BOILER
THERMISTOR
HEATING
-w w ^C^. .-.-I
rzl
w
r
SkG”Hl I I
SOLENOID
VALVE
IGH RATE
IGNITION ELECTRODES
FLAME SUPERVISION
1
I
Fig. 8
b = blue bk = black br = brown ge = green gr = grey or = orange r = red v = violet w = white y = yellow
9
Page 16
1.6.8 ILLUSTRATED WIRING DIAGRAM
FAN
\MESUPERVlSlON 11 , 1
HIGH LIMIT
THERMOSTAT 110”
BOILER THERMISTOR HEATING
240V
50Hz
I
I
L
N
I
Ph
1
EXTERNAL CONTRO
II
ROOM TH
- -
III II II
I
r
UJ
s
II
WATER FLOW SWITCH
I
BOILER POTENTIOMETER
HEATING
---
SELENOID VALVE
-ig. 9
.
HIGH TENSION
II
.,” TRANSFORMER -
ALL CABLES ARE 240V EXEPT WHERE THEY ARE INDICATED 24V
SELECTOR SWITCH t+#-.~ 11
1
tn “AL”q./- ORI!
I-
1111
10
Hki LlMlT (MANUAL RESET) 105”
SECURll-Y
Page 17
2
2.1
2.2
INSTALLATION REQUIREMENTS General
The installation of the boiler must be in accordance
with Gas Safety (Installation and Use) Regulations,
Building Regulations and current Byelaws of the Local Water Undertaking. It should be in accordance also with the current BS Codes of Practice and the British
Gas Specifications for Domestic Wet Central Heating
Systems and any relevant requirements of the local
Gas Region and Local Authority Building Standards
(Scotland) Regulations and the Safety document 635
the Electricity at Work Regulation. Detailed recommendations are stated in the following
British Standard Codes of Practice: B.S. 6891, B.S. 6798, B.S. 5440 : 1 and 2, B.S. 5449: I,
B.S. 7593, BS 5546B.G.DM2, B.S. 4814. B.S. 7074 1 e 2, B.S. 7671.
Note : Gas Safety Installation and Use Reg. It is the law that all gas appliances are installed by competant persons in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure compliance wlth the law.
Location
The boiler is not suitable for external installation. The position chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also permit adequate space for servicing and air circulation around the boiler. The surface on
which the boiler is mounted must be of non
combustible material.
The boiler may be installed in any room or internal
space although particular attention is drawn to the
requirements of the current B.S. 7671 and, in
Scotland, the electrical provisions of the Building
Regulations applicable to Scotland, with respect to the installation of a heater utilising mains electricity in a room or internal space containing a bath or shower. Where the installation of the boiler will be in an unusual location special procedures may be necessary and BS 5546 gives detailed guidance on this aspect. A compartment used to enclose the boiler must be designed and constructed specifically for this purpose.
An existing cupboard or compartment may be used
provided that it is modified for the purpose. Details of essential features of cupboard/compart­ment design are given in BS 6798.
2.3
2.4
Water Circulation System
The STERLING FF is suitable for SEALED SYSTEMS ONLY and should be installed in accordance with the relevant recommendations given in BS 6798, BS
5449:l (for the smallbore or/and microbore systems) and the British Gas Specifications for Central Heating Systems.
Sitfng the Hue Terminal
Refer to section 1.4 for details of wall thicknesses which can be covered.
Detailed recommendations for flueing are given in BS 5440 Pt 1. The following notes are intended to give general guidance.
The boiler must be installed so that the ffue terminal is
exposed to external air. The boiler must NOT be installed so that the terminal discharges into another room or space e.g. outhouse or closed in lean-to. It is important that the position of the terminal allows a free passage of air across at all times. The miniium
acceptable clearances from the terminal to obstructions and ventilation openings are specified below (fig. 10).
Horizontal Flue Terminal positions A - Directly below an opening, windowsetc
or adjacent to an opening . . . . . . . . . . . . . . . . . . . .
B - Below gutters soil pipes or drain pipes . . .
C - Below eaves . . . . . . . . . . . . . . . . . . . . . . . . ..200
D - Below balconies or car port roof . . . . . . . . . . . . 200 mm*
E - From a vertical drain pipe or soil pipe . . . .
F - From an internal or external corner _....... 300 mm*
G - Above ground roof or bs.lcony level . . . . . . . 300 mm
H - From a surface facing the terminal. . . . . . . . 600 mm
J - From an opening in the car port
(e.g. door or window) into dwelling . . . . . . . . 1200 mm
K - Vertically from a terminal on the same
wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
L - Horizontally from a terminal on the
same wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
* ( 107 mm) minimum clearance using kit No. 76216.CK)(G.C.264833)(seesect.h 14.3,fig.3c)
Vertical Ffae Terminal positions
M - Above intersection with Roof . . . . . . . . . . . . . . . .
Mii clearances
300 mm
75 mm
mm*
75 mm
mm
300 mm
Min clearances
150 mm
Fig. 10
L
11
Page 18
BUILDING REGULATIONS excerpt. Approved document J Part B 1.4 (C) (D).
C) Protect with a terminal guard fitted centralIy over the terminal if it could come in contact with people near the building or be subjected to damage.
D) Designed so as to prevent the entry of any matter which might restrict the ffue. (A terminal guard G.C. No 381 782 is available from).
Quinnel Barret & Quinnel Wiieworks Old Kent Road London SE15 INL Tel. 071-639-1357
The air inlet/outlet duct and the terminal of the appliance must not be closer than 25 mm (1 in) to any combustible material . Detailed recommendations on the protection of combustiable material are given inBS5440Pt 1.
IMPORTANT NOTICE : TIMBER FRAMED HOUSES IF THE APPLIANCE IS TO BE FITTED IN A TIMBER
FRAMED BUILDING IT SHOULD BE FITTED IN
ACCORDANCE WITH THE BRITISH GAS
PUBLICATION - “GUIDE FOR GAS INSTALIATIONS IN
TIMBER FRAMED HOUSING” reference DM2. IF IN
DOUBT, ADVICE MUST BE SOUGHT FROM THE LOCAL REGION OF BRITISH GAS OR C.O.R.G.I.
2.5 Air Supply
The room in which the boiler is installed does not require a purpose provided air vent. If the boiler is Installed in a cupboard or compartment permanent air vents are required in the cupboard or compartment, one at high level and one at low level either direct to the outside air or to a room. Both high and low level air vents must communicate with the same space.
Position of vents Air fivm room Air direct fivm outside
High level Low level
2.6
Elect&al Supply
- This appliance must be earthed.
- All wiring externaI to the appliance must conform to the current B.S. 767 1.
- The STERLING FF requires a 240 V - 50 Hz supply.
- Connection of the appliance and any system controls to the mains supply must be through a common isolator and must be fused at 3A maximum. This should preferably be an unswitched shuttered socket outlet and 3 pin plug to BS 1363. AltemativeIy, a double pole isolating switch may be used, provided it has a minimum contact separation of 3 mm in both poles. The isolator should be clearly marked showing its purpose, preferably positioned close to the appliance.
-Fuse the supply at 3A.
-The suppIy cord must be 0.75 mm2 (24 x 0.2 mm) three core to BS 6500 Table 16.
261 cm2 (40 in2)
261 cm2 (40 in2) 130 cm2 (20 In2)
130 cm2 (20 in2)
2.7 Gas Supply
The STERLING FF requires:
2.743 m3fh (96.87 A3/h) gas Ilow. The meter and supply pipes should be capable of
delivering this quantity of gas in addition to the demand from any other appliances in the house.
The complete Installation must be tested for
soundness as described in BS 689 1.
3

