Chaffoteaux & Maury CORVEC Series Manual

Page 1
SYSTEMS
MANUAL
for
CORVEC
DOMESTIC
BOILERS
chaffoteaux~
AA
Page 2
INTRODUCTION
1
W
1.
INTRODUCTION
Chaffoteaux et Maury is one of the largest producers of gas water heaters and boilers in Europe and one of the oldest established manufacturers of these appliances. Chaffoteaux et Maury have been design-
ing and making water heaters since 1919 and low
water content boilers since 1952. The principle of the weil known instantaneous
water heater is not so different from that of the central heating boiler - THEY BOTH HEAT WATER - the former for direct use, the latter as the medium for transmitting heat.
Comparing the functions of the two appliances it
is apparent that the water heater operates in less favnlrrable conditions than the central heating bc
The boiiers made by Chaffoteaux et Maury use a row water content finned copper heat exchanger.
Why copper? - Why low w.ater content?
+
Copper is universally known and used as the best material for conveying water, in addition it is both
easily worked and durable. Most important, it is one of the best conductors of heat.
In the conventional boiler of cast iron or steel, the
boiler probably weighs 80 -. 100 Ibs. with a water content of probably 20 1 40 Ibs. and it is evident that there will be a delay whilst all this mass is heated before the system responds. At the end of
a cycle the boiler dissipates the heat of this mass some of it to atmosphere, through the flue, before the thermostat responds and starts the cycle once ag:
Low water COP+~
,&&nt coupled with light weight means that we have a low mass resulting in a flexible and responsive appliance, having efficiencies of 78% -
80%.
Since a boiler providing central heating is designed to maintain room temperatures at an adequate level when the outside temperature is - l°C -
(30°F) it follows that the boiler will only be working under its design conditions for a few days in the year, for the rest of the time it will cycle due to its output being greater than the demand. With a high mass boiler it is necessary on each cycle to heat not only the water content, but the whole surround­ing mass of metal. High mass boilers show a marked drop in efficiency when working under part load conditions. Low mass boilers, like the Chaffoteaux boiler, show only a very small drop in efficiency between full load and half load, between 3% and
4%. In a high mass boiler the drop in efficiency is
more usually about 20%. It has been suggested that
a domestic boiler works 80% of the time at about 30% of load, part load efficiency is therefore vitally important.
Today with the continual raising of fuel prices and the depletion of natural resources, it makes sense to use low water content boilers.
Our boilers are suitable for either open or sealed systems but because of their construction must be used on fully pumped systems. All commonly used
external system controls can be used. This Guide is not a substitute for Installation and
Servicing Instructions which accompany each boiler. Before going ahead with your first installa­tions please study that booklet.
This publication is not intended to be a text book on central heating but, it is hoped that the informa­tion it contains will help the reader understand our appliances and that the tables and data will be of daily use.
Page 3
2 PRINCIPLES OF OPERATION OF
CHAFFOTEAUX ET MAURY APPLIANCES
2.
PRINCIPLES OF OPERATION OF CHAFFOTEAUX ET MAURY APPLIANCES
The operation of all Chaffoteaux domestic range boilers is the same, the units depend on water flow through the appliance for their operation. It is a safety feature of the boiler that it will not fire unless there is a sufficient flow of water. The minimum flow rates for all models are such that the boilers can only be used on fully pumped
systems and not with gravity systems. Water enters the boiler via the return pipe and flows through the heat exchanger. It then enters the vent’4 (1 ), across the thermostat (2) and out of the w pipe (3). When the boiler is firing the
the
stat capsule (2) closes a by pass (5) and the venturi creates a pressure difference in the water section which lifts the diaphragm (6) against the gas valve spring (7) pressure. When the temperature of the water reaches the pre-set value of the thermostat capsule the capsule lifts off its seat (2a) and allows the by pass (5) to open. The pressure difference across the diaphragm is equalised and the gas valve spring closes the gas valve. The shapes of the gas valve and thermostat capsule ensure a modulation of the burner flame. The thermostat capsule operates at a pre-set temperature of 82°C and no adjustment is necessary. The range of boilers utilise a non-electric multi­functional control that provides all the necessary interlock features required by current Standards.
With the consumer’s control in the ‘off’ position
(A) no gas can reach the pilot or main burner i;res,
:ive of the operation of the water section.
Wht
;ie consumer’s gas control is turned to pilot
position (B) gas is allowed to flow to the pilot head and simultaneously a spark is produced
to
ignite the pilot flame. The pilot flame heats the thermo­couple (8) which energises the electromagnet (9) holding open the thermoelectric valve. When the pilot is established the consumer’s gas control can be turned from the pilot to the main gas position (C) allowing gas to flow to the underside of the main gas valve (10). The operaticn of the water section will now determine when gas is allowed to flow to the burner. The boilers incorporate standard safety features throughout the range:-
i) The water section only allows the gas valve
to operate when the correct flow of water is passing through the appliance. NO WATER FLOW MEANS NO GAS.
ii) The thermocouple and thermoelectric valve
ensure that no gas can pass to either the pilot or main burner in the event of pilot failure.
iii) A high limit temperature overheat is provided
in the form of a fusible link (11) which, if ruptured, interrupts the circuit to the thermo­electric valve and isolates gas from the pilot and main burner.
iv) An interlock is provided so that, if the pilot is
extinguished for any reason, the boiler can only be refired by repeating the lighting sequence. The relighting sequence can only be attempted after a delay of about one minute.
Page 4
VENTURI
FROM HEAT EXCHANGER
THERMOELECTRIC VALVE
GAS & WATER SECTION
TO BURNER
t.
FLOW TO SYSTEM
DIAGRAMATIC ONLY NOT TO SCALE
Page 5
HEAT LOSSES
3. HEAT LOSSES Before a central heating system can be designed it
is necessary to define the parameters on which the design is to be based. The consumer should be made aware that once
installed it will not be possible to increase the
internal ‘temperatures without the installation of additional heating media. Generally, in the UK, domestic heating provides agreed internal temperatures at an external tempera-
ture of - 1°C (30” F).
It may be necessary to consider a lower design temperature in Northern England and Scotland, or if the property is on the coast or exposed to high L
k.
I. * current recommended internal temperatures and air change rates are given in Table 2. Where bedrooms are likely to be used as a study or play­room it is as well to provide a higher temperature of, say, 18°C (65°F).
TABLE 1.
(BS 5449 Pt. 1: 1977)
Temperatures and rates of air changes on which
heat loss calculations should be based.
* These temperatures will only apply for whole
house central heating and for heated rooms with part house central heating.
t Local building regulations may require a specific
rate of air change for particular rooms.
tt When used part time as bedsitting rooms or for
study purposes additional means should be provided for maintaining a higher room tempera­ture.
9 Where continuous mechanical ventilation is
provided due allowance for the greater change
should be made.
Perhaps at this stage it is as well to remember that
mar’, of the mechanical aids available and the ‘rule
Of
lb’ methods are less than accurate and could
result in user dissatisfaction and in the final analysis
*
there is no substitute for proper heat loss calcula­tion. This has the added advantage of highlighting the areas of greatest heat
loss
and gives the designer
the opportunity to consider additional insulation.
It also brings to the designer’s attention, by high-
lighting areas of greatest loss, the positions for radiators. The heat loss of a room is based on three criteria:-
1) Area of components of the structure - walls, windows, floor, ceiling.
2) The conductivity of the component (expressed as a ‘U’ value).
3) The temperature difference between the two faces of the structure.
Common ‘U’ values are set out in Table 5. and worked example is shown. An alternative to using a lower external temperature for properties in exposed positions is to use a per­centage addition as set out in Table 2.
TABLE 2.
I
Orientation
I
Normal
1 Exposed 1
NORTH
10%
20%
EAST
10%
15%
WEST
5%
10%
SOUTH
-
5%
Before commencing the calculation carefully note:-
1) Orientation N. S. E. W. facing.
2) The construction of the building component.
3) The measurements of the component.
4) The temperature of adjacent areas. In semi-detached and terraced houses the prudent designer cannot assume that the adjoining building will be heated to a certain standard and it is customary, in these circumstances, to assume a temperature in adjoining areas of 4O (40°F). As well as the losses through the structure, heat is lost through the air changes in the room. Air change rates are given in Table 1. To obtain the heat loss by ventilalation multiply:-
Volume of room in m3 or it3 by
number of air changes/hour (from Table 1) by
factor given in Table against the temperature difference fI T external to internal air.
Page 6
TABLE 3.
TABLE 4.
I
Temp difference A t 1 Factor 1
I
12 I
0.0036 1
t
I
19 1
0.0057 I
I
22
I
0.0066 I
Temp. difference A t
Factor
in “F
20 0.386 25 0.460 30 0.552
1
I
40
I
0.736
I
EXAMPLE (based on Table 3.)
Room 3 m x 4 m x 2.4 m = 28.8m3
2 Air changes - 22°C t
28.8 x 2 x 0.0066 = 0.380 kW
EXAMPLE (based on Table 4.)
Room 9.84 ft x 13.12 ft x 7.87 ft = 1016 ft
2 Air changes - 40” F t
1016 x 2 x 0.736 = 1495 btu/h
TABLE
5. Building Heat Losses
HVCAhHVE Guide to Good Practice
Usi = The number of watts that will flow through
Uimp = The number of btu/h that will flow through
each square metre for each degree C.
each square foot for each degree F. difference between the internal and ex­ternai temperatures in the case of external walls, or in the case of partition walls between the temperatures on either side of the wail.
I‘ 351 (13% )
Cavity (two leaves brick, air space
and 16 mm. plaster)
Both leaves brick (11” nominal)
As 5, outer leaf 220 mm.
(9” nominal) brick
Cavity as 5, inner leaf 100 mm.
(4”) insulating concrete
As 7, outer leaf 220 mm.
These U values are average figures and apply to most suburban and country dwellings.
For North and North-
East exposures on hill sites, at the coast or at riversides, however,
Single glazed, wood frames
105 mm. brick, plastered 16 +
16 mm. (4%” nominal)
220 mm. brick (9” nominal)
Page 7
! Item
19
20 21
22
23 24
25 26 27
28 29
30 31 32
33 34
35 36
L-
37 38
CONSTRUCTION
Usi
Uimp
Remarks
Plaster ceiiing, asphalte on
100 mm. (4”) concrete
ROOFS (pitched) Tiles on boards and felt Plaster ceiling, roof space above,
tiles on battens
tiles on boards and felt
Plasterboard ceiling, roof space
above
3.41 0.60
2.75
0.48
2.98 0.52
1.92 0.34
tiles on battens and felt
No insulation between joists 25 mm. (1”) glass fibre between
joists
50 mm. (2”) glass fibre between
joists
A
The full difference between internal and external temperature should be taken. Allowance has been made for the fact
that the underside
temperature will be higher than the external temperature.
75 mm. (3”) glass fibre between
joists
50 mm. (2”) vermiculite between
joists
2.50
0.44
0.90
0.16
0.55
0.10
0.39
0.07
0.88
0.15
GROUND FLOORS Ventilated wood floor on ioists,
air brick on one side
bare boards parquet, lino or rubber
Air brick on more than one side
bare boards parquet, lino or rubber
Solid floors in contact with earth
0.61
0.11
0.59
0.10
0.82.
