installation
The system should again be filled, cleard of air locks
and examined for water soundness.
Add inhibitor to the system if required in the specification (see 5.9.)
6.3.2.
Sealed System Only
The whole of the system should be filled and thoroughly
flushed out with cold water without the circulating pump
in position. Ensure that all valves are open. (The system
must be filled with water either from a sealed system filler pump with a break tank, or by any other method
approved by the local Water Undertaking).
With the circulating pump fitted, the system should be
filled and air locks cleared until the pressure gauge registers 1.5 bar (21.5 lbf/in’). (The boiler water section can
be vented if necessary by unscrewing the knurled nut on
the drain valve, see 6.7). Vent all radiators and check for
water soundness.
Manually raise the water pressure to ensure that the
safety valve lifts. This should occur within f 0.3 bar
(+ 4.3 lbf/inZ) of the preset lift pressure, i.e 3 bar (43.5
lbf/ir?).
Release water from the system until the initial system
design pressure is attained, taking into account any difference in height between the pressure gauge and the point
at which the pressure vessel in connected.
Light the boiler as detailed in 6.4.
The water system should be heated to maximum working
temperature and examined for water soundness. Both
gas and water should then be turned off and the water
system rapidly drained whilst still hot.
The system should again be filled, cleared of air locks
and adjusted to the initial system design pressure. Any
set pointer on the pressure gauge should be set to coincide with the indicating pointer. Examine for water
soundness.
Add inhibitor to the system if required in the specification (see 5.9.).
6.4.
Lighting the boiler
The following procedure should be followed :
(a) Check that the gas service tap is open.
(b) Replace the gas control knob.
(c) Turn the gas control knob in an anticlockwise
direction which will automatically light the pilot
N.B. it may necessary to wait a few moments for gas
to reach the pilot.
(d) Wait 15 seconds, then turn the gas control knob
slowly, fully, in an anticlockwise direction. If
pilot is extinguished for any reason, wait 3
minutes before lighting.
(e) The boiler is now ready to operate and will light
when water is pumped through.
(f) Test for gas soundness.
(g) Check and, if necessary, adjust the gas rate as
detailed in 6.5.
6.5.
Gas rate Adjustment
The boiler is not fitted with a governor.
To obtain the riquired output, it may be necessary to
change the restrictor situated in the burner manifold (fig.
17). To alter the heat output remove the pilot supply tube
and the two screws securing the burner manifold to the
burner assembly. Replace the restrictor
with
the required
size as detailed in TECHNICAL DATA. Replace the
burner manifold and pilot tube.
Since the opening of the gas valve depends upon water
flow rate, make the above adjustment when all the air is
removed from the system and all radiator valves are fully
open.
Mark the data badge in the line “SET TO” (against output) to which the boiler has been adjusted. The data
badge is situated inside the case.
6.6.
Balancing the System By-Pass
The system by-pass should be balanced as the final part
of commissioning.
1.
A system by-Pass is not required for the safe
operation of the boiler. which will automatically shut down if the flow rate drops below
450
l/h (1.65 gpm). If however the system may
be required to be used with a large reduction of
heat output at certain times i. e. a reduced number of radiators, then a 15 mm system by-pass
should be used valve and turn off the required
number of radiators to suit the customer’s
needs then open the by-pass until the boiler
lights.
2.
Check system on hot water only. Open by-pass
furher if necessary to obtain correct operation.
6.7.
Draining the Boiler
Close the valves in the pipework connecting the boiler to
the system (fig. 13 or 14). Drain the boiler unscrewing the
knurled nut on the drain valve. F. Fig. 20.
7) BOILER CASE ASSEMBLY
7.1.
Balanced Flue Version
Fit front cover and refit securing screws at the top and
bottom and immediately under the gas control.
Push on gas control knob.
7.2.
Open Flue Version
Fit case and refit securing screw immediately under the
gas control. Push on gas control knob.
Hand the USER’S INSTRUCTIONS to the user for
retention and instruct in the operation of the boiler.
Advise the user of the precautions necessary to prevent
damage to the system and to the building in the event of
the system remaining inoperative during frost conditions.
Finally advise the user that, for continued efficient and
safe operation of the boiler, it is important.that adequate
servicing is carried out at regular intervals recommended
by the local Gas region.
12