SYSTEM GUIDANCE

3.1 General
The low water content STERLING FF boiler indudes
the expansion vessels. safety overheat thermostat, temperature and pressure gauges, and safety valve.
The flow temperature is adjustable and gives a
nominal 82 ‘C (180’ F) on its maximum setting.
When the appliance is connected to a vertical flue. the
temperature adjustment must not be set below the midway position.
Detailed recommendations for water circulation are given In BS 5546. Whilst the boiler provides hot water, there may be occasions when a cylinder wiU be used, for instance, if the property has two bathrooms. Detailed recommendations of this application are given in sections 3.13. Thermostatic control should be used in the heating circuits and the cylinder if one is fitted.
It must be remembered that a combination appliance has a limited volume of hot water that can be supplied at any one time for a given temperature. Indeed in most respects it is equivalent to a multipoint water heater and many of the contraints associated with multipoints apply equally to combination boilers.
The appliance has two separate functions, to provide heating and hot water on demand. It can have a third which is to supply hot water high demand through the use of an Indirect cylinder, where there is more than one bathroom or if the standard and appointments of the property, such as basins in all bedrooms and a large kitchen indicate a high usage of hot water.
Hot water produced IndiiectIy through a cylinder can be used to satisfy high simultaneous demand outlets ­bathrooms etc, whilst the benefits of high effciency in generally small quantities of hot water, can be fully utilised in kitchens, cloakrooms and so on.
Separate time and temperature control over hot water generated in this way can be achieved by the use
either of two port valves or three port valves of a flow share or priority pattern.
It is also possible, where the occupation of the house is variable, to provide either for a small or large load.
This is best achieved with a taII, small diameter cylinder.
See section 5 for possible wiring arrangements.
A domestic expansion vessel is fitted to the boiler with
a capacity of 0.16 litres. prior to the secondary heat exchanger which enables the boiler to be connected to a cold main water supply containing a non-return valve or any device containing a non-return valve.
12
Page 19
IF THE MAINS COLD WATER SUPPLY IS IN EXCESS OF 10 BAR (150 PSI) A PRESSURE LIMITER MUST BE FITTED TO AVOID EXCESSIVE PRESSURE BEING APPLIED TO THE BOILER.
When replacing an existing cylinder storage system
with STERLING FF it is essential that all redundant pipework is removed and dead legs eliminated,
In properties where there are multiple draw-off Points on different levels consideration should be given to the use of non-return valves in the secondary hot water system to avoid “active dead legs”. No non­return valve should be less than 1 m (3 It) above the top of the appliance and ideaIIy should be as close as possible to the hot water outlet.
3.2 System controls
The boiler is electricaky controlled and is suitable for most control schemes currently available including thermostatic radiator valves and motorised valves.
When using motorised valves the controls should be arranged to switch off the boiler when circuits are
satistield. The boiler requires a mink-num flow rate of 300 L/h (1.1 gaI/min) and consequently, if thermostatic radiator valves are fitted to alI radiators, a by pass will be necessary. This will ensure that the boiler will operate correctly when all TRVs are closed.
(see fig. 17).
3.3 Pump
The boiler is fitted with a Grundfos UP.15160 pump
head. The graph (fig. 11) indicates the residual head
available for the system.
flow rate in g.p.m.
6
At the design flow temperature and the initial system pressures quoted the maximum allowable system volume is 75 Iitres.If the water volume is not known
and cannot be accurately assessed from
manufacturers data the following volumes may be
used to give a conservative estimate of the system
volume.
Boiler.. . . . . . . . . . . . . . . . . . . . . . . . . . . ..,.... . . . . . . . . . . 4 litres
Small bore pipework . . . . . . . . . . . .._.__... 0.3 litres (0.07 gals)
Microbore pipework. . . . . . . . . . . . . . . . . . . . . . . . . .7
Steel panel radiators
per 0.292 kW (1000 Btu/h) of system output
Hot water cylinder . . . . . . . . . . . . . . . _.. .2
If the volume exceeds 75 Iitres an additional vessel wilI be required fitted In the flow from the appliances. Refer to BS 7074 Pt. 1 or BS 5449 for details of sizing.
3.5
Mains water connection
There shall be no permanent connection to the Heating System Pipework for filling or replenishing without the approval of the Local Water Authority (see Byelaw No.14 and figs. 12 and 13).
3.6
Fdlhg point
Filling and recharging can be done :
1) Through a temporary hose connection to mains
water. A stop-valve should be fitted to the service main outlet
and a double check valve assembly and stop-valve
should be fitted to the system side of the temporary
hose (see fig. 12).
2) A cistern used for no other purpose connected to
the mains water. The static head provided by the
cistern m be sufticient to satisfy the designed Initial system pressure. The supply pipe from the cistern should include the double check valve assembIy and stopcock (see tig. 13).
3.7
. . . . . . . . . . . . . . . . . . . . . . 2.3 litres
(see
Bs
5449)
litres (0.44 gals)
Make up system
(0,8 gals)
per 0.292 kW
(1.5 gals)
litres
(0.5 gals)
Fig. 11
flow rate in litres/hour
3.4 Expansion vessel
The expansion vessel which is fitted on the front of the combustion chamber accomodates system water expansion. The vessel has a capacity of 5.4 litres
(1.19 gals) and is charged to a pressure of 0.65 bar (9.7 p.s.i.).
THE CONNECTION IN THE CENTRE OF THE EXPANSION VESSEL IS A CHARGING AND NOT A VENT POINT.
13
Provision must be made for replacing water lost from the system indicated by a reduction in pressure shown on the pressure gauge. Recharge through the ftiing point (see section 3.6).
3.8 Pipework
Pipework can be of copper or suitable plastic, small bore or microbore with capillary or compression
jointing to a high standard. Leak sealant must not be
used in the system.
3.9 Domestic expandon vessel
The expansion vessel which is fitted on the cold water
supply to the secondary heat exchanger accomodates domestic hot water expansion. The vessel has a capacity of 0.16 litres (0.035 gals) and is charged to a pressure of 2 bars (30 p.s.i.) ; it has a maximum
working pressure of 10 bars with an allowable
pressure peak of 14 bars.
Page 20
Air inlet
valve
Fig.
12
Double check valve assembly
valve
Test cock
(a) Non-automatic filling and make-up. Temporary hose filling loop avaible, Pt.No.CHL.112
Hose
pion;y-++ zE
@+P
j j
jj
I’ \~-zd!
Te;irgw
Overflow
%o be located
above highest point in the system and satisfy the designed initial system pressure
SUPPlY
Mains
(b) Automatic filling and make-up.
Fig. 13
3.9.1 Boiler replacement (retrofit)
In an old system where the boiler is being replaced, we recommend the use of p strainer, fitted with a
drain tap on the heating return, designed to retain
scale particles and other solid debris It is good practice to use a chemical cleaner with a floctuating agent, used as recommended by the cleanser manufacturer,
to clean the system before the old boiler is removed.
(see BS 7593).
3.9.2 Extsting systems
Valves and joints should be carefulIy checked for leaks
and the appropriate action should be taken either as a
repair or replacement. The old open system has
probabfy only been subjected to a pressure of 0.4 bar
or less. When you change to a sealed system where
the charge pressure will be 1.0 bar and the running
pressure exceeding .1.5 bar, consideration should be
given to the replacement of radiator valves with a
pattern capable of sealing at the higher pressures.
3.10 Cylinder
Where a domestic hot water cylinder is used with the
STERLING FF it MUST be of the indirect and high
recovery type to BS 1566 Pt 1 Single feed cyIinders
are not suitable for use with this appliance. Flow and
return pipework to the cylinder should be in 22 mm
pipe.
3.11 Inhibitors and water conditioners
(see BS 7593)
Chaffoteaux et Maury generalIy recommend the use
3.12
of inhibitors in systems using the STERL-ING FF boiIer. The following are the appliance manufacturer’s
recommendations :
1) Use or@ a British Gas or sImiIar approved inhibitor. These manufacturers can assist with the selection.
Grace Dearbon Ltd - WIdnes - Cheshire WA8 8 UD
Telz 051424 5351.
Fernox Manufacturing Company Limited Britannica
Works, Clavering, Essex CBI1 4Qz
Tel: 0799 085811.
2) Use only the quantities specified by the inhibitor manufacturer.
3) Cleanse the system as required by the inhibitor manufacturer.
4) Add inhibitor only after flushing when fmally re­filling the system.
5) In-line water conditioners both of chemical and magnetic type are suitabIe for use with the S?TIRUNG FF.
Add-on devices
It is important that no external control devices e.g. economisers be directIy fitted to this appliance unless covered by these installation instructions or agreed with the manufacturer in writing. Any direct connection of a control device not approved by the manufacturer could make the guarantee void and also infringe the Gas Safety (InstaIlation & Use) Regulations.
14
Page 21
STERLING FF
instant hot
water low
demand
outlets
Heating & stored hot water - spring return
valves onlv
3.13 Heating and hot water systems
Figs. 14, 15. 16 and 17 indicate various layouts for the production of hot water. It is recommended that only a high recovery indirect cylinder is used and circumstances may from time to time dictate that a special saturated heat exchanger in an indirect cylinder may be desirable.
stat.
When replacing an exisiting cylinder storage system with an instantaneous type system it is essential that all redundant pipework is removed and dead legs elimiialed.
Fig. 14
ins&t hot
water low
demand
outlets
I
‘ig. 15
STERLING FF
STERLING FF
I I
Heating & stored hot
water using flow share
relay required
The consideration of heating systems using thermostatic valves should ensure that the minimum
ffow rate through the appliance is maintained at all times and in this conneclion the remote by-pass is preferred (see fig. 17).
in
hot
Fig. 16
STERLING FF
n
fJ 77
instant AA
hot water
Remote by-pass
L 1r
remote by pass
with US valve
I
15
Page 22
3.14
Shower Applfcatfon
The appliance can be used to supply hot water to separate shower draw-off. It & not be used to supply more than one shower mixing valve.
The recommended pipework arrangement for a shower is shown below and the hot supply to the mixing valve should be the first draw off.
STERLING FF ~
HOT WATER
HOT
COLD 4-1
Fig. 17a
It is important to select a compatible shower for the STERLING FF The following manufacturers can assist with the selection
New Team Ltd
Brunell Road Earlstree Industrial Estate Corby Northants NN17 2LF
Tel.No.0536-62822
Aqualisa Products Ltd
Hortons Way London Road
Westerham
Kent TN1 6 1 BT
Tel.No.0959-63240
Meynell Valves Ltd
Shaw Road Bushbury Wolverhampton West Midlands WV1 0 9LB
Tel.No.0902-28621
Barking Grohe
1 River Road Barking Essex IG11 OHD
Tel.No.081-594-8898
COLD WATER
Do not use the appliance with push on hand showers that tit over hot and cold taps.
16
Page 23
4
4.