0.14
0.68
0.12
0.36
0.06
These heat losses are for a medium 15 x 7.5 metre (1000 ft.2 1 plan detached house. Decrease by 50% for a terraced house. Increase by up to 25% for a small house of 5 x 10 m. (500 ft.2) plan.
INTERMEDIATE FLOORS Wood floor on joists, plaster ceiling
downward transmission upward transmission
Concrete 150 mm. (6”) with
100 mm. (2”) screed
downward transmission upward transmission
Concrete 150 mm. (6”) with
wood flooring
downward transmission upward transmission
1.50
0.26
1.70
0.30
2.20
0.39
2.70
0.48
1.70
2.00
0.30
0.35
Effect of Fabric insulation
The following tableshows examples of the approxl-
mate reduction in heat flow resulting from insula-
tion:-
IFabric/ Type of 1 Reduction of 1
Ceilings
Cavity wails
Insulation
3” glass
fibre
foam
heat flow
80%
Susoended
insulation
2
,I
Page 8
-EXAMPLE OF HEAT LOSS CALCULATIONS
-A
N
W
E
I 3 *..m I I
Temperature in adjoining area
16°C (60” F)
Temperature in
5 I I 0
I
0 0
I’
0 0 0 2.59 m
- I I I--I------II- IS.5 ft)
‘U’ value S.I.
‘U’ value Imp.
SEE TABLE 5
w/m2 /“C btu/ft2 /” F
I
External walls 11” cavity
(un-ventilated)
1.50 0.26 ,
I
Internal walls 3” breeze plastered both sides
2.25
Window - single glazed, wood frame
4.30
0.79
Ceiling - wood floor above ceiling, plastered
1.70 0.30
I
I
I
Floor - solid
I
0.36
I
0.06
I
Exposure - Normal.
internal temperatures 21 “C (70°F) @ - 1 “C (30°F) external.
EXAMPLE Heat loss - SI units
Component
Area
A t
Construction
‘U’
Loss
from Table
Wall N 4.26 m x 2.59 m 11.03m2 22 4 (1.5+ 10%) 400
1.65
Wall W (3.66 m x 2.59 m) -(window) 7.29m2 22 4 (1.5+ 5%) 252
(2.19 m2)
1575
Page 9
Heat Loss - IMP. units
Component
Area
A t Construction
‘U’
Loss
from Table
Wall N
14’ x 8.5’ 1 19 ft2
40
4
(0.26 + 10%)
1333
A 90
Wall W
(12’ x 8.5’) - (window)
78 ft2 40
4
ICI . A’\
1 U.LO
I
1 (0.26 + 5%) 1
842
I
.
IO x41
0.27
Wall E 12’
x 8.5’
102 ft2
Nil
- -
Wall S 14’
x 8.5’
119 ft2
5
15 0.40
238
,O
9 0.79
758
168 it2
1 40 32
0.06
403
16Rft2
I lfl .34
0 30
wM
Glass 6’ x
4’
24 ft2
1 4
Floor
14’x 12’
Ceiling
14’x 12’
.-- --
- -
.
t
-.--
I
V”T
Air change 14’
x 12’ x 8.5’
1428 ft3
1 40 1
- 1 Factor from
1 1052
I
lx
I I I
(Table4 0.736
5129
btu/h
‘JB The very small discrepancy is due to ‘U’ values & dimensions being worked to 2 places only
Page 10
SYSTEM DESIGN
4
4.1 RADIATOR SELECTION
Having determined, by calculation, the heat losses it is the time to select a radiator/heat emitter
to
satisfy the heat loss.
Radiator manufacturers, in their catalogues, generally show an emission based on mean water temperature 170” F. On full load the temperature difference across a Chaffoteaux boiler is 20°C (36°F) i.e. a flow temperature of 82°C (180” F) and a return tempera­ture of 62°C ( 144” F). The mean water temperature
is therefore
‘F = 72°C (162°F)
It is, therefore, necessary to adjust the radiator size
in order to achieve the required output and the
multiplying factors are shown in Table 6 and a worked example is also given.
TABLE 6.
1
21°C
I
1.08
J
EXAMPLE
Room Heat loss
for 21 ‘C/70” F 7018 x 1.08
=
7018 btu/h
7579
Select radiator with output of 7579 btu/h. @ 55°C
(100°F) AT.
are taken to the source of the greatest heat loss. See
Fig. 1. By so doing one can avoid col’d draughts at low level. The word ‘radiator’ is a misnomer, for a
radiator is, in the main, a convector, approximately 70% of the output is in convected heat and only 30% in radiant heat.
Radiators should be placed on wallswith a minimum distance beneath them of 4 in. No shelf, sill or other obstruction should be closer than 2 in. above and should not protrude more than half the width of the radiator. If it does an additional 10% should be added to the output to allow for this. Ensure there is no obstruction to the passage of air over the rear surface of the radiator, i.e. protruding skirting board, mouldings etc. Where full length curtains are likely to be closed in
front of a radiator it must be remembered that a space of 4 in. should be left in front of the radiator
to allow passage of air across the front surface.
Likewise there should be a 4 in. space between the
bottom of the curtain and the .floor and a similar space at the top. See Fig. 2.
To obtain the best entrainment it usually, but not
invariably, means that radiators are placed under,
or adjacent to, windows. When a shelf is used because a radiator is on an
inside wail and it is
necessary
to make a provision to prevent ‘pattern staining’ (dust entrained in the rising air stream which is deposited on and discolours walls above radiators) recommendations are shown in Fig. 3. We have also shown various types of radiator enclosure and the suggested additional output for which allowance should be made. See Fig. 4.
In large or irregular shaped rooms two or more radiators should be considered to provide the best comfort conditions.
Radiator Positioning
The best air ‘entrainment’ is achieved if the radiators
HEATED AIR
/
DISCOMFORT
Page 11
f
FULL LENGTH
RADIATOR SHELF + 5% to 10%
WINDOW
RADIATOR
FOAM SEAL BETWEEN
SHELF &WALL
FIG. 2.
FIG. 3.
ENCLOSED RADIATOR + 20% to 30%
tici.
4.
ACCESS FOR AIR
GRILLE
NB. Make provision for access to valves.
Provide access for venting radiator.
4. 2 PIPE
SIZING
Chaffoteaux boilers are suitable for either one pipe or two pipe systems but, in each case, the pipework must be correctly sized.
1)
So that there is sufficient volume of water
passing through the radiators compatible
with their output.
2)
So that there is a sufficient flow of water
through the boiler so that the boiler achieves full flame.
3)
So that the total system resistance falls within the range of the domestic circulators (pumps) available.
The deficiency with a one pipe system is that there is a temperature drop as the circuit progresses. The last radiators on the loop will receive cooler water than the first and, therefore, the mean water tem­perature will be lower so it will be necessary to in­crease the radiator size to achieve output. Generally a one pipe loop in 15 mm should not be designed to carry more than approximately 20,000 btu/h.
A one pipe circuit is illustrated in Fig. 5. There are available single entry radiators which are suitable for one pipe systems when used in conjunc­tion with a special radiator valve which incorporates
4)
So that the water velocity in any part of the system does not exceed 1 m/set, (3ft/sec) for small boreand 1.2m/sec, (4ft/sec), for micro­bore.
a by-pass.
FIG. 5.
P
ONE PIPE SYSTEM
I
J
RADIATOR
BOILER ISOLATING
. ..-
VALVt m
7
BOILER
%AX 150 mm
(6 ins)
-
‘rn
TAILS SHOULD BE AS SHORT AS POSSIBLE
I
RADIATOR
RADIATOR
A
\
I
PREFERRED ARRANGEMENT SWEEP 7’ IN DIRECTION OF WATER FLOW
BETWEEN Ts SHOULD BE AT LEAST EQUAL TO THE
LENGTH OF THE RADIATOR
Page 12
FIG. 6. FIG. 6.
TWO PIPE SYSTEM
TWO PIPE SYSTEM
FIG. 7.
RADIATOR RADIATOR
BOILER
I
I
SECTION 1
SECTION 2
I
I
SECTION 3
I
i
TWO PIPE - REVERSED RETURN
RADIATOR
RADIATOR RADIATOR RADIATOR RADIATOR
I I I I I
lllll
1
A
\
-
I
I
-
\
I
-
NE. In a revened return wstem the pipe resistance to each
radiator is the same. No balancing is usually required.
The preferred layout is a two pipe system. It will
be seen that the volume of water which flows in
Section 1 is greater than that in Section 2 which
itself is greater than in Section 3. The size of the pipes should take this, into account. Two pipe
systems are illustrated in Figs. 6 & 7.
This would seem an appropriate time to remind ourselves that pipework should be graded towards the radiators and the open vent. Any inverted loops, which should be avoided are provided with an air vent and provision is made at any low point to
drain the system. Where practicable pipes should be fitted clear of timber joists. If a joist is notched it should not exceed 15% of the depth of the joist. (10” joist
maximum depth of notch 1 Y’z”).
Notches in the same joist shall be at least 4” apart horizontally. Notches should be lined with pads of felt to minimise noise. Consideration should be given to the inclusion of protective saddles to prevent damage by nails. Pipe fixings and supports should be fitted at
intervals not exceeding 1.8 m (6 ft.), in exposed or vulnerable positions the interval between pipe fixings should not exceed 1.2 m. (4 ft.). Pipework passing through structure should not be built in but should be provided with a sleeve. All pipes not emitting useful heat should be insulated.
Before the pressure drop (resistance) of the system can be calculated it is necessary to establish the volume of water required in the various circuits.
The flow in Ibs/h is derived from the following
formula:-
Circuit heat output (btu/h)
= Water flow in Ibs/h.
Temperaturedifference (36°F)
When working in S.I. units the flow rate is expressed
in kg/set and is derived from the tollowing:-
Circuit heat output in kW x 0.238 = kg/set Temperature difference (20°C)
The velocity in small bore copper pipes should not exceed 1 m. set (3 ft. set). The resistances for straight pipes are given in Tables 9 & 10. It is also necessary to know the resistance for fittings. The best way of calculating this is in terms of equivalent length of straight pipe. Some of the more usual fittings are shown in Tables
ll& 12.
The equivalent length for reduced ‘T’s motorised
valves, radiators etc. can be obtained from the
manufacturer’s literature. There are two worked examples, one for a one pipe
system and one for a two pipe system.
Page 13
Velocity
in
excess
of3m
secretary
Velocity
in
excess
of1m
secretary
Size
Page 14
RESISTANCE OF PIPE FITTINGS
TABLE 11 Expressed in equivalent length of straight pipe in metres
I
Equivalent length
in feet
I
Type of fitting
TABLE 12 Expressed in equivalent length of straight pipe in metres
Valves
Equivalent length in metres
Type
of fitting 15
22 28
Straight
0.30
0.30 0.60
Angle 1.6
4.3 6.00
Copper elbow
Capillary
0.60
1 .oo
1.30
Compression 0.30
0.30 0.60
Tee branch
Square Sweep
I I
1 .oo
1.60
2.00
0.60
‘1 .oo
1 .oo
EXAMPLE
ONE PIPE SYSTEM
5000 btulh
A one pipe system has load of 17,000 btu/h.