INSTALLING THE BOILER

A vertical flat area is required for the boiIer: 1122 mm high x 591 mm wide (44 in x 23.25 in). The surface on which the
boiler is mounted must be of a non reverberating and of a non combustible material. The appliance is supplied in a single carton which contains :
1) The chassis with all functional parts attached.
2) casing comprisblg : 2 side panels 1 front panel 1 controls fascia cover 1 glass door complete with hinges
4.1
3) Mounting bracket compr3s3ng :
4) Plastic bag containing :
5) Box containing :
6) Box containing :
7) Flue assembly :
6) Plastic bag containing :
N.B. (i) Flue accessories are not supplied as standard, and must be ordered to suit (see section 1.4)
gas and water connections inc.4 above.
control knobs safety valve wall plugs
saews and fixings. flue turret with pressure differential switch and 1st flue duct section plastic wall liner with terminal flue duct plastic turret cover 2nd flue section
flue lockiig ring ‘0’ ring 2 gaskets - one cork and one rubber 4 mounting screws with washers for flue turret
flueguide top support plate spacing strip bottom support plate plastic jig plate connection
gas filter/washer
Positioning the boiler a) Select the location for the boiler referring to the
dimensions shown in 1.1 and 1.3 terminal location positions (2.4 - tig. 10). b) Check flue length (see 1.4 ­figs. 2 and 3).
c) Check clearance on external wall for flue terminal
position (see table 2.4 - fig. 10)
d) Assemble the mounting bracket made up from 4
pieces (fig. 18) using 4 thread forming saews.
e) If for rear flue installation, remember to include the flue
guide plate E, using 2 thread forming screws.
4.2
Tg.
18
‘ig. 19
Rear outlet ffue a) Mark vertical centre line for boiler on wall. b) Mark horizontal centre lie for 107 mm (4.2 in) dia
wall opening and one for upper bracket tixing saews
(A).
c) Using bracket as template mark 4 fixing points (A) and
03. d) Mark wall for flue opening using flue guide plate. e) Drill the wall for the flue opening using a 107 mm (4.2
in) core drill.
fJ Drill 4 fixing holes (A) and (B) 7.9 mm (5116 in) and
Plug.
g) Fii bracket to wall using 6 mm x 50 mm wood saews
provided.
N.B. Ensure bracket is square and plumb to vertical centre line before tightening
17
Page 24
4.3
4.4
Slope 5 mm. per metre
@I’
Side
Dmm Amm
300 400 500
700 1200 1700 2200 2700 2900
N.B. Dimension (A) decreases as dimension (D)
Fig. 20 mm per metre.
increases due to the required decline of flue of 5
166
167.5 167
1E
16i
158.5 E
Fig. 21
D (295 mm minimum)
Y
Sfde outlet fhe
I
a) Mark vertical centre line for boiler on wall (see fig. 20). b) Using bracket as a template mark 4 fixing slots (A) and
(B).
c) Mark horizontal line through the fling slots (A) and
project to side waII.
d) Mark vertical axis of flue opening 112 mm (4.4 in) Born
comer of wall.
e) Mark waII for centre of flue opening 169.5 mm above
the horizontal on side wall.
f) DriII the waII for the flue opening using a 110 mm (4.3
in) core drill.
g) Drill 4 f&g holes (for (A) top of slot) and (for (B)
. 6) Fii bracket to wall using 6 mm x 50 mm wood screws
provided. N.B. Ensure bracket is square and plumb to vertical centre line before tightening.
Jig plate
N.B. By using the plastic jig plate the piping system can bc completed before the boiler is mounted.
a) Attach plastic jig plate to bottom bracket using 4.6 mn x 10 hexagonal screws provided (fig. 21).
6) Fit copper tails and washers to jig plate, the maim water inlet tail (M) is the shorter of the two 15 mm tails c) All connections can either come from above or belou using the standard tails provided. N.B. IF THE GAS CONNECTION IS FROM ABOVE THE PIPE WILL HAVE TO BE SET AROUND THE FLUE OUTLET, IF THE OUTLET IS TO THE REAR.
4.5
4.6
4.7
Tabe dimeter
22 mm
15 mm
22 mm
15mm
22 mm
Fig. 22
‘I ‘I
pttt
K L M N
Gas and water connections
J) Heating return
K) Hot water outlet domestic L) Gas inlet M) Mains water inlet domestic N) Heating flow
Pipework
a) Copper tails are 22 mm and 15 mm to accep
staight connectors.
Water connections
a) Make connections to copper tails using either solder capillary fittings or compression type.
Gas connection
a) The gas connection is 22 mm diameter. b) Make the gas connection using solder capillary fittings.
N.B. The gas supply pipe must not be less than 22 mm diameter
IMPORTANT NOTE :
At this stage the pipework can be completed and tested before the boiler is positioned. Having completed a satisfactory
test on the pipework the boiler can now be fitted or retained for fitting at a later date.
18
Page 25
4.8
:ig. 23
-ig. 24
ounted below the
b) Fit safety valve and secure with grub screw provided. c) Fit support bracket (A).
Fitting the boiler
a)
Remove plastic jig plate from bracket and retain
screws.
6) Hang boiler on mounting bracket, ensure that it is properly located.
c) Fit two screws through the lower part of the support
bracket and into the rear spacers on the boiler.
N.B. Insert washer into union nut and offer assembly to boiler. Use the plain black 3/4 and 112 diameter graphited fibre washers for water unions, and the white 314 filter/washer for the gas union. d) Connect water union using plain washers, working
from left to right.
e) Connect the gas union using the filter/washer packed
separately either way round.
N.B. As an alternative to using the plastic jig plate the tails can be fitted to the boiler before mounting, then connected
to the services.
d) Fit 14 mm tail drain bend using washer provided. N.B. The drain must be 22 mm and the 14 mm drain bend from the safety valve must be installed so that discharge of water is readily visible. A tundish arrangement is acceptable. The connection must NOT be made by a capilary or compression fitting directly between the 14 mm drain bend and the 22 mm discharge pipe without an 2 mm air gap. see fig. 24.
THE 22 MM DISCHARGE PIPE MUST DISCHARGE TO THE OUTSIDE OF THE BUILDING WHERE POSSIBLE OVER A DRAIN. THE DISCHARGE MUST BE SUCH THAT NOT BE HAZiRDOUS TO OCCUPANTS OR CAUSE DAMAGE TO EXTERNAL ELECTRICAL COMPONENTS PIPE SHOULD BE DIRECTED DOWNWARDS. IT MUST NOT DISCHARGE ABOVE AN ENTRANCE OR WINDOW OR ANY TYPE OF PUBLIC ACCESS AS THE TEMF’ERATURJZ OF THE
WATER BEING DISCHARGED MAY REACH 100” C.
OR
IT
WILL
WIRING. THE
Fig. 25
Rtttng the flue up to a)
Cut
plastic
dimension (L). b) Cut same amount from aluminium flue duct (H). N.B. In very cold weather the plastic air duct becomes brittle,
warm before cutting.
c) Remove plastic turret cover (D) from flue turret (B)
700 mm long
duct
(G) to length
required, see fig. 2 or 3
held by two screws.
d)
Peel off protective paper from adhesive side of cork
gasket (A) place on mating side of flue turret (B) Iiniig
up with four clearance holes, press together. e) Assemble second part of flue duct (H), push fit. f) Slide locking ring (C) and ‘0’ ring over plastic air duct. g) Slide air duct over flue duct, engage end of flue duct
into terminal and locate air duct into turret (B). h) Slide ‘0’ ring along air duct (C), to contact with the face
of the turret (B). Locate lugs on locking ring (C)
between lugs on flue turret (B). Push together and
turn to lock.
j) Position square channelled rubber gasket (E) on the
flue hood outlet of the boiler. channel facing
downwards. k) Pass the lIue assembly through the waII and seat turret
(B), onto the flue outlet, secure with 4 screws provided.
N.B.
The terminal must extend 13 mm (0.5 in) past the surface of the externa1 wall (see figs 2 and 3). I) Fit waII plate (F) provided with mastic sealing ring over
air duct to structure.
m) Make good internal waII face where the air/flue duct
assemblies exit the room.
n) Do not fit plastic turret cover ‘D’ until electrical
connections to the pressure switch have been made (see fig.26).
19
Page 26
4.11
Fitting the flue over 700 mm long a) Assembly is precisely as detailed in section 4.10 using
the requisite number of extension flue and air ducts. In particular note the following.
b) The standard flue duct is always used (both sections)
at the appliance end (uncut).
c) The standard air duct is always used at the terminal
end (uncut).
d) When cutting, always cut one extension flue duct and
the same amount from one extension air duct Always cut the plain end NOT the socket end.
e) Full details of dimensions and assembly are given in
figs. 2 or 3 as applicable.
fJ If internal futures prevent the assembled ducts being
passed through the wall from the inside, the ducts
may be pushed through from outside (remove the
Iockiig ring (C) and 0 ring first).
N.B. see also section 4.3
4.12
4.13
Fig. 26
Fig. 27
Connection to the pressure switch a) The 3 wires on the harness must be connected. b) Push spade terminals onto tags COM (P) No (1) and
No
(2)
c) Fit turret cover (D) (fig.25) ensuring that both the air
tube and cables are not trapped. Ensure that the cable retaining clip is positionned inside of the cover as shown, (see fig. 26).
Making the electrical connection N.B. See Section 2.6 for electrical supply requirements THIS APPLHNCE MUST BE EARTHED. a) PuII out fuses (A). c) Open door to left hand side of electrical box. d) Cut the cable entries to the size of the cable being used
which should not be less than 0.75 mm2 e) Remove cable clamp. f) Connect permanent live to L terminal (1) and neutral to
N terminal (2). g) Connect earth to earth tag with the spade connector
provided.
6) Connect external controls - room thermostat etc. across
terminals 3, 4 and 5, (see section 5.).
j) Secure cables with cable clamp and locate flex into clip
on boiler chassis. k) Close door I) Replace fuses.
N.B. The length of the earth wire between the cable clamp and the terminal must be such that the live and neutral wires become taut before the earth wire if the supply cord is pulled.
In the event of an electrical fault after installation preliminary electrical system checks must be carried out. Checks to
ensure electrical safety should be carried out by a competent Person i.e earth continuity, polarity and resistance to earth. USE ONLY VOLTAGE FREE EXTERNAL CONTROL SWITCHING. NO SUPPLY VOLTAGE SHOULD BE CONNECTED
TO TERMINALS 3,4 OR 5.
20
Page 27
Fig. 28
COMBUSTION
A
Q
flue adaptor
i
Positioning the boiler a) Select the location for the boiler refering to the
dimensions shown in 1.1 and 1.3.
b) Select the flue configuration (see section 1.44).
C)
Assemble the mounting bracket made up from 4 pieces using 4 thread forming saews (do not tit rear outlet guide plate).
d) Mark vertical centre line for boiler on wall. e) Mark horizontal lie for upper bracket fixing screws. f) Using bracket as template mark 4 ftig points (A) and
(B).
g) Drill 4 f&g holes (A) and (B) and plug. h) Fii bracket to wall using 6 mm x 50 mm wood saews
provided (see fig. 28).
Fitting the flue adaptor to the boiler a) Peel off potective paper from the adhesive side of the cork
gasket (A) and place on the mating side of the flue adaptor.
b) Position the square channelled rubber gasket (E) on the flue
hood outlet of the boiler channel facing downwards into the boiler.
c) Seat the flue adaptor on top of the boiler making sure that
both gaskets are in place and secure the adaptor to the
boiler by the 4 screws provided, utikzing the 2 right hand
screws to fjx the pressure switch support (D).
d) Connect the small silicon tube between the adaptor
connection (C) and the low pressure connection on the
pressure switch (D) (see fg. 28 a).
e) Connect the 3 wires to the pressure switch (see section
4.11 f$j. 26). Corn P (red) No. 1 (white) No. 2 (black)
Installing the boiler
The connection are made in the usual manner, see sections
4.4 and 4.5 and the bok can now be titted, see section 4.8. Fittii the condensation draia
Fit the retainiig clip by removing the bottom left hand screw from the combustion chamber, placing it through the faring hole in the bracket and replacing the saew with the bracket located (F). Place the condensation trap (J) into the bracket and connect the large silicon tube between the adaptor connection (G) and the trap conn~on 0. The remaining silicon tube is
co~ected
to the condensation trap bottom connection (I) and must be fitted to suitable plastic pipework to ensure that the discharge is over a drain (see tig. 29). Fii condensation trap with water prior to use.
Fitting the ffue The flue can now be fitted into the adaptor via the reducer,
making sure that all sections are tightly secured by pushing them tirmly into position. All sections must be supported to ensure sfakdity and no excessive weight put on the boiler (see
section 1.4.4).
Important fhefi~m~st~v~aminimmnd.SmetersbeEore a bend is fitted. It must only be installed in the manner
shown in section 1.44. Ensure that all joints are fitted with “0” ring and lightly lubri~ted with silicone grease. It is appreciated that in some instances it may be necessary to install the flue prior to the Wing of the boiler. If this is the case, if is important to remember that the measurement between
the horizontal tXng line for the template to the start of the flue
is 245 mm.
21
Page 28
5.

EXTERNAL CONTROL5

Programmer and zone valves
External programmer
240 V - 50 Hz supply
‘ig. 30
i.2.
Honeywell Y plan, Satchwelf
ffow chart or Satchweff mini valves to control zones.
Refer to controls manufacturers literature. Lie to relay coil is the wire in their literature which carries the signal to the boiler.
relay
5.3
kOSt
block
thermostat
N.B. Boiler time control must be set on constant
5.4 Room thermostat
Room thermostat
boiler terminal block
Fig. 31
Fig. 32
22
boiler terminal block
Fig. 32
a
Page 29
6.

COMMISSIONING

6.1
6.2
Fig. 33
Fig. 34
Central heating circuits - fdling
1) Ensure that the isolating valves are open (B and C) (fig.
34).
N.B. Valve (C) must be turned anti-clockwise by the
knurled shaft until it dislocates from the thread and then pulled out horizontally to its extremity
(approximately 30 mm (1 114 ins)).
2) Fill system to charge condition, see section 3.
3) Vent radiators and any high points.
4) Vent air separator by loosening screw (E) (fig. 34) and purging until no air is apparent N.B. : ensure screw E is tightened.
Hot water circuits - f&g
1) Check that stop cocks up stream of appliance are of a fixed jumper type.
2) Open mains cold water inlet valve (fig. 33) (A).
2) Vent installation by opening taps and closing.
4) Check that “dead legs’ have been eliminated.
5) Check for water soundness and rectify if necessary.
6) Set D.H.W. flow rate as required by adjusting screw (D) increase (anticlockwise) decrease (clockwise), see section 6.7.
5) Set system charge Pressure to design cold pressure. For a new installation we suggest 1.0 bar. For an old system see section (3, 9, 2) set to system static head or 0.8 bar which ever is the greater.
6) Check for water soundness and rectify any leaks.
7) Switch on electrical supply.
8) Manually check pump is free to rotate. Remove cap
(D) (fig. 35).
Insert small electrical screwdriver (3 mm blade), locate
in slot in pump shaft, rotate clockwise to ensure that pump is free replace cap (D).
9) Switch to HOT WATER + CENTRAL HEATING on selector switch (A) (fi
10) Allow pump to run OFF.
11) Isolate water supply and drain boiler by disconnecting fill system and opening the drain valve (F). This is incorporated in the safety valve and is achieved by screwing down the head until the valve lifts. Open all low level drain cocks.
12) Remove filter in the return isolating valve (C) and inspect for any installation debris. see section (7.4) to clean and replace.
13) Refill system as above. N.B. It is recommended that this is repeated after the system has been operated up to temperature to ‘hot flush’ to remove fluxes and remaining debris.
. 35) switch position ,@# . .
or further lo-15 minutes. Switch
8
6.3
Fig. 35
Remove protective fXm f&m case. Lighting the boiler
1) Purge gas supply. Switch on electrical supply
2) Turn the lever on the gas service tap (fig. 34) (G) to the
left. In the open position.
3) Temporarily locate the temperature control ‘knob - and
turn to maximum setting.
4) Switch to HOT WATER + CENTRAL HEATING tt El# m on
the selector switch (A). Ensure that any ancillary controls are in the demand position the boiler will now fire automatically.
5) Check for gas soundness using leak detection ffuid or
gas detector.
6) Check and adjust gas pressure/gas rate, see Section
6.4.
7) L.E.D. display sequence.
Green : electrical supply on
Yellow : run
Red : lock-out and if boiler locks out. reset and repeat.
23
Page 30
6.4
Fig.
36
Gas rate atjjustment N.B. Before adjustment check gas pressure on the inlet to
the appliance, with the appliance working - this should be 20 mbar (8 in wg) for natural gas (G 20). The maximum gas rate on hot water is fared and is a function of the restrictor size. The central heating variable adjuster is factory set at 75 % i.e for an output of approx
16.5 kW (56248 Btu/h).
1) Switch boiler to the off (0) central position, see section
6.3 (fig. 35).
2) Remove the pressure test point screw - (B) and connect a suitable pressure gauge.
3) Remove the hexagonal cap from gas rate adjuster exposing the adjusting screw (C).
4) Switch the boiler to hot water and central heating ‘q!# Y and check that any fitted external controls are calling for heat.
5) Adjust. Setting pressures are given in graph figs. 37 and 38. The pressure will be reduced by clockwise
movement of screw, increased by anticlockwise movement. Now select hot water only, adjust hot water regulator, see fig. 4 (20). to miniium and open
the largest volume draw-off tap. The gas pressure should now be the maximum as indicated in Technical Data.
6) Switch boiler off aOn. Remove pressure gauge and replace test point screw and gas rate adiuster hexagon cap. Check for gas soundness around saew.
7) Mark the data badge, located on the front of the combustion chamber below the sight glass to indicate output to heating system.
Output I Burner pressure Output kV$
15 20
25
Input / Burner pressure Input ft3$
14
12
10
6
6s
2
4!!
3 I
OutputJOBtuk :I
03
2:
t E
50
60
70 60
90
z
E
Ii
/
1.00 1.25
Input m3/h
Fig. 37 Fig. 38
50 60 70 60
1.50 1.75 2.00 2 25
90 100
I I I*Ic
2.50 2.75
t
2
24
Page 31
6.5
D.H.W ffow rate amstment This is set by the installer during commissioning. See section 6.1 and 6.7.
6.6
6.7
S RLING FF
I
Remote by-pass
remote by. pass remote by. pass
with US valve with US valve
Adjusting the heating system by-pass Where a by-pass is fitted, see section 3.2, it is necessary
to adjust to obtain the boiler miniium flow requirement
of3OOVh(l.l gal/min).
1) Set boiler thermostat to maximum, switch boiler to HOT WATER + CENTRAL. HEATING << l%i ,.
2) Open all radiators and close the by-pass. Check the temperature rise accross the boiler which should not be greater than 20’ C (36 “F).
3) Adjust system to miniium load. This is normally done
by closing valves on all but two radiators.
4) Open by-pass gradually until the boiler operates
quietly and the temperature rise is maintained. N.B. The by-pass valve should be of the lock shield pattern. The flow switch operates at approx 300 I/h (1.1 gallmin) .
Hot water adjustment
A flow restrictor (A) is fitted on the domestic hot water
outlet. Adjustment of this restrictor enables regulation of the fIow rate of the D.H.W. to suit individual installation conditions and requirements. Adjustment is made by either turning the screw in a clockwise direction to reduce the flow rate and increase the temperature or by turning the saew anti-clockwise to increase the flow rate and decrease the temperature.
6.8
Fig. 39 a
/
PUMP @
I
0
.a0
\
\
Fig. 39 b ’
25
Pump switching adjustment The pump is set to turn ON/OFF via the room thermostai along with the burner, when the central heating mode is selected. It is possible if required, to have the pump running conti­nuously by turning the switch 0 anti-clockwise, (see tig,
39b). the room thermostat then only switching the burner on and off.
Pump and
burner
switched
4%
Burner only
switched
Page 32
6.9
Central heating temperatwe diierential setting adjrrstment (1) The applance is set to give a temperature of differential setting of 12’C on the termistor control (AT2 position). For largers systems, to increase the mean temperature, it is possible to decrease the temperature differential to 7°C by removing the plug Q from AT2 position and inserting it
into AT 1 position. For smaller systems, to minimise cycling a temperature differential of 20 “C be achieved by removing the plug from AT2 position and inserting it into AT3 position, see
r=
6.10
Fig. 39~
Fitting the casing
1) Take from the carton the controls cover (H). the glass door (J) the top front panel (K) the side panels (A) an the rubber grommets (I).
2) Remove control knobs used during testing ant commissioning and tit the four grommets into the hole: at the top of each side panel (I).
3) Fit side panels (A) and secure with screws at botton rear(B).
4) Put the control cover (H) in position and secure win
five screws.
5) Fit the front top panel over the pins at the top of the boiler (C) and secure with two screws at the bottom (D)
6) Fit the central heating control knob.
7) To tit the glass door proceed as follows : N.B. THE TIE ROD (G) MUST BE USED
a) Remove the nuts from the machine saews securing the
tie rod to the hinges.
b) Offer the door up vertically. Engage part (E) in the
profile of the right hand side panel Fii assembly with screw from beneath (F).
c) Pivot the left hand hinge and engage into profile of the
IeA hand side panel. Fix assembly with screw frorr beneath.
Fig. 40
26
Page 33
p.11 Time Clock Operating Instructions
LCD display-unit
The display contains a large number of elements to clearly ;how the various data and information.
1st example :
narker
Days of the week
/
I I
A
\
(Current time)
I
2nd example Days of the week
Hours and
- minutes dis­play
(switching
time)
3nd example
r:rlj’lJlj
CH1 ON
Days
of the week
n l-l , l-l l-l
9.
w order to enter the current time of day.
8
+ Day
8
+ h+O
8
+ m+
he relevant keys are only pressed individually for aII further ntries or to check the programmed switching time.
CH 1
Day
h+ For entering the hours for switching times. m+ For entering the minutes for switching
T\l
To select the standard display (current status)
To select the relevant memory locations for
ON or OFF when programming and
entering in the memory. For selecting the relevant day of the week
for switching times.
times. For manually advancing the switching state
+[ @--~;j+[O~+[OFF]+
to enter the current day of the week
to enter the time (hours) to enter the time (minutes)
M3luVIElHRSAsu
Tie marker
Switching preselection ON
Data admMstration ii&de the time
a) Blocks The time switch is designed as a 7-day clock but can, of tour
se. also be used in 24-hour mode if, for example. all sevei days of the week are allocated to particular switching times.
If you wish switching to take place at the same time on variou days, this can IX done with the following weekday blocks :
Monday - Sunday (MO . . . SU)
Monday- Friday (MO . . . . FR)
Saturday+ Sunday (SA + SU)
Single-day programming is, of course, possible. b) Memory locations
The memory capacity is designed for 16 locations, 8 switchii
pairs being available (8 ON and 8 OFF). c) Implementation of the switching commands
Whenever the program or time is changed (e. g. summer time
winter time switchover), aII memory locations are “interroge ted” and the processor creates the switching state which COI responds to the “current status” according to the program.
swkh
Keypad description - functions
The relevant keys must be pressed in combination with the ke
1.1
+lh
Res. To delete all stored switching times in the
Means constant operation (fix) To select summer time or winter time
memory and the current time in the display.
5nten’ng the current time
: must be assumed that the battery of the time switch is lischarged until the appliance is put into operation. It can take up to 2 minutes until the various segments in the display light up (battery charging procedure).
Jse a pencil or a similar object to press the “Res” key. This setr he electronics to “neutral”. AII segments in the display are isible for approximately 5 seconds.
tlhmlumlHRsAsu
I
)n pressing the re-set button the n\o lisplay will show thus :
RX ; CH1 ONOff IIf1
Aum m-l,l-ll-l
Later 5 seconds, he following the appears :
<outine start : ‘ress the 0 button once. MO (Monday) appears in the
iisplay and the clock starts at 20:O0. be 8 key mast be constar@ pressed in order to enter the
urrent time. Iny sequence of entry is possible.
o lJylJr,r
; tH1
; RX
27
Page 34
IIf the current time is entered during the summer time periode,]
the time may be advanced by one hour with the “+ lh” ke The additional “+ 1 h” identifier appears in the display.
Example :
I
16:20
Thursday
If the h+ and m+ keys are pressed for longer than 2 second roll mode occurs.
Release the key. Make a time check, e.g. radio/television/teI phone speaking clock. A colon flashes between the hours ar minutes display in the display.
Keys : Keep 6 pressed ,$
Day h+, m+
Display :
,
P
r CH1
I
H
I!: I jrI
IlJ’l lj
Pmgramming swkhing times
Entering switch-on and switch-off times is started and compl ted (stored) with thr CH 1 key.
When this key is pressed, the memory locations for an 0
command and then for an OFF command are alternately talk up.
After the individual switching times have been entered, the
are also entered into the memory with the CH 1 or 8 key. Example :
MO, Tu, We, 6:oO ON
The time switch is now ready to accept the fast switch/off tim Corresponding switch-off times are programmed in the san way. If the relevant programming procedure is interrupted for long than approximately 1 - 2 minutes, the display contents chanI back to the current time. Partial entries, e.g. only hours, are recorded in the memory b are not effective as a switching command. See point 10 c.
To return the clock to its normal mode press the 8 key.
33-1, Fr
Keys :
CH 1 - caII up memory location
for ON command, then press day until M.T.W.T.F. appear, then press h+, m+ until correct switch/off time is display I \
This switching command is then stored
by pressing CH 1 again.
Display :
IHl ON
7
Read - change - delete
1) Read The programmed switching times are “read” step-by-step with
he “CH 1” key. Every display content corresponds to a memo­y location.
1) Change 3 command called up with key CH 1 key can be changed (cor-
.ected) in the display - simply overwrite displayed data - but is lot recorded in the memory until “CH 1” key is pressed.
The 8 key is also used to transfer the new-value into the nemory.
fhe time switch is now in the current mode of operation. :) Delete
:f you want to cancel one of the entered switching times, it is sufficient to “deleted” part of the entry. E.g. 06:-- ; or --:30 ; x --:--. The entire contents of the memory, including the time, are deleted with the “Res” key.
Manual actuation of the switching output
fhe switching output can be influenced as follows with the n ‘ey 1.
Starting position n Press once
1”\
\ Press again
Y
\ Press again -
F\
\ Press again
back to automatic mode) ?Jotes :
9 manually changed switching state % ON or n OFF is can :eIIed again by the next automatic switching time, i.e. the nex programming step is carried out again automaticaIIy.
[t is onIy possible to return to automatic mode from the func tions FIX ON and FIX OFF by pressing the \
T
keys.
I
HAND OVER THE USERS INSTRUCTIONS AND EXPLAIN THE BASIC FUNCTIONS OF OPERATING THE APPLIANCE. LEAVE THE INSTALLATION AND SERVICING INSTRUCTIONS WITH THE USER.
28
Page 35
1.
7.