Temperature difference is 36°F. System has 80’ of 15 mm pipe. Heat emission from 15 mm pipe assuming 90°F above room temperature is 36 btu/h per ft. ­Table 7. Therefore heat load = 17,000 btu/h + (80 x 36 (pipes)) = 19,880
From table by interpolation resistance at
552 lb/h = 0.29 in p.ft.
Fittings 6 sweep Ts Eq. L
12 ft of pipe
12 elbows
#I
24 ft of pipe
6 angled valves
30 ft of pipe
3 straight valves
3 ft of pipe
Equivalent length of fittings
69 ft of pipe
Actual lencth of oioe
80 ft.
Water flow =y = 552 Ibs,h
Total pipe & Fittings
149 ft
Resistance = 149 x 0.29
= 43.5 in or 35
ft 7.5 in head.
Page 15
’ TWO PIPE SYSTEM
8 ft.
q
I
I
4 .8000 btulh
I I
SECTION 6
Consider layout and determine the index circuit. The index circuit is the circuit with the highest resistance which often means the circuit with the highest load.
Index circuit is ground floor circuit to rad. 3.
Section A - (Rad. 3 to junction Rads. 4/5)
Load for rad . . . _ . . . . . . . . . . . . . . . 16,000 btu/h
! d for pipes 30 ft of unpainted 15 mm pipe
Room 70” F - mean water 162“ F
Therefore temp. difference
A t =
92:
F
Emission from pipes from Table 7.
(90°F
At
= 36 btu/h/ft)
(99OF
A t
= 41 btu/h/ft)
By interpolation
92°F
At
= 37 btu/h/ft
30 ft x 37 btu/h/ft . . . . . . . . . . . . . 1,110 btu/h
Total Load for section . . . . . . . . . . . 17,110 btu/h
Convert to Ibs/h 17,110 btu/h = 475 Ibs,h
36”FAt
From Table 9. resistance of 15 mm pipe=0.22
in.w.g. per ft.
Length of pipe = 30 ft
(Equivalent length of fittings)
4 elbows = 8ft 2 L valves = 2ft
c
/alent length of pipe
I section
= 40 ft
Resistance in section = 40 x 0.22 in = 8.8 in.w.g.
Section B
Load - Previous Section
. . . . . . . . . 17,110 btu/h
Rads4 & 5 . . . . . . . . . . . _. . . . . . . . 11,000 btu/h
Pipes46 ft. x 37 btu/h . . . . . . . . . . . . 1,702 btu/h
29,812 btu/h
Convert to Ibs:- 29812 btu/h = 828 Ibs
36At
15 mm pipe resistance 0.58” per ft. Length of pipe
= 24 ft. (No fittings).
Resistance = 24 x 0.58 = 13.92 in.w.g.
Section C
Load -
Previous sections . . . . . . . . . 29,812 btu/h
Load for 1st floor:-
Rads . . . . . . . . . . . . . . . . . . . . . _ . . . . 7,000 btu/h
Pipes - 76 ft. x 43°F per ft. . . . . . . . . 3,268 btu/h
Since room temperature is lower
At
is higher.
Therefore pipe emissiokhigher.
Room 60°F - Mean water 162°F
At=
102°F
Load for section . . . . . . . . . . . . . . . . 40,080 btu/h
Convert to Ibs:- 40080 btu/h
36At
= 1 l 1 3 Ibs
(Max. load in 15 mm 1100 Ibs use 22 mm pipe) 22 mm pipe resistance at 1113 Ibs/h = 0.17 in.w.g./ft.
Length of pipe 10 ft x 0.17 = 1.7 in.w.g.
. .
Page 16
Section D
Load - previous sections . . . _ . . . e . 40.080 btu/h
Hot Water. . . . . . . . . ; . . . . . . . . . . . . 8,000 btu/h
Pipes 15 mm 20 ft x 37 btu/ft. . . . . . . . -740 btu/h
Pipes 22 mm 14 ft. x 34 btu/h/ft.
. . . ; -630 btu/h
49,450 btu/h
Convert to Ibs 49,450 btu/h = , 373 ,bs
36.At
Length of pipe ‘14 ft. x 0.21 in.w.g./ft. = 2.9 in.
SUMMARY Total flow 1373 Ibs/h.
1 gal. weighs 10 Ibs. Flow in system = 137.3 gph
= 2.28 gpm
Resistance =
8.8 in.
13.92 in.
1.7 in.
2.9 in.
17.32 in. = 2.27 ft.
Minimum required flow through Maxiflame boiler is 2.6 gpm at which the head loss = 5.5.ft.
.
Required pump duty = 2.6 gpm against head loss.
of 7.77 ft.
FIG. 8.
.
MICROBORE SYSTEM
BOILER
L
e
.:,.:
-.
ZAX 15Omm (6 ins)
SMALL EORE PIPES MICROBORE PIPES
Chaffoteaux boilers are suitable for use with micro- housing. The pipework can be laid in the screed, bore systems. The essential feature of a microbore
with proper provision for insulation, lateral and
system is that each radiator is connected in parallel
linear expansion and of course draining. The advan-
back to a central manifold using 6 mm, 8 mm, or
tages are that lengths can be laid without there
10 mm soft copper pipes.
being joints in the screed. A typical system is illustrated in Fig. 8. Pipe losses and resistances are given in tables 13, 14 & 15. A worked example is also provided.
The velocity in the pipesshould not exceed 4 ft/sec.
- 1.2 m/set.
The advantage of microbore systems is more evident
in new housing with solid floors than in older type
Page 17
TABLE 13
TABLE 14
Microbore
Flow of
water
at
150°F
through
copper pipes.
Microbore
’ Flow Rate 1 kc/s
Bminal pipe size OD
8mm 10mm 12mm
182 46 21 210 55 28 245 68 34 285 81 40 325 94. 47 360 107 53 405 120 60
1 ~4485
1325 536
1670 665 2030 795 2410
925 2830 1080 3280 1235 3780
1408
­1710 ’ 1860
T.. 2030
: 2220
2365 2540
r 2785
Velocity
1.5 m/s .
Loss of head
:__
per 1 foot run in inches :
Flow Rate
WG (62°F)
lb/h
Pipe size -
6mm o.d. 8mm
o.d.
IlOmm o.d.
50
0.86
0.20 I n 05
-.’
60
1.10
0.24 0.06 70 1.38 0.29 0.08 m, an
171
0.10.
90’
2.08 0.41 012
100 2.51
0.47 : 0:“14.
110 2.98
0.55 1 Of16
120 3.48 0.65 1 0.110 130 4.02 0.76 I IT91
In the absence of data
I
this table can be used
for light gauge steel
pipes If an approximation, based on velocity, is
TABLE 15 Microbore
I
Type of fitting Equivalent length
6mm 8mm 10mm
Two angle valves or one twin angle vaive
5.00 6.00 9.00
Minimum radius smooth bend
0.25 0.25 0.50
Manifold connection
2.00 2.00 3.00
Page 18
r
\
EXAMPLE
MICROBORE
7,000 btu/h
“PPElA FL!OOFl
IIIlI[
;.
--
- EQihV. OF 20 ft.
EQUIV. OF 40 ft.
OF 22 mm TUBE. OF 22 mm TUBE.
Section 1
Load - Rad & pipe losses 7,000 btu/h
Flow in Section 4 7 000
L = 194 Jbs/hr
36OFAT
Resist, 0.4 in.w.g. per ft.
60 x 0.4 = 24
in.
Section 2
Load - Rads & pipework
22,000 btu/h
Flow in
section 22,000 = 611 Ibs,h
36”FAT
Resist. 0.034
in.w.g. per ft.
40 x 0.034 = 1.36
in.
Section 3
Load - Rads & pipework
30,000 btu/h
Flow in section 30,000
- = 833 Ibs/h
36OFAT
Resist. 0.09 in.w.g. per ft.
20
x 0.09 = 1.8 in.
System requirement 1.38 g.p.m. against 27.16 in.
4.3 PUMP SELECTION
Having designed your circuits and selected the pump
by reference to the pump manufacturer’s graphs, the pump position relative to the cold feed and open vent must be decided.
it is essential that the designer ensures that:-
1) Water is not expelled over the open vent.
2)
No part of the system is under sub-atmospheric
pressure. The point at which the cold feed enters is called the neutral point. At this point the pressure is constant and is not affected by the flow of water round the system. At
all other parts of the system the pressure is a combination of the pump head plus the static head.
By reference to the pump manufacturer’s graph
against the flow rate for the system, the available
head will be indicated. This is the head available on the outlet to the pump. This head is gradually reduced by the resistance of the system until one
arrives at the inlet side of the pump. Most pump manufacturers require a minimum of 6 ft. static head at the pump inlet.
PUMP PERFORMANCE AT 240V 82’C
1
(180°F) >
Q)-
-7-F E
t
t;’ ~~
LITRES SEC 0.5
1.0
_ 1.6;~
I
GPM
)” 8
I I
I
12.
16r;
‘i&g
_‘.
1.2 gpm
; :
FIG 9.
Fig. 9 shows the graph for a typical domestic pump. Let us assume that the heating load is 26,000 btu/h.
The volume of water we will require the pump to
pass will be:-
Flow rate:
26,000
btu/h = 722 ,bs,h
36°F temp. diff.
72
Ibs/h
-1 .i;iats per ‘.
10 (Ibs in gal) x 60 (minutes)
.fnin. (GPM).
~ “- I -.
At ,I .2 .GPM available head on setting-4 :is approx.
14ft.
.: . .
At .1.2 GPM the head loss
through
the boiter is 4 ft.
of head.
Let us also assume that the system resistance is 5 ft. of head. Figs. 10 to 13 show the pump in various position ,.. relative to the cold feed and open vent.
Since the temperature at which water boils is’ directly dependent upon pressure - the-higher the pressure the higher the boiling point..See*Tabte 16.
If -the water in the heat exchanger approaches’
boiling point or actually boils the results are boiler noise (kettling) or possible damage to-the heat. exchanger. It is, therefore, important. to obtain the highest possible pressure in the boiler.
System 1 The pressure at the open vent is always
higher than the static head so the system will always pump over.
System 2 Pressure in boiler is always less than the
static head. The open vent will suck in air when the static head is 4 ft. or less.
System 3 Open vent pressure is always the same
as the static head so no pumping over or air sucked in.
System 4 Preferred position - Highest pressure in
boiler. Open vent pressure always the same as the static head - no:pumping over or air sucked in.
.
Page 19
--H-==-l
Ii-7
mwr------ ----
I-
FIG. 10.
‘1 PRESSURE AT
&- BOILER OUTL,ET
1
j *-
I
I
! ,I
I _ _.. .I. 1
_..
I
I
(~+p==y
801 LER OUTLET
FIG. 11.
, FIG. 12.
FIG. 13.
Page 20
TABLE 16
Atmospheric pressure 14.7 psi.
4.4 COLD FEEDS AND OPEN VENTS
The movement of water in the open vent is relative to the circuit resistance between the cold feed and open vent - the lower the resistance the lower the risk of introducing aerated water into the system when the pump starts and stops. For this reason Chaffoteaux recommend that the cold feed and open vent are placed within 6 in. of each other on
the inlet side of the pump. The .order in which connections are made is not critical but the pre­ferred order is cold feed, open vent, pump.