ROUTINE SERVICING

To ensure continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation condition and usage, but in general once a year should be adequate. It is the law that any service work must be carried out by a competant person, such as British Gas, other C.O.R.G.I. registered personnel or your local Chaffoteaux Service Centre, in accordance with the Gas Safety (Installation and Use) Regulations. This routine service will normally be confmed to :
1) Cleaning the burner.
2) Cleaning the heat exchanger.
3) Checking the gas controls.
4) Cleaning water filter, hoses and heating filter.
5) Check operation of safety valve and pressure in heating system. The foIIowing schedules are recommended : a) Check the function of appliance, burner pressure, gas flow rate and soundness. b) Observe ilame picture and undertake combustion test.
c) Check, clean or replace components as necessary. N.B. Before commencing any work turn off gas at the gas inlet tap (fig. 34) item (G) and ensure that the electricity supply is disconnected. Isolate water supply and drain appliance if required.
7.1
7.2
Fig. 41
‘ig. 42
-I-
-
- MEI II I
To remove fimnt casing a) Remove two screws (A) bottom rear of boiler.
6) Remove screw (B) centre of lower front panel. c) Remove thermostat knob. d) Remove case by easing forward at bottom and Wing
off lugs at top. If necessary, remove the lower control cover (4 screws) and lift off the upper front panel before removing case.
To remove sealed chamber front panel and combastton chamber front panel to expose heat exchanger
W-q)
a) Remove four screws (A) securing the combustion chamber front panel, and unclip wiring harness to pressure switch.
b) Lift off front panel complete with expansion vessel and hang on hooks provided below boiIer through matching holes on top folded edge.
N.B. Alternatively support on worktop or Boor to avoid damage to ikaxible tube.
- Remove 2 screws (Fl) and remove closure plate (see section 7.3).
c) Remove 8 screws (C) and Iii off heating body front
panel with access panel (B). d) Clean the heat exchanger after removing the burner.
(see section 7.5).
- Replace in reverse order.
29
Page 36
Fig. 43
Remove burner assembly a) Remove two screws (Fl) and remove closure plate by
wlthdrawlng forward.
b) Remove two screws (F2) and remove burner by
withdrawing forwards, taking care not to trap ignition electrode lead.
c) Remove gasket and retain in safe place, or if adhered
to one surface, leave alone as removal may damage the gasket. Replace gasket if necessaq.
d) To clean burner (see section 7.5).
To dean heating retam klfter a) Close heating flow and return valves (B and C) and
drain through safety valve (F) (see section 6.2).
b) Using spanner remove return valve spindle guide
assembly (D). c) Lift filter (E) off assembly. d) Clean in warm water. e) Replace in reverse order. Replace all components
removed in reverse order.
r
Fig. 44
I
Cleaning and replacement of parts a) The burner can be cleaned by inverting and brushing
with a soft brush, Inspect injectors, ensure they are
clear. b) The heat exchanger flueways can be cleaned by
thoroughly brushing the finned surface . After brushing
inspect to ensure that the flueways are completely
clear. c) Examine electrode and clean, the tip. If the tip appears
damaged replace electrode and lead assembly - (see
section 8.1). d) Replace all components in reverse order ensuring that
the gasket between the gas section and the manifold is
correctly positioned upon reassembly. e) Open all isolation valves and repressurise system if
necessary. f) Recommission and check controls. g) After the boiler is lit, check all gas connections for
soundess .
6) Allow the boiler to warm up thoroughly, then check
the burner pressure and adjust as necessary to that
given in the table for required output (see section 6.4).
1) Restore any sytem controls and clocks to their original
setting.
7.6
drain bend
Fia. 45
To check operation of safety valve Turn off the appliance by selecting the 0 position on the Summer and Winter switch. Engage the knurled ring (A) to the thread and turn it clockwise until water can be seen to discharge from the outlet (B). Turn the knurled ring (A) anti-clockwise until it disengage from the thread. Ensure that the pressure has not decreased below 1 bar and repressurise if necessary. (see section 6.2). N.B. If the water does not discharge replace valve (see section 8.33).
30
Page 37
d.
8.