Preferred layouts are shown in Figs. 14 to 16. Since one of the functions of the open vent pipe is to vent to atmosphere air circulating with the water,
it is recommended that a low velocity point is formed. It should be appreciated that, if the open vent connection is made horizontally into the side of a pipe, then it is unlikely that the air will be vented. See Fig 18. The open vent pipe MUST rise throughout its entire length from its junction with the system to atmosphere over the expansion tank.
1
Boiling “C
113.4
116.2
118.7
It is strongly recommended that an arr separatoc is used. Their efficiency is due to the reduction in
the water velocity and to the special,
movement.
given
to the
water.
They are
most:.efficient in
reducing commissioning time and
pump failures
and adding to the life of the boiler.
.‘- J
1 ..a- ., ‘.
,. v
As a minimum an expanded ‘T’ should
be
used.as
Fig. 17.
“. g:.,< ..,
Chaffoteaux recommend that the pump is- placed in the return. In this position, with” the-. cold feed and open vent entering on the low pressure
side of the pump as illustrated, one achieves the
following:-
1) Avoids pumping over and air entrainment.
2) Pump in coolest water-for better performance.
3) All the system will be under positive pressure.
4) Highest pressure in the boiler. The effect of high pressure in the boiler is to ir crease the boiling point of the water and avoib
kettling.
.
Page 21
COLD FEED AND OPEN VENT CONNECTIONS
ARATOR
22 mm OPEN VENT
-a
22 mm OPEN VENT
i
FIG. .14.
i-
FIG. 16.
-7
._
MAXIMUM DISTANCE 150 mm
(6 ins)
“. ,:..r.
FIG. 15.
22 mm OPEN VENT
15 mm COLD FEED
28 mm ‘T’ (EQUAL) WITH ALL BRANCHES REDUCED TO 22mm
.-.
7: . . ..
LOW VELOCITY POINT FORMED IN STRAIGHTL PIPE.
COLD FEED AND OPEN VENT CONNECTIONS
OPEN VENT
COLD FEED
SYSTEM P IPEWORK
WRONG
WRONG
OPEN VENT
:.- . . . . . *
.a.-....
.
v
..:. - .-*.::
;.:.z.z.- . . .
. . . . .-.’
.
.:..=:.~.y
‘.:::~~~~‘~
.a.-
SYSTEM PIPEWORK
Page 22
FIG. 19.
RADIATORS
WITH LOCK-
4.5 BY PASSES
It is recommended that an adjustable by pass is fitted with Chaffoteaux boilersand this is illustrated
in Fig. 19. This is also a British Gas requirement with all low water content boilers. The purpose of the by pass is to ensure that there
is under all conditions a sufficient volume of water circulating through the boiler to enable it to function. This is particularly important in a system utilising thermostatic valves or where hot water control is via a mechanical valve which closes progressively. The method of adjusting the by pass is set out in the installation instructions for all our appliances and is reproduced below. “To set the system by-pass, close the by-pass valve and turn off the required number of radiators to suit the customer’s minimum needs then open the by-pass until the boiler lights.”
4.6.1 EXPANSION TANKS
In an open system the feed and expansion tank performs two functions. It allows the system to fill
and automatically replenishes water lost through
.,. .;
evaporation and minor undetectable leaks. It also. accepts the expansion of the system watercontent. Water, when heated, expands in volume approxi­mately
l/2oth
of its cold volume. The following notes are a guide to installation requirements.
1. Cistern water volume should not. be less than 4 gallons.
?
2. Cistern must accept expansion vofrlme :of system -
(‘/zoth
of water content of system) between the water level cold and -a point not closer than 25. mm (1 in) below-the-overflow, connection.
3. Overflow should be 62.5 mm (2%. in) below entry of cold mains.
‘.,.
4. Stop cock should be fitted adjacent tocistern on mains and should be of BS 1010 pattern.
5. The tank should be supported over whole ara­of base.
,.
6. Tank should be provided with lid.
. .,‘1
7. Tank, if in unheated area, should be insulated over sides and top - not bottom.
:
IA ‘.‘3 ’
.:-
8. Pipes should be insulated.
_‘.
9. Ball valve should be ‘high temperature’;:
,’ ‘i.
FIG. 20.
EXPANSION TANKS
MAINS WATER
OVERFLOW
___.~. --~
-
-
MIN 22 mm
.-.
_-
NOT LESS THAN 25 mm.
-.- - -
WHEN SYSTEM HAS
E
. .
Page 23
4.6.2 EXPANSION VESSELS SEALED SYSTEMS
On the Continent sealed systems are the accepted method of installation. The restriction in the UK is that it is not possible, at the present time, to make a permanent connection to the Water Authority main for filling and refilling.
The basic concept of a sealed system is that a sealed vessel with a flexible membrane replaces
the expansion tank. The vessel must be capable of accepting the expansion volume when the water temperature rises. The vessel is divided into two compartments separated by a membrane. On one side is the system water, the other is charged with either nitrogen or air.
The position for the vessel must be on the low pressure side of the pump.
The advantages of a sealed system are:-
1. Reduction in labour and material costs.
2. The elevation of the boiling point of the water,
thereby eliminating boiler noise (kettling).
3. Air does not enter the system, thereby minimis­ing the problems of corrosion.
4. No cold feed, open vent or expansion tank.
5. Where static head is limited, i.e. flats.
Chaffoteaux boilers are designed, and British Gas approved, for sealed systems and are supplied, and fitted with a high temperature safety device as
standard.
Before selecting a vessel it is necessary to decide
the charge pressure this is usually the pressure to support the static head of the system above the vessel. If the boiler is the highest point on the system the charge pressure should be adequate to support the static head to the top of the.boiler
plus whatever is the minimum static head required,
by the manufacturer, at the boiler. In this connec­tion we recommend that the static head plus .I0 ft.
is adopted for all our domestic appliances.
. .
Vessels are generally available with charge pressures of 0.5 bar to 1.5 bar.
0.5 bar = 7 psi = 5 metres of head = 17-ft:head
1 .O bar = 15 psi = 10 metres of head = 34ft. head
1.5 bar = 22 psi = 15 metres of head = 50 ft. head
The correct size of vessel is important, the-size is
relative to:-
1. System water content.
2. Initial charge pressure. Final operating pressure.
3. The boiler flow temperature. The system water content can be obtained by
reference to Table 17. Chart for vessel sizing is given in Table 18.
TABLE 17
For the purpose of the calculation, the volume of the system shall be determined as accurately as possible using manufacturers’ data as appropriate. Alternatively the volumes given below may be used to give a conservative estimate of the system volume:
Conventional cast iron boiler
10 litres (2.2 gallons)
Low water capacity
boiler
3.5 litres (0.8 gallons)
0.3 litres (0.07 gallons)
Small bore
per 0.292 kW (1,000 -
pipework
btdh) of systems output
Microbore pipework
7 litres (1.5 gallons)
2.3 litres (0.5 gallons)
Steel panel
per 0.292 kW (1,000
radiators
btu/h) of system
output
0.5 litres (0.1 gallons)
Low water 0.292 kW (1,000
capacity radia:ors
btu/h) of system output
Hot water cylinder
a system is extended an expansion vessel of in­Lreased volume may be required unless previous provision has been made for the extension.
(B.G.C. Materials Installation Spec. 3rd Edit.)
calorifier
2 litres (0.44 gallons)
Page 24
TABLE18
Sizing procedure for expansion vessels - vessel
rolume in litres - flow temp. 82°C.
Safety valve
(bar) Vessel charge pressure -bar
Initial system
pressure-bar 0.5
Total water
content of
system
litres 1 gals.
0.5
1.0 1.5
25 5.5 1.68 2.80 5.20 50
11.0
3.36 5.60
10.32
I
I
I I
75 1 16.5 1
5.04 1 8.40 1 15.52
100
22.0 6.64
11.20
20.72 44.08 8.72
15.20 32.96 12.48-f 26.48
125 27.5
8.32
14.00
25.92
55.12 10.88
18.96 41.20 15.60' 33.04..
I
I
150 33.0
1 o.uo 16.80 31.04
175 38.5
11.68 19.60 36.24
200 44.0
13.36 22.40 41.44
I
3.0
I
I
!
1.0
!
1.5'.
I
2.0 j 1.0 1 1.5 1 2.0 / l.5-;-jjo /
I 1
I 1
10.96 2.16
3.76 8.24 3.12:. 6.64 -
22.00 4.32
7.60 16.48 6.24- 13.20. 3
66.08 13.04 22.80
49.44 18.72 '1 39.68
77.12 15.28 26.56
57.68 21&I-. 46.32
88.16
17.44
30.40
65.92 24.96 52.96
Volume of expansion vessel should not be less than that given above. Consult manufacturers literature and use next size up.
For flow temperatures over 93°C multiply by 1.25.
over
88°C muitiply by 1.1
(Tables based on Table 3. BS 5449: Pt 1: 1977)
Page 25
DIAGRAMS SHOWING SYSTEM LAYOUT
PUMP ON THE FLOW
1. EXPANSION VESSEL
2. PRESSURE GAUGE
3. FILLING POINT
PUMP ON THE RETURN
FIG. 21.
4. DRAIN COCK
5. AIR RELEASE POINT
6. SAFETY VALVE
7. TOP-UP BOlTLE (B.G.C. Materials & Installation Spec. 3rd Edit.)
EXAMPLE
System has a connected heating load in panel
radiators of 26,000 btu/h.
Radiator Volume from 26,000 x o 5
Table 17
1000 .
= 13.00
Pipework Volume from 26,000 x o o7 Table 17
1000 *
= 1.82
Boiler Volume Chaffoteaux 45 -
‘-om data sheet
=- 0.58
Cylinder Volume from Table 17
=- 0.44
System water content
= 15.84
Charge pressure 1 bar Safety valve
2.5 bar
Vessel size
3.6 litres
It is necessary to fit a safety valve adjusted to the final system pressure plus 4 psi. The safety valve should discharge outside the building into a drain or safe place. All high points should be vented, in addition it is recommended that an air purger and automatic air vent are fitted into the flow pipe adjacent to the boiler. An altitude/temperature gauge should be fitted.
gig. 21 shows system layouts.
SEALED SYSTEMS
i‘
ACCEPTED METHODS OF FILLING
: HVCA/IHVE GUIDE TO GOOD PRACTICE.
“r. CONNECTION MADE FROM TAP USED
; FOR OTHER PURPOSE
.-: STOP TEMPORARY HOSE .v COCK
FIG. 22.
TEST COCK
2. MAKE UP VESSEL ABOVE HIGHEST POINT OF SYSTEh
/
HEATING MAIN’
NON RETURN VALVE
FIG. 23.
3. MAKE UP USING ‘BREAK TANK’ & PRESSURE PUMP LOW PRESSURE SWITCH TO STAR
STOP MAKE UP PUMP - INTERLD( WITH BOILER
PRESSURE REDUCING
PUMP
NON RETURN
VALVE .,_
Page 26
4.7 PRODUCTION OF HOT WATER
if the storage solution is chosen the hot water cylinder selected must be an indirect, high recovery, coil type cylinder. The cylinder should be to
BS 1566 which ensures a minimum heating surface and should be of a grade suitable for the building static head - generally 30 ft. Grade 3. Self priming cylinders are not suitabte because the
higher pump duties necessary for low water content
boilers, can -break the air seal. this leads to the exchange of water in the system and introduces air and hardness salts. The former can promote
boiler noise and the latter lead to the premature scaling of the heat exchanger.