REPLACEMENT OF PARTS

N.B. 8efore commencing ensure gas and electricity supplies are isolated, and drain appliance if necessary.
8.1
‘-2
Fig.
46
‘I? replace electrodes a) Remove front case (see section 7.1). b) Remove outer front panel and combustion chambe
front panel (see section 7.2),
c) Disconnect from electrical box by pulling off elect&c
lead from the hight voltage transformer.
d) Feed cable up through gas section (H) removing
grommet (J) (see fig. 46), e) Disconnect probe (see section 8.2). fj Remove burner (see section 7.3). g) Remove screws securing electrodes,
6) RepIace in reverse order.
To
replace
probe a) Remove front case (see section 7. l), b) Remove outer front panel and combustion chamber
front panel (see section 7.2)
c) Disconnect from electrical box by pulling off probe lead
at lower left hand rear.
d) Feed cable up through gas section (H) removing
grommet (J) (see fig. 46a),
e) Disconnect electrodes (see section 8.1).
9) Remove burner (see section 7.3). g) Remove screw securing probe h) Replace in reverse order.
8.3
8.4
Fig. 46a
Fig. 47
Fig. 46
To replace safety overheat thermostat 105°C a) Remove front case (see section 7.1)
B
-
b) Remove two screws securing high limit thermostat to bracket (B). c) Remove high limit stat. d) Replace in reverse order. Use heat sink grease between high limit stat and bracket (B).
To replace overheat thermostat 1lO’C a) Remove front case (see section 7. l), b) Remove outer front panel. c) Remove left side panel. d) Remove two screws securing high Iimit thermostat to
bracket. e) Remove high limit stat.
f) Replace in reverse order. Use heat sink grease between
high limit stat and bracket.
31
Page 38
8.5
To replace change over valve microsw3tch a) Remove front case (see section 7.1). b) Undo screw (A) and remove microswitch box cover. N.B. Upper microswitch operates for D, H, W mode. Lower microswitch operates for C H mode. c) LIA spring (B) and pull operating lever off mounting pins. d) Remove respective microswitch from mounting pins. e) Note colour code and pull off electrical tags. fJ Replace in reverse order. When replacing box cover, ensure that the lugs on the connector block are clamped inside the box. N.B. Refer to fig. 9 for colour codes.
Fig. 49
8.6
To replace the flow switch assy. a) Remove air separator (see section 8.13). b) Disconnect high pressure tube at union A. c) Disconnect low pressure tube at union B. d) Replace reverse order. e) Check for leaks
To replace vent&
a) Remove front case (see section 7.1).
b) Isolate from cold mains water supply (A), open an hot water outlet and drain down from valve (E). c) Remove plug (C) from left hand side of change over valve. d) Use small screw driver to gently push out venturi ensure screw driver does not enter throat of venturi. e) Replace in reverse order. 0 Ensure that valve E is closed, restore cold mains water
supply, check for leaks.
32
Page 39
8.9
Fig. 52
To replace primary heat exchanger a) Remove front case (see section 7.1). b) Isolate appliance from system by closing heating flow
and return valves (B and C), see (fig. 34).
c) Drain boiler (primary side) through safety valve (F) (fig.
34).
d) Remove four screws securing the sealed chamber
kont panel and remove (see section 7.2).
e) Remove left and right hand side on chamber Panels by
pulling them carefully towards you.
f) Remove combustion chamber front panel, see section
7.2.
g) Remove burner. (see section 7.3). h) Remove overheat thermostat (C).
1) Remove four screws (A) securing heating body panels to chassis.
j) Undo flow and return pipe unions (E), remove pipes
and slide primary heat exchanger forwards.
j) Replace in reverse order.
Fig. 53
To remove
a) Remove front casing (see section 71). b) Remove fuses by pulling fuse carrier (B) from electrical
electrical control
box
box (see fig. 54).
c) Remove 3 screws (C) lift electrical box cover away and
unplug from PCB.
d) Pull off plug from solenoid valves at PCB. e) Unplug pump connector at PCB and earth wire. f) Unplug connector to change over valve at PCB. g) Unplug connector from fan at PCB. h) Remove one screw (D) and two screws (E). (Electrical
box support bracket to lower chassis) (see fig. 53).
ti
E
1) Carefully ease electrical box forward to allow access to tlow switch lead, also to electrode at bottom rear of
bOX.
j) Disconnect lead from flow switch at connector.
k) Disconnect electrode from rear of electrical box. I) Disconnect the two time clock plugs from the electrical
bOX.
m) Carefully move the electrical box away from the
appliance and to the right whilst straightening the capillary tube from boiler limit thermostat and domestic hot water thermostat.
n) Continue moving electrical box until bottom support
bracket can be positioned on hook at bottom of appliance. To remove the electrical box completely, continue in the following manner.
o) Isolate appliance from the system by closing valve A
(see Section 6.2) (Fig. 34).
p) f;in secondary side by opening drain plug (H) (fig.
?g. 54
33
q) Remove clip and phial from DHW thermostat pocket. r) Unclip and remove limit boiler thermostat phiil.
s) Remove box completely.
To replace electrical box in reverse order note :
a)
Hang box on hook.
b) CapiIlaries must be routed behind any pipework .
Page 40
8.10
To replace pump head a) Remove front case (see section 7.1). b) Isolate boiler from system by closing fIow and return
valves see section 8.11 (B and C, fig. 57).
c) Drain boiler (primary side) through safety valve (see
section 8.11 (F, fig. 57). d) Remove four hexagon headed screws (A). e) Remove pump head noting orientation.
f) Take off electrical connection cover by removing screw
03.
g) Remove lead and transfer to new pump head. h) Replace in reverse order.
j) Open flow and return valves Top up system if
necessary.
N.B. For the STERLING FF the pump is a Grundfos UF’
15-60
8.11
‘ig. 56
C
:ig. 57
F
-
To replace change over valve (C, 0, V) a) Remove front case (see section 7.1). b) Remove the 3 electrical box ftig screws (D) and (E)
(see tig. 53) and carefully pull the electrical box towards
you, taking care not to damage any capillaries or
disconnect wiring. c) Turn off main water at vaIve (see section 6.2 (A)). d) Turn off central heating flow and return valves (see
section 6 (B)). e) Drain secondary side by opening drain plug on bottom
of change over valve (H).
f) Remove safety overheat thermostat from tube and
carefully position to one side.
g) Remove front tube (1) from change over valve unclip
thermometer sensor, unclip high limit thermostat.
h) Remove flow pressure tube (2) from C, 0, V, to ffow
switch.
N.B. Swing microswitch box to give access to union nuts.
j) Remove rear tube (4) from C, 0, V, to secondary heat
exchanger. k) Unscrew union nut (5) of mains water inlet to C, 0, V. I) Unscrew heating flow tube nut (6) from C, 0, V. m) Unscrew union nut (7) of C, 0, V, to secondary heat
exchanger. n) Remove C, 0. V. o) To inspect diaphragm remove height screws (E)
securing valve to water section. N.B. To service the C, 0, V, piston remove spring clips, remove piston, clean and grease. p) Clean or replace diaphragm. q) Flush out water section. r) Replace in reverse order. s) Open flow and return valves. Top up system if
necessary
8.12
:ig. 58
To replace secondaxy heat exchanger
a) Remove front cash (see section 7.1). b) Disconnect and remove electrical box, (see section 8.9) c) Remove change over valve (see section 8.11). d) Unscrew union nut (8) at top of secondary heat
exchanger.
e) Unscrew bottom Ieft hand union nut (9) of secondary
heat exchanger. f) Slacken top screw (A) of heat exchanger to chassis. g) Remove bottom screw (B) and spacer. h) Remove secondary heat exchanger. i) Replace in reverse order. N.B. Do not unscrew the four tie rods in the secondary
heat exchanger.
34
Page 41
8.13
To replace air separator a) Remove front case (see section 7.1). c) Close heating flow and return valves (B & C) (see
section 8.11 (tig. 57))
d) Drain boiler down through safety valve (F) (see section
7.6 (fig. 45)).
Remove electrical box (see 8.11) and disconnect pump.
e) Disconnect flow switch pipe union from pump volute
(EL
f) Disconnect manual vent tube (B) be careful1 not to
loose black washer. g) PuII out spring dip (A) with pliers. h) Disconnect pump connection at union (D) at pump
outlet.
j) Pull pump complete with volute forwards and remove.
k) Disconnect union nut at base of air separator (F). m) Ease air separator forward and disengage integral peg
from chassis bracket,
q) Replace in reverse order, Ensure that washer is
replaced in lower union of separator.
r) Open flow and return valves. Re-pressurise system if
necessary.
Fig. 59
8.14
To replace themistor a) Remove front case (see section 7.1). b) Disconnect the spade connectors. c) Unscrew the knurled ring (A) (fig. 60) retaining
thermistor. d) Remove the thermistor by gently pulling. e) Replace in reverse order using heat sink grease on
thermistor.
Fig. 60
-
35
Page 42
8.15
Fig. 61
To replace boiler limit thermostat a) Remove front case (see section 7.1). b) Remove electrical box (see section 8.11). N.B. Thermostat (B) is situated to right bottom of