Gravity cylinders with an annular heating surface are not suitable since the higher velocities, with a
pumped system, will cause noisewhich will concern
the consumer.
The cylinder should be sized to meet the demands
of the household. For instance, a family of four with one bathroom will require a minimum water storage of 25 gallons, the same with two bathrooms 35 gallons.
It is recommended that the cylinder should be capable of recovering in one hour, which, if a 25 gallon cylinder is utilised, means that the cylinder should initially be capable of absorbing 25,000
btu/h. The high point on the circulating pipework should
be vented preferably using an automatic vent of
the bottle type. To obtain the required flow and keep resistance to
a minimum 22 mm pipes will normally be reqc
,d for the primary circuit. A lockshield valve should be used in the circuit to balance the flow.
It is becoming increasingly popular to pump cylinders contraflow i.e. with the flow zentering the bottom of the cylinder and the return taken
from the higher tapping: The rate of heat exchange
in the cylinder is relative to the. temperature difference between the circulating and the stored water. If the ‘cylinder is pumped contraflow the hottest circulating water is in contact .with the­coolest stored water and therefore the rate of heat exchange is improved. It also helps the venting Tf
the coil.
..-.z‘.,:L :$ ,r:‘,2; :
The allowance made for water heating ;in ‘the:
boiler sizing is a function of the. recoven/ time selected and the method of control,. usually 8 -
10,000 btu/h.
. .
/ +.
,: .
‘>+‘.
There are now available immersion elements whip+
fit a standard 2% in. BSP boss to enable a dir
, cylinder to be converted to indirect. As this type of element has a high resistance, a cylinder by pass may be necessary to maintain the flow rate needed to operate the boiler. The heating of stored water is perhaps the most wasteful use to which a gas fired boiler is utilised.
We not only heat up and continually maintain at
temperature 30 gallons of water in case we might need it, we also lose heat from both the primary and secondary pipework and from the.surface of even an insulated cylinder.
._
,_ :.;.
CONVENTIONALLY CONVENTIONALLY
PUMPED CYLINDER PUMPED CYLINDER
BS 1010 STOPCOCK BS 1010 STOPCOCK
22 mm OPEN VENT
FIG. 25
i
ANK
7
/’
AIR VENT
22mm DOWN SERVICE 22mm DOWN SERVICE
L
ISOLATING ISOLATING
-’ ” -’ ”
GATE VALVE GATE VALVE
15mm COLD FEED
c
MAX 15Omm
(6 ins)
\
DRAIN COCK
75 mm (3 in) INSULATION
LOCKSHIELD-BALANCING VALVE
I
Page 27
! CYLINDER PUMPED CONTRA-FLOW
22 mn
OPEN VENl
Max 15Omn
(6 ins)
AUTO
1
15 mm COLD FEED
PIPE GRADED TO VENT
BALANCE VALVE
FIG. 26.
USE OF CONVERTION ELEMENTS
IR VENT
r
\
15 mm BY PASS WITH /
.,;
LOCK SHIELD VALVE
-
ALTERNATIVE ARRANGEMENT SHOWING T/S VALVE
BY PASS
FIG. 27.”
Certain applications requiring small quantities, at the kitchen sink, for showering and for the small family are more efficiently accomplished by using an instantaneous water heater. Chaffoteaux manufacture a range of singlepoint
and multipoint water heaters and also the first
purpose made gas shower heater, the singlepoint heaters are flueless or open flued, the multipoints and shower heaters are balanced flue.
With the exception of the shower heater they are
available for either mains connection (high pressure)
or for connection to a cold water tank supply (low pressure).
Detaiis of the performance of the water heaters
are in the data sheet included in this booklet. The multipoint water heater is also suitable ,for connection to a shower using a mixer valve to
balance hot and cold water pressure. They are also suitable for connection to most modern washing
machines provided that the machine is capable of accepting one gallon per minute of hot water.
Page 28
CONTROLS’ -
5.
CONTROLS
In these days of rising fuel prices it is increasingly important to have full and adequate control over the two functions of the system.
1) Hot water generation
2). Space heating Hot water can be controlled either electrically or mechanically. Electrically using a cylinder thermo­stat and motorised valve. It is suggested that the thermostat is placed r/a up from the bottom of the cylinder. The setting temperature suggested is 46°C (140°F). There are a number of mechanical valves available all operated by the expansion of a
heat sensitive medium. The most effective have a phial that can be entered via a pocket into the
stored water, the least effective is that which is
attached to the primary return pipe.
Space temperature is more usually electrically
controlled by use of a room thermostat placed in a ‘representative’ position, usually the hall. A room thermostat should:
1) Be sited not more than 5 ft. above the floor level. (when you sit down you are only 3 ft.
tall).
2) Not be influenced by local heat emmitters, radiators, television and the like.
3) Not be influenced by excessive draughts.
4) Not be exposed to direct sun light.
An alternative control is achieved by the use of thermostatic radiator valves, most of these are directional so care should be exercised in siting them. (The valve is stamped with an arrow indicat-
ing the direction of water flow.) If a radiator has been boxed in or is likely to be
behind a curtain then consideration should be given to fitting a valve with a remote sensor. Various system layouts are illustrated together
with some wiring diagrams. For further information you should contact the controls manufacturer. The electrical controls must conform in all respects to the I EE Regulations and the local codes. The installation should be fused with a fuse-of a suitable value, usually 3 amp. The pump should have adjacent to it a means of isolation.
ABBREVIATIONS USED IN THE.F&LOtilN6
DlAG RAMS
AAV
BIV
LSV
TRV
L N S D C.
+.
2 PMV
3 PMV cs-
RS
TC
Prog.
IV vo
VC
.-
,;: :
Automatic Air Vent Boiler Isolating Valve
Lock Shield Valve Thermostatic Radiator Valve Live Neutral Satisfied - (stat. satisfied) Demand - (stat. calling) Common
-.
Earth Two Port Motorised Valve Three Port Motorised Valve Cylinder Thermostat
_ _:, Room Thermostat Time Clock Programmer Isolating Valve Valve Open Valve Closed
NB 1.
Neutrals and earths have not been drawn
2.
The drawings are schematic only
3.
For cylinder cupboard layout see page 30, 4
:.
-_.
_
Page 29
DOMESTlC HOT WATER & CENTRAL HEATING -
MECHANICAL CONTROL
TIME CLOCK CONTROL OVER PUMP
AAV
FIG. 28.
MAX
r
a
BIV
\
c-e,,
,
_________
ALL HEATING RETURNS TO BE COMMONED BEFORE JOINING COMMON RETURN
_‘.
15mmBYPASS
WITH US VALVE
T/CLOCK
FUSE 3a
L””
PUMP
1 LjNj
Chaffoteaux recommend that the hot water thermos&t valve-’ is a 3-Port valve with built in by pass.
N
I
FIG. 29.
\
d
FIG 30.
7
I
DOMESTIC HOTWATER & CENTRAL HEATING -
I 1
MECHANICAL CONTROL OVER HOT WATER
AAV
ROOM STAT & MOTORISED VALVE ON HEATING
(Spring return pattern with auxiliary switch)
Chaffoteaux recommend that the hot water thermostat valve is a 3-Port valva with built in by pass.
I --
PPMV yv
N,
N, RtSTAT
PROGRAMMER
FIG. 31.
- h :. -;
Page 30
FIG. 32.
HOT WATER & CENTRAL HEATING CONTROL BY CYLINDER
THERMOSTAT & ROOM THERMOSTAT
SWITCHING MOTORISED-VALVES.
AAV -.“-
.:. .,~ . .
c ------ ‘““‘, ,
I
. ;
1.
I I I I I I-1.. ;-
.T^ x...
:; y:
,
-.. _
.,
5.
._ ^.
.
-
MOTORISED VALVES WITH SPRING
RETURN WITH AUX. SWITCH
I] PROGRAMMER MV
MOTORISED VALVES - DRIVE .OPEN -
PROGRAMMER
DRIVE CLOSED
t 1
FIG. 34.
FIG; 35.
BIV
AAV
HOT WATER PRIORITY
PROGRAMMER _:._
PUMP
t
.J
):
; C.’
T
_ I
T
I Y
3
I-
3 PMV
, .:-
-. , . .
.-me---------------
A--
i,
MID-POSITION FLOW SHARING VALVE
PROGRAMMER
.+.,:..>.,
d .:<:23;2
3 AMP
.:.;.~.~;~~~~~.~~~~,~
:.:: .i.... . . . . . . .
. . . . . ..~.~.~~.~..~~...~.~....~ .,;
. .
.:‘.?.+.:i’: . . . . . .
,;_
.:. .:.:-.:..: . . ...’ . .
. . . . . . . ..~.. >,.
.::.;:<.;.:-.< .
. . . . ..y ;........
. . . . 1 ,....y.,.: . . . . f
‘.~...~.~...~.~...~~...~~ . . . . . .
‘R
FIG. 36.
“.i$~p..
NO?~%ECOMMENC
d .-
I
Page 31
It is often convenient to group all controls and the
circulating pump in the cylinder cupboard. Ensure
that all components so positioned are accessible.
Chaffoteaux recommend that the flow and return
TIME CLOCK
3 AMP
N-
‘.. N t ,,
s-m*
FIG. 38.
%ROST THERMOSTAT
FIG 39.
FROSTTHERMOSTAT
AUDIO/VISUAL ALARM
ANCILLARY
FIG 40.
LOW WATER LEVEL LOW PRESSURE HIGH TEMPERATURE OR SIMILAR CONTROL
pipework to the cylinder cupboard are run in 22 mm pipework. Cylinder cupboard layouts are given in
Fig. 41.
c.
l
22 mm OPEN VENT
15mmCOLD FEED I
. e-d.---.
t-
I‘ I
AAV REQUIRED IF FLOvli
AAV -
TURNS DOWNWARDS
TO‘RAD:
-..
22 mm RETURN
22 mm FLOW
: 22
22
mm V~CN VCN I
15 mm COLD FEED
I
,
-\
*.
--w-s--
/’
;
a’
/
._--
.-
+lCIFROM RADS.-
.
.~
-TO RADS. --
FPO :
mmFL=. Q
-- _
22 mm RETURN
FIG. 41
Page 32
FLUES AND VENTILATION ta-.
6.
FLUES AND VENTILATION
With all the boilers the installer should ensure that there is adequate combustion and ventilation air, the requirements for domestic boilers are set out
in Table 19.
Open- flues are governed both by the Building
Regulations and the British Gas Regulations and
are summarised in Fig. 43.
Balanced flue terminal positions and the restrictions
on siting are summarised in Fig. 42
If the :terminal is less than 6 ft. above the ground
level it must be protected with a wire guard.
Some Chaffoteaux appliances of the .room sealed
type are approved for use with both Se duct and U
duct installations. Se duct isa method of multiple flueing in a multiple storey dwelling. The appliances on a Se duct
TABLE 19
receive combustion air from, and discharge
their.
products into, the duct. Air for combustion and > for ventilation of the duct is by means of two­horizontal limbs, one to each side of the building at the base of the duct. See Fig. 44.
.’ .
I _I
:.. A variation of the Se duct is the U duct where-air for combustion and ventilation is brought--irt’fror& , roof level.
The air intake duct is installed flush with$he
inside’;
face of the duct. The flue duct from appliance
is”’
cut
to length usuaily extending I’/ in beyond the: -
inner face of the- duct. InstructionS,,: for~~.each
appliance should be studied carefully.
%: ;
A duct has a maximum carrying capacity and’advic
on sizing or the suitability of ducts isavailable from the local gas region.
BOILER COMPARTMENT VENTILATION
POSITION
OF
OPENING
HIGH
LEVEL
LOW
LEVEL
TYPE OF APPLIANCE
OPEN FLUED
BALANCED FLUE
AIR FROM
AIR DIRECT
AIR FROM
AIR DIRECT
ROOM
FROM OUTSIDE
ROOM
FROM OUTSfDE
9 cm2
per kW
’ 2
in2 per 5000
4.5 cm2 per kW
9 cm2 per kW
4.5
cm2 pee kW
1 in2 per 5000
2
in2 per 5000
1 in2
per 5000
btu/h
btu/h
btu/h
btu/h ‘.
a18cm2 perkW
9 cm2 per kW 9 cm2 per kW
4.5
cm2 per. kW
4
in2 per 5000
2 in2 per 5000
2
in2
per 5000
1 in2 per.5000
btu/h
btu/h
btu/h
btulh
FLUELESS WATER HEATER (instantaneous) Not exceeding 12 kW - 40,900 btu/h
Minimum
room volume 6 m3 - 212 ft3. Air vent 35‘cm2.
NB Areas specified are FREE Al R and are related to appliance INPUT.
- - - -‘-US ROUTES FOR VENTILATION
VAUIU
ROOF
n
kY III
APPLIANCE ROOM
ttY
ADJACENT ROOM 1
AIR INLETS1 2,3 4,&6
_. -. .-. _-_ L - -’
I
BELOW FLOOR SPACE
--- OIRECT METHODS
-INDIRECT METHODS
._,_.
Page 33
I
BALANCED FLUES
I
FIG. 42m
_ .-_ .-_
FOR EAVE PROJECTION
--.--k-w-
NOT MORE THAN
n
. . . . . .,..: )..,..$,,,) _:. &;..: ..: :;, ..::,.,:.:,.
if---
;i-i~:~~~~.~~~~.7
3OOmml(l ft)
SPLllTER
I I ’ ’ 3OCtmm 1 I !I
(1 tt1
’ ‘3OOmm
1 I 300mm
(1 ftl
(1 ft)
4 +I &mm 600 mm
NB 1.
TERMINALS MUST NOT BE FITTED
I1
ftl IN SHADED AREAS
(2 ft) ,. .I,
SPLITTER
NOTTO EXTEND
MO
IRE THAN
DEPTH OF
TERMINAL
-
3.
If 300mm (1 ft) BEU SOFFIT 600mm (2 ft) ON ElTHt & EXTENDING TO INCLUDE PLASTIC GUT-
2. ,IF LESS THAN 1,800 mm (6ft) ABOVE GROUND LEVEL FITTERMINAL GUARD
DW EAVE FIT DEFLECTOR TO
fR SIDE OF TERMINAL
TER
FIG. 43.
OPEN FLUES
600 mm _ (2 ftl
I
NE 1. PREFERRED -CHIMNEY LINED WITH
STAINLESSSTEEL LINER
2. EXISTING CHIMNEY MUST BE SWEPT BEFORE LINING
3. ALL EXTERNAL FLUES SHOULD BE INSULATED.
Page 34
SE DUCT & ‘U’ DUCT
COMBUSTION PRODUCTS
4PPLIANCE !
APPLIANCE f;
AIR
SE-DUCT
CHAFFOTEAUX BOILER
TESTING OPEN FLUES
All appliances connected to a conventional open flue should be checked for ‘spillage’. The following are suggested methods:-
1) Hold a lighted taper so that the flame is below the lower edge of the draught diverter (Fig. 46.).
Spillage is indicated by the flame being displaced
outwards.
2) Hold a piece of cold polished metal or mirror close to the lower edge of the draught diverter. Spillage is indicated by the polished surface
becoming clouded.
3) Ignite a smoke pellet in the combustion cham-
ber. Spillage is indicated by escape of smoke from the draught diverter.
If an extractor fan is fitted first carry out test on flue with the fan off. If this is satisfactory open door to room in which appliance is fitted, connect­ing to room in which fan is fitted, and close all other doors. Close all windows in the property.
Switch on fan and repeat test. If spillage is detected
open window until spillage ceases. If the open area of the window is less than 10 in2 put in additional ventilation, equivalent to area of opening.
If the area is greater than 10 in2 consult the local gas region. This test is very important since the installer has a
statutory duty under the Gas Safety Regulations, Section 47:
No person shall use or permit a gas appliance be used if at any time he knows or has any reason to suspect :-
a) That the removal of the products of
combustion from an appiiance is not safely being carried out.
FIG. 46.
TES
Page 35
7 WARM AIR
7.
WARM AIR
Warm air heating is the distribution of heated air,
either directly or indirectly, and with the aid of a fan. and ducting delivering it to the area in which it is required. Chaffoteaux market a range of warm air heaters of the indirect variety. Water heated by a boiler is the heating medium. The heated water passes through a water to air heat exchanger. The heated air is passed to the rooms. See Figs. 52 & 53. With modern building methods, where buildings are of low mass and highly insulated:-
1) a smaller heating requirement is required to be met by the system,
2) because the buildings are low mass the structure does not retain the heat.
The advantages of heating by warm air are:-
1) design temperatures are more quickly met from a coid start,
2) less wall space is used,
3) less conspicuous,
4) continuous air circulation and filtration. Chaffoteaux, with their appliances, can add:-
5) flexibility - the boiler providing thezheated water can also provide hot water or additional
radiators,
6) lower risk of corrosion because the boiler heat exchanger, the water to air heat exchanger and the pipes and cylinder are all copper.
There is also another and important function
which
Chaffoteaux can satisfy. Many of -Ithe::
direct fired units installed in the 1960’s are
now-.
due
for replacement, and a higher level of
comfort
is
now
required, like heated bedrooms. .F$ther, few of the generation of heaters installed-at that time were able to supply domestic hot water, this was provided by an instantaneous water heater or circulator. Warm air heat exchangers are of two basic types:-
Upflow
Air is passed over the heat exchanger and discharged at the top of the unit. (Fig. 47.).
Downflow
Air is passed over the heat exchanger and discharged at the bottom of the unit. ,.
FIG. 47.
DOWN FLOW
UP FLOW
r
-----
1 I
1
FAN
. .
3’
FILTER HEAT EXCHANGER
4
PLENUM - NOTSUPPLIED
BY CHAFFOTEAUX
5
ALTERNATIVE FAN POSITION
: FIG. 48.
-STUB DUCT
k k
HEATER
l/v
,. -
‘FIG. 49.
RADIAL
R ‘-
Jl
R~HEAT<R
1
R
43
R
R
EXTENDED PLENUM
.
L.
Page 36
Distribution of the air is then directed, by ducts, the outlets of which may be:­Stubducts
Registers to rooms directly off
the plenum.
Floor perimeter
Air is passed through round or square ducts from the plenum to discharge through the floor, preferably under windows, to get the best entrainment.
Ceiling perimeter
As floor perimeter but dis­charging from the ceiling (used where there is a loft.or large void above the rooms).
Low side wall TFie registers are placed in the
walk at low level. The dis­charge rate should not exceed
High side wall
300 fpm (ft. per minute).
Registers are placed at high
level on inside walls. Carf 3s to be taken with the choic.. of grille so that no discomfort is caused to the occupants.
The distribution systems are of four types. (See
Figs. 48 to 51).
. ../.
i
. .
Radial The ducts radiate,to. registers
from the centrat .heat source.
Extended Plenum The plenum is extended-.and
the supply to the :jegisters is taken from the 4arge:duct:Air flow should not-:exceed 500 CFM and the;ple&m should not be more than.--20.,ft.,.. iin length.
Step duct
Where the-- duct-- gradually
reduces in size and the supply ducts are taken off Yhe,:main
duct.
FIG. 52.
FIG. 53.
AAV
; I
---.---------------.,
I I
8
I :
I
I I
ADD A RAD :
I I
I
a I I : :
, e----a :------------------------a
ADD A RAD
Page 37
1 GAS SERVICES
‘2,
8.
GAS SERVICE
.
_ -__.
It is equally necessary to correctly size the gas pipes as to size the pipes carrying water. l n the same
way that pipes offer resistance to water so they do
to the passage of gas. The carrying capacities of gas pipes are shown in Table 20.. expressed in ft3 for metres run.
It is therefore a pre-requisite to calculate the volume of gas required. This is obtained by the following:-
Boiler input in btu/h
CV of gas
The calorific value of natural gas is normally
‘30 btu/h/ft3.
I convert from ft3 to m3 divide by 35.31.
.,hen commissioning an appliance it is recommen-
ded that first the pressure is checked with a gauge at the inlet to the appliance when running and all
other gas appliances in the property in operation.
At the inlet to the appliance under the conditions
as above the pressure should not be less than 8 in.w.g.
.._ . .
d
,’
Next the pressure at the burner manifold should be checked and adjusted after 10 minutes in operation. When setting/checking the pressure on a balanced
flue boiler ensure that all doors and windowsare
closed to the room in which the boiler is situated.
Having set the burner pressure all other appliances
should be turned off including the pilot lightsand
the consumption checked at the meter to confirm
that the gas consumption is as shown on the data
badge of the appliance.
TABLE 20.
Discharge on straight horizontal copper tube with 1 mbar differential pressure between ends for gas of .,.
relative density 0.6 (Air = 1).
. .
.
Page 38
LPG 9
9.
LPG
LPG is liquified petroleum gas. The fuel source is either crude oil or direct from the North Sea. The gasses available are either Propane or Butane. The gasses are stored as liquids under pressure.
Propane turns into gas at a lower temperature than butane and is, therefore, stored at a higher pressure.
When the tap is opened the pressure is released, the
liquid boils and gas is evolved.
TABLE 21
49 160 0.12 4.4 0.90 31 1.85 65 3.8 :;135- :
- 55 180 0.12 4.1 0.80 29 1.75 61 3.6 : 130:
- 61 200 0.11 4.0 0.80 28 1.65 59 3.4 120.
OUTSIDE DIAMETER OF COPPER TUBING
i 27 t 90 1 0.041 1.3 1
1.7 1 0.291 10.1 1
6.8
1 61~ t 200 1 0.02 1 0.9 1 1.1 1 0.191 6.7 1 4.5 0.26 1 9.3
Il.01 135.6 ~ 0.79 128.0 ~ 0.68 i 24.6
0.601 21.2
0.50 1 17.8
0.47 16.5
+
0.44 15.7
12.7
0.33! 11.8
1.0
I Imo 1 Metric I Imo 1 Metric I Imo.l­‘%iLl 22mm I K in
28
mm “1 iA .’
ft3 /h 1 m3 /h ft3 /h lft’/h m3/h ft3/h ft3/h
62.018.01 283.01 195.0
15.96 5620 444.0,-
.