electrical box, sensor on flow pipe, on right hand
lower side. c) Remove from flow pipe (A). d) This thermostat is located on moulded pins - ease
forward and remove spade connectors. e) Feed capillary through the control box having removed
the split grommet. f) Replace in reverse order (polarity immaterial).
I
8.16
Fig. 62
To replace domestic hot water thermostat a) Remove front case (see section 7.1). b) Isolate mains water supply - drain t?om valve beneath
the change over valve (see section 8.11 fig. 56 (H)). c) Remove clip which retains phial in wet pocket. d) Remove phial from pocket. e) Remove electrical box front cover (see section 8.11, c). f) Ease thermostat (C) off moulded pegs and pull of
spade connections. g) Feed capillary through the control box, having
removed the split grommet.
h) Replace in reverse order. Polarity immaterial.
I
To replace high tension transformer (spark generator)
a)
Remove front case (see section 7.1).
b) Remove the 3 screws (A).
A
-
c) Unplug electrical connection to the pump. d) Carefully pull the control box forward and angle to give
access to the transformer (see section 8.9.).
e) Remove screw from transformer and disconnect from
amp tags.
f) Replace in reverse order.
36
Page 43
Fig. 64
To replace printed circuit boards (PCBs) a) Remove front case (see section 7.1). b) Remove electrical box front cover (see section 8.9 (C)). c) Unplug LED printed circuit board to replace new LED
printed circuit board. Remove aII plug in connectors.
d) Disconnect mains input cable at terminals 1 and 2 but
not the earth.
e) Disconnect external controls, if fitted, from terminals 3,
4 and 5. f) Remove two screws (A). g) Slide PCB slight@ upwards to disengage guide. h) PuII PC B forward. i) Replace in reverse order.
Vn
Fig. 65
17 18 9 1 11 6
Summer/winter Switch
1
Pump
2
Earth
3
LEDS
4
CH. Limit Thermostat
5
Water Flow Switch
6
ELECTRICAL BOX SHOWING POSITION OF COMPONENTS
13 8
7 D.H.W. Thermostat
Capillary 8 Change Over Valve 9 Time clock
10 Solenoid Gas Valve 11 Fan connection 12 240 V-50 Hz connection
WITH LAYOUT OF PLUGS AND WIRING.
13 Igniter
14
15 Boiler Thermistor 16 Limit Thermostat
17
18 Room thermostat
37
D.H.W. Thermostat
Fuse
connection
Page 44
8.19
To replace solenoid valves a) Remove front case (see section 7.1).
b) Withdraw plugs - colour coded - from solenoids (B). c) Remove six screws (A) securing valve mounting plate. d) Remove mounting plate and solenoids - take care not
to misplace valve springs and plungers.
e) Replace in reverse order using a NEW GASKET.
8.20
8.21
Fig. 66
Fig. 67
Rear lining-
To replace heating body finings a) Remove case (see section 7.1). b) Remove combustion chamber front panel with
expansion vessel (see section 7.2 (A, B, C and D)).
c) Remove burner (see section 7.3 d)) First slide out side
linings followed by rear which is removed by easing upwards and sliding out from bottom.
e) Replace in reverse order.
To replace fan assembly a) Remove case (see section 7.1). b) Remove outer front panel (see section 7 2). c) Remove right hand side sealed chamber panel (see
section 8.8). e) PuII off 3 spade connections from fan. r) Remove 2 screws on ffue hood (A). g) Turn anti-clockwise 10” to disengage lug from rear and
withdraw assembIy.
6) Replace in reverse order using new gasket, N.B. Ensure correct location of fan connections and that the lug at the rear is located correctly. (0) : Red (1) : Brown
(E) : Yellow/Green (2) : Not used.
Fig. 68
38
Page 45
8.22
Fig. 69
sampling tube
To replace pressure switch (Horizontal Ffcre)
a)
Remove two screws (A) retaining plastic turret cover and remove terminal cover.
b) Note position of spade connectors and remove (COM-
P, No 1 and No 2).
c) Disconnect pressure sampling tube by pulling off
nipple. d) Remove two screws retaining pressure switch (B) . e) Replace in reverse order.
N.B. Ensure ‘0’ ring is position on rear of pressure
switch to seal pressure switch - high pressure sample
joint. Transfer 4 mm support screw (C) and nut onto
the new switch if not supplied.
To replace pressure switch (Vertical Fke) a) Note position of spade connectors and remove (COM-
P. No 1 and No 2). b) Disconnect pressure sampling tube
nipple. c) Remove two screws retaining pressure switch (B). d) Replace in reverse order.
by
pulling off
8.24
8.25
Fig. 69a
To re-pressurise expansion vessel a) Remove case (see section 7.1). b) Close heating flow and return valves and drain boiler
through safety valve (see section 6.2 fig. 34 (F)).
c) Remove protective cap and check pressure on
Schroeder valve with gauge.
N.B. The setting pressure is 0.65 bar (9.5 psi). d) To re-pressurise use car foot pump or bicycle pump
with adaptor.
e) Close safety valve. f) Open heating flow and return valves. g) Refill and commission boiler. N.B. Do not me a high pressure air line.
Fig. 70
To replace pressure gauge a) Remove case (see section 7.1). b) Close heating flow and return valves and drain boiler
through safety valve, see section (6.2 fig. 34 (F)). d) Undo union nut (A) on pressure tube at rear of gauge. e) Withdraw gauge. r) Replace in reverse order. g) Open tIow and return valves. Re-pressurise system if
necessary.
Fig. 71
39
Page 46
8.26
8.27
To replace the domestic expansZon vessel a) Isolate cold water mains supply (see section 6.2). b) Drain from valve (E) beneath the change over valve
(see section 8.7) (fig. 51). c) Remove electrical control box (see section 8.11, b). d) Undo connection +- and remove domestic expansion
vessel. Replace in reverse order. Check for leaks.
Fig. 72
To replace main burner a) Remove case (see section 7.1). b) Remove outer t?ont panel, (see section 7.2). c) Remove burner (see section 7.3). d) Replace in reverse order ensuring that the gasket is
correctly positioned between the injector cover plate
and the manifold.
8.28
Fig. 73
To replace the bumer manifold assembly a) Remove the front case (see section 7.1). b) Remove the combustion chamber front panel to
expose the burner manifold (see section 7.2 (a to c.)). c) Remove the two screws Fl and remove the closure
plate . N.B. When replacing the manifold it is advisable to
replace the gasket at the same time. d) Remove the two screws F2 and lift off from Burner
base. e) Replace in reverse order.
‘ig. 74
40
Page 47
8.29
To replace expansion vessel a) Remove front case (see section 7.1). b) Isolate appliance from system by closing flow and
return valves (see section 6.2 fig. 34 (B et C)).
c) Drain boiler (primary side) through safety valve fig. 34
(F) and vent expansion vessel at (C). d) Remove flexible pipe from expansion vessel, at (A). e) Loosen upper securing screw (B) support and loosen
lower screw. Slide out expansion vessel. Q Replace in reverse order, engaging the thread of the
ffexible pipe before screwing fully home screws (B).
The vessel must be central on the front panel. g) Re-pressurise expansion vessel (see section 8.23). h) Open flow and return valves. If necessary, repressurise
system.
(See section 6.2).
Fig. 75
8.30
Fig. 76
A
,B
To replace viewing window a) Remove front case (see section 7.1). b) Remove combustion chamber front panel (A) (see
section 7.2).
c) Remove the screws (B) securing the sight glass bracket
(C). Take care not to loose the two nuts (D).
d) Replace in reverse order referring to diagram opposite.
41
Page 48
8.31
To replace the main gas valve body
a) Remove front case (see section 7.1). b) Remove sealed chamber front panel (see section 7.2). c) Remove burner assembly (see section 7.3). d) Remove electrical control box (see section 8.11, b). e) Disconnect electrodes probe and solendids. f) Remove two screws (P) retaining bracket to gas section
and ease bracket down to clear gas section.
g) Slacken and undo the gas supply union (D) beneath
gas section.
h) Remove two screws (R) retaining gas section to
combustion chamber base.
i) Remove gas section by pulling forward.
j) Reassemble in reverse order and check for gas
soundness.
Fig. 77
8.32
To replace the thermometer a) Remove the front case (see section 7.1).
6) Unclip and remove thermometer sensor from flow pipe (A) (see fig. 78). c) Withdraw gauge (B). d) Replace in reverse order.
Fig. 78
8.33
Fig. 79
42
To replace time clock
a)
Remove front case (see section 7.1).
b) Remove 2 screws tixing the time clock support (A)
(see fig. 79). c) Withdraw “amp tags” noting position. d) Remove 4 screws (D) ftig the time clock to the
support.
e) Replace in reverse order.
Page 49
To replace safety vahre a) Remove case (see section 7.1). b) Close heating flow and return valves and drain the appliance through safety valve (see section 6.2 fig. 34 (0 and section 7.6). c) Ensure that the boiler is completely drained and the pressure gauge is reading zero (0). d) Undo the grub screw (A) and remove the complete assembly by carefuly pulling it in a downwards direction. e) Replace in reverse order. r) Ensure that the valve is in the close position and
repressurise system (see section 6.2). g) Open heating flow and return valves. h) Check for leaks.
43
Page 50