I
75.01 1 4.33)
4
17.5 2.12 52.0 153.0 120.0
15.0 1.85 65.21 45.0 1 3.91 t 138.0 108.0
14.01 1.72 1 60.91 42.0 3.62 1128.0 100.0
13.0) 1.56 I 55.21 38.0 3.34 1118.0 92.0
I
12.0 1.48 52.3 36.0 3.17 112.0 88.0
11.0 1.40 49.3 34.0 3.03 107.0 84.0
-
Page 39
All Chaffoteaux appliances will burn either
propane or butane in their LPG form. Remember,
rvever, if you change gas from propane to butane
or vice versa, it will be necessary to reset the pressure
regulator.
For propane the regulator should be set to give a working pressure of 14.6 in.w.g. at the appliance and 11 in.w.g. for butane. Tables 22. & 23. show the properties of the two gasses.
LPG is heavier than air, and therefore care should be exercised in storing the gas cylinders. They should be stored external to the property and above ground level. So far as installation is concerned the only factors of system design which differ from natural gas are the pressure drop in gas pipes. This is summarised in Table 21. and the necessity to use the appropriate isolating valve (usually a diaphragm type) where the
supply
pipe enters the building and appliance.
-r YCAL PROPERTIES OF BUTANE AND F,‘3PANE.
TABLE OF PROPERTIES
The following tables shown typical physical
properties for commercial grades of Butane and Propane. All Metric units relate to Metric Standard
conditions of 15°C and 1013.25 mbar (dry).
Imperial units relate to Normal Temperature
and Pressure Condition of 60°F and 30 ins. Hg
(saturated).
TABLE 22
STORAGE AND HANDLING
Storage tanks should be located in accordance with Table 24 based upon the capacity of storage con­cerned. The separation distance given in Table 24 must be maintained at all times, and no building extensions, fixed ignition sources, etc. should ever be allowed to encroach within it.
,
The. whole of the area within a distance of 3 m.
from tanks up to 2250 litres water capacity, or 10 n-r from larger tanks, should be maintained at ALL times - free from weeds, long grass or combustible materials. Tanks should not be sited adjacent to
any pits, drains or other depressions.
Tanks should be protected by industrial type
fencing where the risk of trespass or tampering ,is high. Large tanks should always be protected:.
,.
Where damage to LPG systems from vehicular
traffic is a possibility precautions against: suctt~-
damage should be taken. The degree of protection
required will depend on actual site conditions, including the density of traffic, the nature of.the traffic, and the overhang or reach of the vehicles.
Strategically located motorway type crash barriers
or concrete or steel bollards will be suitable for
most installations. Where an earthing point is provided for the dis­charge of static electricity, this should be clearly visible and readily accessible at all times. Metalled vehicular access to the tanks should be provided.
BUTANE
Calorific Value (Vaporised)
Volume of gas produced per
Mass of Liquid
Volume Occupied per Mass of Liquid
Volume of Air to burn Unit
Volume of Gas
METRIC UNITS
121.5 MJ/in3
49.2 MJ/kg
28.2 MJ/litre
0.41 m3/kg
1743 1 /tonne
30‘
IMPERIAL UNITS “‘.
3200 btu/ft3
21150 btu/lb
121610 btu/gal
6.6 ft3/Ib
390 gal/ton
.i
30
4-
TABLE 23
PROPANE.
Calorific Value (Vaporised)
Volume of Gas Produced
per Mass of Liquid
Volume Occupied per Mass of Liquid
Volume of Air to burn Unit
Volume of Gas
METRIC UNITS
95 MJ/m3
50 MJ/kg
25.5 MJ/Iitre
0.54 m3/kg
1957 1 /tonne
23
IMPERIAL UNITS ‘,’
2500 btu/ft3 21500 btu/lb
110080 btu/gal
8.6 ft3/lb . _.
437 gal/ton.
23
“.
Page 40
Location and
spacing for tanks for industrial, commercial and domestic bulk storage.
l-ABLE 24
Maximum water
capacity of any
single
tank
in
Litres (Gallons)
450
(Up to 100)
450-2250
(Over 100-500)
2250-9000
(Over 500-2000)
9000-l 35000
(Over 2000-30 000)
Maximum total
water capacity of
all tanks in
Litres (Gallons)
6750 (1500)
27000 (6000)
Minimum Separation Distance in Metres (Feet)
From building, boundary, prone*
line* or fixed source of ignition
: a. 1.
Between tanks
Below ground
Above Buried Valve assemblyt and Above &low
ground portion
and loading/
ground ground
unloading point
: . .
.1
above ground
n :
None**1 3 (10) 1 3 (10)
1 None Il.5 (5)
..,
=3 (10) 3 (10) 3 (10)
~ .‘.I
l(3) !.5(5) ’
3
(10)
I
7.5 (25)
Whether built on or not. Where tanks up to 450 litres water capacity are sited adjacent to mobile homes, caravans, site huts and similar buildingsof a non-permanent natureconstructed of combustible materials, additional precautions should be taken. In such circumstances the minimum distance between the shell of the tank and the building should be one metre, and the minimum distance between the filler valve on the tank and any door, openable window, ventilator or other point of gas entry into the building, should be three metres.. The isolation valves, filling valves and pressure relief valves located on the manhole cover of the under­ground tank.
Page 41
10 SERVICING AND SY§TElUl FAULT-FINDING’
10.
SERVICING AND FAULT FINDING
Annual servicing should be carried out by a com­petent person and a servicing schedule is set out below. For ease of servicing, Chaffoteaux recom­ment that the boiler isvalved on both sides as shown
in the various system diagrams.
Annual Service
1 Clean the Burner 2 Clean the Heating Body 3 Clean the’ Pilot Assembly, Thermocouple
and Spark Electrode
FAULT FINDING CHAkT -- SYSTEM
I
FAULT CAUSE
Insufficient heat to room
insufficient hot water
4
Clean the Gas Filter
5
Clean the Thermostat Capsule
.
6
Clean the water filter
-. I
Three Yearly Service
1
Clean Burner, Heating Body, Pilot
--‘i
Assembly and Thermocouple
.
2.
Replace the Gas Filter
;.;
3.
Replace the Diaphragm
4 Clean the Gas Valve
I.. 1
n
.
., :. ,,.
.
..,
-.-
__
Insufficient gas flow
Insufficient water flow Boiler not coming up to full gas
! Short cycling around
y cylinder
s Short cycling around by pass
;
Heat loss incorrect
~,. Radiator too small
Radiator obstructed
- Too large a temperature difference
Room thermostat
Cylinder not high recovery. Mechanical valve used with
by pass
Air in coil
+ Cylinder stat. too high
on cylinder
‘.)
REMEDY
Check inlet pressure at gas cock.
,.
Check manifold pressure and adjust.
Open all valves and by pass.
. .
Check by consumption at
.:
meter. Refer to Installation
: and Maintenance Instructions for remedy. Change pump if necessary.
Check a balance valve is fitted and correctly adjusted. _. 1’
Check and adjust - see:
... :
Installation Instructions.
Check system resistance is
within pump duty.
.i
Check heat loss - look for
r excessive ventilation ­unrestricted chimney etc.
Check radiator output and adjust for temperature difference of 20°C.
Remove obstruction or
__
relocate radiator.
Balance System.
1. Out of calibration.
2. Neutral not connected.
3. Influenced by local
heat source, TV etc.
Replace.
Check and fit if necessary and adjust.
Ensure cylinder is vented. Re-locate ‘/3 from bottom
_
of cylinder.
Page 42
FAULT
Delay in switch to heating in DHW priority system (as for insufficient heat) plus
Boiler noise
Noise from system
Overflowing expansion tank
Radiators hot when motorised valve is closed.
WARM AIR
Insufficient heat
Noise (mechanical)
Noise (system)
Cylinder stat. out of calibration
Poor contact between cylinder stat. and cylinder
Air in system
Insufficient Head
Incorrect cylinder fitted
Scale in heat exchanger
Water velocity exceeds recommendations
Air in system
Insufficient capacity
Reverse circulation
Incorrect fan speed incorrect duct sizing
Register not balanced Filter dirty Low mean water
temperature Too large a differential
on room stat.
Fan hunting
Loss of dynamic balance
due to accumulation of dust. Distortion of rotor or
bearings
Fan speed Duct sizing Restricted register
Obstruction in duct
L
CAUSE REMEDY
I
Replace
Clean surface of cylinder and re-locate using heat grease.
.:
Check cylinder and air vent as recommendations in Section 4.2.
._d
Vent high points. . .‘.;
Is charge pressure correct
on sealed system?
_‘, ::
_._
,
.’ . Have recommendations been -’ followed regarding pump, cold feed and vent positions.
--_.“-z
Check cylinder is an indire&” type an’d is not a self priming-
,
type. Check for system leaks.
De-scale heating body if necessary.
Check pipe sizes and
enlarge if necessary.
Vent system thoroughly. Replace.
Ensure heating returns commoned before joining. main return.
i !,
,..
Check calculation and adjust: Increase fan speed (take care Q
with noise).
Rebalance system. Remove and clean.
‘.
Ctieck pump duty and boiler. operation.
Ensure anticipator is
connected. Clean Fan.
Lubricate or replace as
necessary. Clean filters.
Check size of relief grilles and return air register and ensure of adequate size.
Adjust. Replace in correct size.
Adjust.
.
t
Remove.
._, s,..; _-
Page 43
11 DATA
WATER HEATERS
t
Clearances
mm 178
I
50 152
Bottom
1”s 7 2 6
mm NIL
75
NIL
Sides
IITS
NIL
3 NIL
Gas connectron 15 mm copper 15 mm copper 15 mm copper
Water connectron
I
15 mm copper
Inlet 15 mm copper
15 mm copper
Water
flow
rate
Raised
50°C - (90°F)
Raised
?I+,- ,LeII\
1 /mm
w*
t
lmin
6.5
1.44.
111
outlet spout or 15 mm copper
2.5 Raised 6.3
0.55 2O’C (36“ F) 1.39 i
4
16 Raised 36,
Weiaht
Flue we
,,...... I ._. ___- -.-
, avke-,-rl ‘I 1 w*
2.44
-.
0.92 35°C (63°F) .79 -1
I h,^.. Min normal ^^___I
pressure
lbar - 15psi 0.45 bar 6.5 PSI 0.5 bar 7.5 psi
preSS”re lObar - 150psi 10 bar 150 psi 10 bar 150psi
1.3 m 4.26 ft - -
I
essure
Max low _ pressure
1.5” 4.9 ff 25” 82 ft 24 m 80 ft - -
19 Kg 42 Ibs 6.9 Kg 15.25 Ibs 10.7 Kg 23.5 Its 1 Hetght 205 mm 8 ins Flueless or 125 mm 4.9 ins Wrdth 305 mm 12 ins 3 ins0 240 mm 3.4 ins
From
Internal
From
External
Htgh
Low
High
Low
cm1 102
tnz 15.8
cm2 102
In: 15.8
cm’ 51
in: 7.9
cm2 51
1”: 79
I
35
5.4
P!us openmg wmdow
LPG - Propane Burner pressure Restrlcrors Manrfold ~nrector Gas Consumoton
Gds Connecr~on
“‘Ih
ft’/h
10 in.w.g. 10 in.w.g. 10 in.w.g.
None 2.75 mm 41909 3.25 mm 37251
074 14154/19 070 14154/10 072 14154/12
1.17 ,434
.43!
41.3 15.32 15.44
“2 I” RSP
12 mm copper
% I” BSP
N.8. BRITONY LOW PRESSURE
Heat Inr>ut
29.21 kW Heat Output 21.90 kW Burner Pressure 13.5 “bar Mamtold lmector Stze 118 Gas Consumptron
2.70 m’/hr Water Connectron 22 mm cooper Water Flow Plate Raiseo 50°C (90°F) 6.311min
99.600 Btu/h 74,700 Btu/h
5.3 ins.w.g.
98.18 ft’/hr
1.38 g.p.m
Page 44
DOMESTIC BOILERS
Man1 told wxcor
118 1 116 I
113
1 113 1
113 1 113 1
113 I
113 1 118 1 118
lla 1
Min flow rate 450 Ill/h 1.65 qom
450 lit/h 1 65 qom
720 lit/h 2.6 qpm
j head Puma on flow 2.0 m 6.5 ft 2.0 m 6.5 ft 3.5 m 11.5 ft. 3.5 m 11.5 ft 3.0 m 9.75 ft
Max stattc head 30 m 98 ft 30 m 98 ft 30 m 98 ft 30 m 98 ft 30 m 98 ft Weight 13.6 Kg 30 Ibs 13.6 Kg 30 Ibs 14.3 Kq 31.5 Ibs 14 3 Kg 31.5 Ibs 19 Kg 421bs Water capacity I0.182~1it0.Ckloals i 0.182 lit 0.04 aals I 0.58 lit 1 02 ots I 0.58 lit 1.02 ots
I -. - -
Flue size Height 1 125mm 4.9ins 1 4in8 lOOmm0 1 205mm 8ins 1 4in0 lOOmm8 1 205mm eins
Width 1 240mm 9.4 ins 1
4
305 mm 12 ins 305mm 12 ins
High crZ*
90 90 150 150 210
From. 14 14 23 23 31
a
cgm Internal cm’ 90 180 150 300 210
.g f $
Low .
in2
14 xl 33 46 31
I
-Gal
u OCE gTL I External From High r cm2 In2 45 45 7 I I 45 90 7 I I 11.5 75 75 11.5 75 75 15.5 105 105 .
~~
Part No I 14154/10 14154/10 1415400 14154/10
I
14354/10
Gas consumotlon ita 14.12 11 07 14.121 1 11.07 23.1 118.14 13.8 23.1 18 14 1 13.8 31.6 26.23 20.40
m’ I 0.4 i 0.3
I
0.4 I 0.3
I
0.64 1 0.51 1 0.38 0.64 1 0.51 1 0.38 i 0.9 I 0.74 t 0.58
Page 45
FUEL COST ESTIMATING The following table of fuel consumptions is based
n the energy consumption of houses as published
1 the I.H.V.E. (Ref. B-1817).
in the table the following assumptions are made:-
1) Equal amounts of daytime heat for full house heating.
2) Temperatures that are controlled and allowed to fall at night.
3) Properly insulated properties.
4) Consumptions related to the S.E. England
(adjust for other Regions).
TABLE 25.
I
FUEL
CALORIFIC
VALUE
GAS
N. Gas 29.31
kwhltherm
L.P.G. 7.113
(propane)
kwh/litre
OIL
28 set 10.18
kwh/litre
35 kec 10.57
’ kwh/litre
SOLID FUEL
Sunbright E
7.495
kwhlka
L
5) Internal temperatues of 21°C (7O”F), 18°C (65°F) and 16°C (60°F) (see Table 1.).
6) Domestic hot water allowed on a percentage basis.
^.
_-
Estimated consumptions allow for appiiance
efficiencies.
Allow for standing charges,:. hire
- _ _
charges, servicing or the repayment of loans when calculating running costs. To compare fuel cost multiply the fuel consumption by the appropriate fuel cost.
936
1355
therms
therms
3856 5582
litres litres
2802 4079
litres
litres
2689 3915
litres
litres
6022 8672
kg
kg
3908 5631
kg
kg
18777 -27444
kwh kwh
1515 2020
therms
therms
6241 8322
litres
litres
4611 6030
litres
litres
4426 5788
litres litres
9635 12767
kg
kg
6303 8404
kg kg
31054 40804
kwh
kwh
25638
kwh
37064
kwh
41888
kwh
55250
kwh
Page 46
G-LOSSARY 12
‘.
12.
GLOSSARY OF TERMS
Btu/h
Calorific value
Cold feed
Conduction
Contraflow Convection
Delta (symbol A)
Expansion
Gas rate
Grille
Index Circuit K factor
L.P.G. Microbore.
- Is a measure of heat and stands for British Thermal Units per
hour. It is the amount of heat
required to raise 1 lb of water 1°F.
- The amount of heat released by the combustion of a given
quantity of fuel.
- The pipe leading from the feed and expansion tank to join the system through which water is introduced into the system. It should not be less than 15 mm. The point at which the cold feed enters is called the neutral point.
- The transfer of heat from a hot to a cold mass with which it is in contact. (direct means).
- Against the normal direction of flow.
- The transfer of heat from a hot to a cold mass by the action of
air, gas or liquid passing over it.
- Difference - A t = temperature
difference
- A p = pressure difference.
--All liquids gasses and solids expand in volume on a rise in
temperature. In a heating system it is neces-
sary to make provision for:
1. Expansion in water volume.
2. Expansion in pipes.
--The amount of gas consumed in a measured period of time.
- A non adjustable facing used on
the termination of a duct.
- The heating circuit with the greatest resistance.
- A factor given to building materials relative to the resis­tance they offer to the conduct­ing of heat -
surface to surface.
- Liquified Petroleum Gas.
- Systems in which connections to radiators are made in 6 mm,
8 mm or 10 mm tube”usually
from a
central manifold.
Open Vent
- Also called the safety vent pipe or expansion pipe. AT pipe of
not less than 22:‘mm‘-Q) rising throughout its entire .length to
vent atmosphere above thewater’
level in the feed and expansion tank. Its purpose is .to. relieve pressure in the system. in the:
event of thermostat failure and
to accommodate changes in: water level due to the:operation­of the pump.
,..*-. n
Neutral point - Point at which cold feed:. is
connected to the system: Called the neutral point since the pressure is always thestatic head pressure and is not influenced by the operation of the pump.
Plenum - The take off from a warm air
unit to which the distribution ducts are connected.
!
Pump head - The pressure imposed on a
system by the operationof the circulating pump. Tfi3 ability of a pump to overcome a resistance as to support a column of water.
Radiation - The heat transferred -Trbrn. one
body to another bywave motion.
Small bore
- A system of circulation using 15 mm, 22 mm and .2B -mm pipes.
.._ *a,, . ‘;-
.‘“;’ ;.;.
Static head - The pressure imposed on a system
by the height of the:.feed and
expansion tank above -any part’
of it.
I. ,
Thermocouple
- A heat sensitive probe made of I dissimilar metals which,, when heated create an electrical cur-
rent (measured in millivolts) due to the A t between the hot and cold junctions.
‘U’ values
- The amount of heat per hour passing through a measured area of a given material of given thickness per “C or “F.
Venturi
- A restriction in a pipe which creates a pressure differential.
Page 47
‘3 CONVERSION TABLES
13. CONVERSION FACTORS AND USEFUL COMPARISONS MULTIPLICATION FACTORS FOR UNIT CONVERSION
Imperial to SI LENGTH Inch to millimetre (mm)
foot to metre (m)
mile to kilometre (km)
AREA
25.4
Millimetre to inch (in)
0.039
0.305
metre to foot (ft)
3.281
1.609
kilometre to mile
0.621
sq. inch to sq. centimetre (cm’)
VOLUME
0.093
sq. metre to sq. foot (ft’)
10.764
cubic foot to cubic metre (m3 1
bit foot to litre (I) or cubic
decimetre* (dm3 1
pint to litre (I)
gallon to litre (I)
MASS
0.028
28.32
0.586
4.546
ounce to gramme (g)
pound to kilogramme (kg) ton (U.K.) to tonne (t)
HEAT’-
28.35
gramme to ounce (02)
0.454
kilogramme to pound (lb)
1.016
tonne to ton (U.K.)
Btu to-kilojoule (kJ) therm to megajoule (MJ)
HEAT FLOW (Input and Output) Btu/hour to watt (WI
1,000 Btu/hour to kilowatt (kW) 1,000 Btu/hour to megajoule/hour
(MJ/h)
FI .OW RATE
1.055
kilojoule to Btu
105.5
megajoule to therm
0.293
0.293
1.055
,ic foot/hour to cubic metre/hour
(m3/h) (gas) cubic fodt/hour to litre/hour (I/h) cubic foot/hour to millilitre/second
(ml/s)
-gallon/hour to litre/hour (I/h) gallon/hour to millilitre/second
(ml/s)
gallon/minute to cubic metre/hour
h3/g)
gallon/minute to litre/second
PR ESSU R E
0.028
28.32
7.866
4.546
1.263
0.273
0.076
inch w.g. to millibar (mbar) pound force/sq. inch to bar
CALOR I FIC VALUE Btu/cubic foot to megajoule/cubic metre
2.5
millibar to inch w.g. (in.w.g.1
0.4
0.069
bar to pound forcekq. inch
14.5
(MJ/m3)
0.038
SI
to Imperial
cubic metre to cubic foot (ft3 1
litre or cubic decimetre to cubic
foot (ft3 1 litre to pint litre to gallon
watt to Btu/hour (Btu/h)
kilowatt to 1,000 Btu/hour megajoule/hour to 1,000 Btu/hour
(Btu/h)
cubic metre/hour to cubic foot/hour
(ft3/h) (gas) litre/hour to cubic foot/hour millilitre/second to cubic foot/hour
(ft’/h) litre/hour to gallon/hour millilitre/second to gallon/hour
(Gal/h)
cubic metre/hour to gallon/minute
(gal/m) litre/second to gallon/minute
megajoule/cubic metre to
btukubic foot (Btu/ft3 )
35.31
0.35
1.76
022
0.035 2205
0.984
0.948.’
0.00948
3.412 ._
3.412
0.948
35.31 .-
0.035
0.127
0.22.:
0.792
3.67
13.198
26.34
-ubic decimetres will be used in the gas industry to express gas volumes and the space occupied by
appliances, etc.
Page 48
USEFUL.COMPARISONS
1 gallon water = 10 lbs = 0.16 ft3
1 ft3 water = 6.23 gallons = 62.35 ibs.
1 Btu wiil raise 1 lb water 1 o F in 1 hour.
1 K cal will raise 1 Kg (1 litre) water 1°C in 1 hour.
1 m3 water = 1000 Kg = 1000 litres.
OC:to°F= 1.8C+32
“F to “C = s/9 (“F -32)
1 bar=lOmofhead=15psi=34ft.ofhead.
1 psi = 2.31 ft of water = 703.03 mm of water.
ESPOOI
Loading...