FAULT FINDING

3.1 Logic sequence
1 electrici supply 1
change over valve
No
position
D.H.W.
summer
Yes
No
switch position
summer / winter
i
b
v
water flow
switch
Ye:
l
D.H.W.
winter
change over valve
position heating
A
link
L - - - - - - - - -
heating
Yes
(5) -
red lead
manual reset
energised
‘-
security solenoid open
1 st stage solenoid open
high tension transformer energised
J
1 stream of sparks 1
l!!&,
1 time delay; sec. maxi. 1
2nd stage solenoid open
Yes
D.H.W.
high tension transformer energised
I
9
stream of sparks
2nd stage solenoid open
44
No
NO
T>5s
t
t
Yes
Page 51
FAULT FINDING

CENTRAL HEATING OPERATION

SEQUENTIAL FLOW CHART 1
READ IN CONJUNCTION WITH SECTIONS (9.1 & 9.3)
START
Chedc i) System water pressure - 1 bar ii) Gas co& open - gas lines purged
iii) Electrical supply switched on.
Set selector swtch to central heatmg
.,,,,,.,LCI
t
END
45
i) Vent at air separator if) Isolating valves open and all ra-
diators valves open
RMtif~.
I
t
Remove plugs from board and chedc continuity across following : a) Black and orame wires to change o;ervahw ­b) Water flow switch (black leads) c) CH limit stat (Made leads) d) CH control SM (red and Ma&
Is there continuity aaoss all components.
I
1
Page 52
a.3

FAULT FINDING

DOMESTIC HOT WATER OPERATION
SEQUENTIAL FLOW CHART 2
READ IN CONJUNCTION WITH SECTIONS (9.1 & 9.2)
START
t
END
4-1
domestic hot water thermostat ?
YES
t
+I*
connection from printed circuit board. Is there continuity across
jbla&andblwlsads? 1 , f ,
Chedc venturi for blockage.
Ensure all isolating valves and stop co& open.
I
Replace if necessary.
No
t
46
Page 53
9.4 FAULT FINDING TABULAR CHART
PROBLEM CAUSE REMEDY
) Explosive ignition
!) Unstable burner
Poor sparks
i)
ii) Blocked gas filter 2) Clean
l/3 valve not operating
iii)
a) 24 volts supply to valve 3a) Replace solenoids, see section 8.19 b) No voltage at solenoid 3b) Check plugs on printed circuit board,
iv) Crosslighting strip - missing/incorrectly 4) Replace or reposition, see section 8.26
positioned
Incorrect injectors 1) Replace manifold 1.28 mm injectors
i)
ii) Gas pressure at manifold
a) Too high 2a) Adjust, see section 6.4
a) Too low 2b) Check restrictors and inlet pressure,
iii) Terminal incorrectly positioned 3) See section 2.4
iv) Incorrectly assembled flue duct 4) Check and reassemble,
Fan incorrectly located 5) Remove and refit correctly,
VI
vi) Combustion chamber front cover not sealing 6a) Tighten
vii) Heat exchanger fins blocked 7) Clean, see section 7.5
viii) Neoprene gasket in turret not crrectly fitted 8) Fit or refit, see section 4.10
or missing
1) Check electrodes and HT transformer replace if necessary
see sections 8.17 and 8.1
see section 8.18
3c) Replace printed circuit board,
see section 8.18
for natural gas, see section 8.27
see section 1.2
see section 4.10, 1.4.4
see section 8.21
6b) Replace sealing strip
5) Central heating low flow
temperature
i) Boiler thermistor out of calibration
ii) Insufficient gas pressure 2) Check pressure at meter and pipe
iii) 113 blue or 2/3 orange gas valve not opening
a) 24 volts at solenoid 3a) Replace solenoid, see section 8.19
b) No voltage at solenoid 3b) Replace print circuit board,
Hot water valve in change over valve assembly
iv)
sticking a) Dead leg on hot water system 4a) Eliminate
b) Bent spindle in valve
v) By-pass, if fitted, incorrectly adjusted
vi) Pressure switch hunting
47
1) Replace, see section 8.14
sizing, see sections 1.2, 2.1 and 2.7
see section 8.18
4b) Replace, see section 8.11
5) Adjust, see section 6.6
6) Replace, see section 8.22
Page 54
PROBLEM
CAUSE
REMEDY
I) Boiler noisy
i) Hot water does not
operate over temperature range
i) On heating only
a) Low flow rate as result of system resistance
b) Air in system
ii) On hot water and central heating
a) Low pressure in sealed system
b) Pump not running iii) Blocked filter on heating return or blocked pump hose iv) Gas filter fitted to heating flow or return pipes
Heat exchanger scaled
VI
vi) Overgassed
/ii)) isolating valves not fully open
Change-over valve sticking
9
Low inlet water pressure
ii)
Incorrect venturi fitted
iii)
iv) Hot water limit stat out of calibration
v) Solenoids not operating
Pressure switch hunting
vi)
vii) Low inlet gas pressure
I a) Check and if omitted fit by-pass
see section 6.6
lb) Purge by venting radiators
!a) Repressurise to 1 bar cold
see section 3.6
!b) Replace pump head, see section 8.10
3) Clean and replace see section 7.5
4) Remove and reposition see section 4.5 ia) Descale ib) Replace, see section 8.8
ia) Check gas pressure and adjust, see
section 6.4
ib) Check restrictors, see section 1.2
7) Open fully see section 6.2
1) Lubricate or replace see section 8.11
2) Ensure all down stream stop cocks open
3) Replace with 5.4 mm diameter, see section
4) Replace, see section 8.7
5) See section 8.19
6) Replace, see section 8.22
7) See section 1.2
i) No main burner
3 Safety valve
discharges
5) Pump noisy
Lack of water flow
1)
ii) Pump jammed iii) No water iv) Flow switch not operating
Fan pressure switch not operating
VI
i) System pressure too high
ii) Not isolated from mains
iii) Vessel lost air charge
Secondary heat exchanger (water to water)
iv)
internal water leak
i) Air in system
ii) Air in separator
iii) Debris in pump iv) Water filter blocked
1) Checks valves are open see section 6.2
2) Manually check, see section 3.3
3) Fill system, see section 6.2
4) Replace switch, see section 8.6
5) Replace, see section 8.21
1) Adjust 1 bar cold
2) Remove filling loop
3) Recharge 0.65 bar, see section 8.23
4) Replace, see section 8.12
1) Vent radiators
2) Open vent on air separator and purge,
see section 6.2
3) Clean and replace, see section 8.10
4) Clean and replace, see section 7.5
I
48
Page 55
PROBLEM
CAUSE
9) Excessive temperature
rise across boiler
10) Rapid cycling high/low or
high/low/off
11) Fan on continuously
12) Loss of pressure
i) Return filter blocked
ii) Low water flow rate
a) Pump defective b) High system resistance c) Gas filter inadvertantly fitted in flow
of return connection
iii) Gas rate too high
Low water flow rate
i)
ii) Thermistor out of calibration iii) By-pass, if fitted, not regulated iv) Blocked heat exchanger
Temperature differential setting incorrect
VI
i) Defective printed circuit board
Leak on system
1)
ii) Leak on appliance
1) Clean and replace, see section 7.5
2a) Replace, see section 8.10
2b) Fit by-pass, see section 6.6
2c) Remove and refit,
see section 4.4
3) Adjust, see section 1.2
1) See ‘System guidance’ section 3.13
2) Replace, see section 8.14
3) Adjust, see section 6.6
4) Clean or replace, see section 8.8
5) Adjust. see section 6.9
1) Replace, see section 8.18
1) Locate and rectify
2) Locate and rectify
I-
13) Gain in pressure shown on gauge
Filling loop still fitted and letting by
0
ii) Blockage in expansion chamber flexible hose
iii) Secondary heat exchanger (water to water)
internal water leak
1) Close stop cocks and remove
2) Clear blockage
3) Replace, see section 8.12
49
Page 56
Chaffoteaux et Mauty Limited,
Trench Lock, Trench, Telford, Shropshire TFI 4SZ
Telephone: (01952) 222727 Fax: (01952) 243493
Looking Good. Heating
Better
~fl(01939)232.796~
ESPOI 5
Loading...